The SEL-751A Feeder Protection Relay, manufactured by Schweitzer Engineering Laboratories (SEL), is a microprocessor-based protection, monitoring, automation and control device designed for industrial and utility distribution systems.
The relay provides comprehensive protection for radial and looped feeders, including phase and ground overcurrent protection, voltage and frequency protection, optional arc-flash detection, automatic reclosing, breaker monitoring and flexible communication capabilities.
The SEL-751A is suitable for engineers involved in electrical protection, substation engineering, commissioning, maintenance and distribution network operation.
This guide explains the SEL-751A’s applications, ANSI protection functions, hardware options, configuration, communication, testing and practical engineering considerations.
Important product-selection note: SEL recommends selecting the newer SEL-751 instead of the SEL-751A for new applications. However, SEL states that it will continue to support and warranty the SEL-751A. Existing installations and replacement projects should therefore be assessed against their actual hardware, firmware, application requirements and available options.
SEL-751A Feeder Protection Relay: Complete Guide to Applications, Protection Functions, Settings and Testing
- 1. SEL-751A Feeder Protection Relay Overview
- 2. Applications of the SEL-751A Relay
- 3. SEL-751A Protection Functions and ANSI Device Numbers
- 4. SEL-751A Arc-Flash Protection
- 5. Automatic Reclosing and Breaker Control
- 6. Hardware, Inputs and Outputs
- 7. Communication Protocols and Substation Automation
- 8. SEL-751A Settings and Configuration Using QuickSet
- 9. SEL-751A Testing and Commissioning
- 10. Event Reports and Disturbance Analysis
- 11. SEL-751A vs SEL-751 vs SEL-451
- 12. Advantages of the SEL-751A
- 13. Frequently Asked Questions
- What is the SEL-751A relay used for?
- What is the difference between SEL-751 and SEL-751A?
- Does the SEL-751A support IEC 61850?
- Does the SEL-751A support arc-flash protection?
- How many reclosing shots does the SEL-751A support?
- Which software is used to configure the SEL-751A?
- Can the SEL-751A be tested using OMICRON?
- Does the SEL-751A support breaker failure protection?
- Is the SEL-751A still supported by SEL?
- 14. Learn SEL Protection Relays and Practical Feeder Protection with Elec-Engg
1. SEL-751A Feeder Protection Relay Overview
<image-placeholder>SEL-751A front panel product photograph</image-placeholder>
The SEL-751A combines several functions in one device:
- Feeder phase and ground fault protection.
- Instantaneous and time-overcurrent protection.
- Voltage and frequency protection.
- Optional arc-flash detection and protection.
- Automatic reclosing.
- Breaker failure protection.
- Breaker wear monitoring.
- Metering and power monitoring.
- Programmable logic and control.
- Communication with SCADA and substation automation systems.
- Event recording and disturbance analysis.
The relay is designed for applications where protection, monitoring and control need to be integrated into a single feeder protection device.
Its modular design provides different current and voltage input arrangements, communication options and additional input/output modules. The exact functionality depends on the selected model and ordering configuration.
2. Applications of the SEL-751A Relay
The SEL-751A can be applied in several types of electrical installations.
2.1 Medium-voltage feeder protection
One of its primary applications is protecting medium-voltage distribution feeders against phase-to-phase and phase-to-ground faults.
Typical applications include:
- 11 kV distribution feeders.
- 13.8 kV industrial distribution systems.
- 33 kV distribution networks.
- Industrial plant distribution substations.
- Utility feeder protection panels.
- Transformer outgoing feeders.
- Cable and overhead-line feeders.
The relay uses current transformers to measure feeder current and operates the circuit breaker when configured protection elements detect an abnormal condition.
2.2 Industrial feeder protection
In industrial plants, the SEL-751A can protect feeders supplying:
- Large motors and motor control centers.
- Transformers.
- Industrial distribution boards.
- Auxiliary power systems.
- Process plant equipment.
- Critical industrial loads.
The protection settings must be coordinated with downstream motor, transformer and feeder protection devices.
2.3 Arc-flash protection in switchgear
An optional arc-flash detection system can be installed to detect light associated with an internal arc fault.
The relay combines optical detection with current-based supervision to improve security against unwanted operation.
This application is particularly important in medium-voltage switchgear, where reducing fault-clearing time can reduce incident energy.
2.4 Feeder automation and reclosing
The optional autoreclosing function allows the relay to perform programmed reclosing sequences after selected protective operations.
This is particularly useful for overhead distribution feeders, where some faults are temporary.
2.5 Substation automation
The SEL-751A can exchange measurements, status signals, alarms and control information with a substation automation or SCADA system through supported communication interfaces and protocols.
3. SEL-751A Protection Functions and ANSI Device Numbers
The following table summarizes important protection functions available in the SEL-751A family. Some functions require specific hardware or ordering options.
| ANSI code | Protection function | Application |
|---|---|---|
| 50P | Phase instantaneous overcurrent | Fast phase-fault detection |
| 51P | Phase time-overcurrent | Phase-fault protection and coordination |
| 50N | Neutral instantaneous overcurrent | Neutral fault detection |
| 51N | Neutral time-overcurrent | Neutral overcurrent protection |
| 50G / 51G | Ground overcurrent | Ground-fault protection |
| 50Q / 51Q | Negative-sequence overcurrent | Unbalanced fault detection |
| 50PAF / 50NAF | Arc-flash overcurrent | Arc-flash current supervision |
| AFD | Arc-flash detection | Optical arc detection |
| 27 | Undervoltage | Low-voltage protection |
| 59 | Overvoltage | High-voltage protection |
| 81U / 81O | Underfrequency / overfrequency | Frequency protection |
| 81R | Rate-of-change-of-frequency | Frequency disturbance detection |
| 81RF | Fast rate-of-change-of-frequency | Optional islanding mitigation |
| 25 | Synchronism check | Supervision of breaker closing |
| 79 | Automatic reclosing | Automatic feeder restoration |
| 50BF | Breaker failure | Backup protection for breaker failure |
| 32 | Directional power | Power-flow supervision |
| 60LOP | Loss of potential | Detection of voltage circuit failure |
The availability of individual elements depends on the selected model and options. Always verify the applicable instruction manual and settings documentation before engineering a protection scheme.
3.1 Phase overcurrent protection – 50P and 51P
Phase overcurrent protection is one of the most important functions of the SEL-751A.
The relay measures the three-phase currents:
- IA
- IB
- IC
The instantaneous overcurrent element (50P) operates when the measured current exceeds its configured pickup value.
The time-overcurrent element (51P) operates according to a selected time-current characteristic.
The SEL-751A supports multiple time-current curves, including:
- Moderately inverse.
- Inverse.
- Very inverse.
- Extremely inverse.
- Long-time inverse.
- Short-time inverse.
Both IEC and US curve families are available.
Practical engineering consideration: The 51P pickup and time dial should be selected after studying the maximum load current, minimum and maximum fault current, downstream protection settings and upstream protection coordination.
3.2 Ground overcurrent protection – 50G, 51G, 50N and 51N
Ground-fault protection is essential in distribution networks because a single-phase-to-ground fault may produce a relatively low current depending on the system grounding method.
The SEL-751A can use calculated residual current or an optional measured residual current input, depending on its hardware configuration.
Calculated residual current is:
(I_G=I_A+I_B+I_C)
The relay also supports neutral current measurement and optional sensitive neutral input arrangements.
The distinction between ground and neutral current inputs is important when designing the CT circuit and selecting protection settings.
Engineers should verify:
- CT location and polarity.
- Residual connection arrangement.
- Neutral CT ratio.
- Grounding system.
- Minimum earth-fault current.
- Maximum external ground-fault current.
- Required sensitivity and coordination margin.
3.3 Negative-sequence overcurrent protection – 50Q and 51Q
Negative-sequence current is useful for detecting unbalanced faults.
Unlike positive-sequence current, negative-sequence current is normally low during balanced three-phase loading.
This makes negative-sequence protection useful for detecting certain phase-to-phase faults and abnormal unbalanced conditions.
The 50Q element provides instantaneous protection, while 51Q provides time-delayed protection.
3.4 Voltage protection – 27 and 59
With the appropriate voltage input option, the SEL-751A provides undervoltage and overvoltage protection.
Applications include:
- Detection of abnormal feeder voltage.
- Voltage-based load shedding.
- Alarm and trip schemes.
- Supervisory logic for automatic switching.
- Protection of sensitive industrial loads.
Voltage inputs can be configured for supported wye, open-delta or single-voltage arrangements. Correct VT wiring and the corresponding relay settings are essential.
3.5 Frequency protection – 81U and 81O
The SEL-751A provides underfrequency and overfrequency protection.
These elements can be used for:
- Load shedding.
- Generator interconnection protection.
- Frequency disturbance detection.
- Network separation schemes.
- Alarm and trip applications.
Optional rate-of-change-of-frequency functions provide additional capabilities for applications involving rapid frequency disturbances.
3.6 Breaker failure protection – 50BF
Breaker failure protection provides backup when a circuit breaker does not interrupt the fault current after receiving a trip command.
A typical breaker failure sequence includes:
- A protection element detects a fault.
- The relay issues a trip command to the circuit breaker.
- The breaker failure logic starts its timer.
- The relay checks whether the breaker has successfully interrupted the current.
- If the breaker fails to clear the fault within the configured time, the breaker failure output operates.
The resulting trip signal can be connected to an upstream breaker or another appropriate isolation scheme.
The timer, current supervision and breaker auxiliary contact logic must be engineered carefully.
3.7 Automatic reclosing – 79
The SEL-751A can be ordered with an optional automatic reclosing function.
The recloser supports up to four reclosing shots before lockout.
Typical applications include overhead distribution feeders where temporary faults may disappear after the circuit breaker opens.
The engineer can configure:
- Reclosing initiation.
- Reclosing dead time.
- Reclosing shot sequence.
- Reclosing lockout.
- Reset conditions.
- Dead-line closing supervision.
- Synchronism-check supervision where supported.
- Coordination with downstream protective devices.
Automatic reclosing must be coordinated with the protection philosophy and equipment limitations. It should not be enabled indiscriminately on cables, transformers or equipment where reclosing could create additional damage.
4. SEL-751A Arc-Flash Protection
<image-placeholder>SEL-751A arc-flash protection arrangement with optical sensors inside switchgear</image-placeholder>
One of the important optional features of the SEL-751A is arc-flash detection.
An internal arc fault in medium-voltage switchgear can cause severe damage and create a serious risk to personnel.
Conventional overcurrent protection may require additional operating time because it must distinguish fault current from load current and coordinate with other protection devices.
An optical arc-flash system provides an additional detection method.
4.1 How arc-flash detection works
The SEL-751A can use optional fiber-optic arc-flash detector inputs.
The basic operating principle is:
- An arc fault occurs inside the switchgear.
- The optical sensor detects the light produced by the arc.
- The relay receives the optical signal.
- The configured arc-flash logic evaluates the light and current conditions.
- The relay issues a trip command to the circuit breaker.
The combination of light detection and overcurrent supervision improves protection security.
4.2 Arc-flash sensors
The SEL-751A supports four-channel optical arc-flash detection with the applicable optional hardware.
The manufacturer’s documentation describes point sensors and clear-jacketed fiber sensor arrangements.
The optical system also performs sensor circuit monitoring to identify certain sensor or fiber-loop failures.
4.3 Arc-flash operating time
SEL specifies an arc-flash time-overlight element pickup time of approximately 2–5 ms.
The actual time to isolate the fault also depends on the output circuit, breaker operating time and the complete protection scheme.
Therefore, the relay’s detection time should not be confused with the total fault-clearing time.
4.4 Engineering considerations
When designing an arc-flash protection scheme, engineers should consider:
- Sensor location.
- Optical coverage of the switchgear compartments.
- Fiber routing and mechanical protection.
- Current supervision settings.
- Trip output configuration.
- Breaker clearing time.
- Sensor supervision alarms.
- End-to-end functional testing.
Arc-flash protection should be validated through a complete scheme test rather than simply checking that the relay detects light.
5. Automatic Reclosing and Breaker Control
The SEL-751A includes programmable front-panel operator controls.
Depending on the model and configuration, the operator can use the relay for local breaker trip and close commands, auxiliary control and reclosing functions.
The optional autoreclosing feature supports up to four shots before lockout.
A typical sequence for an overhead feeder could be:
- A temporary fault occurs.
- The 51P or 51G element operates.
- The relay trips the breaker.
- The programmed dead time starts.
- The relay checks the required closing conditions.
- The breaker receives a close command.
- If the fault has disappeared, the feeder returns to service.
- If the fault remains, the protection operates again according to the programmed shot sequence.
The engineer must ensure that reclosing is coordinated with downstream fuses, reclosers and other protective devices.
6. Hardware, Inputs and Outputs
<image-placeholder>SEL-751A rear panel showing communication ports and expansion slots</image-placeholder>
The SEL-751A has a modular hardware architecture.
The base system includes current measurement, a power supply, control inputs and outputs, processor and communication facilities.
The exact arrangement depends on the ordered model.
6.1 Current inputs
Available current input ratings depend on the selected hardware and include:
- 5 A secondary.
- 1 A secondary.
- 50 mA secondary.
- 2.5 mA high-sensitivity secondary.
The correct input type must be selected according to the CT secondary rating and intended application.
Never connect a conventional 1 A or 5 A CT circuit to an incompatible sensitive-current input.
6.2 Voltage inputs
Optional voltage input cards allow the relay to measure feeder voltage for voltage, frequency, power and synchronism-check functions.
Voltage input arrangements can include:
- Three-phase voltage inputs.
- Synchronism-check voltage input.
- Monitoring and protection packages.
- Arc-flash detection combinations.
- Measured residual current input combinations.
Check the actual ordering code before preparing wiring diagrams.
6.3 Digital inputs and outputs
The standard system includes two digital inputs and three digital outputs.
Optional I/O cards expand the available connections.
Applications include:
- Circuit breaker status.
- Protection trip signals.
- External interlocks.
- Local and remote control.
- Alarm indications.
- Reclosing initiation and blocking.
- SCADA status signals.
6.4 RTD inputs
Optional RTD facilities support temperature monitoring applications.
The SEL-751A documentation describes support for internal RTD options and an external SEL-2600 RTD module, depending on configuration.
These inputs can be useful for monitoring equipment temperature where the selected application and hardware support the required sensors.
7. Communication Protocols and Substation Automation
The SEL-751A supports several serial and Ethernet communication options.
Depending on the ordered communication hardware and firmware, supported protocols include:
- IEC 61850.
- DNP3 Serial.
- DNP3 LAN/WAN.
- Modbus RTU.
- Modbus TCP.
- SEL Mirrored Bits.
- SEL ASCII and related protocols.
- SNTP.
- FTP.
- Telnet.
- IEEE C37.118 synchrophasor communication.
The relay can be integrated into SCADA and substation automation systems to provide measurements, status information, alarms and control capabilities.
Important: Protocol availability is configuration-dependent. Do not assume that every SEL-751A has Ethernet, IEC 61850 or every listed protocol enabled.
7.1 IEC 61850 communication
Where the appropriate option is installed, the SEL-751A can be integrated into an IEC 61850-based substation automation system.
Typical engineering activities include:
- Reviewing the IED capabilities.
- Configuring communication parameters.
- Preparing and validating SCL files.
- Mapping logical nodes and data objects.
- Configuring MMS reporting.
- Engineering GOOSE communication where supported.
- Testing communication with the station-level system.
Engineers should check the exact IEC 61850 edition and supported services for the specific relay configuration.
7.2 Time synchronization
Accurate time synchronization is important for event analysis and comparison of disturbance records from different IEDs.
The SEL-751A supports time synchronization options including IRIG-B and optional network-based time services such as SNTP, depending on the hardware configuration.
8. SEL-751A Settings and Configuration Using QuickSet
<image-placeholder>SEL acSELerator QuickSet relay configuration software screenshot</image-placeholder>
The SEL-751A can be configured using acSELerator QuickSet SEL-5030.
QuickSet is used to prepare, edit, download and retrieve relay settings.
Typical engineering tasks include:
- Establishing communication with the relay.
- Retrieving the existing relay settings.
- Selecting the correct device and firmware configuration.
- Entering CT and VT ratios.
- Configuring phase overcurrent elements.
- Configuring ground and neutral protection.
- Selecting time-current curves.
- Configuring voltage and frequency protection.
- Preparing breaker failure logic.
- Configuring automatic reclosing where installed.
- Preparing SELogic control equations.
- Configuring communication parameters.
- Downloading and verifying the settings.
8.1 CT and VT ratio configuration
Correct CT and VT ratios are fundamental to protection engineering.
For example, if a feeder CT has a ratio of 600/1 A, the relay settings and displayed primary quantities must reflect the actual CT ratio.
Incorrect CT or VT ratios can cause errors in metering, protection pickup calculations and event analysis.
8.2 Overcurrent settings
The engineer should calculate and verify:
- Maximum feeder load current.
- Emergency loading conditions.
- Minimum phase fault current.
- Maximum phase fault current.
- Minimum ground fault current.
- Maximum ground fault current.
- Downstream relay and fuse settings.
- Upstream protection coordination.
- CT performance and saturation considerations.
The selected curve and time dial should provide adequate coordination while maintaining acceptable fault-clearing time.
8.3 SELogic control equations
SELogic allows engineers to create customized logic using relay measurements, protection elements, digital inputs, timers and internal logic variables.
Possible applications include:
- Breaker interlocking.
- Trip and close supervision.
- Reclosing permissive logic.
- External trip initiation.
- Alarm aggregation.
- SCADA control.
- Blocking and enabling protection elements.
A well-designed logic scheme should be documented and tested before commissioning.
9. SEL-751A Testing and Commissioning
<image-placeholder>Protection engineer testing an SEL feeder relay using an OMICRON CMC test set</image-placeholder>
Testing and commissioning are essential to verify that the SEL-751A operates correctly under normal and fault conditions.
A complete test plan should include hardware inspection, wiring checks, secondary injection, logic verification, communication testing and circuit breaker interface testing.
9.1 Visual inspection and wiring verification
Before energizing the relay, verify:
- Correct relay model and ordering code.
- Auxiliary supply voltage.
- CT input connections.
- VT input connections.
- CT polarity.
- Digital input wiring.
- Output contact wiring.
- Breaker trip and close circuits.
- Communication connections.
- Earthing and panel wiring.
Never open-circuit an energized CT secondary.
9.2 Secondary injection testing
A secondary injection test set, such as an OMICRON CMC, can be used to test the relay’s protection functions.
Typical tests include:
| Test | Purpose |
|---|---|
| Phase current injection | Verify 50P and 51P operation |
| Ground current injection | Verify ground-fault elements |
| Negative-sequence injection | Verify 50Q and 51Q |
| Voltage injection | Verify 27 and 59 |
| Frequency injection | Verify 81U and 81O |
| Breaker failure simulation | Verify 50BF logic |
| Reclosing sequence test | Verify 79 operation |
| Arc-flash sensor test | Verify optical detection and trip logic |
| Digital input simulation | Verify external control signals |
| Output contact test | Verify trip, alarm and control outputs |
9.3 Overcurrent protection testing
For 50P and 51P, engineers should verify:
- Pickup current.
- Dropout or reset behavior where applicable.
- Operating time.
- Selected time-current curve.
- Time dial.
- Phase selection.
- Output logic.
- Event and target indications.
For inverse-time elements, test multiple current points rather than checking only one operating point.
9.4 Arc-flash protection testing
For the optional arc-flash system, verify:
- Correct sensor channel assignment.
- Optical sensor operation.
- Sensor loop supervision.
- Light detection.
- Current supervision.
- Trip logic.
- High-speed output operation, where installed.
- Event recording.
Follow SEL’s recommended test procedure and use suitable test equipment. Do not create an actual arc fault to test the protection system.
9.5 End-to-end functional testing
A final functional test should verify the complete protection chain:
CT/VT → SEL-751A → Protection logic → Output contact → Trip circuit → Circuit breaker
Where relevant, also test:
- Breaker auxiliary contacts.
- Trip circuit supervision.
- Reclosing logic.
- SCADA indications.
- Remote control.
- Communication failure alarms.
- Event recording and time synchronization.
10. Event Reports and Disturbance Analysis
The SEL-751A provides event recording and sequential event information that can help engineers understand relay operation.
After a fault, engineers can examine:
- Phase current waveforms.
- Ground and neutral current.
- Voltage waveforms, if available.
- Protection element pickup.
- Trip output status.
- Breaker status.
- Digital input changes.
- Sequence of events.
- Fault duration.
SEL Synchrowave Event software can be used to analyze supported event reports and COMTRADE files.
A systematic review of event records helps identify whether the fault was cleared correctly, whether protection coordination was maintained and whether any unexpected logic operation occurred.
11. SEL-751A vs SEL-751 vs SEL-451
These relays serve related but different applications. Selecting the correct relay requires consideration of protection functions, bay control requirements, communication options and future expansion.
| Feature | SEL-751A | SEL-751 | SEL-451 |
|---|---|---|---|
| Main application | Feeder protection | Advanced feeder protection | Protection, automation and bay control |
| Phase overcurrent | Yes | Yes | Yes |
| Ground overcurrent | Yes | Yes | Yes |
| Directional overcurrent | More limited options | Expanded options | Supported options |
| Arc-flash detection | Optional | Optional | Application/configuration dependent |
| High-impedance fault detection using AST | Not listed as a standard 751A capability | Supported | Do not assume equivalent functionality |
| Fault location | Not listed as a 751A feature | Available | Application dependent |
| Automatic reclosing | Optional | Available options | Available options |
| IEC 61850 | Optional | Available options | Available options |
| Modern digital secondary options | More limited | Expanded options | Variant-dependent |
| Bay control | Basic feeder control | Feeder control | Advanced bay control |
SEL’s official comparison identifies differences in protection elements, arc-flash inputs, data acquisition, event records, GOOSE messaging, synchrophasors and communication protocols. Check the exact ordering configuration rather than relying only on the family name.
Which relay should you choose?
- Select the SEL-751A when maintaining an existing installation, replacing an older relay or working with an established protection design that already uses the 751A.
- Consider the SEL-751 for new feeder protection projects requiring newer protection and communication options.
- Consider the SEL-451 when the application requires more extensive bay automation and control functions.
12. Advantages of the SEL-751A
The SEL-751A offers several practical advantages:
- Integrated feeder protection: Multiple protection functions are available in one relay.
- Flexible hardware: Optional I/O, voltage, communication and arc-flash modules support different applications.
- Arc-flash mitigation: Optional optical detection can provide fast arc-flash protection.
- Automation capabilities: SELogic equations support customized control schemes.
- Reclosing: Optional automatic reclosing supports distribution feeder applications.
- Communication flexibility: Serial and Ethernet options support integration with different control systems.
- Event analysis: Oscillographic and sequential event information assists troubleshooting.
- Harsh-environment operation: SEL specifies an operating temperature range of −40°C to +85°C.
- Retrofit support: Mounting adapters and retrofit kits can simplify replacement projects.
13. Frequently Asked Questions
What is the SEL-751A relay used for?
The SEL-751A is primarily used for industrial and utility feeder protection. It provides overcurrent protection, optional voltage and frequency protection, breaker control, reclosing, monitoring and communication capabilities.
What is the difference between SEL-751 and SEL-751A?
The SEL-751 is the newer feeder relay recommended by SEL for new selections. It adds capabilities such as high-impedance fault detection, fault location, an integrated web server, additional communication options and a touchscreen option. The SEL-751A remains supported and warranted by SEL.
Does the SEL-751A support IEC 61850?
Yes, IEC 61850 is available as an optional communication capability. The exact supported services and configuration should be checked against the relay’s hardware and firmware documentation.
Does the SEL-751A support arc-flash protection?
Yes. The SEL-751A can be ordered with optional fiber-optic arc-flash detector inputs and protection elements. The relevant hardware and sensors must be installed.
How many reclosing shots does the SEL-751A support?
With the optional reclosing feature, the SEL-751A supports up to four reclosing shots before lockout.
Which software is used to configure the SEL-751A?
The SEL-751A is configured using acSELerator QuickSet SEL-5030.
Can the SEL-751A be tested using OMICRON?
Yes. An OMICRON CMC test set can be used for secondary injection and functional testing of the relay’s protection elements, logic and outputs.
Does the SEL-751A support breaker failure protection?
Yes. The relay includes breaker failure protection for one three-pole breaker, subject to the applicable configuration and engineering settings.
Is the SEL-751A still supported by SEL?
SEL states that it will continue to support and warranty the SEL-751A, while recommending the SEL-751 for new selections.
14. Learn SEL Protection Relays and Practical Feeder Protection with Elec-Engg
Understanding a protection relay requires more than knowing its ANSI function numbers. Protection engineers must understand CT and VT circuits, relay settings, coordination, logic, communication and practical testing.
Elec-Engg provides practical power system protection and substation automation training for protection, commissioning, operation and maintenance engineers.
Training topics include:
- SEL protection relays and feeder protection.
- Protection principles and coordination.
- CT and VT circuits.
- Overcurrent and directional overcurrent protection.
- Relay settings and configuration.
- SEL QuickSet software.
- IEC 61850 and substation automation.
- OMICRON CMC relay testing and commissioning.
- Practical protection and control applications.