SEL-351S Relay: Feeder Protection, Settings, Reclosing and Testing

The SEL-351S Protection System from Schweitzer Engineering Laboratories (SEL) is a multifunction protection, automation and control platform designed primarily for utility and industrial distribution feeder applications. It combines directional and nondirectional overcurrent protection, automatic reclosing, breaker monitoring, programmable logic, communications and synchrophasor measurement in one device.

The SEL-351S is particularly useful where engineers need more than conventional feeder overcurrent protection. Its operator interface, optional independent trip/close pushbuttons, Mirrored Bits communications, and integration capabilities make it suitable for advanced feeder control and substation automation schemes.

This guide explains the SEL-351S relay’s applications, protection functions, ANSI device numbers, settings, communication capabilities, engineering workflow and commissioning tests.

SEL-351S Protection System: Complete Guide to Feeder Protection, Applications, Settings and Testing

Table Of Contents
  1. 1. What is the SEL-351S Protection System?
  2. 2. Main protection functions and ANSI device numbers
  3. 3. Automation, control and breaker operation
  4. 4. Communication protocols and substation automation
  5. 5. Monitoring, metering and disturbance recording
  6. 6. SEL-351S relay settings and configuration
  7. 7. SEL-351S configuration using acSELerator QuickSet
  8. 8. SEL-351S testing and commissioning
  9. 9. SEL-351S vs SEL-351 vs SEL-751 vs SEL-451
  10. 10. Common applications and engineering examples
  11. 11. Advantages of the SEL-351S
  12. 12. Frequently asked questions
  13. 13. SEL-351S training and practical engineering

1. What is the SEL-351S Protection System?

The SEL-351S is a microprocessor-based protection system designed to protect and control distribution feeders and associated electrical equipment.

Typical applications include:

  • Medium-voltage distribution feeders.
  • Industrial power distribution systems.
  • Utility substations.
  • Radial and looped distribution networks.
  • Industrial cogeneration facilities.
  • Feeder protection with downstream recloser coordination.
  • Automatic substation restoration schemes.
  • Main-tie-main breaker control applications.
  • Underfrequency load shedding and other programmable control schemes.

The relay combines protection functions with automation, metering, event recording and communication capabilities.

Its principal advantages include:

  • Comprehensive phase and ground overcurrent protection.
  • Directional protection for looped and interconnected networks.
  • Sensitive earth-fault protection options.
  • Four-shot automatic reclosing.
  • Synchronism-check and voltage-check logic.
  • Breaker failure detection.
  • Built-in fault-location calculation.
  • IEEE C37.118 synchrophasor measurement.
  • Mirrored Bits relay-to-relay communications.
  • Optional IEC 61850 integration.
  • Programmable operator controls and optional SafeLock trip/close pushbuttons.

2. Main protection functions and ANSI device numbers

The SEL-351S provides a comprehensive set of feeder protection functions. The availability of individual functions and elements depends on the relay configuration, firmware and application settings.

2.1 Phase overcurrent protection – ANSI 50/51

The relay provides instantaneous and time-overcurrent protection for phase faults.

ANSI 50 – Instantaneous overcurrent

Instantaneous overcurrent elements operate when the measured phase current exceeds a configured pickup threshold.

Typical applications include:

  • High-current phase-to-phase faults.
  • Close-in three-phase faults.
  • High-current feeder fault protection.
  • Fast fault clearing where selectivity permits.

ANSI 51 – Time overcurrent

Time-overcurrent elements provide delayed operation according to the selected characteristic.

The engineer can coordinate the relay with:

  • Downstream feeder relays.
  • Distribution fuses.
  • Reclosers.
  • Upstream transformer protection.
  • Other circuit-breaker protection systems.

Inverse-time characteristics and pickup settings must be selected according to the network fault levels, equipment ratings and protection coordination study.

2.2 Ground overcurrent protection – ANSI 50G/51G and 50N/51N

Ground faults are among the most common faults in distribution systems.

The SEL-351S supports residual-ground and neutral-ground overcurrent protection, with directional control where appropriate.

Applications include:

  • Phase-to-earth faults.
  • High-resistance ground faults, subject to available current sensitivity.
  • Ground-fault backup protection.
  • Protection of grounded distribution systems.

The engineer must distinguish between residual current calculated from phase CTs and current measured through a dedicated neutral or core-balance CT input.

Correct CT connections and polarity are essential for reliable ground-fault detection.

2.3 Negative-sequence overcurrent – ANSI 46

Negative-sequence current is useful for detecting unbalanced system conditions.

The relay provides negative-sequence overcurrent protection for conditions such as:

  • Phase-to-phase faults.
  • Unbalanced loading.
  • Open-phase conditions.
  • Asymmetrical faults.

Negative-sequence elements can provide sensitive detection where phase overcurrent elements may not respond quickly enough.

2.4 Directional overcurrent protection – ANSI 67/67N

Directional overcurrent protection is important in looped distribution systems, interconnected networks and industrial systems with multiple sources.

The SEL-351S uses voltage-polarized directional logic for phase protection and provides ground directional functionality.

One important feature is SEL’s Best Choice Ground Directional Element logic. It is designed to maintain secure and dependable ground directional decisions under different system grounding conditions.

This is particularly relevant to networks using:

  • Solid grounding.
  • Resistance grounding.
  • High-impedance grounding.
  • Ungrounded systems.
  • Petersen coil grounding.

The appropriate directional method and current input arrangement must be selected for the actual grounding system.

2.5 Sensitive earth-fault protection – SEF

The SEL-351S supports low-range neutral-current input options for sensitive earth-fault applications.

This can be useful where conventional phase CT residual current is insufficiently sensitive to detect the required ground-fault current.

Applications include:

  • High-resistance-grounded systems.
  • Ungrounded distribution networks.
  • Petersen coil-grounded systems.
  • Networks requiring sensitive earth-fault detection.

The relay’s low-range neutral-current channel can also support directional control applications, depending on the ordered configuration.

Engineers should verify the exact input range, CT or sensor arrangement and supported directional logic before selecting the relay.

2.6 Voltage protection – ANSI 27/59

Under- and overvoltage elements can be used for feeder protection and control applications.

Typical applications include:

  • Undervoltage load shedding.
  • Abnormal voltage detection.
  • Voltage supervision of control schemes.
  • Alarm generation.
  • Programmable tripping and interlocking logic.

Voltage protection settings should consider normal operating variations, transformer voltage regulation and system operating philosophy.

2.7 Frequency protection – ANSI 81U/81O

The SEL-351S provides frequency protection for distribution and industrial power systems.

Its frequency-related capabilities include multiple levels of underfrequency and overfrequency protection, as well as rate-of-change-of-frequency elements.

Typical applications include:

  • Underfrequency load shedding.
  • Generator and network decoupling schemes.
  • Frequency disturbance monitoring.
  • Programmable load-shedding stages.
  • System restoration logic.

The relay provides up to six levels of frequency elements and four rate-of-change-of-frequency elements, subject to the applicable configuration.

2.8 Rate-of-change-of-frequency protection – ANSI 81R

Rate-of-change-of-frequency (ROCOF) elements detect rapid changes in system frequency.

They can be used in load-shedding and system separation schemes, where a rapid frequency decline may indicate a generation-load imbalance.

ROCOF settings must be selected carefully to avoid unwanted operation during switching events, measurement disturbances or transient conditions.

2.9 Breaker failure protection – ANSI 50BF

Breaker failure protection detects situations where a circuit breaker fails to interrupt the fault current after receiving a trip command.

The SEL-351S provides a fast-dropout breaker failure element and native breaker failure logic.

A typical breaker failure scheme includes:

  1. A protection element detects a fault.
  2. The relay issues a trip command.
  3. Breaker failure logic starts.
  4. Current and/or breaker-status conditions are monitored.
  5. If the breaker fails to clear the fault within the configured time, backup tripping is initiated.

The actual scheme may trip an upstream breaker, operate a bus protection interface or initiate other isolation actions.

The complete protection design must include the appropriate current supervision, breaker auxiliary contacts, timers and trip outputs.

2.10 Automatic reclosing – ANSI 79

Automatic reclosing is an important feature in overhead distribution systems because many faults are temporary.

The SEL-351S supports up to four shots of automatic reclosing.

The reclosing function can include:

  • Programmable dead times.
  • Reclosing sequence control.
  • Synchronism-check supervision.
  • Voltage-check supervision.
  • Manual and automatic supervision.
  • Sequence coordination with downstream reclosers.
  • Reclose lockout logic.

A typical operating sequence is:

  1. A feeder fault occurs.
  2. The relay detects the fault and trips the breaker.
  3. The configured dead time starts.
  4. Voltage and synchronism conditions are checked if required.
  5. The breaker receives a close command.
  6. If the fault has disappeared, the feeder returns to service.
  7. If the fault remains, the protection system trips again and proceeds through the configured sequence.

Correct coordination with downstream reclosers and fuses is essential.

2.11 Second-harmonic blocking

Transformer energization can produce high magnetizing inrush current. This current may be interpreted as a fault by overcurrent protection.

The SEL-351S provides second-harmonic blocking elements that can be used to block selected tripping elements during transformer energization.

The engineer must identify which protection elements should be supervised by the harmonic blocking logic and verify the scheme under realistic inrush conditions.

2.12 Load encroachment

Load encroachment logic helps distinguish heavy-load conditions from fault conditions in applications where the current and voltage operating point may approach protection boundaries.

This improves protection security under heavy loading conditions.

The load encroachment settings should be based on the maximum expected load, minimum operating voltage and system operating limits.

2.13 Fault locator

The SEL-351S includes an impedance-based fault locator.

It estimates the distance to a fault using measured electrical quantities and configured line data.

The fault-location estimate can help maintenance and operations teams identify the likely faulted section and reduce restoration time.

For meaningful results, engineers must enter appropriate line impedance data and consider the effects of fault resistance, source conditions and network configuration.

3. Automation, control and breaker operation

The SEL-351S is not only a protection relay. Its programmable control functions make it useful in substation automation applications.

3.1 Programmable operator controls

The front panel includes operator controls and programmable pushbuttons.

These can be used for functions such as:

  • Local/remote selection.
  • Reclosing enable/disable.
  • Ground protection enable/disable.
  • Hot-line-tag logic.
  • Breaker control.
  • Automatic restoration schemes.
  • Application-specific control commands.

The exact button arrangement and labels depend on the selected hardware and configuration.

3.2 SafeLock independent trip/close pushbuttons

An important feature of the SEL-351S is the optional SafeLock trip/close pushbutton arrangement.

These pushbuttons provide direct breaker control independently of the relay’s normal internal trip/close logic.

Their contacts and indication circuits are separately wired to the rear terminals.

This can be useful for breaker operation and maintenance procedures, including situations where the relay is out of service.

The SafeLock arrangement should be engineered and tested as part of the complete breaker control circuit.

3.3 Main-tie-main automatic transfer schemes

The SEL-351S can be used in main-tie-main applications.

For example, a substation may have two incoming sources, two main breakers and a bus-tie breaker.

A typical scheme may include:

  • Monitoring of both incoming supplies.
  • Detection of source failure.
  • Verification of the healthy source.
  • Opening of the failed-source breaker.
  • Closing of the bus-tie breaker.
  • Interlocking to prevent unintended parallel operation.

SEL provides design templates for two-relay and three-relay main-tie-main applications.

The final logic must be adapted to the actual single-line diagram, interlocking philosophy and utility operating requirements.

3.4 SELogic control equations

SELogic control equations allow engineers to implement customized protection and control logic.

Typical applications include:

  • Trip and close logic.
  • External interlocking.
  • Alarm generation.
  • Reclosing supervision.
  • Breaker status monitoring.
  • Automatic transfer schemes.
  • Communications-assisted protection.
  • Load shedding.

A clear logic design and appropriate documentation are important for future maintenance and troubleshooting.

4. Communication protocols and substation automation

The SEL-351S provides multiple communication options for integration with SCADA systems, protection relays and substation automation platforms.

Supported protocols and interfaces depend on the ordered configuration.

4.1 IEC 61850

IEC 61850 communication can be used to integrate the SEL-351S into a digital substation or conventional SAS architecture.

Depending on the configuration, IEC 61850 can support:

  • MMS client/server communication.
  • GOOSE messaging.
  • Substation monitoring and control.
  • Interoperability with other manufacturers’ IEDs.
  • Integration with station-level SCADA systems.

Engineers can use SEL acSELerator Architect SEL-5032 for IEC 61850 system configuration and documentation.

The actual supported services and options should be verified against the relay’s order code and firmware documentation.

4.2 Mirrored Bits communications

Mirrored Bits is SEL’s relay-to-relay communication technology.

It allows protection and control information to be exchanged between devices.

Typical applications include:

  • Communications-assisted protection.
  • Fast transfer schemes.
  • Automatic restoration.
  • Coordination with downstream recloser controls.
  • Remote interlocking.
  • Breaker and feeder status exchange.

For example, an SEL-351S can coordinate with an SEL-351R recloser control using Mirrored Bits communication.

4.3 Modbus TCP and Modbus RTU

Modbus communication allows the relay to exchange measurements, status information and control data with SCADA or HMI systems.

The available interfaces include Ethernet-based Modbus TCP and serial Modbus RTU.

4.4 DNP3

DNP3 is widely used in utility SCADA systems.

It can provide access to relay measurements, status indications, alarms and control points.

The point mapping and communication parameters must be coordinated with the SCADA system.

4.5 Synchrophasors – IEEE C37.118

The SEL-351S includes a built-in phasor measurement capability.

IEEE C37.118 synchrophasors can be transmitted at rates up to 60 messages per second.

This supports applications such as:

  • Wide-area monitoring.
  • System stability analysis.
  • Voltage and frequency monitoring.
  • Disturbance investigation.
  • Monitoring of interconnected networks.

Synchrophasor applications require appropriate time synchronization and a compatible phasor data concentrator or monitoring platform.

4.6 Other communication features

Depending on the selected hardware and configuration, the relay can provide:

  • Ethernet communication.
  • Dual copper Ethernet ports.
  • Single or dual fiber-optic Ethernet options.
  • EIA-485 serial communication.
  • SNTP time synchronization.
  • FTP and Telnet services.
  • Built-in web server.
  • Parallel Redundancy Protocol (PRP).

The relay’s web server can provide access to basic information such as status, metering, settings and Sequential Events Recorder data. Access requires appropriate authentication.

5. Monitoring, metering and disturbance recording

The SEL-351S includes monitoring functions that help engineers understand system performance and investigate disturbances.

5.1 Breaker monitoring

The relay can monitor breaker operating data, including trip and close operating times.

Its breaker monitoring capabilities include trending information for up to 128 previous operations.

This information can help maintenance teams:

  • Identify changes in breaker operating time.
  • Detect possible mechanical deterioration.
  • Plan preventive maintenance.
  • Compare breaker performance over time.

5.2 Sequential Events Recorder – SER

The Sequential Events Recorder records changes in relay logic and status information.

SER data is useful for reconstructing the sequence of events during a fault or switching operation.

For example, engineers can investigate:

  • Which protection element operated first.
  • When the trip output changed state.
  • Whether the breaker auxiliary contact changed correctly.
  • Whether the reclosing sequence started.
  • Whether an external interlock prevented operation.

5.3 Oscillography and event reports

Event records provide information about voltage, current and relay operation during a disturbance.

Engineers can use these records to investigate:

  • Fault current magnitude.
  • Phase relationships.
  • Ground-fault conditions.
  • Protection operating time.
  • Trip output timing.
  • Breaker operation.

SEL synchroWAVe Event software can be used to display and analyze supported SEL event reports and COMTRADE files.

5.4 Harmonic metering

The SEL-351S supports harmonic metering up to the 16th harmonic.

This can help engineers investigate power-quality issues and identify harmonic content in the measured electrical quantities.

5.5 Voltage sag, swell and interruption monitoring

Voltage sag, swell and interruption (VSSI) recording is available with the applicable firmware option.

This feature helps engineers investigate voltage disturbances over time and assess their effects on industrial loads and distribution networks.

6. SEL-351S relay settings and configuration

Correct configuration is essential for reliable operation. Settings must be calculated using the actual network data and protection philosophy rather than copied directly from another installation.

6.1 CT and VT configuration

Start by confirming the instrument transformer data:

  • CT primary and secondary ratings.
  • CT polarity and connection.
  • Neutral or residual current measurement arrangement.
  • VT primary and secondary ratings.
  • Phase rotation.
  • Nominal system frequency.
  • Voltage connection and grounding arrangement.

Incorrect CT or VT configuration can affect directional protection, metering, fault detection and event analysis.

6.2 Phase overcurrent settings

For phase overcurrent protection, engineers should calculate:

  • Maximum expected load current.
  • Minimum phase fault current.
  • Maximum phase fault current.
  • CT ratio.
  • Pickup current.
  • Instantaneous operating level.
  • Time-overcurrent curve.
  • Time multiplier or time dial.
  • Coordination margin with upstream and downstream devices.

The settings must provide sensitivity to faults while maintaining selectivity during normal operation and external faults.

6.3 Ground overcurrent settings

Ground protection settings depend on the network grounding method.

For example, a solidly grounded network may require a different ground protection philosophy from a resistance-grounded or Petersen coil-grounded system.

The engineer should evaluate:

  • Minimum ground-fault current.
  • Maximum ground-fault current.
  • Neutral CT ratio.
  • Residual current measurement accuracy.
  • Ground directional polarization.
  • Sensitivity and security requirements.

6.4 Directional protection settings

Directional protection requires correct voltage and current reference connections.

Important checks include:

  • Phase rotation.
  • CT polarity.
  • VT polarity.
  • Directional reference quantities.
  • Forward and reverse operating directions.
  • Ground directional logic.
  • Polarization under low-voltage fault conditions.

Directional tests should be performed using appropriate current and voltage injection angles.

6.5 Reclosing settings

The reclosing settings should reflect the utility or industrial operating philosophy.

Typical parameters include:

  • Number of reclosing shots.
  • Dead time for each shot.
  • Reclose enable conditions.
  • Synchronism-check supervision.
  • Voltage-check supervision.
  • Reclose reset time.
  • Reclose lockout conditions.
  • Manual close supervision.
  • Coordination with downstream reclosers.

The engineer must also consider whether the feeder supplies overhead lines, underground cables, transformers or mixed loads.

6.6 Frequency and load-shedding settings

For underfrequency and ROCOF applications, settings should be based on the system study.

The study should consider:

  • Frequency thresholds.
  • Time delays.
  • Rate-of-change thresholds.
  • Load-shedding stages.
  • System recovery requirements.
  • Coordination with generators and other protection devices.

6.7 Communication and logic settings

Communication configuration includes:

  • IP address and Ethernet parameters.
  • Serial communication settings.
  • SCADA protocol configuration.
  • DNP3 or Modbus point mapping.
  • Mirrored Bits configuration.
  • IEC 61850 configuration, if ordered.
  • Time synchronization.
  • Access security.

For programmable logic, engineers should document the input conditions, logic equations, output assignments and interlocks.

7. SEL-351S configuration using acSELerator QuickSet

SEL acSELerator QuickSet SEL-5030 is the main engineering tool used to configure and manage the SEL-351S.

A typical engineering workflow includes:

  1. Connect to the relay through the supported communication interface.
  2. Retrieve the existing relay settings.
  3. Confirm the relay model and firmware.
  4. Configure CT and VT ratios.
  5. Enter the protection settings.
  6. Configure reclosing and breaker failure logic.
  7. Configure programmable operator controls.
  8. Develop SELogic control equations.
  9. Configure communication protocols.
  10. Review settings and logic assignments.
  11. Download the approved settings.
  12. Retrieve the settings again and verify the final configuration.

For IEC 61850 projects, acSELerator Architect SEL-5032 is used for the supported system engineering and configuration tasks.

Important: Always maintain a backup of the original settings and approved final settings. Changes should follow the organization’s engineering approval and management-of-change procedures.

8. SEL-351S testing and commissioning

A complete commissioning program should verify the protection functions, logic, communication, metering and breaker control circuits.

OMICRON CMC test equipment with suitable test software can be used for secondary injection testing.

8.1 Visual and wiring inspection

Before applying test signals:

  • Check the relay model and nameplate.
  • Verify auxiliary supply voltage.
  • Inspect CT and VT wiring.
  • Confirm CT shorting arrangements.
  • Check trip and close circuit wiring.
  • Verify binary input and output connections.
  • Inspect communication connections.
  • Confirm the relay grounding arrangement.

8.2 Secondary current injection

Inject current into the relay and verify the expected pickup and operation of:

  • Phase instantaneous overcurrent.
  • Phase time overcurrent.
  • Ground overcurrent.
  • Negative-sequence overcurrent.
  • Sensitive earth-fault elements, where configured.

Compare measured pickup and operating time with the approved settings and manufacturer tolerances.

8.3 Directional overcurrent testing

Directional protection should be tested using controlled current and voltage injection.

Verify:

  • Forward operation.
  • Reverse restraint.
  • Directional characteristic.
  • Polarizing quantities.
  • Phase directional elements.
  • Ground directional elements.
  • Correct response to different fault types.

Testing only the current pickup is insufficient for a directional protection function.

8.4 Voltage and frequency testing

Where these functions are configured, test:

  • Undervoltage.
  • Overvoltage.
  • Underfrequency.
  • Overfrequency.
  • ROCOF.

Verify pickup, dropout, timers and associated control outputs.

8.5 Automatic reclosing testing

The reclosing function should be tested as a complete sequence.

Verify:

  • Initial trip.
  • Reclosing initiation.
  • Dead-time measurement.
  • Reclose enable conditions.
  • Synchronism-check supervision.
  • Voltage-check supervision.
  • Subsequent shots.
  • Reset conditions.
  • Final lockout.

Testing should include both successful and unsuccessful reclosing scenarios.

8.6 Breaker failure testing

Simulate a breaker failure condition by maintaining the appropriate current or breaker-status conditions after the trip command.

Verify:

  • Breaker failure initiation.
  • Timer operation.
  • Current supervision.
  • Breaker auxiliary contact supervision.
  • Backup trip output.
  • Reset logic.

8.7 Binary input and output testing

Test all configured binary inputs and outputs.

Typical signals include:

  • Breaker open.
  • Breaker closed.
  • External trip.
  • Reclose enable.
  • Local/remote status.
  • Interlocking signals.
  • Alarm outputs.
  • Trip circuit supervision signals, where implemented.

8.8 Communication testing

Verify the required communication interfaces and services:

  • SCADA communication.
  • Modbus or DNP3 point mapping.
  • Mirrored Bits exchange.
  • IEC 61850 services, if configured.
  • Time synchronization.
  • Ethernet redundancy, if used.
  • Remote status and control.

For IEC 61850 projects, check the actual configured datasets, reports, GOOSE subscriptions and control model rather than assuming that successful network connectivity proves the complete configuration.

8.9 End-to-end scheme testing

Where the SEL-351S participates in a multi-relay protection or automation scheme, test the complete system.

For example, a main-tie-main transfer scheme should be tested with the associated relays, breakers, interlocks and communication links.

9. SEL-351S vs SEL-351 vs SEL-751 vs SEL-451

These relays belong to SEL’s broader feeder protection and control portfolio, but they are not identical products.

RelayMain applicationKey characteristics
SEL-351SFeeder protection and controlDirectional overcurrent, reclosing, synchrophasors, expanded operator controls
SEL-351Feeder protectionDistribution protection, overcurrent, automation and communication options
SEL-751Modern feeder protectionFeeder protection with a different feature set and hardware options
SEL-451Protection, automation and bay controlFeeder protection with advanced bay control capabilities

SEL-351S vs SEL-351

The SEL-351S adds a particular combination of operator controls, synchrophasor measurement, communication options and breaker control features.

Although the two products share aspects of the SEL-351 design family, engineers should not assume that settings files, hardware options or every feature are interchangeable.

SEL-351S vs SEL-751

The SEL-751 is another feeder protection relay in SEL’s portfolio.

The best selection depends on the required protection functions, I/O, communication interfaces, installation requirements and future expansion plans.

SEL-351S vs SEL-451

The SEL-451 is positioned as a protection, automation and bay control system.

It may be more appropriate where the application requires broader bay-level control functionality or a different protection and automation arrangement.

Always compare the exact ordering options and current technical documentation before selecting a device.

10. Common applications and engineering examples

Application 1: Utility distribution feeder

A utility distribution feeder requires phase and ground overcurrent protection, directional control, automatic reclosing and coordination with downstream reclosers.

The SEL-351S can provide these functions together with event recording and breaker monitoring.

Application 2: Industrial distribution system

An industrial plant may have multiple incoming sources and interconnected distribution feeders.

Directional overcurrent protection and programmable control logic can help maintain selectivity and support safe operation.

Application 3: Main-tie-main substation

The relay can participate in a main-tie-main automatic transfer scheme.

The scheme can monitor incoming sources, supervise breaker positions and initiate transfer operations according to the approved interlocking philosophy.

Application 4: Underfrequency load shedding

The relay’s frequency elements and programmable logic can be used in staged load-shedding schemes.

The engineer can configure multiple frequency thresholds and time delays to disconnect selected loads when system frequency falls.

Application 5: Sensitive ground-fault detection

For suitable grounding arrangements, the low-range neutral-current input option can support sensitive earth-fault applications.

The CT or sensor arrangement and ground directional method must be selected according to the actual network.

11. Advantages of the SEL-351S

The main advantages include:

  • Multifunction feeder protection in one device.
  • Directional and nondirectional overcurrent protection.
  • Sensitive earth-fault input options.
  • Four-shot automatic reclosing.
  • Breaker failure protection.
  • Built-in fault-location calculation.
  • Programmable automation and control logic.
  • Optional independent SafeLock trip/close pushbuttons.
  • IEEE C37.118 synchrophasor measurement.
  • Mirrored Bits relay-to-relay communications.
  • Optional IEC 61850 integration.
  • Breaker monitoring and event recording.
  • Harmonic metering and optional voltage disturbance recording.

12. Frequently asked questions

What is the SEL-351S relay used for?

The SEL-351S is primarily used for utility and industrial feeder protection, automation and breaker control. It provides overcurrent protection, directional protection, automatic reclosing, monitoring and communication functions.

Does the SEL-351S support directional overcurrent protection?

Yes. It provides phase and ground directional protection capabilities. The directional configuration should be selected according to the network grounding method and CT/VT connections.

Does the SEL-351S support automatic reclosing?

Yes. The relay supports up to four shots of automatic reclosing, with sequence coordination and voltage and synchronism-check logic.

Does the SEL-351S support IEC 61850?

IEC 61850 is available with applicable configurations. Confirm the ordered model and firmware before designing the substation communication architecture.

Can the SEL-351S be used for main-tie-main control?

Yes. SEL provides two-relay and three-relay main-tie-main application design templates for the SEL-351S. The logic must be adapted and tested for the actual substation arrangement.

Does the SEL-351S support synchrophasor measurement?

Yes. It provides IEEE C37.118 synchrophasor measurement, with reporting rates up to 60 messages per second.

Which software is used to configure the SEL-351S?

The main configuration tool is acSELerator QuickSet SEL-5030. acSELerator Architect SEL-5032 is used for supported IEC 61850 engineering tasks.

Can the SEL-351S detect sensitive earth faults?

Yes. Applicable low-range neutral-current input options support sensitive earth-fault applications. The exact capability depends on the ordered configuration and grounding arrangement.

Can the SEL-351S replace an SEL-751?

Not automatically. Both are feeder protection relays, but their functions, hardware options and application capabilities differ. Selection should be based on the project requirements and current technical documentation.

13. SEL-351S training and practical engineering

Understanding a protection relay requires more than reading its data sheet. Engineers should know how to interpret the single-line diagram, calculate protection settings, configure logic, test protection elements and analyze fault records.

At Elec-Engg, practical power system protection and relay engineering training covers subjects such as:

  • Feeder protection principles.
  • Phase and ground overcurrent protection.
  • Directional protection.
  • CT and VT circuits.
  • Relay setting calculations and coordination.
  • Automatic reclosing and breaker failure protection.
  • Relay configuration and programmable logic.
  • Secondary injection testing using OMICRON CMC.
  • Commissioning procedures and event analysis.

Online, structured self-paced and customized company training can be arranged according to the project requirements.

For training information, visit Elec-Engg or contact us directly.