Error Code | Action to be Taken | |
0X83810002 | Check Software is loaded correctly into the relay. Upgrade the Firmware. | |
0X83818001 | Replaced Analog Opto Card, Ethernet Card, Relay Upgraded,& found Healthy & OK | |
0x0c0e0000 | The relay card is defective. Replace the Relay card. | |
0x0c250018 | Either the Processor Card or Analog Input Card is defective. Replace the Processor card or Analog Input Card. If the problem persists replace both cards. | |
0x0c0ddb1c | The Analog Input card is defective. Replace the Analog Input card. | |
0x0c170017 | The processor Card is defective. Replace the Processor card. | |
0x0c0ddb15 | The Analog Input card is defective. Replace the Analog Input card. | |
0x8c810000 | The Analog Input card is defective. Replace the Analog Input card. | |
0x0c170018 | The processor Card is defective. Replace the Processor card. | |
0x83810007 | The processor Card is defective. Replace the Processor card. | |
0x81170000 | The co-Processor Card is defective. Replace the Co-Processor card. | |
0x0c160011 | The processor Card is defective. Replace the Processor card. | |
0x0cc020041 | Model Number mismatch. Check the Model Number & reload the Model Number and Serial Number once again to the relay. | |
0x838b0808 | Opto card No.3 is defective. Replace Opto card No.3 | |
OX838b2008 | Opto card No.2 is defective. Replace Opto card No.2 | |
OX83818001 | Replaced CT/VT Module& Opto card 2 & 3 Relay Tested, Measured & found Healthy & OK. | |
0x838188001 | Replaced CT/VT Module, Relay Tested, Measured & found Healthy & OK. | |
0x02070be0 | The processor Card is defective. Replace the Processor card. | |
0x0202000e | Replaced CPU card, Analog input card, Opto card, hood, and backplate | |
0x0c0ddb1c | Replaced CPU card. Relay tested in Automatic Test bench. Found OK. Relay energized for 48 hours. Since the CPU card is defectively unable to extract & download the customer’s settings & PSL. | |
0x812A0003 | The Analog Input card is defective. Replace the Analog Input card. | |
0x0c220028 | The processor Card is defective. Replace the Processor card. | |
0x0c0ddb1c | The Analog Input card is defective. Replace the Analog Input card. | |
0x0c1600b3 | Relay card No.3 is defective. Replace Relay card No.3 | |
0x351afe03 | Ethernet Card is defective. Replace Ethernet Card. | |
0x0c1600b1 | Relay card No.1 is defective. Replace Relay card No.1 | |
0x0c1600b2 | Relay card No.2 is defective. Replace Relay card No.2 | |
0x0c0ed920 | Either the Processor Card or Analog Input Card is defective. Replace the Processor card or Analog Input Card. If the problem persists replace both cards. | |
0x08118000b | Opto Card is defective. Replace Opto card. | |
0x020b0b4a | The processor Card is defective. Replace the Processor card. | |
0X0C140002 | The processor Card is defective. Replace the Processor card. | |
0x8c01000. | The power Supply Card is defective. Replace the Power Supply card. | |
0x0c020020 | The processor Card is defective. Replace the Processor card. | |
0x81180002 | The processor Card is defective. Replace the Processor card. | |
0x07020020 | Communication card is defective. Replace Communication card. | |
0x0c020028 | Either Processor Card or Analog Input Card is defective. Replace Processor card or Analog Input Card. If the problem persists replace both cards. | |
0X811E0000 | Either Processor Card or Co-processor Card is defective. Replace Processor card or Co-processor Card. If the problem persists replace both cards. | |
0x82021C98 | Co-Processor Card is defective. Replace Co-Processor card. | |
0x8c8100000 | Anolg Input card is defective. Replace Anolg Input card. | |
0X8118002 | Anolg Input card is defective. Replace Anolg Input card. | |
0x0c0ddb15 | Opto Card is defective. Replace Opto card. | |
0x8c18000 | Replaced Transformer , relay tested and calibrated and found in order. | |
0x0c1600d00 | Either Processor Card or Analog Input Card is defective. Replace Processor card or Analog Input Card. If the problem persists replace both cards. | |
0x1c1200f6 | Processor Card is defective. Replace Processor card. | |
0x83818000 | Replaced CT/VT module from the P743 relay Excess stock to the defective relay. Relay tested from CP dept. Found OK. | |
Error code 0x0C220028 | indicates that the IED configuration – based on the MCL file downloaded to the relay – cannot be initialised in flash memory. This can occur if the MCL file being downloaded to the relay is too large (>32kB) or the MCL file is corrupted during download. | |
What does the error code 0x0C170017 on a MiCOM P14x
What is the meaning of error code 0x0c170018
What does this Micom hex error code mean?
Error Code During Operation – GE MiCOM P40 Agile