protection relay 2

– During one phase PT failure, will overflux relay work? Has anyone seen this kind of voltage transformer connection?
– Why b phase winding is grounded on the secondary side?
– Can u share nameplate details of the PT
– yes, in an oil company, usually they only use 2 PT input and make it as delta connection in relay
20digsi 4, 11:51 – abb pcm600: That’s an open delta voltage transformer (or potential transformer)
20digsi 4, 11:52 – abb pcm600: It’s mainly used as an input to detect earth faults using neutral voltage displacement ..
20digsi 4, 11:54 – abb pcm600: Typically the sum of the voltage across D7 and D9 is zero ….however should there be an earth fault and one of the phases hit the ground … you will get voltage across the open point ….
20digsi 4, 11:55 – abb pcm600: Such schemes are used in ungrounded systems or on generator – transformer sets …. there is no path for earth fault …
20digsi 4, 11:57 – abb pcm600: Sorry open wye … but the scheme is same …
20digsi 4, 13:04 – abb pcm600: Open delta connection , Yellow phase normally will ground.

But as per drawing seen some conflict..
Norammly 2 VT Winding we can seen..
20digsi 4, 13:05 – abb pcm600: IMG-20200420-WA0001.jpg (file attached)
Normally like this


20digsi 4, 13:05 – abb pcm600: This is star connection with y phase grounded. Not an open delta. I was reading on internet its some old practice followed in UK.
20digsi 4, 13:35 – abb pcm600: Yeah … that’s an open Wye or Open Star … works the same way ..
20digsi 4, 20:11 – abb pcm600:
Anyone have PDF of this book
21digsi 4, 03:07 – abb pcm600: Hollo, anyone have any worksheet for the theoretical calculation of the differential and restriction currents in general electric T60?
21digsi 4, 14:06 – abb pcm600: Who has the Relay Testing Handbook by Valence to assist me
22digsi 4, 12:10 – abb pcm600: Thanks!!
22digsi 4, 12:11 -abb pcm600: Thank you.
22digsi 4, 12:26 – abb pcm600: Thanks
22digsi 4, 12:52 – abb pcm600: Thanks guys to accept me to this group.
22digsi 4, 12:53 – abb pcm600: I m an instument engineer with base here in the netherlands
22digsi 4, 12:54 – abb pcm600: Welcome
22digsi 4, 12:54 – abb pcm600: Glad to help, if I can, but also I will ask for tips… 💪🏽
22digsi 4 – abb pcm600: Thnkas Zimuto
22digsi 4, 12:56 – abb pcm600″: Thanks
22digsi 4, 13:07 – abb pcm600″: Hi all, it’s Kashif.
Engineering Coordinator Saipem, working in KSA.
23digsi 4, 13:23 – abb pcm600: https://www.linkedin.com/posts/cikit-electricals-technologies_thunder-strike-during-summer-activity-6658963455237849088-kWUB
23digsi 4, 16:13 – abb pcm600: Hi, anybody in this group who has experience with Digsi Manager from siemens?
23digsi 4, 16:42 – abb pcm600″: @966537578990 A. A
23digsi 4, 16:42 – abb pcm600: ??

23digsi 4, 16:43 – abb pcm600″: Nothing just Hi
23digsi 4, 20:35 – Elec Engg: @966539154087 Pls read the group rules and maintain the objective of the group
https://elec-engg.com/whatsapp-group-for-protection-engineers/
25digsi 4, 18:22 – abb pcm600: Anyone have any experience with diesel genset parraleling on common neutral resistor
25digsi 4, 18:36 – abb pcm600: Any drawing, and what you wanna know about?
25digsi 4, 21:38 – abb pcm600: How many generators can work connected on resistor and how many can work isolated in parallel mode
26digsi 4, 05:04 – abb pcm600: That’s a very big open question …
26digsi 4, 05:07 – abb pcm600: Yes, it is really problematic to solve its protection system
26digsi 4, 05:16 – abb pcm600: Yes we typically run the neutrals to a common neutral bar. Install atleast 3 of neutral earthing resistor and and contactors
26digsi 4, 07:41 – abb pcm600: Are you talking about medium voltage generators
26digsi 4, 07:41 – abb pcm600: Yeah …
26digsi 4, 07:42 – abb pcm600: How did you calculate the size of resistors
26digsi 4, 07:42 – abb pcm600: Please, can you share some calculations
26digsi 4, 07:45 – abb pcm600:
What_is_NGR_How_to_calculate_NGR_Resistance__1584160054
26digsi 4, 10:06 – abb pcm600: Please share as much as you can
26digsi 4, 10:06 – abb pcm600:
26digsi 4, 10:06 – abb pcm600: https://tinyurl.com/y7kf9gwq
26digsi 4, 14:56 – abb pcm600: Thank you, right this perfectly describes ngr under the fault
26digsi 4, 14:59 – abb pcm600: I want to show you this example
26digsi 4, 15:00 – abb pcm600:
14.pdf
28digsi 4, 10:16 – abb pcm600: IMG-20200428-WA0002.jpg (file attached)
28digsi 4, 17:56 – abb pcm600: Hello every one
28digsi 4, 19:05 – abb pcm600: Hi all
I need setting guid for directional protection
28digsi 4, 19:06 – abb pcm600: If any example for Double feed Sub-Station with the tie breaker normally closed
Mohamed badr: What is Apts scheme
28digsi 4, 19:15 -abb pcm600“: This message was deleted
28digsi 4, 19:16 -abb pcm600“: https://www.researchgate.net/publication/340665077_A_Double_Wye_Ungrounded_Fuseless_Shunt_Capacitor_Bank_Protection_and_Control_Overview_in_A_High_Voltage_Substation_using_an_IED

https://www.researchgate.net/publication/339988674_An_Overview_of_High_Impedance_Differential_Scheme_Design_Protection_and_Simulation_for_a_132_KV_Double_Bus_Bar_Single_Breaker_System
For this system, with the two Transformers secondary breakers and the tie breaker are normally closed, and installing directional on the two secondaries, I need some guid on how to Make the setting for the directional, And if any one has a similar case i will be glad if he shares his settings and how to Make them
29digsi 4, 06:41 – abb pcm600: the intention of the Directional on the secondary side is for backup protection? i ever encounter application that uses the secondary side 67 as a backup by looking up into the transformer and if it operates it will trip both HV and LV. DOC (Isetting : full txf rating, TMS:0.1 , +30degree), DEF (Isetting: 0.1A, TMS: 0.1, 0 degree)
29digsi 4, 17:05 – abb pcm600: Can anybody share about the zig zag transformer? Principle operation of it.
29digsi 4, 20:05 – abb pcm600: Thanks🌹
29digsi 4, 20:34 – abb pcm600:
Winning COVID-19 – Preparedness and Response Management.pdf
29digsi 4, 20:34 – abb pcm600: Please enroll
30digsi 4, 13:08 – abb pcm600″: Anyone has SR 469 , SR 650 and SR 750 test formats? Which is the software used for these relay? Anyone pls help.
01etap, 05:30 – abb pcm600: IMG-20200501-WA0002.jpg (file attached)
01etap, 05:36 – abb pcm600: IMG-20200501-WA0001.jpg (file attached)
01etap, 05:36 – abb pcm600: IMG-20200501-WA0000.jpg (file attached)
01etap, 17:37 – abb pcm600: 🤷🏿‍♂️???
01etap, 20:52 – abb pcm600: More courses like this?
01etap, 21:10 – abb pcm600:
What is actually bandwidth voltage ???
01etap, 21:20 – abb pcm600: Sorry..Just found the answer above it🙏🙏
01etap, 22:13 – abb pcm600:
is there any wrong with this statement and calculation… ????
01etap, 23:57 – abb pcm600″: Anyone has GE f650 relay test format?
03etap, 08:47 – abb pcm600: Any?
06etap, 11:54 -abb pcm600:
what could be cause of SF alarm?
06etap, 11:54 -abb pcm600: PLC is communicating with another PLC over profibus
06etap, 11:56 – abb pcm600: Well, it can be a lot of stuff, but the first thing I always have for this alarm. SISTEM FAULT it means that you may have some unit programmed inside your PLC that is not connected in the field.
06etap, 11:56 – abb pcm600: So if it still works let it be
06etap, 11:56 -abb pcm600: with that alarm all parameters of slave address beocme red
06etap, 11:56 -abb pcm600: ok
06etap, 11:57 – abb pcm600: Is not something to concern, just be sure you have a good backup of the PLC program.
06etap, 11:58 -abb pcm600: but if it remains,it will not let startup of Engine
06etap, 12:09 – abb pcm600: Yes, but if it is already working, maybe is only a module programmed in the PLC but not connected in the field, but I say, I saw processes going on Years with this SF and nothing ever happend.



07etap, 09:36 – abb pcm600: we have a problem in the Genetaror Micom P343 that does not boot, please help us how to fix it, thanks
07etap, 09:39 – abb pcm600: Check the ribbon resistance of hmi to relay
07etap, 09:40 – abb pcm600: We have faced the same and ask Alstom ..then after they checked and replace the ribbon and fix the issue .
07etap, 11:21 – abb pcm600: 👍🏽
07etap, 19:43 -abb pcm600“: Where is ribbon?
07etap, 19:48 – abb pcm600: Open the front side of the relay then their is a connecting ribbon cable u can find
07etap, 22:45 – abb pcm600: Hi everyone
This not Bad contact Rubbon the message is clear (Micom Booting) with Led Alarm lightning in red Fast…
It’s like PC booting
I think it’s microprocessor …issue
07etap, 22:51 – abb pcm600: We have faced the same problem in our reliance industries jamnagar plant and Alstom it self give us solution and change all the ribbons. Micom rebooting issue may be from the HMI problem / relay power card problem but if it comes even after replacing HMI look forward with manufacturers.
It’s not just like pc booting issues. Their is no any chance of error in relay or bugs like microprocessor.
07etap, 22:53 – abb pcm600: I might be wrong but I share what i experienced with the same problem.
07etap, 23:00 – abb pcm600: 👍🏽💪🏽
07etap, 23:06 – abb pcm600: Any vacancy for Facilities Manager
07etap, 23:06 – abb pcm600: Job
08etap, 14:29 – abb pcm600: How do i determine distance characteristic in L90 GE relay
08etap, 14:30 – abb pcm600: do someone has commissioning manual for L90 relays
08etap, 16:29 – abb pcm600:
Remote Audit and Training -Electical.pdf
08etap, 16:43 – abb pcm600: hello good morning everyone, will any of you have high voltage protection information?
09etap, 09:48 – abb pcm600: Hello guys

I want to know what you guys as an Electrical Department is doing to to fight COVID 19 in their workplace.
09etap, 10:43 -abb pcm600: This message was deleted
09etap, 12:41 – abb pcm600: This message was deleted
10etap, 20:33 -abb pcm600: 132kv circuit tripped showing R Y B phase and zone 1. And the same circuit is energized from other end at no load. Also no fault found on the circuit during patrolling. What will be the fault. Distance Relay type micom P 441
10etap, 20:35 – abb pcm600: It could be transient or pic up fault
10etap, 20:35 – abb pcm600: Pick up I mean
10etap, 20:36 -abb pcm600: Weather sunny
10etap, 20:36 – abb pcm600″: Does it show any distance in zone 1?
10etap, 20:37 -abb pcm600: Grid staff is not too much efficient to check fault recorder
10etap, 20:37 -abb pcm600: I will go to check it tomorrow and will discuss again
10etap, 20:37 – abb pcm600″: What is the status now does the line charged from both ends?
10etap, 20:38 -abb pcm600: Only from other end at no load
10etap, 20:41 – abb pcm600″: Sir but usually these transients will be blocked by numerical relays rights
10etap, 20:41 – abb pcm600: PTT-20200510-WA0020.opus (file attached)
10etap, 20:42 -abb pcm600: I think it may be DC grounding
10etap, 20:43 – You added abb pcm600
10etap, 21:02 – abb pcm600: Sir thanks for adding me…
10etap, 21:58 – abb pcm600: Check the fault recorded to see the fault current and voltage
10etap, 22:43 -abb pcm600: Lighting
10etap, 22:55 – abb pcm600: Depending on the magnitude and relay Makes. We have have had similar invent without any trace to physical cause
11etap, 06:01 – abb pcm600: can you share us the comtrade file?
11etap, 06:02 – abb pcm600: the .cfg and .dat that can be extracted from the relay
11etap, 15:01 – abb pcm600: We thank you for your registration for the Webinar on How to Implement Solid Waste Management Programs in Industries as per MSW Rules, May 11th, 2020 at 3:00 p.m.

Kindly Join the Webinar on May 11, 2020 at 2:55 p.m. through CISCO WEBEX App using PassCode – 2020 and by clicking on :
Kindly mark your Calendar or Timer so that you do not forget to join. Look forward to seeing you during webinar.

Best Regards,

Surender Kumar Verma
Joint Director 
Federation of Indian Chambers of Commerce & Industry
Federation House, 1, Tansen Marg, New Delhi 110001, INDIA

M: +91-9818186253  (Whats App Call Preferrably)
11etap, 15:01 – abb pcm600: Please join the webinar on how to implement solid waste management programs
11etap, 20:28 – abb pcm600: hi.. sorry to disturb, does somebody ever experience calculating the stability factor of busbar protecton of siemens 7ss85
11etap, 22:03 – abb pcm600: Hello to all
What is the standard setting of the characteristic angle for directional overcurrent phase and ground (67/67N)?
12etap, 23:43 – abb pcm600: Hello
13etap, 02:49 – abb pcm600: IMG-20200514-WA0005.jpg (file attached)
13etap, 02:49 – abb pcm600:
13etap, 09:35 – abb pcm600:
13etap, 09:35 – abb pcm600: does somebody has this relay technical manual
13etap, 09:35 – abb pcm600: ABB PCD
13etap, 09:35 – abb pcm600: for recloser
13etap, 10:24 -abb pcm600: I think May 12th is yesterday 😃
13etap, 11:11 – abb pcm600: Which time zone is this? Here in Zimbabwe it is already 13th of May, 0745hrs
13etap, 12:00 – abb pcm600“: Follow Indian Standard Time zone
14etap, 12:20 – abb pcm600: Hi anyone have static VAR compensator (SVC) protection scheme that can share?
14etap, 12:20 – abb pcm600: thanks
14etap, 13:32 -abb pcm600“: https://www.researchgate.net/publication/340665077_A_Double_Wye_Ungrounded_Fuseless_Shunt_Capacitor_Bank_Protection_and_Control_Overview_in_A_High_Voltage_Substation_using_an_IED
14etap, 13:38 – abb pcm600: okthanks
14etap, 15:49 – abb pcm600: Hello to all
What is the standard setting of the characteristic angle for directional overcurrent phase and ground (67/67N)?
14etap, 15:54 – abb pcm600: For typical distribution networks (upto 33 kV), I set it to 30 degrees. For sub transmission/transmission, I set it to 45 degrees, between the current phase and voltage polarizing quantity.
14etap, 15:55 – abb pcm600: However different scenarios may require different angles … and have to be worked out.
14etap, 15:58 – abb pcm600: This angle for directional phase overcurrent? What about the angle for directional ground overcurrent 67N?
14etap, 15:59 – abb pcm600: Are there any refferences for how to Make the setting for directional phase and ground overcurrent 67/67N?
14etap, 16:00 – abb pcm600: I would typically read the relay manual …
14etap, 16:00 – abb pcm600: And use the default recommended value
14etap, 16:01 – abb pcm600: The actual math behind setting them can be very tricky ..
14etap, 16:05 – abb pcm600: Which relay are you using ?
14etap, 16:09 – abb pcm600: Sepam s40
14etap, 16:10 – abb pcm600: The application is two parallel Transformers
14etap, 16:21 – abb pcm600: What’s the voltage level and how far is the relay from the supply transformer ?
14etap, 17:11 -abb pcm600“: From experience, RCA is 20~40
14etap, 17:42 – abb pcm600: For 67N, the value is dependent on the type of grounding.
Please refer to NPAG, it was clearly explained there
14etap, 17:45 – abb pcm600: Anyone have digsi4 Activation Key.?
14etap, 17:46 – abb pcm600: And for 67, if I am not mistaken, RCA is set based on impedance angle of the system
14etap, 18:00 – abb pcm600 left
15etap, 22:37 – abb pcm600: Any one tested Transformer DIFFRENTIAL 7SR242 DUOBIAS..
I have some dbout on bias characteristics..!
Could you please help..
15etap, 22:42 – abb pcm600:
7SR242_Duobias_Complete_Technical_Manual.pdf
15etap, 22:43 – abb pcm600: This is the complete manual, but bias equation is not clear on it..!
17etap, 14:15 – abb pcm600:
17etap, 14:15 – abb pcm600: http://tiny.cc/etp8oz
17etap, 17:23 – abb pcm600: Is it free
17etap, 17:30 – abb pcm600: yes
17etap, 18:30 -abb pcm600″: https://www.linkedin.com/posts/doble-engineering_attend-one-of-our-virtual-protection-training-activity-6666090125748953088-aF-M
17etap, 19:36 – You added abb pcm600
17etap, 22:32 – abb pcm600 left
22etap, 10:21 – abb pcm600: Does any one here got any information about ct accuracy class 0.1 PL 270 R6
22etap, 10:22 – abb pcm600: I want to know knee point voltage and resistance
22etap, 17:57 – abb pcm600 “: IMG-20200523-WA0004


For Allen Bradley which is the Scada Software
22etap, 18:32 -abb pcm600: Install Studio Enterprise this is combination of all scada….
22etap, 18:32 -abb pcm600: & it will work as per your lisencing….
22etap, 18:38 – abb pcm600 “: Ok Thank You
22etap, 18:39 -abb pcm600: Welcome……😊😊😊😊
24etap, 06:22 – abb pcm600: یہ دن آپ اور آپ کے اہل خانہ کے لئے باعث برکت بنیں۔ اللہ آپ اور آپ کے چاہنے والوں پر اپنی ڈھیروں نعمتیں عطا کرے۔ عید مبارک
24etap, 07:39 – Elec Engg: 🙏Please maintain the group objectives🙏

https://elec-engg.com/whatsapp-group-for-protection-engineers/
24etap, 07:45 -abb pcm600 “: STK-20200524-WA0011.webp (file attached)
24etap, 07:45 -abb pcm600 “: Ok
24etap, 12:23 – abb pcm600: hi Guys
24etap, 12:23 – abb pcm600: does anybody here has experience with toshiba relayy?
24etap, 12:23 – abb pcm600: GRL 200
24etap, 12:23 – abb pcm600: i want to ask about IO config
24etap, 22:20 – abb pcm600: IMG-20200525-WA0002.jpg (file attached)
25etap, 11:30 -abb pcm600 “: STK-20200525-WA0006.webp (file attached)
25etap, 11:31 -abb pcm600 “: Why don’t you Let admin look into it27etap, 09:16 – abb pcm600″: Please send me any study material regarding AVR
27etap, 09:17 – abb pcm600″: For a substation
27etap, 09:17 – abb pcm600″: Little emergency for my undergraduate project
27etap, 14:04 -abb pcm600: i can send you datasheet of Engine AVR
27etap, 14:04 -abb pcm600: ABB Unitrol 1000
27etap, 14:05 -abb pcm600:
AVR Unitrol-1000 Data sheet
27etap, 14:06 -abb pcm600: can ask if stucked stucked at any point
27etap, 14:31 – abb pcm600″: Sir if u have some documents like reading material for begginers
27etap, 20:04 -abb pcm600:
AVR Operating modes
27etap, 20:05 -abb pcm600: not exactly what you want, but will help you
27etap, 20:32 – abb pcm600″:
27etap, 20:32 – abb pcm600″: I have to change CT/VT ratio in a Elster A1800 energy meter. Already got established communication with meter via Metercat 3.5 software. I believe CT/VT ratios can be changed via function “Program” but I am not able to proceed as everything at the “Program” popup window is grey (not editable), I request you to support me in changing the CT/VT ratios. Please refer above snapshot. Thank you!
28etap, 03:26 – abb pcm600: You have to enable changing xt ration on parameters function
28etap, 08:47 – abb pcm600″: This message was deleted
28etap, 08:48 – abb pcm600″:
There is no Parameter menu in Functions? please clarify in details or send some snapshot
28etap, 12:15 – abb pcm600″: Hi Guys, I have a question
For 220KV level, which is suitable either CVT or IVT(PT)? And why
28etap, 12:16 – abb pcm600″: Usually we are adopting IVT(PT) in Andhra Pradesh India
28etap, 12:16 – abb pcm600: CVT always
28etap, 12:17 – abb pcm600″: Sir can you please support your statement… As we have observed the drift in secondary voltages are more in CVT compared to IVT over time span
28etap, 12:19 – abb pcm600: Mainly installation reasons …. they are lighter, cheaper
28etap, 12:20 – abb pcm600: Safer (transfer of emf when fault occurs)as there is no direct connection to the primary voltage source .
28etap, 12:20 – abb pcm600: Can you explain how does the voltage drift?
28etap, 12:22 – abb pcm600″: Deterioration in the capacitance levels over period of operations results in variations in secondary voltages
28etap, 12:29 – abb pcm600: Can’t that be fixed during maintenance? (Note: I don’t have any experience in maintenance and operation)
28etap, 12:31 – abb pcm600″: Even I don’t any experience in Maintenance. But I am not sure we can improve this in effective manner
28etap, 12:31 – abb pcm600: CVT for transmission circuits or High Voltage i.e greater than 66kV and IVT for distribution circuits 33kV and below
28etap, 12:33 – abb pcm600″: Moreover we are mostly using IVT in 220KV levels also so, I am not aware of fixing methods
28etap, 14:50 – abb pcm600: I believe it’s a cost trade off.
In India IVTs in 220kV class are more affordable than CVT. And yet you may see them actively used in 220kV stations where the transmission system is at 220kV level. This is because the same CVT would be used as coupling capacitor for PLCC communications as well.
28etap, 14:50 – abb pcm600: That’s my understanding
28etap, 18:04 – abb pcm600: This message was deleted
28etap, 18:05 – abb pcm600:
Hi guys,
Why when we calculate short circuit at transformer secondary we should consider no load ph to phase voltage not rated voltage?!
28etap, 18:26 – abb pcm600: Yes.CVT is more affordable to be used since the consideration of its(equipments) isolation to H.V.
28etap, 18:30 – abb pcm600: Yes, we can track and analyze its dissipation factor( Tan Delta measurement) 👍👍
28etap, 21:52 – abb pcm600: This message was deleted
28etap, 21:53 – abb pcm600: Which position??
28etap, 21:55 – abb pcm600: Sorry.. Mistakenly forwarded in this group
29etap, 13:19 – abb pcm600:
29etap, 13:21 – abb pcm600: ziv
29etap, 13:21 – abb pcm600: This is an AVR relay from ZIV bringing that message
29etap, 13:22 – abb pcm600: This message was deleted
29etap, 13:22 – abb pcm600: you could contact him
29etap, 13:22 – abb pcm600: Who can help me
29etap, 13:22 – abb pcm600: he is representative of ZIV in Indonesia
29etap, 13:22 – abb pcm600: maybe he can help
29etap, 13:22 – abb pcm600: Thank you
29etap, 13:22 – abb pcm600: after you save
29etap, 13:22 – abb pcm600: i will delete
29etap, 13:23 – abb pcm600: Pliz help me i was adding
29etap, 13:23 – abb pcm600: The number
29etap, 13:23 -abb pcm600″:
Anyone have the pin configuration of this relay?
29etap, 14:37 – abb pcm600: If you mean bias setting, then I would say it has to be calculated based on the transformer parameters
29etap, 17:42 – abb pcm600: Hello everybody, good morning. any of you run the digsilent program?
30etap, 10:12 – abb pcm600: What /which are the switching operations and commissioning procedures of HV / EHV
equipment considering the safety rules of power system operation??Plz tell anyone,thank you
30etap, 17:13 -abb pcm600”: P94V undervoltage relay showing continuous trip,but no alarm present and all functions disabled,need technical support .can anybody please help.
30etap, 17:14 -abb pcm600”:
30etap, 18:04 -abb pcm600″: Go to view record and and reset led
30etap, 19:01 -abb pcm600”: Did ,but still not going
01etap, 22:11 – abb pcm600:
01etap, 22:15 – abb pcm600: To increase the contact Resistance with Ground..!!.
01etap, 22:17 -abb pcm600: To minimize step potential
01etap, 22:17 -abb pcm600: Yes
01etap, 22:18 – abb pcm600: How
01etap, 22:18 – abb pcm600: Why stone and wether it’s the only solution ?
01etap, 23:37 -abb pcm600: Cheapest bro
02etap, 04:00 – abb pcm600: Another reason stones are used is ‘cause it helps in fire 🔥 mitigation, especially where oil traps/ sump pumps are not available.

The leaked oil will have less surface area exposed to air that can burn, there by reducing the fire hazard.
02etap, 08:55 – abb pcm600: Thanks brother
05etap, 15:32 -abb pcm600:
Weather dry sunny temp 35c approximately Fault 132kv lighting arrestr and HV bush of power transformer 20/26MVA damaged
05etap, 15:33 -abb pcm600: 132kv CT side clamp
05etap, 15:34 -abb pcm600:
Counter of lighting arrestr
05etap, 15:34 -abb pcm600:
05etap, 15:35 -abb pcm600: Lighting arrestr
05etap, 15:35 -abb pcm600:
05etap, 15:35 -abb pcm600: Structure damaged
05etap, 15:36 -abb pcm600:
05etap, 15:36 -abb pcm600:
After fault jamper
05etap, 15:37 -abb pcm600:
05etap, 15:45 -abb pcm600: Analysis as per our senior most retired chief Engineer such type of fault occurres due to delay of lighting arrestr counter delay. These type of fault occurred in Pakistan time by time where lightning arrestr having counter are installed. Due to delay HV bush of power transformer also damaged
05etap, 15:50 – abb pcm600: Did the Hv bushing passed the lighting impulse test?
05etap, 15:58 -abb pcm600: At the time of manufacturing or now
05etap, 16:00 -abb pcm600:
05etap, 16:00 -abb pcm600: Bushing may damaged due to pressure of conductor
05etap, 16:48 – abb pcm600: Available 132kv surge arrester if required plz context 03214484444
05etap, 17:19 – abb pcm600: I wonder if you have the fault recorder of this lighting surge impulse on your relay
06etap, 15:30 – abb pcm600: Is there any lightening arresters in the top of transformers firewall/ other location ?
06etap, 15:32 – abb pcm600: What’s the fault in protection relay or fault recorder ?
07etap, 01:35 -abb pcm600: Ds agile documentations please
08etap, 18:06 – abb pcm600: Please guys how can I get cooling oil for a 1000 volt transformer
09etap, 16:44 – abb pcm600: What is the relay
saturation of IDMT curve in sepam T80 and S82 ?
09etap, 17:15 – abb pcm600: Let me check
09etap, 17:15 – abb pcm600: Sorry…no
10etap, 13:28 – abb pcm600: IMG-20200620-WA0004.

Any have experience In Reyroll Relays.! I need help how to change the “Out of service mode”.
10etap, 13:54 – abb pcm600″: IMG-20200620-WA0005.jpg (file attached)
Dear All,
We need to do 87L test, as you can see in secondary current to relay is very low 0.044A. We did secondary injection for GE L90 relay and found it doesn’t read 0.044A.
Value is fluctuating and getting stable at 0.1A.

please provide some solution.
11etap, 04:13 – abb pcm600″: Any ideas why the 51N protection of the REF615A relay operates in an almost constant time of 0.06 seconds
11etap, 04:13 – abb pcm600″: reviewing the operation curve the minimum operation time is 0.02 seconds
11etap, 04:15 – abb pcm600″: IMG-20200620-WA0006.jpg (file attached)
11etap, 04:17 – abb pcm600″: IMG-20200620-WA0007.jpg (file attached)
11etap, 04:21 – abb pcm600″: at least the first 3 tests would have given me the correct value
11etap, 04:37 – abb pcm600: check the other serting
11etap, 07:43 – abb pcm600″: Check the type of curve selected in relay
11etap, 07:43 – abb pcm600″: Whether it is definite time or IDMT
11etap, 07:53 -abb pcm600: 1 group setting might b clashing with another one,check all stage setting group wise.
15etap, 11:33 – abb pcm600 “: Work Is for Automation Visit in Kolkata. Just visit the site at Kolkata only people from Kolkata plz contact me..
15etap, 12:56 – abb pcm600: Please send me the details, I will help you
15etap, 12:58 -abb pcm600: Can I call you???
15etap, 13:04 – abb pcm600: Yes
17etap, 22:42 -abb pcm600“: A Power distribution full project including design of LV and MV component
17etap, 22:42 -abb pcm600“: https://www.researchgate.net/publication/342243379_Electrical_Works_For_A_Housing_Area
17etap, 22:59 -abb pcm600′: Niceee thanks
17etap, 23:00 -abb pcm600: This message was deleted
20etap, 11:10 – abb pcm600: https://youtu.be/q6RIJmqLVj0
20etap, 16:34 – abb pcm600: https://youtu.be/mAOYOZJVU3I
21etap, 03:21 -abb pcm600: 40mva x-mer tripped on differential during charging of 33kv feeder with Idr= 0.49pu, Idy= 0.50pu and Idb,= 0.53pu.
Both side LA has physically verified and found ok.
21etap, 06:34 -: Did you check the %of Harmonics during charging from the DR?
21etap, 06:35 -abb pcm600: I will check
21etap, 07:09 – abb pcm600″: please do stability test and after that examine the results.
24etap, 14:55 -abb pcm600“ left
26etap, 15:04 – abb pcm600: Hi, might anyone have the design book of transformers with CRGO steel core and amorphous metal core
26etap, 16:54 -abb pcm600: Please guide how to reset DR full alarm in DPR micom p442 Schneider electric
26etap, 16:59 – abb pcm600:
Maybe you can right click on the device and select supervise device
28etap, 21:44 – abb pcm600:
transformer-inspectiontestingwayne-smith.pdf
28etap, 21:54 – abb pcm600: 👍👍👍
29etap, 02:37 – abb pcm600: Thanks!!
29etap, 04:07 – abb pcm600: 👍👍👍👍

To join our protection relay WhatsApp group, please send interest on Whatsapp +989129613659https://elec-engg.com/whatsapp-group-for-protection-engineers/


29etap, 08:08 – abb pcm600″: Anyone have VALANCE book on “How to Test Breaker Failure Element Logic”
29etap, 10:54 – abb pcm600: Thanks a lot for sharing this useful book.
29etap, 11:10 -abb pcm600″: This message was deleted
29etap, 11:10 -abb pcm600″: This message was deleted
29etap, 11:10 -abb pcm600″: This message was deleted
29etap, 11:10 -abb pcm600″: This message was deleted
29etap, 11:10 -abb pcm600″: This message was deleted
29etap, 16:53 – abb pcm600: Big like for this
30etap, 11:52 – abb pcm600:
I have a problem in Micom P443 for Distance Protection. I have a problem in System Checks for Autoreclose,anyone can tell me what is the difference between CS1 Close Enable dan C/S AR Immediate ??
30etap, 12:35 -abb pcm600″: Cs1 close enable is the setting of sync check on which you want to recloser the cirxuit breaker like on Live Line Live Bus or Live bus Dead Line or Dead Line Dead Bus
30etap, 12:37 -abb pcm600″: If you enable c/s AR immediate then it means that if during the dead time system check conditions are met then it will reclose the breaker without waiting for the remaining dead time period,
30etap, 12:37 -abb pcm600″: Like for example if dead time is 1 sec
30etap, 12:38 -abb pcm600″: And system check conditions are met during 0.6 seconds of dead time ,then relay will give reclose command without waiting for the remaining 0.4seconds of dead time,
30etap, 12:39 -abb pcm600″: But you habe disables the system check conditions on shot1 that means it will reclose the breaker wothout looking into any system check conditions,
30etap, 12:39 -abb pcm600″: Sys check on shot 1 should be enabled too,
30etap, 15:20 -abb pcm600: Hi guys….
Any one can help to join any VFD & plc related group….!!!
30etap, 15:31 – abb pcm600: I’ld like to join one as well !!
30etap, 15:35 – abb pcm600: Hi Guys I have a question: what is the problem with a 3phases motor runned by A frequency driver, if I want to run it very slow for instance at at 4HZ normally it runs at a modulated Frquency variable between 50Hz and 0 but what happen to a very low frequenzy?
30etap, 15:38 – abb pcm600: I know that it will run slow, but it will warm up a lot right?… but more than that what wil it happen?… somebody some documentation to explain this fhenomen?
30etap, 19:01 – abb pcm600: Somebody help?
30etap, 20:56 – abb pcm600: It depends on the loading.. The higher its loading, more power needed to turn the output torque.. If you don’t have a load, just make sure your lower frequency setting has a minimal current to move the rotor..otherwise it will be overheat..
30etap, 20:57 – abb pcm600: Thanks.
30etap, 20:57 – abb pcm600: 👍👍👍
02etap 10:54 – abb pcm600″: How to solve this error
02etap 10:54 – abb pcm600″:
02etap 13:41 – abb pcm600″: I even reinstalled my windows not going, I checked internet settings also
02etap 19:37 – abb pcm600 “:
Automation-PFMEA.xlsx
02etap 19:37 – abb pcm600 “: Can any help me in this Programming
04etap 20:48 – abb pcm600 “: Does anyone have the know how we can develop HMI screen of operator name tag id selection in Schneider Vijeo Designer Basic HMI software
04etap 22:10 -h: Can Anyone suggest or provide link for low cost alternatives for moxa Uport 1150 type connectors with similar capabilities?
04etap 23:02 – abb pcm600:
USB to Serial converter
06etap 22:39 – abb pcm600: Hello
Any one have sft sav diagnostic software for sepam relay?
08etap 21:06 – abb pcm600 “: Does Anyone Have the knowledge of selec twix-2 PLC communication with Schneider hmi
08etap 22:44 – abb pcm600: Please have some one ever configured SEL 487B busbar protection ?
08etap 22:45 – abb pcm600: I need assistance please
08etap 23:28 – abb pcm600: hello follows the data sheet, unfortunately I can’t help much
08etap 23:28 – abb pcm600: 487B-1_DS_20200229.pdf (file attached)
487B-1_DS_20200229.pdf
08etap 23:30 – abb pcm600: The SEL Technical Support Line is available at +1.509.338.3838
09etap 11:37 – abb pcm600: hi
09etap 11:37 – abb pcm600: does anybody here has SUE3000 configuration tool
09etap 11:37 – abb pcm600: would you mind to share it
09etap 17:38 – abb pcm600: Thanks
10etap 21:12 – abb pcm600: Make money online buy watching videos,I did it and I earned 150 dollars, here is the link .All u have to do is to register and start watching.https://eolvideon.xyz/410125606693328/
10etap 21:35 – abb pcm600: Some example of End Fault Protection with SEL 487B??
11etap 15:05 – abb pcm600 was added
11etap 11:03 – abb pcm600: Make money online buy watching videos,I did it and I earned 150 dollars, here is the link .All u have to do is to register and start watching.https://eolvideon.xyz/410125606693328/
11etap 15:05 – abb pcm600 left
11etap 12:21 – abb pcm600: How does this guy get into this group? 🤷🏿‍♂️
11etap 14:15 – My Irancell Saeed Roostaee removed abb pcm600
11etap 20:12 – abb pcm600: STK-20200711-WA0011.webp (file attached)
11etap 20:12 – abb pcm600: STK-20200711-WA0012.webp (file attached)
11etap 21:11 – abb pcm600: This message was deleted
11etap 22:32 – abb pcm600: 🤷🏿‍♂️
11etap 22:32 – abb pcm600: 🤷🏿‍♂️
11etap 22:34 – abb pcm600: Any body can please share with ME Schneidsr Software SFT SAV?
15etap 17:33 – abb pcm600: IMG-20200716-WA0005.jpg (file attached)
Hello, could someone tell me what does this number mean 6000 of this RCD?
15etap 17:33 – abb pcm600: It can open currents upto 6000A
15etap 17:33 – abb pcm600: 6kA
15etap 17:34 – abb pcm600: Note it’s RCBO not RCD
15etap 17:34 – abb pcm600: Yep🤦🏼‍♂️😅
15etap 17:34 – abb pcm600: Thanks alot
15etap 17:34 – abb pcm600: What s the difference?
15etap 17:35 – abb pcm600: Because some tell me it is the max number of trips
15etap 17:37 – abb pcm600: RCBO stands for residual current circuit breaker. It can open faults upto 6000A. It can be used for short circuit protection as well as sensitive faults of 30ma.

RCD is residual current device. It’s used only to pick up sensitive 30ma faults. They can’t open full short circuit currents.

Think of RCBO as RCD+MCB
15etap 17:37 – abb pcm600: No it’s the rated fault level ..
15etap 17:38 – abb pcm600: 👍 thanks
15etap 17:38 – abb pcm600: Very useful.
16etap 20:35 – abb pcm600″: Follow me on Instagram of new account only for testing and technical related my I’d is “ELEC_TONIC”
16etap 20:49 – abb pcm600″: Hello everyone
We have the following problem with ER make DUOBIAS relay for Tranformer differential protection
16etap 20:50 – abb pcm600″: VID-20200717-WA0001.mp4 (file attached)
16etap 20:51 – abb pcm600″: Can anyone gudie what to be done with this
17etap 14:10 -abb pcm600“: 👉Capacitors protection
https://www.researchgate.net/publication/342243379_Electrical_Works_For_A_Housing_Area
18etap 05:33 – abb pcm600: Hi anyone have testing commissioning motor differential protection relay procedure please Sharing
18etap 10:57 – abb pcm600: Short circuit level for this device
18etap 13:04 – abb pcm600″: IMG-20200718-WA0002.jpg (file attached)
This kind of error shows in sverker 900 Megger relay test kit anyone have idea what is this
18etap 13:04 – abb pcm600″: IMG-20200718-WA0001


18etap 13:07 – abb pcm600: Maybe you could try to restart the device.And try to jumper each phase RST to neutral phase ..
18etap 13:09 – abb pcm600″:
Jumper are arranged like this is it ok?
18etap 13:10 – abb pcm600″: I have restarted kit but it not working
18etap 13:12 – abb pcm600: Jumper I1to neutral , then I2 to neutral and so on.
18etap 13:16 – abb pcm600: Simultaneously inject small current to monitor the device
18etap 13:16 – abb pcm600″: Voltage ports are also not working
18etap 13:17 – abb pcm600: How about the current ports ?
18etap 13:18 – abb pcm600″: They are also not working
18etap 13:37 – abb pcm600: Make sure when you start the device the knob selector in off position..
18etap 13:52 – abb pcm600: Check the fuses too
18etap 14:29 – abb pcm600″: How to check ot
18etap 14:29 – abb pcm600″: It
18etap 15:23 – abb pcm600″:
This fuse is ok
18etap 18:25 – abb pcm600″: Anyone have idea why this is not working
21etap 05:23 – abb pcm600″: Does anyone know if you can force or simulate voltage on an ABB relay? That is, without using a device like Omicron
21etap 07:11 – abb pcm600: someone help,how can i test GE L90 diff relay as a stand alone…without connecting with another one
21etap 07:52 – abb pcm600: You can only force digital outputs and simulate inputs. You can’t force analog signals such as voltage and currents. You need an external source
21etap 07:53 – abb pcm600″: Ok, thanks
21etap 07:55 – abb pcm600: I’ve never dealt with this relay but If it is for line differential, chances are that you’ll need two relays…the receiver and transmitter
21etap 07:57 – abb pcm600: But you can still use primay injection method to do the testing
21etap 08:09 – abb pcm600: Do you have to test line differential ?
21etap 08:09 – abb pcm600: This message was deleted
21etap 08:10 – abb pcm600: ?
21etap 08:10 – abb pcm600: You can go to setting , testing , channel test and loop back
21etap 08:11 – abb pcm600: Inject currents, relay will consider one current as local and one as remote
21etap 08:12 – abb pcm600: Thank you
21etap 08:34 – abb pcm600: Welcome mate
21etap 17:58 – abb pcm600:
Hello guys, i’d like to ask maybe some of you ever test this type of relay ?
21etap 17:59 – abb pcm600: Where we can find the tms
21etap 18:02 -abb pcm600”: I think tms is 2
21etap 18:03 -abb pcm600”:
21etap 18:03 – abb pcm600″: TMS is nothing but round dial
21etap 18:03 -abb pcm600″:
21etap 18:03 -abb pcm600″: Yess it is 2
21etap 18:03 – abb pcm600″: In this case it’s 2
23etap 12:50 – You added Fatima
24etap 05:46 – abb pcm600: IMG-20200724-WA0004.jpg (file attached)
for ref relay input problem anyone
24etap 05:46 – abb pcm600: Ref620
24etap 09:46 – abb pcm600: From the drawing, check the terminal point associated to this input. Isolate it then troubleshoot that circuit to find out where the “high/positive” signal is coming from
24etap 11:18 – abb pcm600: Y inside relay see this messages drawing not problem
24etap 18:20 – abb pcm600 left
25etap 20:37 – abb pcm600: Hi,
I am working with 2X300 MW thermal power plant in India and our 400 kv switchyard is having alstom MICOM P 441, REL 670 for protection also for generator we are having siemens make 7UM622 and MICOM p345.
Is there any standard which speaks of about frequency of relay testing.
What is your experience…
Please share
25etap 21:20 -abb pcm600: Normally frequency of Numerical Relay testing depends on the utility practices.

In our utility we do annually. But in my opinion it is not required annually.
Numerical relay can be tested 5 years once.
Scheme testing can be done annually.
25etap 21:20 – abb pcm600: Thanks
26etap 00:25 – abb pcm600: Anty one have crack version of ase IED smart or IED scout for IEC 61850 simulation?
26etap 10:46 – abb pcm600 “:
How to do scaling of this pressure sensor
26etap 11:17 -abb pcm600: these transmitters are of fixed range
26etap 11:17 -abb pcm600: you cant calliberate it
27etap 16:56 – abb pcm600:
Anyone this pcm600 this messages
27etap 17:08 – abb pcm600: 615 series?
27etap 17:19 – abb pcm600: RET620
27etap 17:19 – abb pcm600: try to use new project
27etap 17:19 – abb pcm600: if still like that
27etap 17:19 – abb pcm600: try to factory reset the ied
27etap 17:26 – abb pcm600: but if it still opetation
27etap 17:26 – abb pcm600: dont do
27etap 20:32 – abb pcm600″:
27etap 20:32 – abb pcm600″: How to connect GPS to this siemens relay 7VE632
27etap 20:36 – abb pcm600″: synchronization via IRIG-B
27etap 20:38 – abb pcm600: someone assist me with cpc 100 software,thanks in advance
27etap 21:19 – abb pcm600: You either need IRIG B port on GPS receiver….or you need NTP to IRIG B convertor
28etap 10:29 – abb pcm600: does anyone has any Training materials en software of cpc 100
28etap 12:02 – abb pcm600: Please find below the parameters you are expected to used as discussed with RTM;
Reactance = 0.2215 ohm/km
Inductance = 0.20808 ohm/km
Suseptance = 0.07573 ohm/km
Distance = 313km
28etap 12:02 – abb pcm600: Please how can i find the positive and zero sequence impedances from the above parameters thanks
28etap 12:07 -abb pcm600: 400 KVAR 90 UNITS
132KV CAPACITOR BANK
neutral CT 5/5
132kv CT 400/5
Capacitor protection or unbalance relay current setting? Relay type SPAJ 160 C
28etap 12:15 – abb pcm600: This message was deleted
28etap 12:21 – abb pcm600: Normaly Unbalance protection have one special other CT different from CT 132kv phase or CT neutral but if This CT 5/5A is just for SPAJ protection we ajust setting unbalance between 10 (..)20% In for nominal current this CT 5/5A
28etap 12:36 -abb pcm600: 👍
28etap 16:22 -abb pcm600: Please explain the working of reverse power relay at consumer end for the small hydro power plant of declared capacity 24.75 MW
29etap 10:21 – abb pcm600:
Application-of-Modbus-RTU-DNP3-and-IEC-61850-in-substation-protection-and-automation.pdf
29etap 10:21 – abb pcm600: Have everyone ever read about this book ?
29etap 10:22 – abb pcm600: Need some references about that topics
29etap 11:36 -abb pcm600: Nice one, thanks
29etap 12:09 – abb pcm600: Hello everyone. Does anyone have reference books for Earthing Adequacy study.
29etap 14:58 – abb pcm600: 👍
29etap 23:55 – abb pcm600: Hello Gents,

What is recommended Characteristic angle for Directional Earth Fault protection (67N) on SEPAM S42 relay based on following data:
Sepam relay is on closed loop network.
Sytem grounding: resistance grounded (Two NGR Prallelled: 2x800A: 1600A).
Type used for 67N on Sepam: Type-02 (the protection function uses I0 vector magnitude).
Residual Current input on Sepam: Calculation of Summation three phase current (not residual CT).
Your support will be really appreciated.
31etap 01:13 – abb pcm600:
31etap 05:20 – abb pcm600:
31etap 11:48 – Fatima: If anyone interested in ETAP discussion Whatsapp group, send ETAP to me on Whatsapp 🙏😊
Topics, ETAP software, Relay coordination, power system, industrial design
31etap 13:59 – abb pcm600: ETAP
31etap 17:54 -abb pcm600: ETAP
31etap 20:11 – abb pcm600 “: I want to know if my raw data for sensor is 0 to 32767 and I wanted it to show in HMI in the format of 0 to 100 bcoz if in system sensor by mistakly get faulty or I have to replace sensor and the sensor of any other company in my system, so due to this I can change from HMI raw data in the format of 0 to 100 is it is possible??
31etap 20:15 -abb pcm600:
Hello
Micom p-243 protect compressor after start 15 minutes then trip
The indication in local hmi (motor fault alarm )but in the protection relay no indication but became open position
When i go to the record i see this in the pic
31etap 20:15 -abb pcm600:
31etap 20:15 -abb pcm600:
31etap 20:24 -abb pcm600: I do isulation resistance for motor by using 5kv meggar the result was 4Gohm
31etap 23:09 – abb pcm600: Any contribution?!
01etap, 05:57 – abb pcm600: ETAP
01etap, 06:10 -abb pcm600: ETAP
01etap, 11:12 – abb pcm600: This message was deleted
01etap, 11:13 – abb pcm600: Etap
01etap, 12:11 – abb pcm600 “: Hello Guys. We are Providing Protection Data Management System
IPS-EPIS
If you need to discuss send IPS to me on my personal WhatsApp
01etap, 12:12 – abb pcm600 “:
01etap, 13:38 – abb pcm600: This message was deleted
03etap, 19:40 – abb pcm600 “: In HMI how to create operator name error
03etap, 20:07 – abb pcm600: PTT-20200803-WA0002.opus (file attached)
04etap, 19:45 – abb pcm600: It’s over Current …what’s your start motor current start pick and protection micom configuration …?
04etap, 21:47 -abb pcm600: Respected members, Please guide me how to carry out the Hi-Pot Test/Dielectric strength test for 22kV 3ph Breakers/Bus bar.
If the available source is DC for testing, how much voltage is to be applied and any references of the standard for the same.
Thanks in advance.
04etap, 21:51 – abb pcm600: Hi Fatima,
05etap, 10:03 – Fatima added abb pcm600
05etap, 10:06 – abb pcm600: Thank you Fatimah
05etap, 10:09 – Fatima: Welcome
06etap, 22:48 – abb pcm600 “: How to write scripting language for 0 to 50 Low and 50 to 100 high value in C programming for HMI
12etap, 10:50 -abb pcm600:
Is it possible to rectify at site. Please guide…
13etap, 10:57 – Elec Engg: Hello everyone,

13etap, 21:34 – abb pcm600: Hello, please i need assistance on nari pcs9611 relay
Its new, so when powered on it displayed sub supervision Alarms:
Alm-device
Alm -time sync .
How can I cancel
13etap, 21:40 – abb pcm600: ok
13etap, 21:41 – abb pcm600: set the time synchronization to off instead of sntp
13etap, 21:42 – abb pcm600: Under settings?
13etap, 21:42 – abb pcm600: under device config or communication
13etap, 21:42 – abb pcm600: Ok
14etap, 15:36 -abb pcm600: Does any have idea of Proof Testing of equipments?
14etap, 19:26 -abb pcm600″: STK-20200815-WA0000.webp (file attached)
15etap, 01:11 – abb pcm600 “: Any one interested in Protection Data management system? Text me.
15etap, 09:47 – abb pcm600 “: Sounds good. Many thanks to all who are interested to know more about Protection data management system . We are planning to go for life demo if you are interested text me and I will share the zoom link
15etap, 14:00 -abb pcm600: Hi interested
15etap, 14:36 -abb pcm600: Does anybody has ZX0 ABB seitchgear O&M.manual
15etap, 14:37 -abb pcm600: Especially Gas handling procedures
15etap, 14:37 – abb pcm600:
HB 600-05 en
15etap, 15:10 -abb pcm600: HB 605 Gas handling Manual for ZX0
15etap, 17:44 – abb pcm600:
18etap, 17:46 – abb pcm600: Hi ,
I have tested my lightning arrestor for 11KV after removing from line and the IR value was 400 meg.
Few minutes laters I have tested it again the value raised to 15 Gig.
What can explain that?

9etap, 15:20 – abb pcm600: Hello guys,
19etap, 15:20 – abb pcm600: Please i need the manual of siprotec 7SA87
19etap, 17:28 – abb pcm600:
RelionRelaySelectiontable_2NGA000141_ENc
19etap, 19:43 – abb pcm600: This message was deleted
19etap, 19:43 – abb pcm600: This message was deleted
19etap, 19:44 – abb pcm600: This message was deleted
19etap, 19:45 – abb pcm600: This message was deleted
19etap, 19:49 – abb pcm600: This message was deleted
19etap, 19:51 – abb pcm600″:
19etap, 19:51 – abb pcm600″: Hello everyone, could you help me about the function of the TC1 on the delta winding ?
19etap, 20:04 – abb pcm600: Its a current transformer for the winding temperature gauge
19etap, 20:55 – abb pcm600″: Thank you !
19etap, 21:16 – abb pcm600″: someone knows what is the difference between I> and I >>
19etap, 21:16 – abb pcm600″: ??
19etap, 21:18 – abb pcm600: I> is the short time protection setting and I>> is the instantaneous protection settings of overcurrent relay
19etap, 21:19 – abb pcm600″: Ok, Thank you
19etap, 21:20 – abb pcm600: Can somebody tell me what happened if the tripping coil resistance and closing coil resistance of vcb is same ..then thier is any impact on performance of vcb ?
19etap, 21:25 – abb pcm600: You can return to the datasheet of the circuit breaker and closing and tripping coil, you can find the standard values of the resistance of the trip and closing coil and compare it to the measurement
19etap, 21:26 – abb pcm600: I just want to know the theoretical ans. Behind this ..
19etap, 21:26 – abb pcm600: As a electrical engineering point of view
19etap, 21:30 – abb pcm600: https://www.linkedin.com/pulse/parameters-decide-value-coil-resistance-breaker-bharat-v
19etap, 21:30 – abb pcm600: Read this paper
19etap, 21:30 – abb pcm600: It is very helpful
19etap, 21:40 – abb pcm600: closing coil resistance is designed much less than tripping coil resistance to have a stronger magnetic field
19etap, 21:44 – abb pcm600: Yes I know it is designed ..but my question is ..if they are same then …what happened ?
19etap, 22:26 – abb pcm600 changed their phone number to a new number. Tap to message or add the new number.
20etap, 20:06 – abb pcm600: MAM,
20etap, 20:06 – abb pcm600: I would like to relay professional video training pack.I need your help.To take this training,Can you help me a little.
21etap, 12:54 – abb pcm600: hi
21etap, 12:55 – abb pcm600: does somebody here have some “how to configure modbus protocol in SEL relays” document or somekind like that?
21etap, 13:41 – Fatima: Replied privately
22etap, 11:18 – abb pcm600: Someone have a method statement of Testing CVT Tan Delta
22etap, 11:18 – abb pcm600: Do you need procedures
22etap, 11:19 – abb pcm600: yes
22etap, 11:19 – abb pcm600: Ok will send
22etap, 11:19 – abb pcm600: Your mail ID
22etap, 11:20 – abb pcm600: njorad@yahoo.com
27etap, 23:13 – abb pcm600 “: You now can book for online demo using this link
https://www.ips-energy.com/en/contact/book-online-demo/
31etap, 20:13 – abb pcm600: Hi friends,,
31etap, 20:14 – abb pcm600: Does any body have a project of RED670 relay.
31etap, 20:14 – abb pcm600: ?!
31etap, 20:14 – abb pcm600: Yeah …
31etap, 20:14 – abb pcm600: Can i have it please 🙏
31etap, 20:15 – abb pcm600: Ok … I’ll send the pcm600 files tomorrow …
31etap, 20:15 – abb pcm600: Anything in particular you are after !’vv
31etap, 20:15 – abb pcm600: ??
31etap, 20:16 – abb pcm600: Current line differential relays are fairly straightforward..
31etap, 20:17 – abb pcm600: Is there a difference ?!
31etap, 20:43 – abb pcm600: Anyone knows what is the problem when a source (power plant) transmit power to a substation, then the neutral current monitored in power meter is a bit higher normally…
31etap, 20:46 – abb pcm600: I know that It means that there is an unbalance current on each phase. But what else can be that causes of phenomenon..
31etap, 20:49 – abb pcm600: The P.F on phase R and S is lagging 0.9, but the phase T shows a leading P.F
02etap 20:56 – abb pcm600:
Hello guys, i need some understanding on this problem..
02etap 20:57 – abb pcm600: In case it’s internal fault, just assume that the 87 T relay and Ref relay will trip…
02etap 20:58 -abb pcm600: your understanding is correct
02etap 20:59 – abb pcm600: But apart from it, if primary Overcurrent (50/51P) works, it will trip the CB 150 kV and how avout the CB 20 kV ??
02etap 21:00 – abb pcm600: Is it required to trip the CB 20 kV too ?
02etap 21:03 – abb pcm600: 87T trip, REF not really, depend on the fault. PP fault or 3P internal fault wont initiate REF
02etap 21:04 – abb pcm600: yep… to isolate the power from LV side too, in case bus section in 20 kV side is closed
02etap 21:05 – abb pcm600″: Depends on the control scheme we use…in most of the cases we adopt if HV side CB trips on protection LV CB also gets trip
02etap 21:08 – abb pcm600: REF is more sensitive for earth faults in the differential zone
02etap 21:08 – abb pcm600: If it is an earth fault REF trips faster than Diff.
02etap 21:12 – abb pcm600: Okayy..thank you everyone for the answer..
02etap 21:14 – abb pcm600: I think that 20 kV CB will need to trip too to prevent reverse power from remanent voltage (power) at Bus 20 kV side
02etap 21:15 – abb pcm600: But if there is a remanent voltage in 20 kV side, is it possible to induced voltage in primary winding to create a current..
02etap 21:16 – abb pcm600: Since you have NGR…earth fault close to neutral may nit be detected by REF
02etap 21:16 – abb pcm600: Percentage of unprotected zone can be calculated based on relay settings and CT ratio
02etap 21:31 – abb pcm600: Yes..due to the resistance, the sensitivity will be limited..
02etap 21:40 – abb pcm600: Have everyone ever tried, to induced voltage on secondary winding of step down Transformer i.e. lets say 150/33 kV. How about the primary winding transformer, does it will generate a low current or a harmonic current
02etap 23:29 -abb pcm600: Actually fault moves towards source. In actuall LV will not trip because fault current will move towards source side(150kv) side but if intertrip function is available then LV 20kv side will trip too
06etap 18:27 – abb pcm600:
06etap 18:29 – abb pcm600: Anyone knows about the calculation to get the value of Z1 Sensit. Iph>1 ? 🙏🙏
06etap 18:29 -abb pcm600″: Fault current should be above this value to identify zone 1 or zone 2 faults
06etap 18:30 – abb pcm600: 👌I got it.. But how to get this value ..
06etap 18:33 – abb pcm600: Okay. I have found it was 1.2 x CCC / CT Ratio
06etap 18:42 -abb pcm600″: Thanks
06etap 18:43 – abb pcm600: Youre welcome bro 💪
06etap 19:18 -abb pcm600: CCC indicates which value please clarify I have doubt in this
06etap 19:31 – abb pcm600: Current Carrying Capacity
06etap 19:33 – abb pcm600: Of the conductor
06etap 19:36 -abb pcm600: Thank you
07etap 17:27 – abb pcm600: In Distance Relay
07etap 17:27 – abb pcm600:
Anyone knows the CB IS( In Service) Time function ??
07etap 17:30 – abb pcm600: Since I close my CB thenthe IS time starts to count to set AR Block
07etap 17:32 -abb pcm600″: If cb is manually closed than after this time CB will be considered in service and Auto Recloser function will be enabled too,
07etap 17:33 – abb pcm600: Oh i see
07etap 17:33 – abb pcm600: But why it AR block indication is appeared.
07etap 17:34 – abb pcm600: After the CB IS Time starts to count..
07etap 17:35 – abb pcm600:
Still strugling on this distance relay
07etap 17:43 -abb pcm600″: Because during CB IS time AR Function is disabled to block the AR on SOTF fault,
07etap 18:06 – abb pcm600: change to ABB REL670
07etap 18:07 – abb pcm600: What type of relay is this one
07etap 18:26 – abb pcm600: Hahaha..Need to be scheduled soon 🤗
07etap 18:26 – abb pcm600: P443 Micom
08etap 09:54 – Fatima added A1 5414r.
12etap 19:19 – abb pcm600: hi guys
12etap 19:19 – abb pcm600: does anybody here has p14d modbus register
16etap 14:18 – abb pcm600: Hey….who knows ZIV default password
16etap 14:18 – abb pcm600: thanks
16etap 14:37 – abb pcm600: Any ZIV relays specialist
16etap 19:47 – abb pcm600: Hello all, does anyone has a GRL 200 Toshiba Line Current Diff Manual Book ?
16etap 19:48 – abb pcm600: 🙏🙏
16etap 20:02 – abb pcm600: Four corner numbers 7931
17etap 12:04 – abb pcm600 “: Dear Sir/Mam
Our Specializations

  • Manufacturing of all types of Automation Panels, PLC Panels, SCADA Control Panels, Drives, VFD, Sensor, HMI, PLC Controller, Communication Cables,etc
  • All type of control panels as per customer requirements.

Thanks
Regards

Contact Us
Trividh Tech Solution
Mob. +918668859174
Telegram: @trividhautomationsales
Email: technical@trividh.co.in

Everything About Automation, Electricals, Instrumentation
17etap 13:17 – abb pcm600: Hello guys..i have a Zivercom relay for Tap changer…everything looks fine but its not Tapping who can assist tanks
18etap 12:12 – abb pcm600: is anyone familiar with Siemens Siprotec 4 7SD Line Current Differential relay? For example one end of the relay is select in Commissioning mode(test mode), will the remote end relay differential protection be in commissioning mode or test mode also? Thanks
18etap 13:55 -abb pcm600: Commissioning mode at one line end will not turn on commissioning mode automatically to other side..Plus commissions mode is completely different from test differential mode
18etap 13:56 – abb pcm600: Thanks for the explanation
18etap 13:56 – abb pcm600: Can you explain a bit more on the test differential mode?
18etap 13:56 – abb pcm600: Does turning the test differential mode at one end will also activate the test differential mode of the remote end?
19etap 08:08 – abb pcm600:
Anyone REM620 relay this message what problem please
19etap 18:33 – abb pcm600:
25etap 18:01 – abb pcm600: Any one has the actual standard IEEE 485 or an excel sheet?
25etap 18:02 – abb pcm600: I need to size substation batter charger please !!
25etap 18:48 -abb pcm600″: IEEE 485-2020?
25etap 19:20 – abb pcm600: Yes please ..
25etap 20:18 – abb pcm600″: Do you have an email that I can send it to?
25etap 20:27 – abb pcm600: Siddhartha.Majumdar@gmail.com
25etap 20:27 – abb pcm600: Thank you sir!!!
25etap 20:37 – abb pcm600: K
26etap 01:16 – abb pcm600″: Does anyone know what these signals are used for?
26etap 01:16 – abb pcm600″:
26etap 01:17 – abb pcm600″: Apparently they are permissive of Switches
26etap 01:17 – abb pcm600″: RECEPTION RRR, RRA, RRX and RRY
26etap 01:18 – abb pcm600″: the arrangement of the substation is as follows
26etap 01:18 – abb pcm600″:
26etap 14:39 – abb pcm600: Have anyone tested Cap bank differential protection in Siprotec 5 7SJ85 relay ??
29etap 16:33 – abb pcm600:
who can help please
29etap 16:33 – abb pcm600: This message was deleted
29etap 16:34 – abb pcm600: constantly getting this error while writing to the IED
29etap 16:42 – abb pcm600: delete the hmi page first
29etap 16:42 – abb pcm600: do the lisence update tool
29etap 16:42 – abb pcm600: okey
30etap 01:12 – abb pcm600:
30etap 01:13 – abb pcm600: Does any one hav software for this relay micom2.1
30etap 01:14 – abb pcm600: is this micom or ziv
30etap 01:14 – abb pcm600: This cant be Micom i doubt
30etap 04:46 – abb pcm600: Yes i need ziv and micom 2.1 both
30etap 04:48 – abb pcm600: I hav found micom software if any one can giv ziv software as well plz
02etap, 23:47 – abb pcm600:
In our substation incomer feeder is tripping at downstream and upstream without any fault when switching on outgoing feeders.
02etap, 23:47 – abb pcm600: Please suggest any idea to solve the above mentioned issues
03etap, 09:35 – abb pcm600“: What fault recorded by relay?
03etap, 11:13 – abb pcm600: There is no fault on relay but upstream and downstream is tripping when switching on any outgoing feeders.
03etap, 16:35 – abb pcm600:
Dear All members
We will very excited to present your our Test set Relay.
Product Details :The VEBKO AMT 105 Universal Relay Test Set and Commissioning Tool is the universal solution for testing all generations and types of protection relays. Its powerful six current sources (three-phase mode: up to 128 A / 400 VA per channel in AC) (one-phase mode: up to 64 A / 200 VA per channel in AC)with a nice dynamic range, make the unit capable of testing even high-burden electromechanical relays with very high power demands. The VEBKO AMT 105 Relay Test Set and Commissioning Tool is the best choice for applications requiring the highest capability, amplitude and power.
In addition The VEBKO AMT 105 have the ability of testing this instruments : Transformer,Circuit Breaker,Resistance,CT,CVT,Meter,RTD
03etap, 16:36 – abb pcm600: waaa….upto 64 Ampere….
3etap, 16:40 – abb pcm600:
Product Details :
The VEBKO AMT 105 Universal Relay Test Set and Commissioning Tool is the universal solution for testing all generations and types of protection relays. Its powerful six current sources (three-phase mode: up to 128 A / 400 VA per channel in AC) (one-phase mode: up to 64 A / 200 VA per channel in AC)with a nice dynamic range, make the unit capable of testing even high-burden electromechanical relays with very high power demands. The VEBKO AMT 105 Relay Test Set and Commissioning Tool is the best choice for applications requiring the highest capability, amplitude and power.
In addition The VEBKO AMT 105 have the ability of testing this instruments : Transformer,Circuit Breaker,Resistance,CT,CVT,Meter,RTD

Please don’t hesitate to contact me for furthers information
mail :kais.abdaoui@gmail.com
Web site: https://www.vebko.ir/?lan=en
03etap, 16:43 -abb pcm600: Can i ask how much the price??
03etap, 16:45 – abb pcm600: This single kit can test transformers, relays, cts, vts and breakers?
03etap, 16:51 – abb pcm600: Yes Mr Sir
For more information
YouTube channel: https://m.youtube.com/channel/UCwW2xv757_AZBXwpY8_gHsQ
06etap 18:10 – abb pcm600:
AMT105 is a universal solution to testing all types of protection relays and instruments such as power transformers, current transformers, potential transformers, capacitor transformers, circuit breakers, cable and RTD. This device is capable of testing all electromechanical relays and protection instruments and equipped with six 32 A current sources (64 a in 3PH mode, 128 A in 1PH mode), four 150V voltage sources (450V in single-mode), current and voltage combination cable, 8 analog binary inputs, 2 DC analog current and voltage inputs with high accuracy, 4 binary outputs, Dc voltage sources (212V). We can assure you that AMT105 is one of the most outstanding machines on the market, and our confidence in it is supported by our three-year-warranty.
06etap, 21:54 -abb pcm600“: This message was deleted
06etap, 22:04 – abb pcm600: battery voltage please ?
09etap, 20:29 – abb pcm600: guys
09etap, 20:29 – abb pcm600: does anybody here has acSELerator software from sel?
09etap, 23:05 – abb pcm600: Yes
09etap, 23:23 – abb pcm600: aaa…
09etap, 23:23 – abb pcm600: would you mind to share it here 😍😍😍
09etap, 23:40 -abb pcm600: Yes
09etap, 23:41 -abb pcm600: I will sent tomorrow
09etap, 23:48 -abb pcm600: Any circular regarding fare service life of various testing equipments in power sector.
12etap, 13:14 – abb pcm600:
Hi, has anyone every replace this mauell annunciator window tiles with a 3rd party tiles? or other alternative ? thanks….just looking for other price-reasonable alternative…
12etap, 14:30 – abb pcm600: Put a piece of paper
12etap, 14:46 – abb pcm600: ok thanks for the idea
14etap, 13:25 – abb pcm600″:
14etap, 13:25 – abb pcm600″: Hi Guys
We are facing this kind of rebooting issue with AREVA Micom P742 peripheral Unit for busbar protection. Anyone have any idea regarding this issue. How to overcome this??
16etap, 21:42 – Fatima: Protection Relay Discussion Group in Telegram

https://t.me/joinchat/Cmyg2FiXX-qlTYqyXQ_pjg
17etap, 15:03 -abb pcm600: Can we use 10 ac drive on 15 hp motor
17etap, 15:08 -abb pcm600: 12.5 hp drive on 15 hp motor
21etap, 17:24 – abb pcm600: Hi All, do you guys ground the shield of control cables at both end or only single end?
21etap, 17:37 -abb pcm600: PTT-20201022-WA0000.opus (file attached)
21etap, 17:38 – abb pcm600: Single end
21etap, 17:41 – abb pcm600: I see..thanks for your response. How about for CT VT Cable?
24etap, 10:48 -abb pcm600: Anybody know alind relay password please
28etap, 10:49 – Fatima added abb pcm600
28etap, 10:35 – abb pcm600: May I know would there be issue if we use a CT with high Burden (15VA for example) for a protection relay (microprocessor type). For old mechanical type i understand that the CT need higher burden to drive the armature
28etap, 15:51 – abb pcm600:
05etap, 14:40 – abb pcm600:
when i turn on generator in this panel my generator has unstable frequency but when i operate it on manualy the frequecy stabilize. what may be the cause of this?
05etap, 14:40 – abb pcm600:
here is my genset set.
05etap, 14:43 – abb pcm600: Is ur gen set is synch with other gen
05etap, 14:43 – abb pcm600: no sir.
05etap, 14:59 – abb pcm600: What is voltage
05etap, 15:01 – abb pcm600: plzz check the gain & other setting for ur operator panel
05etap, 15:03 – abb pcm600: 460v
05etap, 15:03 – abb pcm600: there is no probel with engine & gen set itself it is the only problem with operator panel feed back signal which will be generate as per setting
05etap, 15:06 – abb pcm600:
05etap, 17:44 – abb pcm600: It is wierd
05etap, 17:44 – abb pcm600: Cause freq regulation is in generator itself not in woodward
05etap, 17:47 – abb pcm600: yes kind of.
05etap, 17:47 – abb pcm600: we try to bleed fuel on generator. but nothing happend
05etap, 18:17 – abb pcm600: I thought Woodward only do parallel synchronisation
05etap, 18:18 – abb pcm600: And some protection functiona
05etap, 18:19 – abb pcm600: but are only using small loads thats why we dont sync. our generators
05etap, 18:24 – abb pcm600: I looked at the manual for easygen
05etap, 18:24 – abb pcm600: Actually there is a function frequency control
05etap, 18:26 – abb pcm600: I have same system
05etap, 18:27 – abb pcm600: But never got time to check every function in Woodward
05etap, 18:28 – abb pcm600: i do check some function but the configuation has a password. the management told me that the supplier has the access to its unit .
05etap, 18:30 – abb pcm600: Please, contact the supplier
05etap, 18:30 – abb pcm600: And post answer here
05etap, 18:31 – abb pcm600: yes wir.
05etap, 21:36 – abb pcm600: U can check the access code or password in the manual may be the manufacturer didn’t change the default password
07etap, 01:47 -abb pcm600: document_très_intéressant 📕ÉTUDE DES PROTECTIONS DES RÉSEAUX ÉLECTRIQUES MT (30 et 10 kV) PDF : 👇Télécharger_maintenant👇 https://bit.ly/3p1aJLm
09etap, 15:18 – abb pcm600″: does anyone knows about arc resistance and tower footing resistance value for 765KV transmission line.
10etap, 16:06 – abb pcm600 “: Be careful a huge Cyber attack is going around in whatsapp
10etap, 16:06 – abb pcm600 “: Don’t trust any one from your friend list if he send you a link or ask for any information call him first
13etap, 07:41 – abb pcm600:
13etap, 07:41 – abb pcm600:
13etap, 07:42 – abb pcm600:
13etap, 07:42 – abb pcm600:
13etap, 07:42 – abb pcm600:
13etap, 20:36 -abb pcm600:
30etap, 08:37 -abb pcm600”: Dear sirs

I need to disable goose controls in REF 615 ABB relay.Is it possible from HMI?
30etap, 15:52 – abb pcm600: Any expert in L&T emx3 softstarter
03etap 11:16 – abb pcm600 “: Any one required Schneider plc HMI or vfd
03etap 14:01 – abb pcm600: Anyone have Micom P632 Data Model Manager
03etap 14:46 – abb pcm600:
04etap 12:20 – abb pcm600: who can assist me with an ied scout thats licenced
04etap 15:44 – abb pcm600: REG630 how to testing method DOPPDPR function Power Angle setting anyone have formula
07etap 13:47 – abb pcm600: Hello..Could anyone be having transformer test guides preferably based on megger make test equipment?
13etap 11:36 – abb pcm600″,abb pcm600, abb pcm600 and abb pcm600 left
09etap 12:36 – abb pcm600: Pacis configurator from Schneider, can anybody have this software if yes kindly send me the link, it’s urgent please help me
09etap 13:37 -abb pcm600: Somebody have REX640 TERMINAL DIAGRAM??
09etap 14:23 – abb pcm600: Does anyone know how to choose zero sequence transformer
09etap 18:50 -abb pcm600: share mail id n which version u want?? SCE ?
10etap 00:21 – abb pcm600: biswajit@rsconindia.com
10etap 00:22 – abb pcm600: biswajit@rsconindia.com, any version, yes SCE
11etap 16:21 -abb pcm600:
In VAMP300 relay display LED continye glow without assign ,without mapping with DI points… what is the issue please kindly suggest!!
11etap 17:15 – abb pcm600: Vacancy: We have a requirement of service engineer for different IED configuration. Preferred candidate from West Bengal or Orissa
11etap 17:16 – abb pcm600: If interested kindly send me your resume.
11etap 18:03 – abb pcm600: Any lead also welcome
Those who want to change their role can inform me and inform the vacancies to your college circle, i give referal gift vouchar to our engineers. Share below message in all know electrical group, college group
15etap 09:43 – tdyt: Great thank you
17etap 12:02 -abb pcm600: This message was deleted
18etap 00:52 – abb pcm600: https://youtu.be/-Sl8oYRYQ8s
18etap 17:06 -abb pcm600″: This message was deleted
18etap 17:07 – abb pcm600: 👏🏻👏🏻👏🏻
18etap 17:11 – abb pcm600: 👌👍👍👍
18etap 17:13 – abb pcm600: Why is it deleted
18etap 17:17 -abb pcm600″:
(PPBES)Practical Protection Engineering Basic.pdf
18etap 17:19 – abb pcm600: Thanks
18etap 17:19 – abb pcm600: 🙏
18etap 17:21 -abb pcm600″: Pleasure ,
18etap 17:24 – abb pcm600: Thanks for this book…a very nice one
18etap 17:26 -abb pcm600″: Pleasure,
18etap 17:28 – abb pcm600: Thanks 👍👍👍
18etap 17:29 -abb pcm600″: Welcome,
18etap 18:11 – abb pcm600″: Fine book….thanks for sharing this.
18etap 18:14 -abb pcm600″: Welcome
18etap 18:17 – abb pcm600: Excellent
18etap 19:04 -abb pcm600″: Welcome
18etap 19:08 – Hemani: 👌🏼👏🏼
18etap 19:10 – Khetha“: This message was deleted
21etap 15:15 -abb pcm600: Need help in ABB RVC APFC Relay programming.
Mohamed badr: If any one have any video or PDF explain ISA three phase secondary injection
I need to configure some issues in REB500 software related to the renaming of Bay units.
If anyone have a license for REB500. Can help me please.
01etap11:13 – abb pcm600 left
31etap 12:00 – abb pcm600: ABB normally do not release that license which allows you to configure
31etap 12:00 – abb pcm600: The user license there isn’t much you can do with it.
31etap 12:17 abb pcm600”: Thanks for your response
How can I do now?
31etap 12:59 – abb pcm600: Contact ABB
01etap09:48 – abb pcm600:
01etap12:58 -abb pcm600: May the NEW YEAR bring you happiness, peace and prosperity. Wishing you a wonderful 2021 to you and your family members 💐💐💐
03etap12:48 – abb pcm600″: Hello everyone, I hope all are fine 👍
03etap12:48 – abb pcm600″: Kindly someone tell me that in C264 Relay, how to change sychro-check parameters and find the passwords.????
03etap12:58 -abb pcm600: Connect to Cat tool to these device n check network parameter
03etap18:09 – abb pcm600: https://youtu.be/-Sl8oYRYQ8s
05etap07:40 – abb pcm600:
Trying to read the setting but the reading takes some few hours .. Is there Any solutions ??
05etap09:39 -abb pcm600″: I assume some delays in the network..try connecting them one-to-one if possible..
05etap11:00 – abb pcm600: Try to reboot the relay
05etap11:45 – abb pcm600: what could be the problem if Generator Shuts Down on High or Over Frequency, Over Frequency Runaway
05etap11:47 – abb pcm600: If you are connected to the grid:

  • Burn the rotor due to induced currents.
    If you are in islanders mode:
  • damage the connected equipments
    05etap11:57 – abb pcm600: https://youtu.be/R0TbgyyNswE
    05etap12:21 -abb pcm600″: Thanks
    05etap12:46 -abb pcm600: Please resend this document (PPBES) Practical protection Engineering Basic.pdf
    05etap12:52 -abb pcm600″:
    (PPBES)Practical Protection Engineering Basic.pdf
    05etap12:53 -abb pcm600: Thank you.
    05etap13:00 -abb pcm600″: Welcome
    05etap13:53 – abb pcm600: is it ok to run a generator that varies 59.9-60.1 frequency ?
    05etap15:26 -abb pcm600: yup
    08etap14:23 – abb pcm600:
    08etap14:23 – abb pcm600:
    08etap14:24 – abb pcm600: Trying to read ABB RET 670, but the messages show up like this
    08etap14:24 – abb pcm600: Any insights of this problem
    08etap14:24 – abb pcm600: 🙏🙏
    11etap12:43 – abb pcm600: Doea anyone know how to add delay time in VT Fail ABB RED 670
    11etap13:42 -abb pcm600″: Not very sure but….Inconsistent state means the current values in pcm are not reflecting the ied values. If a read does not resolve this try to see if there is a new version of pcm.
    11etap16:50 – abb pcm600: https://youtu.be/0Yy8tO9h1Qs
    11etap16:50 – abb pcm600: https://youtu.be/0Yy8tO9h1Qs
    12etap20:28 – abb pcm600″: 132kV transformer HV breaker was close on NO load and LV breaker was open, but suddenly differential relay operate and give differential trip. In fault study, HV side current was 860 Amp. Somebody tell me that what could be reason??
    12etap20:30 -abb pcm600″: For how much time the transformer was on no load?
    12etap20:31 -abb pcm600″: 132/11.5kV ?
    12etap20:31 – abb pcm600″: Approximately 10 to 15 minutes
    12etap20:31 -abb pcm600″: MVA?
    12etap20:32 – abb pcm600″: 132/22 kV (wind power plant)
    12etap20:32 – abb pcm600: Not inrush current
    12etap20:32 -abb pcm600″: Yess
    12etap20:32 – abb pcm600″: Yes
    12etap20:32 -abb pcm600″: There must b some issue ,
    12etap20:32 – abb pcm600: So this is not inrush
    12etap20:32 -abb pcm600″: Do TTR and winding resistance,
    12etap20:35 – abb pcm600: If it is the new commissioned plant then the issue will be in relay setting otherwise check transformer winding…do the IR…
    12etap20:35 – abb pcm600″: I did excitation test @ 10 kV and results was OK.
    12etap20:36 – abb pcm600″: Plant is in operation from last 4 years.
    12etap20:37 -abb pcm600″: You will have to do TTR and winding resistance to diagnose the matter ,
    12etap20:37 -abb pcm600″: Hope you will get the problem by doing these tests,
    12etap20:37 – abb pcm600″: OK
    12etap20:38 – abb pcm600″: Thanks to all
    12etap21:13 -abb pcm600: Any mechanical protection PRD,BUCH has operated..Did u retrieved the fault records from relay..
    12etap21:14 – abb pcm600: TTR??
    12etap21:15 -abb pcm600: turns ratio test
    12etap21:20 – abb pcm600″: No any trip from mechanical protection.
    12etap21:21 – abb pcm600″: In fault record HV current was 860Amp and LV current was 0 amp
    12etap21:24 – abb pcm600″: Check the CT ratio adopted in the differential relay….and what was the differential current setting adopted and actual current during relay operated
    12etap21:38 -abb pcm600″: Transformer turns ratio
    12etap21:45 -abb pcm600″: HI 👋
    860AMP WAS SINGLE PHASE
    OR TWO PHASES
    OR
    IN 3 PHASES
    12etap21:47 – abb pcm600″: In 3 phase
    12etap21:49 -abb pcm600″: Did you check lighting arrester AT 132 KV SIDE
    12etap21:52 -abb pcm600″: Yes surge arrestor can also be damaged or weakened ,as you are using Yard CT for Differential protection,
    12etap21:54 -abb pcm600″: @923236933469 do also check your HV arrestors,
    12etap21:55 – abb pcm600: Can anyone help me in PACiS configurator
    12etap22:28 – abb pcm600″: Physically that was OK, for counter I will check
    12etap22:29 -abb pcm600″: Do hipot test of arrestors,might be differential tripped because of arrestors,
    12etap22:41 – abb pcm600: If u have secondary injection kit like omron or preja plzz do the secondary injection to know that there is no problem from the relay side…
    13etap10:30 – abb pcm600:
    13etap14:55 – abb pcm600: can i ask why my plc doesnt read flow
    13etap14:55 – abb pcm600:
    13etap18:49 – abb pcm600:
    13etap18:53 – abb pcm600: Check that analog signal is reaching from ur flow meter to plc?
    13etap18:54 – abb pcm600: Check 4 to 20 amp signal
    13etap18:54 – abb pcm600: let me do tommorow thank you sir . for tips and info
    13etap18:55 – abb pcm600: is this available for overseas?
    13etap18:56 – abb pcm600: Only for India
    13etap18:58 -abb pcm600″: PTT-20210113-WA0003.opus (file attached)
    14etap09:40 – abb pcm600: Hi, any update on the tripping ? curious to know…thanks
    16etap04:51 – abb pcm600: https://youtu.be/F-HYUYzFmmY
    19etap12:22 – abb pcm600: https://youtu.be/obHpYfl3SSA
    19etap12:22 – abb pcm600: Subscribe. All free
    19etap16:20 – abb pcm600″: Any one have relay test sheets for AREVA relays
    20etap17:39 – abb pcm600:
    What does this error means while connecting siprotec 07SJ6021 relay
    20etap17:39 – abb pcm600:
    21etap01:16 – abb pcm600″ left
    25etap10:48 – abb pcm600: Hello guys, does anyone know how to avoid distance trip when VT Fail occured on 3 phase in REL 670 ?
    25etap12:10 – abb pcm600 “: Any one has any material for Artificial intelligence application in Protection?
    25etap12:15 – abb pcm600:
    Pls help me how to install pcm 2.10
    25etap14:24 – abb pcm600: Strongly recommend installing on virtual machines
    25etap14:25 – abb pcm600: After 3~4 different versions they always conflict and give errors …
    25etap14:25 – abb pcm600: I run different virtual machines on esxi hyper visor
    26etap19:41 – abb pcm600:
    ZM02-START.pdf
    26etap19:43 – abb pcm600: I need help to analyze this Disturbance Fault Record whether it is due to Lighting or Flash ..🙏🙏
    26etap19:46 – abb pcm600: It was fault on Line Diff and Reclose on Phase R
    26etap22:19 – abb pcm600: Anyone Plz tell me,what is relay coordination and its functions,thanks
    26etap22:45 -abb pcm600″: Kindly send .cfg file
    26etap22:46 -abb pcm600″: Line auto-reclosed successfully?
    27etap01:27 – abb pcm600:
    WAVEWIN REPORT Disturbance Record GI CERME BAY SGMD II.rar
    27etap01:27 – abb pcm600: Yes Sir
    27etap17:12 – abb pcm600: This message was deleted
    27etap17:35 – abb pcm600: This message was deleted
    27etap17:36 – abb pcm600: This message was deleted
    29etap08:51 – oijoi: We have 50/1 5p15 CT installed on 33 kv feeder whos fault current initially was very less but now Power supplier has installed 50MVA transformer 11% impedance
    29etap08:55 – abb pcm600: And fault current is almost 8000Amps, I believe I need to upgrade protection CT in order to meet high fault current
    29etap08:55 – abb pcm600: Can anyone suggest
    29etap08:56 – abb pcm600: What’s the 33kv fault level ?
    29etap08:56 – abb pcm600: Now it is 8000 amps
    29etap08:56 – abb pcm600: Fault current level
    29etap08:58 – abb pcm600: 50 MVA transformer installed at state electricity board substation and we are consumers with 33 kv feeder voltage
    29etap09:00 – abb pcm600: 50MVA 220/33 KV star/ star connected transformer 11% impedance
    29etap09:01 – abb pcm600: Is the ct used only for over current and earth fault ?
    29etap09:01 – abb pcm600: Yes 50,51, 50G, 51G
    29etap09:04 – abb pcm600: Strictly speaking, I would put 200/1 5P40 2.5 VA
    29etap09:04 – abb pcm600: However if the relays have CT saturation detection, you could go lower.
    29etap09:04 – abb pcm600: What’s the relay being used ?
    29etap09:05 – abb pcm600:
    Micom P117
    29etap09:06 – abb pcm600: P127
    29etap09:07 – abb pcm600: Do you have the CT test results. In particular the DC resistance of the CT.
    29etap09:07 – abb pcm600: No sir
    29etap09:08 – abb pcm600: Can you give your consideration or calculations for this selection
    29etap09:08 – abb pcm600: 8000/200 =40.
    29etap09:09 – abb pcm600: So you need an accuracy limit factor of 40, with a low burden
  • https://elec-engg.com/wp-
  • 9etap09:09 – abb pcm600: You won’t need much burden as the relay is numerical and installed inside the switchgear
    29etap09:10 – abb pcm600: Got it Thanks
    29etap09:10 – abb pcm600: Noted
    29etap09:11 – abb pcm600: Your existing 50/1, 15 VA may actually work if you knew the DC resistance.
    29etap09:12 – abb pcm600: Do I have to check with CT testing kit??
    29etap09:12 – abb pcm600: I believe CT supplier should I have this information
    29etap09:13 – abb pcm600: Yeas if you have a test equipment (Omicron CR analyzer or similar) that should be easily possible
    29etap09:13 – abb pcm600: That’s possible, however normally the manufacturer will not specify the DC resistance for 5P/10P class act’s. No harm in asking them though
    29etap09:13 – abb pcm600: CT’s
    29etap09:14 – abb pcm600: CT Analyser
    29etap09:15 – abb pcm600: Ok I will check with him today, as I don’t have omicron kit available near by That the only option I have
    29etap09:15 – abb pcm600: How you coordinate DC resistance with fault current
    29etap09:20 – abb pcm600: Wait
    29etap09:20 – abb pcm600: I’ll write it down can’t type it it’s a bit of a process
    29etap09:21 – abb pcm600: Ok thanks
    29etap09:28 – abb pcm600:
    29etap09:29 – abb pcm600: So if Rct<= 1.75 ohm, you can use it 29etap09:30 – abb pcm600: For a 50/1 A ct this may be achievable. 29etap12:14 – abb pcm600:
    My suggestion will be , need to Replace 33 kv side CT with ,. 1000/1A, 5P10,15 VA
    29etap12:29 – abb pcm600: With this approach, I’ld reckoned checking the pick up values.

06etap 15:17 – abb pcm600: Ynynd1
06etap 15:18 -abb pcm600″: And tertiary (delta winding) is unloaded??
06etap 15:18 – abb pcm600: Yes, I agree too 😁
06etap 15:18 – abb pcm600: Yes. Its unloaded
06etap 15:18 -abb pcm600″: Then no issue transformer will follow system phase sequence,
06etap 17:17 – abb pcm600: Hmm i see thank youu
06etap 17:18 -abb pcm600″: We have situations like this ,
06etap 18:02 – abb pcm600: This message was deleted
06etap 18:10 – abb pcm600: Yeaabb pcm600..luckily 💪
07etap 20:21 – abb pcm600: https://vivosvip.xyz/hw/?v=20210205
08etap 11:42 – abb pcm600: IMG-20210223-WA0002.jpg (file attached)
What is the difference of IN-HV Deriv Angle and IN-HV Measd Angle on monitoring online
08etap 11:46 -abb pcm600″: Derived means the neutral current have been calculated by summation of IA, IB and IC where as measured means neutral wire of ct secondary is connected to neutral element of the relay, and it is actually being measured,
08etap 11:50 – abb pcm600:
08etap 12:11 – abb pcm600: What is dead zone in protection??
08etap 12:13 -abb pcm600: Dead zone is Zone between CT & Open CB
08etap 12:14 – abb pcm600: It’s the point not seen in the zone of protection that of a relay. If a fault occurs at this point, the relay will not issue a trip. Usually between CT and breaker
08etap 13:48 – abb pcm600: Oabb pcm600 i see..IN HV deriv is neutral vector calculation, meanwhile In HV measd is a neutral REF winding
08etap 13:49 -abb pcm600″: We cannot say it is neutral ref winding until we see the setting of the relay,
08etap 13:52 – abb pcm600: Hmm okay..setting of the wiring diagram right .
08etap 13:53 -abb pcm600″: Setting of the relay and schematic drawing depicting connection of the ct secondary wires with the differential reay,
08etap 13:53 -abb pcm600″: Differential relay*
10etap 17:07 -abb pcm600: Hi,what is different between Vk and Vk/2 in kneepoint explains please
10etap 23:55 -abb pcm600: VID-20210223-WA0003.mp4 (file attached)
12etap 14:15 – abb pcm600″: Some body have this software?? SEL-5030 acSELerator QuickSet Software,
12etap 14:16 – abb pcm600″: For SEL protection relays… Kindly share this software.
12etap 14:19 – abb pcm600: Did u try their website.
12etap 14:19 -abb pcm600″: You can easily download it from sel website by creating account
12etap 14:19 -abb pcm600″: Account should be of company oriented,
12etap 14:58 – abb pcm600″: Yeah, I created account on website but now they reviewing account. After that I can download software or manual etc.
16etap 15:46 – abb pcm600: IMG-20210223-WA0004.jpg (file attached)
18etap 10:18 – abb pcm600: Any one has relay setting calculation file with all details ?Plz do share in group,thanks
19etap 16:45 -abb pcm600: How can be calculate MDI
20etap 20:56 – abb pchttps://elec-engg.com/wp-content/uploads/2020/01/9IBA015362_720x540.jpg

To join our protection relay WhatsApp group, please send interest on Whatsapp +989129613659https://elec-engg.com/whatsapp-group-for-protection-engineers/

Electrical engineers can find us on WhatsApp, Likundon, Instagram, site and email.
To follow
And use the content described and easily talk to engineers around the world.
Electrical engineer Dr. Saeed Roostaee with his online training on using and working with relays will help you learn to work with relays in the shortest possible time and at a reasonable price.
Follow us on

Whatsapp +989129613659

Telegram
t.me/elec_engg

Instagram
instagram.com/elec_engg

Website
Elec-Engg.com
ProtectionRelay.com

Email
info@elec-engg.com

protectien relay m

07etap training, 20:16 – digsi 5: Thanks😌
07etap training, 20:22 – digsi 5: Thanks 👍👍
08etap training, 09:41 – digsi 5: Anybody have ppt on SIEMENS SAS for basic knowledge
08etap training, 11:06 – digsi 5: How to extract Alstom & ABB Relays settings into xml formats??
08etap training, 11:26 – digsi 5: IMG-20200710-WA0011.jpg (file attached)


08etap training, 11:39 – digsi 5: IMG-20200710-WA0012.jpg (file attached)


08etap training, 11:40 – digsi 5: xml is not available in S1 Agile 1.3.1
08etap training, 11:40 – digsi 5: Thanks for response.
08etap training, 11:54 – digsi 5: 👍🏼
08etap training, 12:07 – digsi 5: This message was deleted
08etap training, 12:07 – digsi 5: Any one have idea ?
Please share..
08etap training, 12:31 – digsi 5: Update version you will get latest format
08etap training, 12:56 -digsi 5: How to calculate capacitor in mfd
08etap training, 14:56 – digsi 5″: 👍👍👍
08etap training, 15:11 – digsi 5: Step by step distance quadrilateral characteristic for all zones how to draw. please give me any documents sir
10etap training, 13:23 – digsi 5: Please suggest Which one is better for bus voltage measurement Induction VT or Capacitive VT?
10etap training, 13:27 – digsi 5: Would selecting any of these two make any difference, especially in bus voltage measurements? I don’t think so..
10etap training, 15:15 – digsi 5″: Capacitive surpass Power Line Carrier (PLC) otherwise they mau consider cost on their design.
10etap training, 15:33 – digsi 5: Cost it seems IVT is more at higher voltages..
10etap training, 15:34 – digsi 5:
10etap training, 15:34 – digsi 5: Anyone?
10etap training, 16:07 – digsi 5 “: This online app will help you for cable calculation and selection.
10etap training, 16:07 – digsi 5 “: https://www.generalcable.com/eu/en/information-center/tools-applications/gc-app-low-voltage
10etap training, 16:22 – digsi 5: Thanks
11etap training, 12:10 -digsi 5″: Hello engineers
11etap training, 12:16 – digsi 5: Hello
11etap training, 12:16 -digsi 5: Dear friends I need transformers and motors and electrical panels erection documents..
11etap training, 13:06 -digsi 5″: Any one help me for 7sl86 distance with ug cable application
12etap training, 01:38 – digsi 5: Can anyone share how to use sverker for relay testing
12etap training, 01:53 – digsi 5: SVERKER900 Training
https://www.youtube.com/playlist?list=PLYTxYZDacFh5edoOPTZWKS_tGsdFXVSSD
RTMS with SMRT Training
12etap training, 01:53 – digsi 5: Sverker900 training 👆
12etap training, 02:24 – digsi 5″: Thanks eng مرتضى
12etap training, 09:49 – digsi 5: Thanks
12etap training, 19:28 -digsi 5: 😍 See this now xxxv.com-xxa.com
13etap training, 21:47 – digsi 5:
How to configure this gps. Does anyone have a procedure to configure this..
14etap training, 04:55 – digsi 5: S
14etap training, 04:56 – digsi 5: Give ur mail id
14etap training, 08:27 – digsi 5: saurabh.gupta830@gmail.com
14etap training, 08:48 – digsi 5: Can anybody share digsi training material pl…14etap training, 12:11 – digsi 5: Mail sent …material and configuration file
14etap training, 12:13 – digsi 5: Okay
Thanks a lot..
14etap training, 12:17 – digsi 5: Hi Admin
14etap training, 13:16 – digsi 5: Thank you
14etap training, 13:20 – digsi 5: Thank you!
14etap training, 15:13 – digsi 5“: Hello to all dear friends
Would you please recommend a book or reference for testing protection relays?
15etap training, 07:29 – digsi 5″: This one
15etap training, 07:29 – digsi 5″: Is good
15etap training, 07:57 – digsi 5″: Hi any one has any training materials for IEC 61850 configuration and testing. Please share. Thanks in advance.
15etap training, 09:43 – digsi 5: https://elec-engg.com/iec-61850-training-course/
15etap training, 09:44 – digsi 5: I used this training pack, very informative and helpfull 👌
15etap training, 10:49 – digsi 5″: Does it got configuration in IED scout?
15etap training, 11:42 – digsi 5: Yes
15etap training, 11:43 – digsi 5″: How much is the course?
15etap training, 13:44 – digsi 5: Contact @917303437524
16etap training, 19:33 – digsi 5: 5_6089106918020743388.pdf (file attached)
5_6089106918020743388.pdf
16etap training, 19:34 – digsi 5″: Thanks
16etap training, 20:02 – digsi 5″: thanks
16etap training, 20:14 – digsi 5″: Thanks for sharing
16etap training, 20:52 -digsi 5″: Thanks bro
16etap training, 21:27 – digsi 5: 👍👍
17etap training, 13:06 – digsi 5: Anyone have manual of ABB aux relay model RXPSU14n
17etap training, 13:06 – digsi 5: IMG-20200717-WA0010.jpg (file attached)
17etap training, 16:07 -digsi 5: 4 contacts.vcf (file attached)
18etap training, 13:33 -digsi 5′: IMG-20200718-WA0003.jpg (file attached)
Hai everyone plz anyone tell me what are this feeders 1. 11kv Substaion loop feeder with fiber optic cable. 2. 11kv Substaion loop feeder with pilot wire (send end supervision relay time). 3.11kv Substaion loop feeder with ( receive end supervision relay type)
18etap training, 19:57 – digsi 5“: hello
Can you please share this again as i am unable to download it
18etap training, 22:13 – digsi 5:
The_Relay_Testing_Handbook_Principles_and_Practice-h1_2557.pdf
18etap training, 22:25 – digsi 5“: Thanks
21etap training, 16:43 – digsi 5:
Please tell which terminals are to be used for Carrier Send & Carrier Receive?

21etap training, 16:46 – digsi 5″: this for scheme logic distance protection ?
21etap training, 16:46 – digsi 5: Yes
21etap training, 16:48 – digsi 5: From highlighted portion u can understand
21etap training, 16:48 – digsi 5: Sir, 1&2 for Carrier send and 5&6 for Carrier receive?
21etap training, 16:49 – digsi 5″:
21etap training, 16:50 – digsi 5: Thanks a lot !!
24etap training, 16:41 – digsi 5:
Can anyone tell me details of these terminals, it’s a ABB make ACB, SACE PR 121/p ( SACE Emax E2)
Open coil
closing coil
motor supply,
then Indication ckt
Contactors ckt,
24etap training, 19:06 – digsi 5:
this may help you.
24etap training, 19:07 – digsi 5: 1SDC200006D0209_EMAX EN.pdf (file attached)
1SDC200006D0209_EMAX EN.pdf

24etap training, 19:08 – digsi 5: hello Ankur Sir, Pls refer chapter#8 ( page#195, 197)
24etap training, 19:18 – digsi 5: Thanks Kunjan bhai👍🏻👍🏻
24etap training, 19:18 – digsi 5: Thanks 👍🏻
24etap training, 19:21 – digsi 5: 👍 😊
25etap training, 03:39 – digsi 5: Respected group members
I want to learn configuration of
sifang csc 162 distance and 326 differential relay
25etap training, 03:40 – digsi 5: Can anyone share their experience on above relays
28etap training, 16:56 – digsi 5: An off topic question
28etap training, 16:56 – digsi 5: Can any one please name a few line auto reclosure 11kv and 11kv and 33kV fault passage indicator manufactures based in India
28etap training, 16:58 – digsi 5: This message was deleted
28etap training, 16:58 – digsi 5: Can anyone give to solution of board change ABB REF542+ relay
28etap training, 17:51 – digsi 5: Which type of communication cable require for ABB make REF542plus ?
29etap training, 23:56 – digsi 5: What could be the issue that the Ready LED is not glowing?
29etap training, 23:56 – digsi 5:
29etap training, 23:56 – digsi 5: Ready LED of D400 is not glowing..and our SLDC ppl are not getting data of entire substation..
29etap training, 23:56 – digsi 5: Please suggest how to rectify the problem..
30etap training, 18:40 -digsi 5: If anybody have 220KV substation all equipment SOP for operation & Maintenance .Please share
31etap training, 11:49 – Fatima: If anyone interested in ETAP discussion Whatsapp group, send ETAP to me on Whatsapp 🙏😊
Topics, ETAP software, Relay coordination, power system, industrial design..

31etap training, 11:50 -digsi 5″: Hii engineers
31etap training, 11:50 – digsi 5: ETAP
31etap training, 11:51 -digsi 5″: Have any one idea about the overcurrent coordination between generator and generator transformer
31etap training, 11:57 – Fatima: Pls reply privately
04etap training, 17:23 – digsi 5: pls tell me how to decide Bus coupler CT ratio in 220 kV Double bus bar system?
04etap training, 17:36 -digsi 5: Need IEC 60623
04etap training, 17:36 -digsi 5: Pls share if any member has it
04etap training, 18:03 -digsi 5″: What is the busbar current rating
04etap training, 18:18 – digsi 5: quad moose
06etap training, 17:47 – digsi 5: Can anyone reshare the pdf for electrical notes
11etap training, 13:19 – digsi 5: Anyone who knows ziv relays plz contact me
11etap training, 13:23 – digsi 5: U want ziv relay person no?
11etap training, 13:23 – digsi 5: Yes i need some help on that
11etap training, 13:24 – digsi 5: Ziv Anand.vcf (file attached)
11etap training, 13:24 – digsi 5: Contact above service person..he will help you
11etap training, 13:30 – digsi 5: Thanks 😊
12etap training, 01:13 – Elec Engg: Hello everyone,
2etap training, 03:09 – digsi 5″: How to join PSCAD group?
12etap training, 07:26 -digsi 5: Substation automation. Please
12etap training, 08:00 – digsi 5: SAS WhatsApp group
12etap training, 08:17 – digsi 5: ETAP whatsApp group
12etap training, 08:49 – digsi 5″: ETAP WhatsApp group
12etap training, 08:49 – digsi 5″: SAS WhatsApp group
12etap training, 09:10 – digsi 5: Substation Automation & SIPROTEC & DIGSI Whatsapp group please
12etap training, 09:12 -digsi 5: SAS whatsapp group
12etap training, 09:13 – digsi 5: SAS WHATSAPP GROUP
12etap training, 09:13 -digsi 5: SAS whatsapp group
12etap training, 09:13 – digsi 5: Siprotec and digsi group please
12etap training, 09:14 -digsi 5: Substation Automation & SIPROTEC & DIGSI Whatsapp group
12etap training, 09:17 – digsi 5: ETAP whatsapp group
12etap training, 09:18 – digsi 5: Substation Automation & Protection Engr whatsapp group
12etap training, 09:18 – digsi 5: Substation Automation & SIPROTEC & DIGSI Whatsapp group
12etap training, 09:18 – digsi 5: ETAP WhatsApp group
12etap training, 09:18 – digsi 5: Substation Automation & SIPROTEC & DIGSI Whatsapp group
12etap training, 09:44 – digsi 5: Siprotec, Digsi 4, 5 group
12etap training, 09:47 – digsi 5: ETAP
12etap training, 09:48 – digsi 5: Substation Automation &, SIPROTEC & DIGSI and SCADA Whatsapp group please
12etap training, 09:51 – digsi 5: SCADA
12etap training, 09:53 – digsi 5: SAS
12etap training, 10:09 – digsi 5″: SAS
12etap training, 10:23 – Fatima: Please do not send here, to join grps read the rules then send the selected grp on my private Whatsapp
12etap training, 10:29 -digsi 5: ubstation Automation & SIPROTEC & DIGSI Whatsapp group
12etap training, 10:57 -digsi 5: Lakshmi Narasimhan mindia: SAS
12etap training, 12:40 – digsi 5: All groups
12etap training, 12:47 – digsi 5: Please add me in all groups as I am working in all field including the HVDC systems.
13etap training, 10:05 -digsi 5: please any one have sel 487v technical Manuel for negative sequence
13etap training, 16:48 – digsi 5: Hi, anyone knows ZIV scada??
13etap training, 17:19 – digsi 5: Can anyone send me Complete Design calculation PCC/MCC with 11KV / 0.415 V Substation.
14etap training, 01:36 – digsi 5: Can anyone share electrical notes latest version
16etap training, 09:41 – digsi 5: Substation Automation & SIPROTEC & DIGSI Whatsapp group please
16etap training, 16:11 -digsi 5: Hello guys i should to cables tray, 90 degrees, 60 degrees, 45 degrees and upsets and down set formula please help me
18etap training, 11:01 -digsi 5:
Assalamualaikum friends our generator after start display come like this why my friend’s please give solution
19etap training, 22:01 – digsi 5″: الريلاى GE 369
الباسوورد ناسيه
كيف أفتحه ؟؟؟
كيف الغى كل القديم و أعمل password جديد و الغى القديم ؟؟؟
19etap training, 22:03 – digsi 5″: I have Relay GE 369
The password is forgotten How do I open it ??? How do I delete the old one and make a new password and delete the old one ???
19etap training, 22:18 – digsi 5: Password reset is done in GE Canada only
19etap training, 22:30 – digsi 5″: STK-20200819-WA0001.webp (file attached)
19etap training, 22:33 – digsi 5″: STK-20200819-WA0002.webp (file attached)
23etap training, 17:31 – digsi 5: Can any one give me information on how much the Clearance for 132/33/11 kv windings and the tank for 63 or 90 MVA according to IEC? Or Company design? And if possible the discription how oil insulation process work according to this distance?
23etap training, 17:31 – digsi 5: Guide me plz.?
23etap training, 17:47 – digsi 5: Mean insulation between HV winding and tank
24etap training, 09:32 – digsi 5: anyone please share HVDC station Single Line Diagram..
26etap training, 17:53 -digsi 5″: Can any one of the engineer having p632 transformer differential protection calculations
26etap training, 18:25 – digsi 5: Share ur mail id..
I had calculations for p633
26etap training, 18:25 – digsi 5: P643
26etap training, 18:49 – digsi 5: P633 is for 3 winding transformer differential protection and P632 is for 2 winding one?
26etap training, 18:55 – digsi 5: I had dealed with 642 and 643
26etap training, 18:55 – digsi 5: Relays in transformer differential
26etap training, 18:55 – digsi 5: No idea on 63..series
26etap training, 19:02 – digsi 5: We are using P643 as 3-winding Transforner differential protection.
26etap training, 19:03 – digsi 5: And P-633 as Overall differential protection comprising Geberator, Generator Transformer and Auxiliary transformer
26etap training, 19:29 – digsi 5: K
26etap training, 20:21 -digsi 5″: sharan.jael@yahoo.com
26etap training, 20:21 -digsi 5″: Thanks
26etap training, 21:01 – digsi 5″: Could you please send me also?
6etap training, 21:04 – digsi 5: also pls share to suryanathc@gmail.com
26etap training, 22:19 – digsi 5: Any one have software for freja ver R03N
26etap training, 22:40 – digsi 5:
26etap training, 23:01 – digsi 5: 👍
26etap training, 23:38 – digsi 5″: رجاء بعد إذن الأدمن إضافة الرقم 👇👇
27etap training, 08:06 -digsi 5″: Thanks this very useful
27etap training, 08:07 – digsi 5: Thank You.
27etap training, 14:18 – digsi 5 “: Any one have document SLD for bay Reactor? Please share to me..thanks
27etap training, 17:23 – digsi 5″: Thanks
27etap training, 19:06 – digsi 5: Dear friends,
I am thulasiraman from chennai ( india )
I have 6 years experience in electrical testing engineer position
( 3 years india and 3 years gulf experience)
Now i am looking for job so please kindly help me for job… 🙏
27etap training, 20:41 -digsi 5: If anyone has REM615 backup file please share. christothomasijk@gmail.com
30etap training, 21:37 -digsi 5 changed their phone number to a new number. Tap to message or add the new number.
01etap training0, 19:48 -digsi 5′: Plz share any one modebus function codes
02etap training0, 10:25 – digsi 5:
Astrum…..any one have software for this converter
02etap training0, 10:29 – digsi 5: Type rs232 to usb converter drivers
02etap training0, 10:29 – digsi 5: In google
02etap training0, 10:43 – digsi 5:
02etap training0, 10:43 – digsi 5: Micom(areva) P121 software version is 6.H relay don’t connect with relay
02etap training0, 10:44 – digsi 5: Using Micom s1 studio and Micom s1agile
02etap training0, 10:45 – digsi 5: Anyone give to solution
02etap training0, 10:46 – digsi 5: I downloaded all data model still same error present
02etap training0, 11:09 – digsi 5: Change usb port of your laptop and try again
02etap training0, 11:14 – digsi 5: Go to device manager in laptop
02etap training0, 11:15 – digsi 5: Check driver settings
02etap training0, 11:15 – digsi 5: Assign as per p121 communication parameters
02etap training0, 13:03 – digsi 5: Is your OS Windows 10? Then it will be working without driver. To check whether it is working go to Device manager and see the listed Com ports.
02etap training0, 13:04 – digsi 5: I downloaded the software now its working
02etap training0, 13:07 – digsi 5: Windows 7?
02etap training0, 13:07 – digsi 5: No 10
02etap training0, 13:07 – digsi 5: Ok
02etap training0, 13:42 – digsi 5:
02etap training0, 13:42 – digsi 5: Please share this relay terminals details..
02etap training0, 13:42 – digsi 5: or manual ..
02etap training0, 13:55 – digsi 5: 12 and 34 are NO/NC contacts
02etap training0, 13:55 – digsi 5: 9 & 10 are current coil
02etap training0, 13:56 – digsi 5: 1,2
02etap training0, 14:01 – digsi 5: After coil operation…what the status of NO contac
02etap training0, 14:25 – digsi 5: Thanks !
02etap training0, 14:29 – digsi 5: 3&4 would normally be used for trip wiring as it has a trip isolator switch in series.. see the red tab on the grab handle of the relay..
02etap training0, 14:37 – digsi 5:
Pls tell about this relay terminal detaila
02etap training0, 16:24 – digsi 5: This particular model is self powered type. So terminals 5,6,7,8 are not used. Power is derived from CT terminals 9&10.
02etap training0, 17:19 -digsi 5: Please resend it also
02etap training0, 17:55 – digsi 5: Sorry missing above files☝️
02etap training0, 17:58 – digsi 5:
TRANSFORMER_PROTECTION_CIGRE.pdf
02etap training0, 17:58 – digsi 5:
Very Excited Course from ABB about Distance/EF protections.pdf

02etap training0, 18:41 -digsi 5: It doesn’t open.
03etap training0, 18:43 – digsi 5:
03etap training0, 18:43 – digsi 5: Can any one give settings for this transformer….. relay is. Areva P633
03etap training0, 19:26 – digsi 5: All what you need from this name plate are
1.Trxm rating 20000kVA

  1. Voltage levels 66/11kV
  2. Vector group YNyno
  3. CT ratio if you are using the bushing CT?
    03etap training0, 19:27 – digsi 5: No i want relay settings for areva p633
    03etap training0, 19:28 – digsi 5: I’m sorry I don’t have it but you can get it from the manual
    03etap training0, 19:30 – digsi 5: No problem…. actually protection engineer who is doing relay calculation can provide this
    03etap training0, 22:13 – digsi 5: Anyone pls me the digsi 4.93 serial number
    03etap training0, 23:15 – digsi 5′:
    Try this,
    03etap training0, 23:48 – digsi 5:
    Please brothers
    Any one have manuals for this temperature switch for transformer
    03etap training0, 23:49 – digsi 5:
    04etap training0, 14:09 – digsi 5: Please share any procedure to communicate with CSC 326 relay using CSPC software
    04etap training0, 14:37 – digsi 5: Match the communication parameters
    04etap training0, 14:39 – digsi 5:
    CSPC & DR USER GUIDE.pdf
    04etap training0, 19:00 – digsi 5: Can anyone share drive selection guide: I want to convert one dc motor drive to vvf drive
    04etap training0, 20:28 – digsi 5: Thanks a lot sir !!
    04etap training0, 20:55 – digsi 5:
    04etap training0, 20:55 – digsi 5: hi anyone, I have problems with this device, dont send out excitation voltage
    04etap training0, 20:56 – digsi 5: maybe, if I got a manual, I could check it and solve problem
    04etap training0, 20:57 – digsi 5: Siemens 6RU3030-7AA
    06etap training0, 11:32 – digsi 5: Please share Secure Premium 100 meter manual.
    06etap training0, 11:40 – digsi 5:
    Premier_300_User_Manual.pdf
    06etap training0, 11:47 – digsi 5: sir, Premier 100 please..
    06etap training0, 12:00 – digsi 5: sorry, i don’t have premier 100 series manual
    06etap training0, 12:23 -digsi 5: I need Secure Prodigy meter manual. Can anyone share please?
    06etap training0, 18:18 – digsi 5: okay sir
    08etap training0, 10:30 – digsi 5: What is the standard followed for 132 kv cable ampacity calculation?. ( Installation method above ground).
    08etap training0, 11:19 – digsi 5: This message was deleted
    08etap training0, 12:50 – digsi 5: Dear members,
    08etap training0, 12:51 – digsi 5: i required paper presentation of -IEEE Std. C57.109
    08etap training0, 12:51 – digsi 5: hope any one can help m
    08etap training0, 22:52 – digsi 5:
    “Anyone can use TRIZ anywhere anytime.”

09etap training0, 22:45 – digsi 5: Anyone please share Operating time formula for Normal.Inverse 1.3 seconds curve..
09etap training0, 22:59 – digsi 5: this is for Normal Inverse 3 seconds curve i think
09etap training0, 23:03 – digsi 5: sorry i didnt get ?
09etap training0, 23:09 -digsi 5: In case of 1.3 inverse curve instead of 0.1414 take 0.0613 value should be used.
09etap training0, 23:10 – digsi 5: Thanks a lot👍👍👍
09etap training0, 23:11 – digsi 5: This message was deleted
09etap training0, 23:14 – digsi 5: Does Overcurrent Highset setting for feeder depends on Transformer capacity in substation?
09etap training0, 23:18 -digsi 5: Suppose bus fault current 12 KA, and no of connected 3,den 4ka per tr, 400O o/ c high set. Instantaneous
09etap training0, 23:21 – digsi 5: You are very correct in order to preserve the transformer life span
09etap training0, 23:21 – digsi 5: we have 132/33 kV and 220/33 kV substations with 33 kV Feeders…one of my friend told Overcurrent Highset depends on Transformer capacity..
09etap training0, 23:24 – digsi 5: how to decide oc highset pls tell?
09etap training0, 23:24 – digsi 5: any thumb rules pls?
09etap training0, 23:25 – digsi 5: The sum of all the feeders load must be equal to your transformer LV capacity
09etap training0, 23:26 – digsi 5: it depends on the load on each feeder
09etap training0, 23:42 -digsi 5: See bus fault current frst u hv 2 calculate
09etap training0, 23:43 -digsi 5: For both the cases
09etap training0, 23:43 -digsi 5: Den divided it by no. Of tr
09etap training0, 23:43 -digsi 5: Make it ur hv o/c high set
09etap training0, 23:44 -digsi 5: Tr mva/ tr percentage impeadence.. Highet fault mva for ur transformer
09etap training0, 23:45 -digsi 5: Pm me.. For ur query
10etap training0, 12:09 – digsi 5:
Please tell how to reset MJT314 relay password..
10etap training0, 12:44 – digsi 5: We also faces difficulty with password of this relay. YouTube videos did not help.
10etap training0, 12:45 – digsi 5: If anybody could help
10etap training0, 15:33 -digsi 5: Dear Sir’s,
How can we reduce tripping of transformer due to insrush current.
10etap training0, 15:33 -digsi 5: Transformer 10MVA,66/11KV
HV side CT ratio 125/1A
LV side CT ratio 800/1 A
Relay Micom P642
10etap training0, 15:33 -digsi 5:
10etap training0, 15:34 -digsi 5: Settings of harmonic
10etap training0, 15:45 – digsi 5: If I’m not wrong, in modern transformer because of core material , the Inrush current harmonics are sometimes less than 20% of fundamental frequency component due to which differential relay operates. So, we can keep the setting at 15%
10etap training0, 15:45 – digsi 5: For second harmonics we can keep this at 15%
10etap training0, 21:04 – digsi 5:
10etap training0, 21:04 – digsi 5: anyone knows passwords to change settings?
10etap training0, 21:04 – digsi 5: 000000
10etap training0, 21:05 – digsi 5: thanks, I will try it
11etap training0, 22:21 – digsi 5: please tell what is the general delay time used for Overcurrent or Earth Fault Highset protection?
12etap training0, 01:15 – digsi 5″: Depend on your coordination
12etap training0, 02:08 – digsi 5″: Zero
12etap training0, 06:49 – digsi 5: 100msec
12etap training0, 06:49 – digsi 5: To allow line zone 1 to clear fault first
13etap training0, 18:11 – digsi 5: hi, anyone has a ZIV RELAY course about programming its logical control and interlocks? I need to understanding completely but is not possible only using manual brand, located in their website. Thanks
13etap training0, 22:48 – digsi 5:
13etap training0, 22:48 – digsi 5: Any one faced this problem while adding relay to iec station in sip5?
14etap training0, 12:28 – Fatima added digsi 4
15etap training0, 08:38 -digsi 5: If anyone having sepam relay thermal calculation sheet please share with me.
Mail : christothomasijk@gmail.com
15etap training0, 11:16 – digsi 5:
15etap training0, 12:33 -digsi 5: If CT gets saturated .what is solution after CT get’s saturated.We want to replace CT or any other solution
15etap training0, 12:36 -digsi 5″: CT secondary current flow to secondary winding
15etap training0, 12:36 -digsi 5: Please explain in detail
15etap training0, 13:00 – digsi 5: How are confirming that CT got saturated?
15etap training0, 13:01 -digsi 5: Sir for knowledge purpose if CT gets saturated in future
15etap training0, 13:03 – digsi 5: This message was deleted
15etap training0, 13:04 – digsi 5: This message was deleted
15etap training0, 13:07 -digsi 5: If in future we observe these types of problem how can we overcome with these types of problems.
15etap training0, 13:52 -digsi 5′: Which purpose bypass resistor used in modbus communication ??
15etap training0, 13:53 – digsi 5″: What is the burden of your CTs?
15etap training0, 13:56 – digsi 5: Saturation is purely a magnetic property issue …
So there is no alternative solution to do corrections in the circuit ..rather than core replacement.
15etap training0, 13:58 – digsi 5″: You need not replace your CT there are ways to demagnetise the ct
15etap training0, 13:59 – digsi 5: Dear Mebin
Can you explain in detail the theory of core saturation in ct ‘s
15etap training0, 14:00 -digsi 5: How can we demagnetise the CT
15etap training0, 14:01 – digsi 5: We had followed demagnetisation in transformer ..whenever we got erroneous values while testing dc winding resistance
15etap training0, 14:05 – digsi 5″: The easiest way to demagnetize a CT is to apply test current at a level that approaches it’s excitation ‘knee’, then
slowly decrease the input current to zero.This can be done with secondary excitation or primary current injection.
15etap training0, 14:07 – digsi 5″: I think some tester offer this option
15etap training0, 14:10 – digsi 5″: Like omricon ct analyzer
15etap training0, 14:10 – digsi 5″: Can you explain why you need to replace your ct
15etap training0, 14:16 -digsi 5: What is the solution of these types of problem
15etap training0, 14:22 – digsi 5: Anyone having method Statement for how to create logic for Sepam Relay using SFT2841
15etap training0, 14:45 – digsi 4: Engineering is not only a study of 45 subjects but it is moral studies of intellectual life- Prakhar Srivastav
(𝙃𝙖𝙥𝙥𝙮 𝙚𝙣𝙜𝙞𝙣𝙚𝙚𝙧𝙨 𝙙𝙖𝙮).?
15etap training0, 17:29 – digsi 5:
15etap training0, 17:29 – digsi 5: we are getting above error when communicating with RET650…Please tell what could be the problem?
15etap training0, 17:29 – digsi 5: Roll back package software needs to be updated using Update manager of PCM600
15etap training0, 17:34 – digsi 5: Thank you sir, I will try
15etap training0, 17:50 – digsi 5: sir, I couldnot find the Roll back package software..pls tell me where will it be
15etap training0, 19:42 – digsi 5: It’s in update manager, select relevant relay IED connectivity package. In that package, there is one rollup package that’s automatically installed
15etap training0, 22:28 – digsi 5: hi everybody, It is possible anyone has ptl omicrom template for Ingeteam relays
15etap training0, 22:29 – digsi 5: PZ1000, PL300, PD300, PL70.thanks in advance
15etap training0, 22:50 – digsi 5: 33 kV ABB circuit breaker Trip coil and close coil have a PCB connected to it..Pls tell what is use of that PCB?
15etap training0, 23:00 – digsi 5: I think PCB meant for capacitive tripping device CTD
16etap training0, 00:02 – digsi 5: CTD separate unit is present sir
16etap training0, 00:03 – digsi 5: This message was deleted
16etap training0, 00:04 – digsi 5: black colour portion in above image
16etap training0, 00:06 – digsi 5:
16etap training0, 05:14 – digsi 5: Check the drawing
16etap training0, 05:15 – digsi 5: Share if available
16etap training0, 08:40 – digsi 5:
16etap training0, 08:41 – digsi 5: While Exporting,
Icd from Abb relay -PCM 600
the icd file in Browser,
showing TEMPLATE
any knows how to solve

16etap training0, 09:14 – digsi 5:
Drawing of ABB breaker
16etap training0, 09:14 – digsi 5: I have shared sir
16etap training0, 09:47 – digsi 5: Anyone worked with
ABB
ICD file, ??????
16etap training0, 10:16 – digsi 5: In scheme ..no drawing of pcb…the electronic ckt pcb meant for coil protection purpose / to safe guard coil.
As coil is designed for short time not for continuous.
16etap training0, 11:20 – digsi 5: what kind of protection is used sir?
17etap training0, 13:46 – digsi 5: what are the steps to be followed when synchronizing new 220 kV Transmission Line to a existing 220 kV Bus?
17etap training0, 13:47 – digsi 5: Please tell
19etap training0, 09:30 – digsi 5: Anyone have WINCC script for addition of tag and display on HMI screen.
19etap training0, 18:20 – digsi 5:
This is 220 kV ABB make LTB245E1 type circuit breaker..Please tell what is the use of S7-A circled in above figure
19etap training0, 18:52 – digsi 5: Did you lookup S7 in legends?
19etap training0, 18:57 – digsi 5″: This message was deleted
19etap training0, 19:19 – digsi 5: I think you could find working philosophy in breaker manual
19etap training0, 19:19 – digsi 5: I dont understand its function,
19etap training0, 19:22 – digsi 5:
Anyone has settings file from these ingeteam relays? Thanks
19etap training0, 20:14 – digsi 5: It is mentioned Blocking switch
19etap training0, 20:14 – digsi 5: but the function of it is not mentioned anywhere?
19etap training0, 20:14 – digsi 5: This message was deleted
19etap training0, 21:48 – digsi 5″: For emf voltage discharge
19etap training0, 21:49 – digsi 5″:
They are opposite
19etap training0, 21:52 – digsi 5: I think they are for anti pumping system , isn’t it ??
19etap training0, 22:00 – digsi 5: Antipumping will come only in the Closing path.. This is an AC motor (Spring charge) circuit I think.
19etap training0, 22:01 – digsi 5: Spring charge also need to cut of , so I thought
19etap training0, 22:08 – digsi 5: Motor Cut off will be via Q1 contacts in series.. S7 contact is, like AN said, for discharging stored EM energy in the motor winding..
20etap training0, 09:17 -digsi 5: Anyones knows how to download cid file from sepam relays and how to do goose configuration?
21etap training0, 18:00 – digsi 5: Kindly Share anyone Having IEC Documents.
22etap training0, 01:46 – digsi 5:
22etap training0, 01:47 – digsi 5: hi, anyone has a manual for this relay
22etap training0, 01:47 – digsi 5: Google says, it not exist
22etap training0, 22:20 – digsi 5″: Hello guys, please how do I program the LED of ABB REF615.
22etap training0, 22:20 – digsi 5″:
22etap training0, 22:21 – digsi 5″: My main challenge is to change the parameter setting from false to true.
22etap training0, 22:21 – digsi 5″:
22etap training0, 22:21 – digsi 5: Any one pl suggest whatsapp group for plc programming
22etap training0, 22:24 – digsi 5: Hello colleagues, I have question, in case there is a fault on 33kv or 11 kv side is there any impact on 132kv side protection equipment? Mean did the protection will sense the fault?
22etap training0, 22:26 – digsi 5: overcurrent relays on 33kv fron TP, maybe send a trigger
23etap training0, 00:58 – digsi 5″: From application configuration
23etap training0, 01:01 – digsi 5″: Yes 132 side will sense the downstream faults but it will work as backup protection for downstream protection
23etap training0, 07:22 -digsi 5: Dear all, in abb REM 615 RELAY, HOW WE CHANGE NO OF HOT START FROM 1 TO 2, WHICH PARAMETERS OF STPPMSU HAVE TO CHANG,PLEASE EXPLAIN
23etap training0, 17:14 – digsi 5:
I need this IEEE paper. Please help.

23etap training0, 18:58 – digsi 5: Use “scihub” website
24etap training0, 19:17 – digsi 5:
24etap training0, 19:18 – digsi 5: This is relay name or some other?? Please advise
24etap training0, 19:33 – digsi 5: Those are s
sepam relay
model nos
24etap training0, 19:39 – digsi 5: Thanks..

Is anyone having these relay manuals.
24etap training0, 20:08 – digsi 5: U can find all manuals in www.se.com
24etap training0, 21:44 -digsi 5: I think these are sepam 80 series. All these models comes under sepam 80 series, so u can refer sepam 80 series manual….
24etap training0, 21:45 -digsi 5:
Sepam-20-40-60-80.pdf
24etap training0, 22:06 – digsi 5: Hi Guys

How to calculate phase sequence angle in cable
24etap training0, 23:00 – digsi 5: 👍🏼
26etap training0, 16:40 – digsi 5:
Hi…. Anyone pls explain how to set the power calculation for reverse power relay…
26etap training0, 23:35 – digsi 5: is there any good.group like this on Power electronics?
27etap training0, 20:01 -digsi 5: How to download CID file from Sepam 80 series relay ??? If anybody knows please tell me
27etap training0, 21:36 – digsi 4: How to calculate size of earthing cable for DCS or PLC???
29etap training0, 19:51 – digsi 5: Hi Please guide as to how to fix this error.
29etap training0, 19:51 – digsi 5:
29etap training0, 19:52 – digsi 5: Services
29etap training0, 19:53 – digsi 5: SQL SERVER MAKE MANUAL START
29etap training0, 19:53 – digsi 5: Then open PCM Again
29etap training0, 19:58 -digsi 5: Please reply this experts
29etap training0, 20:00 -digsi 5: 1.press windows +R
2.type services.msc and enter
3.right click on SQL server (PCMSERVER) AND THEN START
30etap training0, 10:38 – digsi 5:
30etap training0, 10:39 – digsi 5: It is showing like this
30etap training0, 10:39 – digsi 5: when i start services
30etap training0, 12:08 – digsi 5: Reinstall the
Sql server 2014
30etap training0, 21:38 – digsi 5: Please can anyone help me with the primary impedance R1 + jx1/ km and R0 +jx0/km value of a Bear conductor ASCAR 250mm² with diameter of 23.45mm
01/etap training, 02:41 – digsi 5″: Hello guys! Anyone working with GE Multilin D30? I have relay that seems to be unconfigured on distance. Backup OC and EF are enabled but seems no contact is assigned for tripping though it shows indication during testing.

  • 50/51, 50N/51N
    01/etap training, 11:31 – digsi 5″: Power Swing Block is used and activated in Distance Relay to block its operation in case of Swing period disturbance
    01/etap training, 11:35 – digsi 5″: It’s not about definition. I want abc concerning enervista.
    01/etap training, 14:04 – digsi 5: Emanuel start reading D30 manual…its very clear on the protection functions..
    For configuration point of feel free to contact me
    01/etap training, 16:12 – digsi 5″: Thanks
    02/etap training, 16:22 -digsi 5: What should be OLTC AVR relay PT Lower and raise voltage settings.
    02/etap training, 22:06 – digsi 5:
    Secure Premium 300 energy meter is showing like this in the parameters..please tell what is its meaning?
    02/etap training, 23:55 -digsi 5″: CT low means very less amps detected by ct
    03/etap training, 00:53 -digsi 5: What is the meaning of VT polarity
    03/etap training, 01:02 – digsi 5″: VT polarity mean instant of increasing live terminal to positive is the same instant of increasing live terminal in secondary to positive
    in this case polarity is good and this secondary terminal is x1 and x2 is grounded
    But if vice versa x2 become live and x1 is grounded
    For VT polarity Test the same ways of CT polatity Test
    03/etap training, 01:20 -digsi 5: Thanks alot
    03/etap training, 01:25 – digsi 5″: Is it effect relay operation
    03/etap training, 01:52 – digsi 5″: Ofcourse , if this relay is Directional or Distance or Reverse power Relays and also if powering measuring device as kwh meter
    03/etap training, 07:52 – digsi 5: thank you sir
    03/etap training, 07:56 – digsi 5: will anyone please share ABB/ ALSTOM/GE/SCHNEIDER/SIFANG/NR Substation Automation ppts? I am willing to pay nominal fee for them.
    03/etap training, 09:23 -digsi 5: What we have to check if transformer tripped in
    03/etap training, 09:40 – digsi 5″: DGA, Insulation, Ratio, Magnetic balance and Winding Resistance
    03/etap training, 10:27 – digsi 5: Hi guys, do you Know where i could to find bibliografy for protection for photovolics systems conected on grid?
    03/etap training, 10:57 – digsi 5: I need to know a siemens V4 relay can work as a time source for micom relays
    03/etap training, 10:57 – digsi 5: Thanks
    03/etap training, 14:43 – digsi 5″: شكرا ياباشا مهندس محمد
    03/etap training, 18:42 -digsi 5: ???
    03/etap training, 20:04 – digsi 5: Magnetising current, Short circuit impedance test of transformer are also important to check for any deformation of windings
    03/etap training, 20:05 – digsi 5: Turns ratio test and DC resistance test of winding.
    03/etap training, 20:06 – digsi 5: SFRA test is also one of the diagnostic test but it’s not done in most of the companies
    03/etap training, 21:55 – digsi 5″: Do you mean the bandwidth (this determine when the tap to shift up/down)?
    04/etap training, 00:14 -digsi 5:
    04/etap training, 08:35 -digsi 5: Yes
    04/etap training, 16:55 – digsi 5:
    Powersp_201004_131735.pdf
    04/etap training, 18:23 – digsi 4: https://www.facebook.com/1979263252399988/posts/2742329109426728/?sfnsn=wiwspwa
    05/etap training, 12:01 – digsi 4: Dear colleagues
    Hope all will be fine and Good Health
    it is my pleasure to Participate in Technical group for Protection, Hope we can interest from information of each other and we Service in better way
    thanks again for accepting me
    05/etap training, 14:42 – digsi 5″: Welcome
    05/etap training, 16:42 – digsi 4: Please I need interlock table for one & half scheme
    05/etap training, 19:34 – digsi 5: Which type of relay in
    33KV incomer
    TX,
    11KV incomer
    33KV outgoing
    11KV outgoing
    05/etap training, 19:44 – digsi 5: Please tell the ‘distance’ below which ‘Line Differential Relay’ should be used for protection of 220 kV or 132 kV Transmission line?
    05/etap training, 20:06 – digsi 4: Line differential use mostely for under ground cable not over head line for e.g RED670 Abb line differential and for OHL REL670 will be use
    05/etap training, 20:07 – digsi 4: In addition RED670 have ability to protect distance too
    05/etap training, 20:14 – digsi 5: sir, why is it that Differential is used for cable and not line?
    05/etap training, 20:16 – digsi 4: Because with differential you are normally using fiber Optic, laying parallel with feeder
    05/etap training, 20:17 – digsi 4: It is common to use line differential for under ground cable and distance relays for over head feeders
    05/etap training, 20:18 – digsi 5: Cant we have line diff if we have OPGW with the line?
    05/etap training, 20:19 – digsi 4: As much I know there is no distance length specified for Line differential relays
    05/etap training, 20:19 – digsi 4: Line differential protection is also being used in overhead lines especially short lines and for high voltage lines that have a redundant protection such as 400 kv
    05/etap training, 20:20 – digsi 4: Yes I think possible, line can be use with opgw too, but I never face that actually in our system
    05/etap training, 20:21 – digsi 4: Right
    05/etap training, 22:24 – digsi 5: anyone has 2 phase transmission line with ‘line Differential protection’?
    05/etap training, 22:29 – digsi 5: Line differential protection is being used for very short lines say less than 1 km. We are using it on 550 metres 220kv line.
    05/etap training, 22:34 – digsi 5: okay sir👍
    05/etap training, 23:11 – digsi 5: will anyone please the type of curve used by indian railways for Overcurrent protection of the traction feeders?
    06/etap training, 00:28 – digsi 5: Very inverse characterstics
    06/etap training, 08:05 – digsi 5: sir why is it used and not Normal Inverse or Extremely Inverse?
    06/etap training, 10:22 – digsi 5: Main protection is over current protection for railways..they adopt very inverse in the downstream network..so for relay coordination we use same curve
    06/etap training, 10:22 – digsi 5: Any one can correct me..if am wrong
    06/etap training, 10:24 – digsi 5: Anyone know how to configure goose signal at abb pcm software.pls share documents if u have
    06/etap training, 19:35 -digsi 5: How to check I/O Status in sepam80 relay
    06/etap training, 19:35 – digsi 5: In HMI, Or Software
    06/etap training, 19:35 – digsi 5: ??
    06/etap training, 21:38 -digsi 5: I have used this once before, now i am not getting it
    06/etap training, 21:50 – digsi 5: Once Relay is Connected with ur Lap, There is Spanner Symbol Available in Icons

Open it , Directly it will go to I/O Monitering
06/etap training, 21:51 – digsi 5: In HMI ,

Press Main Menu ,

U ll Get IO page Directly , Press Enter then Side Arrow for Next page
06/etap training, 23:02 -digsi 5:
Main menu means this one?
07/etap training, 00:34 – digsi 5:
07/etap training, 00:34 – digsi 5: Press 13 , then Options will come as IO
07/etap training, 06:27 -digsi 5: 👍
07/etap training, 06:27 -digsi 5: Thanks jii
07/etap training, 06:32 -digsi 5: Jii one more doubt
07/etap training, 06:35 -digsi 5:
If I am using this protection output in logipam, then where I want to enable it and give settings
07/etap training, 06:37 -digsi 5:
For 50/51N_1_3, I enabled unit 1. Then where I have to give setting. In group A 3 or 1
07/etap training, 15:25 – digsi 5: Anyone please share Power Swing testing file for Omicron CMC356?
07/etap training, 16:36 -digsi 5: Anyone have EMCO AVR relay service engineer contact no in india
07/etap training, 20:00 -digsi 5: How to calculate transmission line loss from line length
07/etap training, 20:02 – digsi 5: i^2 * (unit R/km*line length) will give for one phs
07/etap training, 20:03 -digsi 5: It worked… Thank youu
08/etap training, 12:45 – digsi 5:
09/etap training, 01:32 – digsi 4: Dears how to activate the help file “about” in digsi4 software
09/etap training, 09:49 -digsi 4: Anybody have manual of ETL 41 ABB PLCC equipment?
Kindly share.
Required urgently.
10/etap training, 19:18 -digsi 5:
10/etap training, 19:18 -digsi 5: In EMCO AVR relay at the parallel of PT supply component used which is burnt is capacitor or resistor
10/etap training, 19:28 – digsi 5: To test directional earth fault relay, voltage I’m giving is healthy and how much current to give and it’s angle
10/etap training, 19:44 – digsi 5: In earth fault make voltage less in one phase
10/etap training, 19:44 – digsi 4: Your test will fail because you inject a healthy phases voltage, that’s mean there is no zero sequence voltage which needed to operate the relay
You should simulate a real fault , if an earth fault happens to phase A the voltage of this phase will drop to a low value
10/etap training, 21:02 – digsi 4joined using this group’s invite link
10/etap training, 21:48 – digsi 4joined using this group’s invite link
10/etap training, 21:57 – digsi 4: Hello every one
I’m Ali Ahmadi come from Iran. I work in field of substation Automation at SALCO company for 3 years. I’m so happy to join this group.
10/etap training, 22:04 – digsi 4: Welcome ahmedi
11/etap training, 08:08 – digsi 5: Thanks for help
11/etap training, 08:09 – digsi 5: Thanks for help. I did as you told and testing was successful.
12/etap training, 01:32 -digsi 4 joined using this group’s invite link
12/etap training, 01:39 -digsi 4: Hi everyone, my name is José Concha, I’m a chilean electronics engineer, currently working in a protections maintenance project in Mejillones, Antofagasta, pleased to meet you all
13/etap training, 21:39 – digsi 4:
Dears’ please support ‘ I’m trying to press about button but the help don’t open the specific tab explain ‘ although I reinstall the device drivers
13/etap training, 21:48 – digsi 5: Install the Device driver with help from siemens site
13/etap training, 21:49 – digsi 4: Already installed but it appears as total manual in pdf not individual parameter
13/etap training, 23:19 – digsi 5: Anyone have logic for sotf on manual close command in p444 micom
14/etap training, 20:35 – digsi 5: Hi everyone,

Anybody having Precommissioning and Commission procedure or MOS for Substation Upgrade projects

Thanks in Advance
15/etap training, 10:54 – digsi 5: What is the Siprotec 5 Relay Password??
15/etap training, 10:55 – digsi 4: 6 times 0
15/etap training, 10:55 – digsi 4: Try
15/etap training, 10:56 – digsi 5: Tried, not Working
15/etap training, 10:56 – digsi 5: Anything else
15/etap training, 10:56 – digsi 5: 222222
15/etap training, 10:56 -digsi 4″: 222222
15/etap training, 10:56 – digsi 5: Okay, let me try
15/etap training, 11:01 – digsi 5: Not working
15/etap training, 11:01 – digsi 4: try 000000
15/etap training, 11:02 – digsi 5: Tried both

To join our protection relay WhatsApp group, please send interest on Whatsapp +989129613659https://elec-engg.com/whatsapp-group-for-protection-engineers/

15/etap training, 11:02 – digsi 5: But it is new relay, not yet configured
15/etap training, 11:02 – digsi 5: 666666
15/etap training, 11:59 – digsi 4: Check manual default password
15/etap training, 13:00 – digsi 5: check this one
15/etap training, 13:17 – digsi 4: 11111115/etap training, 18:42 -digsi 5″: 123456
15/etap training, 19:34 -digsi 4: It Should be 000000.

I am facing a problem with SFT2841 authorization code/registration.

Any one can help
23/etap training, 15:15 – digsi 5: Register with ur mail ID, code link will come
23/etap training, 15:34 -digsi 4: But I am not schnieder
23/etap training, 15:35 – digsi 5: Gmail works
23/etap training, 15:39 -digsi 4:
23/etap training, 15:39 -digsi 4: What should I do now 😔
23/etap training, 15:40 -digsi 4:
23/etap training, 15:40 – digsi 5: Select any one and proceed
23/etap training, 16:22 – digsi 4:
/etap training, 21:02 -digsi 5: U can give any mail ID, and number. It will get registered.
23/etap training, 22:03 -digsi 4:
Thanks 👍👍👍, I got it registered
23/etap training, 22:04 -digsi 4: But still can not log into the sepam, any ideas
23/etap training, 22:04 -digsi 4:
23/etap training, 22:05 -digsi 4:
Their is no com ports available
23/etap training, 22:49 – digsi 4: Do you use USB to serial adapter or you have built in serial port?
23/etap training, 23:37 -digsi 4:
23/etap training, 23:39 – digsi 4: What’s the relay model
23/etap training, 23:39 -digsi 4: S42
23/etap training, 23:40 -digsi 4:
23/etap training, 23:40 – digsi 5: Is this cable fit for
Front port communication ???
23/etap training, 23:40 -digsi 4: Yup
23/etap training, 23:40 – digsi 5: I think
Old Mouse pin
Type

Pin will be there
23/etap training, 23:49 – digsi 4: Hello everyone i had a problem with siemens siprotec 7vk61 relay it is not measuring injected current and the relay is not showing measurements could anyone please help me out in this
Thanks
23/etap training, 23:50 – digsi 5: Relay showing
Measurements in

” ——– “
Like this ?
23/etap training, 23:50 – digsi 5: One measurements page
Pic please
23/etap training, 23:50 – digsi 4: Yes sir
23/etap training, 23:50 – digsi 5: Is there any
Error led ???
23/etap training, 23:51 – digsi 4: No led
23/etap training, 23:51 – digsi 5: Try to initialize the

To join our protection relay WhatsApp group, please send interest on Whatsapp +989129613659https://elec-engg.com/whatsapp-group-for-protection-engineers/

New ly created
MLFB file with same version
Then configure as per ur system
Then check
23/etap training, 23:51 – digsi 5: For what purpose this relay used?
23/etap training, 23:51 – digsi 5: Breaker Management
23/etap training, 23:51 – digsi 5: Eg, like TIE bays
23/etap training, 23:52 – digsi 4: Auto reclose
23/etap training, 23:52 – digsi 5: Yeah,
AR for tie.. and alll
23/etap training, 23:52 – digsi 5: Inside software you checked the measurements?
23/etap training, 23:52 – digsi 4: It is showing “———” this on measurements
23/etap training, 23:52 – digsi 5: Error in IED
23/etap training, 23:53 – digsi 4: Yes also it is not showing in digsi software
23/etap training, 23:53 – digsi 5: Check the Control options in
Relay
23/etap training, 23:53 – digsi 4: Ok
23/etap training, 23:54 – digsi 4: Which options sir ?
24/etap training, 06:39 -digsi 5: Yes
-24/etap training, 21:59 – dgfdh: Hi all, my name is Sofiane, I am Algerian, I work at transmission power company, I am specialist in protection engineer
24/etap training, 22:00 -digsi 4: Hi Soufiane
24/etap training, 22:01 -digsi 4: I am Amr Mohamed From Egypt
24/etap training, 22:01 -digsi 4: Working as electrical engineering manager
24/etap training, 22:01 – digsi 4: Fine, nice to meet you
24/etap training, 22:02 -digsi 4: it is my honor
24/etap training, 22:03 – digsi 4: Thanks a lot
24/etap training, 22:08 – digsi 5: Yo soy de Bolivia soy ING. Eléctrico especialista en Sistemas de Protección en Centrales Hidroeléctricas Subestaciones y Lineas de transmisión
24/etap training, 22:14 – digsi 5: Biemvenido
24/etap training, 22:40 -digsi 5: This message was deleted
24/etap training, 22:43 -digsi 5: Use English guys
25/etap training, 00:43 – digsi 5: Yes
25/etap training, 01:38 – digsi 4: Hi Everyone, my name is Julio, I am Brazilian, I work at electrical maintenance, I am specialist in protection engineer
25/etap training, 01:39 – digsi 4: Hello Julio..!
25/etap training, 02:14 – digsi 4: This message was deleted
25/etap training, 02:15 – digsi 4: Hi
25/etap training, 02:45 – digsi 4″: Hola
25/etap training, 07:32 – digsi 4: Hi everyone am from India, am working as an electrical maintenance engineer in power generation plant.
25/etap training, 07:37 – digsi 4: In Which plant are you working
25/etap training, 07:45 – digsi 4: Coal based power plant, Power mech O&M, IL&FS client company, Cuddalore, Tamilnadu
25/etap training, 21:04 – digsi 5:
25/etap training, 21:04 – digsi 5: Please help
26/etap training, 16:50 – digsi 4 joined using this group’s invite link
27/etap training, 13:01 – digsi 5: Anyone having Areva P521 pilot wire Relay Technical Manual .

Need Areva not Schneider.
28/etap training, 09:44 -digsi 5: How to find slope for low impedence REF in sepam T81
30/etap training, 21:20 – digsi 5: Please tell What value of Contact Resistance is acceptable for 33 /132/220/400 kV Circuit breakers?
30/etap training, 21:32 – digsi 5: ABB de 30 a 40 micro ohm
30/etap training, 21:34 – digsi 4: The contact resistance value depends on the current of the circuit and not on the voltage.
30/etap training, 21:35 – digsi 4: You should evaluate the manufacturer’s tests
30/etap training, 21:37 – digsi 4: also evaluate the dissipated power in the resistance found. Then compare with the short circuit power of the circuit breaker
01etap training, 00:32 – digsi 4:
What is the password in thia Relay?
01etap training, 00:33 – digsi 4: 000000
01etap training, 00:33 – digsi 4: Thanks
01etap training, 00:34 – digsi 5: 000000
01etap training, 00:43 – digsi 4: Thanks
01etap training, 10:37 – digsi 5:
Anyone pls send me the template of the relay
01etap training, 10:39 – digsi 5: https://support.industry.siemens.com/cs/document/109747364/reyrolle-overcurrent-earth-fault-protection-argus-7sr10-?dti=0&pnid=24240&lc=en-US
01etap training, 10:40 – digsi 5: Install all the minimum required template s and
7sr100 rk template tooo,
01etap training, 10:40 – digsi 5: Then check
01etap training, 10:46 – digsi 5: If I install 7sr100 rk all template then i got the 7sr100 r4h-1a.. it’s crt
01etap training, 10:47 – digsi 5: U installn
Rk range

It will begin
k l m n…..
01etap training, 10:48 – digsi 5: H series will come
In minimum all template
01etap training, 10:49 – digsi 5: Ok bro ..
01etap training, 11:42 – digsi 4:
Hello everyone the 7vk61 is not showing measurements do anyone have solution for it
01etap training, 13:04 – digsi 5: Anyone with guide notes for using sverker 780 relay tester
01etap training, 13:05 – digsi 5: On vamp relay
01etap training, 15:44 -digsi 4: What is this in fuse failure relay
Please explain
01etap training, 16:40 – digsi 5: Looks like selenium rectifiers
01etap training, 16:40 – digsi 5: 3 phase
01etap training, 16:44 – digsi 5: Also called metal rectifier
01etap training, 17:45 – kk 1313 Riki Khomarudin joined using this group’s invite link
02etap training, 11:53 – digsi 4: This message was deleted
03etap training, 15:46 – digsi 4:
03etap training, 15:46 – digsi 4:
03etap training, 16:13 -digsi 5: hellow
can any one help me on how to test over excitation on generator by cmc
03etap training, 16:13 -digsi 5: V/f =1.2
03etap training, 16:19 – digsi 5: Votage KV rating how much
03etap training, 16:19 -digsi 5: 11kV
03etap training, 16:21 – digsi 4: There are two methods to check one is increasing voltage and second decreasing frequency method.

  1. Keep frequency constant and raise the voltage.
  2. Keep voltage constant and decrease frequency.
    In both cases plz continues monitor the v/f meter on display.
    03etap training, 16:26 -digsi 5: thanks 🙏🏿
    03etap training, 16:27 – digsi 4: This message was deleted
    03etap training, 16:28 – digsi 4:
    Do any one have solution for this relay it is not showing measurements
    03etap training, 16:33 – digsi 4: Kindly check the logs onces.
    I was assuming that there is a configuration issue. Because device healthy condition.
    Apart of that this is a sync relay so there is no ct connection and this window is for current measurement.
    03etap training, 16:34 – digsi 4: Sorry not Sync it is auto recolse relay
    03etap training, 16:53 – digsi 5: Trigger the check syn
    Input,
    Manual or
    Give the all measurements properly
    03etap training, 16:54 -digsi 5″: What is Best method to find zero sequence impedance of line
    03etap training, 16:57 – digsi 4: U have to take it from conducter manfucter he provid you R0 and X0 and you can calculate.
    03etap training, 19:31 – digsi 4: Ct are connected
    09etap training, 11:31 – digsi 4 Sharma and A1 1241 Sasikumar Dharmalingam was added
    03etap training, 20:24 – digsi 4: Does anyone have PCM600 software from ABB?
    03etap training, 20:25 – digsi 5″: You can download it free from abb website
    03etap training, 20:26 – digsi 4: http://www.mediafire.com/file/60nbchg1imwwidn/pcm.rar/file
    04etap training, 12:55 – kk 1313 Riki Khomarudin: Does anyone guide me for understand about pcm 600 for remote relay reb 6700
    05etap training, 03:43 – digsi 5: Dear brothers
    Any one knew:
    How can I synchronize the relay time and date with the labtop time and date in siprotec 5 Siemens relays
    05etap training, 15:07 -digsi 5: How to check this curve 2 in sepam m87 relay
    06etap training, 20:44 -digsi 5: Hellow any one have ideas for loss off comm on SIEMENS 7SR1811.
    we checked the fibre comm is ok but the comm link still failed.
    06etap training, 21:23 – digsi 5: How you checked fibre communication?
    06etap training, 22:25 -digsi 5: by applying laser light end to end
    Abb when we read this error coming any sloution ro read. Rec670
    09etap training, 10:02 – digsi 5: Kindly provide auto reclose logic for ABB bcu. For one and half scheme 400kv.
    Thanks
    09etap training, 12:09 – digsi 4: Dears,
    There is two SEL relays for the same line prot. have different order number while one comm. channel used for direct fiber and one used with media converter . Still found a comm. Fail can you help
    09etap training, 13:46 – kk 1313 Riki Khomarudin: Do i can use pcm 600 for version 2.8 in relay?
    09etap training, 17:13 – digsi 5″: Yes. But must have connectivity package of the relay you are communicating.
    10etap training, 12:33 – digsi 4: Dears , please I need data model for Schneider p923
    10etap training, 13:13 – digsi 4: Urgent please👆
    10etap training, 13:35 – digsi 4: This message was deleted
    10etap training, 13:35 – digsi 4: The file that you need
    10etap training, 13:36 – digsi 4:
    p923.sdma
    10etap training, 13:47 – digsi 4: Thank u
    11etap training, 16:47 – digsi 5: Anyone done synch in micom relays?
    11etap training, 16:48 – digsi 5: P143
    12etap training, 00:21 – digsi 4:
    12etap training, 00:30 – digsi 4: Does anyone know how to communicate Double F6150e with the F6300?
    12etap training, 06:01 – kk 1313 Riki Khomarudin: Use network for communication using pc
    14etap training, 19:51 – digsi 5: Good evening Guys

Can anyone have the ODEN programma Technical user Manual. Pdf

Thanks in Advance
14etap training, 19:56 – digsi 5: https://megger.com/primary-current-injection-test-system-oden-at
14etap training, 19:57 – digsi 5: Log in and download the manual
Its about 35mb
15etap training, 13:02 – digsi 5: Good morning guys
Please:
Can I change power disconnectors or isolator’s control in substations from working by classic control to work by PLC ( programmable logic controller) ??
17etap training, 00:23 -digsi 5′: Plz share NEMA Standards anyone …
17etap training, 00:27 – digsi 5: Same generators on parallel connection but one either not taking load or shedding of load at 50%
What can be the coz
17etap training, 10:58 – digsi 5:
21etap training, 10:13 – digsi 5: Any one sees
ASHIDA relay
Model :ADR245B

Can I have the software tools pls
21etap training, 10:20 – Fatima added digsi 4
21etap training, 10:15 – digsi 5″: This is self power relay ????
21etap training, 10:25 – digsi 4:
21etap training, 10:25 – digsi 4:
21etap training, 10:25 – digsi 4: Hi friends can any seen this relay..befor
21etap training, 10:26 – digsi 4: Please send the software link & device template for this model..
21etap training, 10:46 – digsi 5″: I have software for ASHIDA ARD241s
21etap training, 10:47 – digsi 5″: at any case my friend
I will sent you this software and try it
May be for multi version
21etap training, 10:48 – digsi 4: Ok..pls send…
21etap training, 10:50 – digsi 4: vijayakumaralagupandi@gmail.com
21etap training, 10:54 – digsi 5″: Ok
I will sent now
Because its size is 141 MB
So I try here but failed
21etap training, 10:56 – digsi 4: 👍
21etap training, 11:07 -digsi 4: Anyone know cable testing iec formula both ac and dc?
21etap training, 11:14 – digsi 5″: Check your e-mail
21etap training, 11:14 – digsi 4: Yes…
21etap training, 11:28 – digsi 5″:
21etap training, 11:28 – digsi 5″:
21etap training, 11:47 – digsi 4: Ok I will check..now only installed.thanks
21etap training, 17:51 – digsi 5: Anyone have 7um generator test report?
21etap training, 20:37 -digsi 4: i need download link for sft2841 for relay spam
21etap training, 20:38 -digsi 4: Would any one help please
21etap training, 20:40 – digsi 5: https://download.schneider-electric.com/files?p_enDocType=Software+-+Release&p_File_Name=setup_SFT2841_16.7.0.exe&p_Doc_Ref=Setup_Software_SFT2841
22etap training, 16:30 – digsi 4:
Hi my friends, We have a 7SJ62 Siemens relay protection. In event log, the time and date have question mark (?). The source protocol of our device is Ethernet NTP. Why we have question mark in time and date of event?
22etap training, 16:51 – digsi 4: Your device time is not Sync with GPS Clock
22etap training, 17:52 – digsi 4: Thanks
23etap training, 20:52 – digsi 5: Pls guide anyone how to check the spring charge motor trip test using B10E megger kit
23etap training, 20:53 – digsi 5″: Hello all, I need advise on protection on a 132kV transmission line to connect to a solar PV plant producing 92MW.
23etap training, 20:53 – digsi 5″: This is the first generating plant like this proposed in the country.
23etap training, 20:53 – digsi 5: How to handle this kit
23etap training, 20:54 – digsi 5:
23etap training, 20:59 – digsi 5: Hi
Are you in India now?
23etap training, 20:59 – digsi 5: No am n gcc
23etap training, 21:00 – digsi 5: Where to give you the right support
23etap training, 21:03 – digsi 5: Here
26etap training, 20:17 – digsi 4:
26etap training, 20:17 – digsi 4:
26etap training, 20:18 – digsi 4: Hi for everyone
26etap training, 20:19 – digsi 4: Does anyone know how to make logic equations in Areva P921?
29etap training, 15:57 – digsi 5:
29etap training, 15:58 – digsi 5: Exact solution for this??

This problem is comming in Digsi while communicating via Usb.
29etap training, 15:58 – digsi 5: Any ?
29etap training, 16:54 – digsi 5: In taskbar there is comtask32 close that first then close digsi and restart with run as administrator or restart the laptop
29etap training, 17:53 – digsi 5: Apart from this
29etap training, 18:03 – digsi 5: No
29etap training, 18:03 – digsi 5: Means i dnt know
29etap training, 19:24 – digsi 4: This is happen whenever you disconnect the device at online mode. If this is happening only one or two time while communicating device then you have to follow the same procedure as mentioned.
However if same thing happens after doing this then you have to repair your digsi.
29etap training, 19:35 – digsi 5: Digsi repair also tryed,
Same problem arraising, Random at some periods
29etap training, 19:36 – digsi 4: Some Times devices connected? After repairing.
29etap training, 19:36 – digsi 5: Different devices only,
29etap training, 19:37 – digsi 4: Then try to connect in anthor project don’t connect on same file,
29etap training, 19:41 – digsi 5: Im, using Digsi for a while.

Randomly I have got this error
Once this error camed almost all times same error repeat while communicating,

Still i could get the Proper solution for this , and also cause for this error,

I have searched In digsi manual
But nothing mentioned regarding Comtask32,
29etap training, 19:42 – digsi 5: All the minor checks – All seems okay
29etap training, 19:44 – digsi 5: Instalar una actualización de digsi vers. 9
29etap training, 19:44 – digsi 5: Y se arregla el problema
29etap training, 19:44 – digsi 5: Tendría que ser win10
29etap training, 19:44 – digsi 5: Problem in siprotic 4,
Im using software 4.93
29etap training, 19:45 – digsi 5: Hay también una actualización del Simatic
29etap training, 19:45 – digsi 5: Estep7
29etap training, 19:45 – digsi 4: Then you have to reinstall your windows as well digsi.
29etap training, 19:45 – digsi 5: Step 7 ??
29etap training, 19:45 – digsi 5: En la página de Siemens
29etap training, 19:45 – digsi 5: Está la actualización
29etap training, 19:45 – digsi 5: Im faced this issue in different laptops / different os too
02etap training, 23:43 – digsi 5: Anyone have omicron ct analyzer software version 4.51
Pls send link
03etap training, 09:03 – digsi 5:
DIRECT RECRUITMENT Advertisement No. 05-2020.pdf

04etap training, 11:56 – digsi 4: How could we check trip log and event log in IED Scout in siemens Siprotech Relays
05etap training, 09:45 – digsi 5: What is the type of this FO port please?
05etap training, 09:46 – digsi 5: LC/SC/ST like this?
05etap training, 09:46 – digsi 5: LC
05etap training, 09:48 – digsi 5: these two please?
05etap training, 09:49 – digsi 5: LC
05etap training, 09:49 – digsi 5: SC
05etap training, 09:49 – digsi 5: Thanks 👍👍
05etap training, 09:54 – digsi 5: The above relay has FO LC type rear ethernet port and its protocol is IEC60870-5-103. Will it support time synchronization with SANDS make GPS ?
06etap training, 00:57 – digsi 4: Abb rec670 relay restarting again again after double point status included.Does anyone know how to solve this restarting issue please send me message…
Thank you..
06etap training, 05:30 – digsi 4: This change is in the 61850?
06etap training, 09:35 – digsi 4: No just changed binary input status…
07etap training, 18:16 -digsi 5: What will be the default password for GE L90
07etap training, 18:21 -digsi 5: It is showing local access denied, while changing settings from HMI
08etap training, 22:59 – digsi 4:
08etap training, 22:59 – digsi 4: I am getting this error when i send application configuration to the relay.
08etap training, 22:59 – digsi 4: REF 615
08etap training, 23:01 – digsi 4: I can able to read but not able to write what will be the reason!?please anyone knows how to solve this issue message me..
Thank you..
08etap training, 23:08 – digsi 4: Hi guys
08etap training, 23:09 – digsi 4:
08etap training, 23:09 – digsi 4:
08etap training, 23:11 – digsi 4: Can someone help me to configure this relay ABB REF 541?
08etap training, 23:24 – digsi 4:
INRPHAR REF-615.pdf
09etap training, 00:14 – digsi 4: Breaker feeding primary of 6.6/.415 kv transformer is tripping on earthfault during inrush
09etap training, 00:15 – digsi 4: 6.6kv is grounded through 50 Amps NGR
09etap training, 00:16 – digsi 4: 51n is set at 10 amps idmt at 200 एमएस
09etap training, 00:16 – digsi 4: Msec
09etap training, 00:16 – digsi 4: 50n is set at 20amps dt at 50 msec
09etap training, 00:17 – digsi 4: Please guide for the 68 setting in ABB ref 615 relay
09etap training, 06:41 – digsi 5: It’s tripping on Earth fault Highest function?
09etap training, 06:44 – digsi 5: Earth fault highest setting may be less. We keep it as 8-10 times of idmt setting. For example if CT is 600/1A, then earth fault highest function is kept at 2A (10 times of 0.2A)
22:10:19
15etap training, 07:13 – digsi 4: any one having thermal overload calculation sheet for transformer kindly share
18etap training, 12:10 -digsi 5′: Any one work in testing department
18etap training, 12:10 -digsi 5′: Transformer testing
18etap training, 12:25 – digsi 5: Hi, have a good day
18etap training, 12:26 – digsi 5:
Could someone, explain, how i calculate that VA? thanks
18etap training, 13:41 – digsi 5:
18etap training, 13:42 – digsi 5: Please tell What is the use of the rings in above Voltage Transformer?
18etap training, 13:42 – digsi 5: Any sip5 engineer who know to change phase current name for DR
18etap training, 14:49 -digsi 5: Corina rings
18etap training, 14:50 -digsi 5: *Corona
19etap training, 14:55 – digsi 5:
Hi everyone I am facing this problem for ABB615. Whenever I given the read from IED that time showing this error.. How can I solve those error and read relay files from relay ..
19etap training, 14:56 – digsi 5:
19etap training, 15:24 – digsi 5:
Anyone pls send me the ABB REF615 Relay version 5.0.13 relay connectivity pakage
19etap training, 15:32 – digsi 4: Use and update manager or go to their website
19etap training, 15:32 – digsi 5: Updated manager no option for searching
19etap training, 15:33 – digsi 5: Kindly update the license by right click on relay and use license updation tool.
19etap training, 15:34 – digsi 5: Please, can anyone help. CB always trip back after single phase Auto reclose. The PD is 60s
19etap training, 15:35 – digsi 5: Kindly make it clear????
19etap training, 15:37 – digsi 4:
19etap training, 15:38 – digsi 5: After the relay give AR command to the CB it will close and trip back immediately and after that the CB will trip other phases on PD. I’m doing commissing the line not charge
19etap training, 15:39 – digsi 5: *commissioning
19etap training, 15:39 – digsi 5: Here showing the option 5.0.1. But I need 5.0.13 .. how can I download the pakage
19etap training, 16:18 – digsi 5: Did you check for ny trip signal presence to the single pole trip relays?
19etap training, 17:39 – digsi 5: Yes. The feedback is on the relay to test set.
19etap training, 17:43 – digsi 5: Breaker should be in close position for AR
19etap training, 17:43 – digsi 5: In open condition AR should block
19etap training, 17:45 – digsi 5: It was in close position and I trip the CB with the relay on 21Z1 Ph-G fault. Then CB open and the relay send a reclose command
19etap training, 17:47 – digsi 5: Which relay?
19etap training, 17:48 – digsi 5: Did you check the outputs which are getting high on single phase trip
19etap training, 17:51 – digsi 5: NR PCS 931. I have checked it very well because the test kit show the duration of the trip. About 0.038s
19etap training, 17:53 – digsi 5: No other outputs are getting high?
19etap training, 17:53 – digsi 5: Yes
19etap training, 17:55 – digsi 5: Disable TOR function and then check
19etap training, 17:56 – digsi 5: TOR?
19etap training, 18:16 – digsi 5: Trip on reclose function which is there in every numerical relay
19etap training, 18:17 – digsi 5: Disable this function and then check the autoreclose
19etap training, 18:20 – digsi 5: Correct cb state must be provided for the AR relay/21 for AR to work. As I understand AR will work if the CB is open, not when it is closed, along with other interlock conditions.
19etap training, 18:22 – digsi 5: The problem is that the CB is reclosing and trip back immediately
19etap training, 18:23 – digsi 5: Which means some trip signal is tripping it.. its not the ar logic which is at fault.
19etap training, 18:23 – digsi 4: This message was deleted
19etap training, 18:24 – digsi 5: You need to remove the particular phase’s trip input to the single phase trip relay and then try a reclosing function test..
19etap training, 18:25 – digsi 5: If it works, you are going to find out which relay keeps issuing the trip positive to the 1 phase trip relay.
19etap training, 18:29 – digsi 5: If you reclose the CB from AR function of the the relay the CB close and remains. If there is an output that is high it should not stay
19etap training, 18:31 – digsi 5: That’s the logic.
19etap training, 18:32 – digsi 5: The problem happens only when I trip the CB from Close to open and back to close?
19etap training, 18:32 – digsi 5 “: You can check also timer on CB for pole dicrepancy..sometime you need delay more for reclose test.
19etap training, 18:35 – digsi 5: This is where I have doubt really.
19etap training, 18:38 – digsi 5: That s a basic check .. make sure that the dead time is not more than the reclaim time & PD time. Even though as per your description its not what trips the CB on reclosing…
19etap training, 18:41 – digsi 5 “: Please check this one..
Adjust timer on cb..after that reclose succesfully signal comming.😁
19etap training, 18:42 – digsi 5: If its a new cb, after conducting the cB closing timing test, set the deadtime above the closing time of cb too..
19etap training, 18:47 – digsi 5: it’s a new CB
19etap training, 18:47 – digsi 5: Normally, the closing time is 100msec and dead time is set as 1sec. Remove other 2 phases trip relays and then apply singlephase fault with one trip relay. Check if AR works
19etap training, 18:48 – digsi 5: Keep one trip relay in circuit with other trip relays drawn out
19etap training, 18:48 – digsi 5: Suppose you apply Red phase fault, keep red phase trip relay in circuit
19etap training, 18:49 – digsi 5: If others are there definitely it will trip the CB on 3Ph
19etap training, 18:50 – digsi 5: That’s what we are doing
19etap training, 18:50 – digsi 5: No, I’m saying you apply Red phase to earth fault using testing kit and keep Red phase trip relay in circuit
19etap training, 18:50 – digsi 5: Ok
19etap training, 18:51 – digsi 5: Have you checked that Breaker is closing on Single phase fault AR and then tripping
19etap training, 18:51 – digsi 5: If others are active the relay will show TrpA, TrpB and TrpC
19etap training, 18:52 – digsi 5:
19etap training, 18:52 – digsi 5: Thats what he says.. its closing on ar, but again tripping on single phase trip relay..
19etap training, 18:52 – digsi 5: And later due to PD timer, remaining phases trip too
19etap training, 18:52 – digsi 5: Yes
19etap training, 18:57 – digsi 5: You said that it’s again tripping on Trip relay. Check the Auxiliary contact 52A of circuit breaker which is in series with the trip coil. This contact can malfunction. This contact is meant to break DC circuit of Trip relay
19etap training, 18:57 – digsi 5: If trip relay remains in energised state it can again trip the breaker
19etap training, 18:57 – digsi 5: This message was deleted
19etap training, 18:58 – digsi 5: This message was deleted
19etap training, 18:58 – digsi 5: Are you using trip relay NC contact in closing circuit of breaker?
19etap training, 18:59 – digsi 5: Thanks
19etap training, 19:00 – digsi 5: Most welcome.
19etap training, 19:00 – digsi 5: Thank you everyone for your support
19etap training, 19:00 – +974 5512 4508: Electric duct heater 240 volt, 3500 w what are meggar valves
19etap training, 19:02 – digsi 5: This would not lead to successful Autorecloser.
19etap training, 19:02 – digsi 5: If the CB aux switch s faulty and a trip signal persists, the TC will get burned out.
19etap training, 19:03 – digsi 5: Mybad.. you are right
19etap training, 19:04 – digsi 5: Yes, trip coil can burn
19etap training, 19:05 – digsi 5: But I don’t find any other reason. I think they need to check trip coil resistance too,
19etap training, 19:05 – digsi 5: As the coil has not burned, its not the CB aux switch that s causing the issue..
19etap training, 19:09 – digsi 5: Can we extract fault waveform, I mean one more thing needs to be checked: testing kit needs to stop injecting fault after first trip, is it being ensured.
19etap training, 19:10 – digsi 5: Correct! And if the kit feedback point of the trip is correct..
19etap training, 19:11 – digsi 5: Yes I confirmed it. It shows 0.038s
19etap training, 19:11 – digsi 5: If you remove feedback the test kit continues
19etap training, 19:14 – digsi 5: Check the Programming logic of the relay, may be Autoreclose digital output signal may have been connected to the trip output contact of Relay
19etap training, 19:16 – digsi 5: Check the PSL or configuration of Distance relay
20etap training, 08:08 -21etap training, 08:41 – digsi 5: I have only three-phase supply without neutral, in my system newly 1 phase loads are being added. how can I provide neutral wire to this loads, without implementing any Trafo (Delta-Wye)?
Please advise..
21etap training, 09:40 – digsi 5: Has your problem been resolved?
21etap training, 10:31 – digsi 4:
Hi guys. How Can i reset these ledes?
21etap training, 10:36 – digsi 4: Reset, then reset indication leds
21etap training, 10:36 – digsi 4: Check the BB switch if it’s on or off
21etap training, 16:28 – digsi 4: I did it but it doesn’t work.
21etap training, 16:29 – digsi 4: Where can i find BB switch?
21etap training, 16:30 – digsi 4: On the same panel
21etap training, 16:38 – digsi 4: Its ok thanks 👍
21etap training, 22:11 – digsi 5:
21etap training, 22:12 – digsi 5: This is the sepam Relay s configuration,
Could any one explain,

Why we are using ()
In not gate function,

It is mandatory to use the set bracket s
22etap training, 07:45 – digsi 5: ???
22etap training, 08:56 – digsi 5: Not Required
22etap training, 08:57 – digsi 5: If u Want to Invert a Input , U Can use NOT directly
22etap training, 09:10 – digsi 5: So set brackets
Were not important right?
24etap training, 10:57 – digsi 4: Hi guys,
Anyone doesn’t have the RET 615C connectivity package?
24etap training, 11:10 – digsi 4: How to rest led of abb make ret541
24etap training, 12:01 – digsi 4: Password for RET541 ABB
24etap training, 18:39 – digsi 4: This message was deleted
24etap training, 18:39 – digsi 4: Hi guys do anyone have Digsi 4 professional product key and Digsi 5
24etap training, 18:39 – digsi 4: Kindly share
24etap training, 18:40 – digsi 5: Digsi 5 is premium you have to buy license
24etap training, 18:40 – digsi 4: Any price
24etap training, 18:41 – digsi 5: Around 1 lakhs
24etap training, 18:41 – digsi 5: Usd
24etap training, 18:41 – digsi 5: 1428 usd
24etap training, 18:42 – digsi 5: Its better if you contact siemens for that
24etap training, 18:42 – digsi 5: May be in your area it will be different
28etap training, 16:10 – digsi 5: IED scout
Key ???
28etap training, 16:34 – digsi 4: I don’t think you willfind a key free
You can use the free trial for one month and renew it using a virtual machine
28etap training, 20:12 -digsi 5′:
Megger values are lessthan 1 M ohms when on condition plz help how to take megger values
28etap training, 21:47 -digsi 4: What is the ambient temperature
02etap training, 20:31 – digsi 5: Anyone do you have a omicron software version 3.20 on your Google drive. Pls send me the link.its an emergency.
nileshkamal342@gmail.com
03etap training, 11:32 – digsi 5″: Register at omicron website then download
03etap training, 23:21 – digsi 4:
What software do I use to work with?
03etap training, 23:21 – digsi 4: Help me
04etap training, 03:15 – digsi 5: Doble F6 test and F6000 control panel or latest version protection suite with licence copy
05etap training, 12:38 – digsi 5:
05etap training, 12:38 – digsi 5: p343
05etap training, 12:38 – digsi 5: What is the meaning of this error code please?
05etap training, 12:44 – digsi 4: This error code means that analogue input module serial E2ROM Failure.
05etap training, 12:45 – digsi 4: We advise to replace analogue input module through authorized repair center.
05etap training, 12:47 – digsi 5: Thank you !
05etap training, 12:47 – digsi 4:
05etap training, 12:58 – digsi 5: 👍👍👍
07etap training, 12:56 – digsi 5: Anyone know how to trigger DR in sip4 either online or manually
07etap training, 16:05 – digsi 5: Yes
07etap training, 16:05 – digsi 5: How
07etap training, 16:05 – digsi 5: Online you can do
07etap training, 16:06 – digsi 5: Can you tell me the steps
07etap training, 16:06 – digsi 5: Open relay online and go to test then double click on test waveform
07etap training, 16:06 – digsi 5: DR will be triggered
07etap training, 16:06 – digsi 5: Simple
07etap training, 16:06 – digsi 5: Ok thanks
08etap training, 20:23 – digsi 5: Any one used
IED SCOUT for signal simulation ???
08etap training, 21:28 -digsi 5″:
HMI in LabView with IEC 61850 (MMS) Communication
08etap training, 21:28 – digsi 5: Ufff thank you
08etap training, 21:32 – digsi 4: Which sofware u are using
08etap training, 21:33 – digsi 4: Its just a simulation or HILT ( LOOP IN TESTING)
08etap training, 21:45 -digsi 5: Lakshmi Narasimhan mindia: 👌🏻
08etap training, 22:22 -digsi 5″: First I configure the SEL 751 in QuickSet software, then I use the SEL Architect softwate for IEC 61850 configuration, in the end I use the RELAB OPC SERVER software to read the reports I created and the software transforms them to OPC signals and the LabView can read that data in real time.
08etap training, 22:24 -digsi 5″: You can also use Kepserverx to transform MMS or GOOSE data to OPC
09etap training, 00:52 -digsi 5″:
10etap training, 15:42 – digsi 4:
10etap training, 15:43 – digsi 4: Value under switch on condition means in case of differential
11etap training, 10:51 – digsi 5: Dear all
I have good knowledge of digsi4 but no knowledge og digsi5 software. Anyone have any guidelines to access digsi5. I need to see how signal is configured for SAS OR GOOSING.
11etap training, 10:51 – digsi 5: Yes
11etap training, 10:52 – digsi 5: Actually in 5 no need to assign any signal for iec all are pre configured
11etap training, 10:52 – digsi 5: In file there is option of iec structure …on that you can see
11etap training, 13:11 – Arshad:
11etap training, 19:58 – digsi 5: Anybody
Simulated signals from IED SCOUT???
12etap training, 14:41 – digsi 4:
12etap training, 14:41 – digsi 4: This block “MVGAPC1” used for SAS in the REF615 ,but I dont need it to appear on the events
12etap training, 14:47 – digsi 4: Dear all , any one can help please
13etap training, 12:06 – digsi 5: Any body has .manual for this?
13etap training, 12:06 – digsi 5:
13etap training, 15:41 – Abinraj: Hai ,can anybody tell me the difference between short term overcurrent trip and long term overcurrent trip
13etap training, 22:11 – Adigsi 4: ….
13etap training, 22:22 – digsi 4: What is the password of SEL 551?
13etap training, 22:24 – digsi 4: Try TAIL
Or OTTER
13etap training, 23:16 -digsi 5: Lakshmi Narasimhan mindia: Sometimes the password for ftp might be FTPUSER too. If you have quickset settings, you will get the information in it
14etap training, 13:41 – digsi 5″: Hi all,

To join our protection relay WhatsApp group, please send interest on Whatsapp +989129613659https://elec-engg.com/whatsapp-group-for-protection-engineers/

Does anyone faced time inaccuracy in OMICRON CMC256 only if trip time <1 second 14etap training, 17:36 – digsi 5: What are you testing? 14etap training, 17:36 – digsi 5″: Phase Overcurrent 14etap training, 17:37 -digsi 5: Anyone who wants to sell omicron relay testing kit please inform me 14etap training, 19:09 – digsi 5: What are you using? Quick cmc, state sequence or auto 14etap training, 22:43 – digsi 5: Please anyone can share MATLAB software? 14etap training, 22:43 – digsi 5: I need to download and use 14etap training, 22:43 – digsi 5: Pls help 14etap training, 22:47 -digsi 5″: youtube 14etap training, 22:59 – digsi 4: https://downloadly.net/2020/26/9256/03/matlab-2/16/?#/9256-matlab-r-212101012114.html 15etap training, 06:58 – digsi 5: Thanks a lot Sir 👍🏼👍🏼👍🏼🙏🏽🙏🏽 15etap training, 16:36 – digsi 5″: Good day friends. We use a 125V DC system for our substations. The string consists of 93 NiCad cells. The charger is SENS. The only settings available on the charger is FLOAT, set at 1.37VpC 122V, and EQUALIZE, set at 1.57Vpc 138V. These values appear to be assuming the string consists of 88 cells. Should I just adjust the FLOAT to 130V? I don’t see any way to set the number of cells in the string. 15etap training, 23:31 -digsi 5′: How separate furreol in canon mk2600 printer 16etap training, 14:10 – digsi 5: Anyone worked on micom 546 relay. Line differential relay 16etap training, 14:11 – digsi 5: I am facing one problem that the tx of differential communication geting on off frequently. 16etap training, 14:14 – digsi 5″: in back relay tx is getting on off , or in your mux .. 16etap training, 15:07 – digsi 5: In HMI of relay 16etap training, 15:07 – digsi 5: Value is getting 1 and 0 16etap training, 18:00 – digsi 5″: maybe you can check in measurement 4 in display relay , same or not with tx on hmi 16etap training, 18:16 – digsi 4:
What is the password o thia relay SR-489
16etap training, 18:19 – digsi 4: Help me
16etap training, 18:20 – digsi 5: Try 0
16etap training, 18:20 – digsi 5: Factory default pass code is zero (0)
16etap training, 18:39 – digsi 4: Thanks
16etap training, 18:45 – digsi 5″: Quick CMC
16etap training, 19:17 – digsi 5: Do you have feedback connected to the Omicron
16etap training, 19:18 – digsi 5: Also, you can try state sequence
17etap training, 01:18 – digsi 5″: Hey all, just an update. Was able to find in the setting where there are the number of cells for the string, but was not allowed to change the value which was found to be 93. Will try to contact the manufacturer to address.
19etap training, 13:23 – digsi 5: What’s the difference between WCDM11 type relay and WCD type? Both are reverse power protection relays but can we interchange them
20etap training, 16:42 -digsi 5:
20etap training, 16:43 – digsi 4: how i install Digsi 4 in widows 8 or windows 10?
20etap training, 16:43 -digsi 5: Hi the above relay SIEMENS show the error LED and monitor SMS. can you help me to solve this issue.
20etap training, 16:48 – digsi 5: Busbar relay 7ss52?
20etap training, 16:49 – digsi 5: Actually it fall back in monitor mode ….go down there will be one option of reset ….do that.
21etap training, 00:02 – digsi 5″: Yes. Otherwise nothing will show in time
28etap training, 05:18 – digsi 5: hi, could anyone shares PDF standar library “IEC 60255-6 ELECTRICAL RELAYS -PART6:MEASURING RELAYS AND PROTECTION EQUIPMENT” ? Thanks
28etap training, 07:36 – digsi 5″:
IEC 60255-6-1988 scan.pdf
28etap training, 16:59 – digsi 5: thanks a lot
28etap training, 17:13 -digsi 4: Excuse me some one has the ISA -101, thank you
28etap training, 21:26 -digsi 4″:
28etap training, 21:27 -digsi 4″: Does anyone have manual for this relay or how to read the settings for this relay ?
28etap training, 21:27 -digsi 4″: Really appreciate the reply for this. Thanks
29etap training, 09:30 – digsi 4:
29etap training, 11:39 – digsi 5: Anybody have iedscout with license. I need it
Thanks for your consideration
29etap training, 13:39 – digsi 5: Hi everyone
Anyone pls share me the Digsi 4.93 Serial code..
30etap training, 03:15 – digsi 5: IEC 60255-6 is withdrawn.

“IEC 60255-6:1988 | IEC Webstore” https://webstore.iec.ch/publication/14330
30etap training, 03:16 – digsi 5: IEC 60255-1:2009 is the latest
30etap training, 03:23 – digsi 5:
30etap training, 03:23 – digsi 5: If anyone having above copy
Please share it.
Thank you
01etap training, 22:38 – digsi 4: This message was deleted
03etap training, 17:12 – digsi 5:
Pls share the error code
03etap training, 17:13 – digsi 5: Which relay?
03etap training, 17:14 – digsi 5: Micom p444
03etap training, 17:34 – digsi 5: Once ..switch off auxiliary suplly
03etap training, 17:34 – digsi 5: And switch on
10etap training, 13:45 – digsi 4: This message was deleted
10etap training, 18:47 – digsi 5″: any one have IEEE C37.90 ?
11etap training, 23:04 -digsi 5 changed their phone number to a new number. Tap to message or add the new number.
12etap training, 19:25 – digsi 5: IMG-20210221-WA0004.jpg (file attached)
Please give any suggestions


12etap training, 22:12 -digsi 5: IMG-20210221-WA0005.jpg (file attached)
13etap training, 13:59 -digsi 4: I have a question about inrush on Transmission line:

Is it inrush current created during energize of under-ground transmission line?
13etap training, 14:00 -digsi 4: On voltage level of 132kV and 6.5KM
13etap training, 15:07 – digsi 4: No, inrush current produces during charging of transformer.
13etap training, 22:38 – digsi 5: Anyone have rio file for field failure and pole slip
13etap training, 23:19 – digsi 5: Anyone worked with ABB REB670?
15etap training, 21:42 – digsi 5: IMG-20210221-WA0006.jpg (file attached)
What is the default password of this Siemens Relay?


15etap training, 21:42 – digsi 5: Any one have 3.61 data model for this relay?
15etap training, 21:49 – digsi 5: +-+- enter
15etap training, 21:49 – digsi 5: Try this
15etap training, 21:50 – digsi 5: E(enter)
15etap training, 21:53 -digsi 5: 000000
15etap training, 21:53 -digsi 5: Try dis
15etap training, 21:54 – digsi 5: -+- works. Thanks
15etap training, 21:54 – digsi 5: 👍👍👍
15etap training, 21:55 – digsi 5: Sorry I little bit confused
15etap training, 21:55 – digsi 5: Will be glad if anyone have firmware.
15etap training, 21:56 – digsi 5: Data model
15etap training, 22:01 – digsi 5: Why u need
15etap training, 22:34 – digsi 5: To communicate and see Fault Recorder
15etap training, 22:36 – digsi 5: I think It can be use HMI only
15etap training, 22:36 – digsi 5: And modbus communication ports only available
15etap training, 22:42 – digsi 5: Ok. That is also ok. I can use that only as long as I have respective firmware.
16etap training, 02:47 – digsi 5 “: Guys anyone have this book?! Can anyone upload it??
16etap training, 02:47 – digsi 5 “: Transformer Inspection and Testing (Electrical Power Plant Maintenance Book 1) pdf
16etap training, 02:47 – digsi 5 “: I will be thankful
16etap training, 12:31 – digsi 5: Anyone please provide ABB India contact person details who can send C&R panel drawings ?
17etap training, 03:44 – digsi 5:
Any one have a document or manual for this temperature device
17etap training, 10:07 -digsi 5′: IMG-20210221-WA0011.jpg (file attached)
17etap training, 10:07 -digsi 5′: IMG-20210221-WA0012.jpg (file attached)
17etap training, 10:07 -digsi 5′: IMG-20210221-WA0009.jpg (file attached)
17etap training, 10:07 -digsi 5′: IMG-20210221-WA0010.jpg (file attached)
17etap training, 10:08 -digsi 5′: IMG-20210221-WA0007.jpg (file attached)
17etap training, 10:08 -digsi 5′: IMG-20210221-WA0008.jpg (file attached)
17etap training, 10:09 -digsi 5′: Hello any one work this type of MDB ??
17etap training, 10:09 -digsi 5′: Please reply any one work ?
17etap training, 10:23 – digsi 4: This is not MDB look like control panel.
17etap training, 10:23 -digsi 5′: Sir Are you work on this panel ?
17etap training, 10:24 – digsi 4: What you need?
17etap training, 10:24 -digsi 4: Looks like ifsc and Rtu panel
18etap training, 12:46 – digsi 5: Please send link go to download TDMS software for DRTS 64 testing kit
18etap training, 15:54 -digsi 5″: Hello engineers
18etap training, 15:54 -digsi 5″: Any one having earth loop impedance calculation

With some examples
18etap training, 15:55 -digsi 5″: Please share
18etap training, 16:42 – digsi 4: Good morning
Someone has the norm IEEE 1584-2018?
18etap training, 17:26 – digsi 4: Hi does anyone have MComp suite software of L&t relays
18etap training, 17:45 – digsi 5:
1584-2018.pdf
18etap training, 17:45 – digsi 4: Thanks
18etap training, 17:46 – digsi 5: Your welcome
18etap training, 17:51 – digsi 5: thanks
18etap training, 20:45 -digsi 5: 👍

Hardware Configuration in PCM600

  1. Right click on IED & select Hardware Configuration.

2. To compare hardware configuration between PCM600 & IED, click on icon C.

3. You can see PCM Configuration & IED configuration & information saying Confirmation is matching.

4. create an intentional difference in Hardware configuration by changing & saving it. Then compare Hardware configuration to see the changes made.

5. You can see the difference in IED and PCM configuration ( highlighted) & information saying configuration is miss-matching.

6. Change the Display type & compare after saving it.

7. You can compare configuration by click IED, compare configuration

8. To print Hardware configuration, click on magnifier icon

9. To save this report or hardware configuration, click on Save icon

These pictures are part of our supplementary files for ABB PCM 600 training that is mix with Oral explanations to help you in the best way of understanding this course. These auxiliary files have gathered and attached to our ABB PCM600 training course, you can get more information by clicking on the following link:

https://elec-engg.com/abb-pcm-600-training/