MiCOM error codes

Error CodeAction to be Taken
0X83810002Check Software is loaded correctly into the relay. Upgrade the Firmware.
0X83818001Replaced Analog Opto Card, Ethernet Card, Relay Upgraded,& found Healthy & OK
0x0c0e0000The relay card is defective. Replace the Relay card.
0x0c250018Either the Processor Card or Analog Input Card is defective. Replace the Processor card or Analog Input Card. If the problem persists replace both cards.
0x0c0ddb1cThe Analog Input card is defective. Replace the Analog Input card.
0x0c170017The processor Card is defective. Replace the Processor card.
0x0c0ddb15The Analog Input card is defective. Replace the Analog Input card.
0x8c810000The Analog Input card is defective. Replace the Analog Input card.
0x0c170018The processor Card is defective. Replace the Processor card.
0x83810007The processor Card is defective. Replace the Processor card.
0x81170000The co-Processor Card is defective. Replace the Co-Processor card.
0x0c160011The processor Card is defective. Replace the Processor card.
0x0cc020041Model Number mismatch. Check the Model Number & reload the Model Number and Serial Number once again to the relay.
0x838b0808Opto card No.3 is defective. Replace Opto card No.3
OX838b2008Opto card No.2 is defective. Replace Opto card No.2
OX83818001Replaced CT/VT Module& Opto card 2 & 3 Relay Tested, Measured & found Healthy & OK.
0x838188001Replaced CT/VT Module, Relay Tested, Measured & found Healthy & OK.
0x02070be0The processor Card is defective. Replace the Processor card.
0x0202000eReplaced CPU card, Analog input card, Opto card, hood, and backplate
0x0c0ddb1cReplaced CPU card. Relay tested in Automatic Test bench. Found OK. Relay energized for 48 hours. Since the CPU card is defectively unable to extract & download the customer’s settings & PSL.
0x812A0003The Analog Input card is defective. Replace the Analog Input card.
0x0c220028The processor Card is defective. Replace the Processor card.
0x0c0ddb1cThe Analog Input card is defective. Replace the Analog Input card.
0x0c1600b3Relay card No.3 is defective. Replace Relay card No.3
0x351afe03Ethernet Card is defective. Replace Ethernet Card.
0x0c1600b1Relay card No.1 is defective. Replace Relay card No.1
0x0c1600b2Relay card No.2 is defective. Replace Relay card No.2
0x0c0ed920Either the Processor Card or Analog Input Card is defective. Replace the Processor card or Analog Input Card. If the problem persists replace both cards.
0x08118000bOpto Card is defective. Replace Opto card.
0x020b0b4aThe processor Card is defective. Replace the Processor card.
0X0C140002The processor Card is defective. Replace the Processor card.
0x8c01000.The power Supply Card is defective. Replace the Power Supply card.
0x0c020020The processor Card is defective. Replace the Processor card.
0x81180002The processor Card is defective. Replace the Processor card.
0x07020020Communication card is defective. Replace Communication card.
0x0c020028Either Processor Card or Analog Input Card is defective. Replace Processor card or Analog Input Card. If the problem persists replace both cards.
0X811E0000Either Processor Card or Co-processor Card is defective. Replace Processor card or Co-processor Card. If the problem persists replace both cards.
0x82021C98Co-Processor Card is defective. Replace Co-Processor card.
0x8c8100000Anolg Input card is defective. Replace Anolg Input card.
0X8118002Anolg Input card is defective. Replace Anolg Input card.
0x0c0ddb15Opto Card is defective. Replace Opto card.
0x8c18000Replaced Transformer , relay tested and calibrated and found in order.
0x0c1600d00Either Processor Card or Analog Input Card is defective. Replace Processor card or Analog Input Card. If the problem persists replace both cards.
0x1c1200f6Processor Card is defective. Replace Processor card.
0x83818000Replaced CT/VT module from the P743 relay Excess stock to the defective relay. Relay tested from CP dept. Found OK.
Error code 0x0C220028indicates that the IED configuration – based on the MCL file downloaded to the relay – cannot be initialised in flash memory. This can occur if the MCL file being downloaded to the relay is too large (>32kB) or the MCL file is corrupted during download.

What does the error code 0x0C170017 on a MiCOM P14x


What is the meaning of error code 0x0c170018


What does this Micom hex error code mean?
Error Code During Operation – GE MiCOM P40 Agile

Leave a Comment

Your email address will not be published. Required fields are marked *

Scroll to Top