- 1. Introduction to ABB RES670
- 2. What Is a Phasor Measurement Unit?
- 3. Main Applications of ABB RES670
- 4. Main Features of RES670
- 5. RES670 Synchrophasor Measurement
- 6. Time Synchronisation in RES670
- 7. IEEE C37.118 Communication
- 8. IEC 61850 Communication
- 9. Backup Protection Functions
- 10. Protection and Monitoring Functions in More Detail
- 10.1 Directional Phase Overcurrent Protection – OC4PTOC
- 10.2 Directional Residual Overcurrent Protection – EF4PTOC
- 10.3 Undervoltage Protection – UV2PTUV
- 10.4 Overvoltage Protection – OV2PTOV
- 10.5 Underfrequency and Overfrequency Protection
- 10.6 Rate-of-Change-of-Frequency Protection
- 10.7 Power Swing and Out-of-Step Functions
- 11. RES670 Hardware and I/O Configuration
- 12. RES670 Configuration Using PCM600
- 13. Commissioning and Testing of ABB RES670
- 14. Common RES670 Problems and Troubleshooting
- 15. RES670 Compared with Conventional Protection Relays
- 16. RES670 Compared with Other Relion 670 IEDs
- 17. Important Engineering Considerations
- 18. Frequently Asked Questions About ABB RES670
- What is ABB RES670?
- What is the main function of RES670?
- Does RES670 support IEEE C37.118?
- Does RES670 support IEC 61850?
- How many phasors can RES670 report?
- Does RES670 require GPS?
- What is the difference between a PMU and a PDC?
- Can RES670 provide protection?
- Which software is used to configure RES670?
- Can RES670 be used in a digital substation?
- 19. Conclusion
ABB RES670 Phasor Measurement Unit (PMU) – Complete Technical Guide

1. Introduction to ABB RES670
The ABB RES670 Phasor Measurement Unit (PMU) is part of the Relion 670 series of protection and control IEDs. It is designed to measure electrical quantities in power systems and provide time-synchronised phasor data for wide-area monitoring, protection and control applications.
A conventional protection relay measures electrical quantities locally to detect abnormal operating conditions and initiate protective actions. A PMU has an additional role: it measures voltage and current phasors with a common time reference, allowing measurements from different substations to be compared accurately.
RES670 can provide voltage and current phasors, including single-phase phasors and symmetrical components such as positive-, negative- and zero-sequence quantities. Depending on the configuration, it can report up to 32 analog phasors through two data streams.
The device supports synchrophasor communication based on IEEE C37.118 and integrates with substation automation systems using communication protocols such as IEC 61850 and DNP3.0.
RES670 is therefore particularly useful in modern power networks where operators need better visibility of system-wide voltage angles, frequency behaviour, oscillations and dynamic operating conditions.
2. What Is a Phasor Measurement Unit?
A Phasor Measurement Unit is an electronic device that measures electrical waveforms and calculates their corresponding phasors using a precise time reference.
The corresponding phasor represents the magnitude and phase angle of the sinusoidal quantity.
In a conventional measurement system, phase angles are generally referenced to a local measurement reference. In a synchrophasor system, measurements are referenced to a common absolute time reference, making it possible to compare phase angles measured at different locations.
This is the main difference between an ordinary phasor measurement and a synchrophasor measurement.
2.1 Why time synchronisation is important
Consider two substations connected through a long transmission line. Each substation measures its local voltage magnitude and phase angle.
If both measurements use a common time reference, the control centre can compare the phase angles and evaluate the voltage-angle difference between the two locations.
This information can help operators and engineers investigate:
- Power transfer conditions across transmission corridors
- Voltage-angle stability
- Frequency deviations
- Inter-area oscillations
- Disturbances propagating through the network
- Dynamic responses following major switching operations
- System separation and islanding conditions
GPS or an appropriate IRIG-B time reference can be used to establish the required synchronisation, subject to the supported hardware and configuration.

3. Main Applications of ABB RES670
RES670 is intended for applications requiring synchronised electrical measurements and wide-area monitoring.
3.1 Wide-Area Monitoring System (WAMS)
A Wide-Area Monitoring System collects synchrophasor measurements from multiple substations and transfers them to a central monitoring system.
A typical WAMS architecture includes:
- RES670 PMUs installed at selected substations
- GPS or another supported precise time reference
- Communication infrastructure
- Phasor Data Concentrators (PDCs)
- Wide-area monitoring software
- Control-centre visualisation and analysis systems
The PDC collects measurements from multiple PMUs, aligns the data according to their timestamps and forwards the information to monitoring applications.
RES670 provides the measurement data; the PDC and higher-level applications perform data concentration, visualisation and system-wide analysis.
3.2 Transmission Network Monitoring
RES670 can be installed at important transmission substations to monitor voltage and current phasors at different points in the network.
By comparing measurements from different locations, engineers can obtain information about:
- Voltage-angle differences
- Frequency variations
- Transmission corridor loading
- Disturbance propagation
- Dynamic system behaviour
3.3 Power System Stability Monitoring
Synchrophasor measurements can support the analysis of power-system stability.
For example, following the disconnection of a major transmission line or generator, the system may experience changes in voltage angles and frequency.
Measurements from several RES670 devices can help engineers observe the dynamic response of the network and identify abnormal operating conditions.
3.4 Inter-Area Oscillation Monitoring
Large interconnected power systems may experience low-frequency electromechanical oscillations between groups of generators or geographical areas.
RES670 measurements can be used by suitable monitoring applications to analyse:
- Oscillation frequency
- Relative phase-angle movement
- Oscillation damping
- Dynamic responses following disturbances
The PMU provides time-synchronised measurements; specialised applications are required to perform advanced oscillation analysis.
3.5 Post-Disturbance Analysis
Synchrophasor data can help engineers investigate major disturbances by comparing the behaviour of different substations on a common time axis.
This is particularly valuable when conventional event records from separate IEDs are difficult to compare because their time references or sampling arrangements differ.
3.6 Smart Grid Applications
RES670 can contribute to advanced grid-monitoring systems where real-time measurements are used to improve situational awareness and support control decisions.
Examples include:
- Wide-area situational awareness
- Dynamic line and corridor monitoring
- Voltage stability monitoring
- Frequency monitoring
- Disturbance detection
- Advanced control-centre applications
4. Main Features of RES670
The main functions of RES670 include:
- Synchrophasor measurement of AC voltages and currents
- Time-synchronised phase-angle measurement
- Positive-, negative- and zero-sequence phasor reporting
- Single-phase phasor reporting
- IEEE C37.118 communication
- IEEE 1344 protocol support, depending on product version
- Multiple PMU data streams
- Analog and binary data reporting
- Frequency and related measurement reporting
- IEC 61850 station communication
- IEC 61850-9-2 process bus support in applicable configurations
- DNP3.0 communication
- Backup protection functions
- Disturbance recording and event monitoring
- Configurable logic and signal processing
The exact functionality depends on product version, selected configuration, hardware modules and ordering information.
5. RES670 Synchrophasor Measurement
The most important function of RES670 is its ability to provide time-synchronised phasor measurements.
A synchrophasor describes the magnitude and phase angle of an electrical quantity relative to a common time reference.
5.1 Voltage Phasor Measurement
RES670 can measure voltage phasors from connected voltage transformer circuits or supported process-bus measurement sources.
The reported information can include:
- Voltage magnitude
- Voltage phase angle
- Positive-sequence voltage
- Negative-sequence voltage
- Zero-sequence voltage
- Selected single-phase voltage phasors
The selected measurement channels and phasor reporting arrangement must be engineered according to the application.
5.2 Current Phasor Measurement
Current phasors can be used to monitor power-system loading and current relationships at different locations.
Typical applications include:
- Transmission-line current monitoring
- Transformer current monitoring
- Power-flow analysis
- Sequence-current monitoring
- Disturbance analysis
The correct CT ratios, polarity, phase identification and input-channel configuration are essential for accurate measurements.
5.3 Sequence Components
For an unbalanced three-phase system, the phase quantities can be separated into symmetrical components.
The positive-sequence component represents the balanced component with the normal phase rotation.
The negative-sequence component represents the component with the reverse phase rotation.
The zero-sequence component represents the component with equal magnitude and phase in all three phases.
These components are important for analysing unbalanced faults, system asymmetry and abnormal operating conditions.
5.4 Phasor Data Capacity
RES670 product documentation describes configurations supporting up to 32 analog phasors in two different data streams.
The actual number of available phasors and reporting blocks depends on the selected product configuration and version.
6. Time Synchronisation in RES670
Accurate time synchronisation is essential for synchrophasor measurement.
If two PMUs use different time references, their reported phase angles may not be directly comparable. A common time reference is therefore required for meaningful wide-area measurements.
6.1 GPS Synchronisation
A GPS-based time reference provides a common timing source for PMUs installed at geographically separated substations.
The time reference is distributed to the IED using the supported hardware and signal interface.
6.2 IRIG-B Synchronisation
IRIG-B is another commonly used time-synchronisation method in protection and substation automation systems.
RES670 documentation identifies GPS and IRIG-B as supported sources for synchrophasor applications, with the required hardware and configuration.
6.3 Time Synchronisation Engineering
During engineering and commissioning, verify:
- The selected time source
- GPS receiver or IRIG-B interface availability
- Correct time-source configuration
- Synchronisation status
- Time quality and alarm indications
- Consistent time reference across all PMUs
- Correct handling of loss of synchronisation
An incorrect or unreliable time reference can compromise the accuracy of phase-angle comparisons across the network.
7. IEEE C37.118 Communication
IEEE C37.118 is one of the most important communication standards associated with RES670.
It defines communication arrangements for synchrophasor measurement systems.
RES670 uses the standard to transmit phasor measurement information to external applications such as Phasor Data Concentrators.
7.1 PMU Data Frames
The synchrophasor communication stream can contain information such as:
- Phasor measurements
- Frequency
- Rate of change of frequency
- Analog measurements
- Binary status information
- Time information
- Data quality and status indicators
The exact contents depend on the configured reporting blocks and data-stream settings.
7.2 PMU Configuration
The PMU configuration must define the communication and measurement parameters required by the receiving system.
Important engineering parameters include:
- PMU identification
- Data-stream identification code
- Communication port
- IP address and network settings
- TCP or UDP communication mode
- Phasor reporting configuration
- Phasor type
- Phasor representation
- Reporting rate
- Service class
- Analog and binary reporting configuration
The settings must match the configuration expected by the receiving PDC or PMU client.
7.3 TCP and UDP Communication
RES670 supports synchrophasor communication through TCP and UDP arrangements, depending on the selected configuration.
TCP provides a connection-oriented communication method.
UDP can be used for unicast or multicast data transmission, depending on the network and application requirements.
The communication architecture should be designed with appropriate network capacity, latency, redundancy and cybersecurity considerations.
7.4 Multiple PMU Data Streams
RES670 can be configured to transmit multiple data streams.
Different streams can be configured to provide different measurement sets or reporting characteristics, depending on the supported product configuration.
This can be useful when different monitoring applications require different data arrangements.
8. IEC 61850 Communication
RES670 can be integrated into substation automation systems using IEC 61850 communication.
8.1 IEC 61850-8-1
IEC 61850-8-1 is used for station-bus communication.
It supports communication between IEDs and station-level systems through services such as:
- MMS client-server communication
- GOOSE messaging
- Reporting
- Monitoring and control information exchange
This allows RES670 to participate in an existing substation automation architecture.
8.2 IEC 61850-9-2 Process Bus
IEC 61850-9-2 is associated with sampled-value communication in process-bus architectures.
In applicable RES670 versions and configurations, process-bus communication can be used to receive measurement data from merging units.
This makes it possible to integrate RES670 into digital substation architectures where conventional analog CT and VT wiring is replaced or supplemented by sampled-value communication.
The exact supported process-bus arrangement must be checked against the relevant product guide and hardware configuration.
8.3 GOOSE Communication
GOOSE messaging can be used for fast exchange of binary status and control information between IEDs.
For example, RES670 may exchange selected status information with other protection and control devices where the application requires it.
The engineering of GOOSE signals should include correct publisher/subscriber configuration, dataset design, supervision and testing.
9. Backup Protection Functions
Although RES670 is primarily a Phasor Measurement Unit, it also includes a selection of protection and control functions from the Relion 670 platform.
Depending on the configuration, available functions can include:
- Directional phase overcurrent protection
- Directional residual overcurrent protection
- Overvoltage protection
- Undervoltage protection
- Underfrequency protection
- Overfrequency protection
- Rate-of-change-of-frequency protection
- Directional underpower protection
- Directional overpower protection
- Negative-sequence overcurrent protection
- Loss-of-excitation-related protection applications
- Power swing detection and out-of-step-related functions
- Fuse failure supervision
- Current circuit supervision
- Circuit-breaker monitoring
- Disturbance recording
These functions can provide backup protection or supplementary monitoring. RES670 should not automatically be considered a replacement for dedicated primary protection relays. Protection design must be based on the actual application, redundancy philosophy and selected functions.
10. Protection and Monitoring Functions in More Detail
10.1 Directional Phase Overcurrent Protection – OC4PTOC
OC4PTOC provides multi-step directional phase overcurrent protection.
It can be applied as backup protection for transmission and sub-transmission circuits.
The directional element uses voltage and current information to determine the fault direction, subject to the configured polarising method and settings.
10.2 Directional Residual Overcurrent Protection – EF4PTOC
EF4PTOC provides multi-step directional earth-fault protection.
It can be used to detect earth faults and provide backup protection in systems where directional earth-fault protection is required.
Correct CT connections, residual-current measurement and directional polarising arrangements are essential.
10.3 Undervoltage Protection – UV2PTUV
UV2PTUV detects undervoltage conditions using configured voltage thresholds and time delays.
It can support system monitoring and backup protection applications.
10.4 Overvoltage Protection – OV2PTOV
OV2PTOV detects excessive voltage conditions.
It can be used for equipment protection and power-system voltage supervision, depending on the application.
10.5 Underfrequency and Overfrequency Protection
Frequency protection functions can monitor abnormal frequency conditions.
Underfrequency protection is relevant to load-shedding and system-restoration schemes.
Overfrequency protection can be applied where excessive frequency must be detected.
10.6 Rate-of-Change-of-Frequency Protection
Rate-of-change-of-frequency protection monitors how quickly system frequency changes.
This information can be useful in applications involving generation-load imbalance and rapid system disturbances.
10.7 Power Swing and Out-of-Step Functions
Power swing detection and out-of-step protection functions can support monitoring and protection applications in transmission networks.
Their application requires careful coordination with distance protection, system stability studies and the wider protection philosophy.
11. RES670 Hardware and I/O Configuration
RES670 is based on the Relion 670 hardware platform.
The hardware configuration depends on the selected product variant and application requirements.
Typical hardware elements may include:
- Power supply module
- Main processing module
- Optical Ethernet module
- Binary input modules
- Binary output modules
- Combined input/output modules
- Current and voltage measurement inputs
- Time-synchronisation interfaces
- Communication modules
11.1 Optical Ethernet Module
The optical Ethernet module supports communication arrangements such as station-bus communication and synchrophasor data transmission.
Depending on the selected hardware and port allocation, it can be used for:
- IEC 61850-8-1
- IEEE C37.118
- IEC 61850-9-2LE process-bus communication
Port allocation must be planned carefully, especially when redundant station communication and process-bus communication are required.
11.2 Binary Inputs and Outputs
Binary inputs can receive external status signals, while binary outputs can be used for alarms, indications and configured control or protection outputs.
Typical signals may include:
- External blocking
- Breaker status
- Protection operation
- Time synchronisation alarm
- Communication alarm
- Equipment status
The actual I/O arrangement depends on the selected hardware modules.
12. RES670 Configuration Using PCM600
ABB PCM600 is used for engineering and configuration of Relion IEDs, including RES670.
The engineering process includes project creation, IED configuration, communication setup, signal engineering and parameter configuration.
12.1 Creating the PCM600 Project
A typical workflow includes:
- Open PCM600.
- Create a new project.
- Add the RES670 IED.
- Select the correct product version.
- Confirm the IED configuration.
- Import or create the required application configuration.
- Configure communication and measurement channels.
The product version selected in PCM600 must match the installed IED.
12.2 Application Configuration
Application Configuration Tool (ACT) is used to configure the IED application logic.
Typical engineering tasks include:
- Connecting measurement signals
- Configuring protection functions
- Assigning binary inputs and outputs
- Creating internal logic
- Configuring status and alarm signals
- Connecting signals to communication functions
12.3 Parameter Setting
Parameter settings should be developed from the approved protection and measurement design.
Important settings include:
- CT and VT ratios
- Primary system quantities
- Measurement-channel selection
- Phasor reporting parameters
- Time-synchronisation settings
- Communication settings
- Protection function settings
- Binary signal configuration
12.4 Signal Matrix
Signal Matrix Tool (SMT) is used to connect internal signals with physical inputs and outputs and other relevant signal destinations.
Correct signal mapping is essential for reliable operation and monitoring.
12.5 IEC 61850 Engineering
IEC 61850 engineering includes configuration of logical devices, logical nodes, datasets, report control blocks and GOOSE communication where required.
The SCL engineering workflow should be coordinated with the station-level engineering system and the other IEDs in the substation.
13. Commissioning and Testing of ABB RES670
Commissioning must verify both the measurement performance and the communication functionality of the PMU.
A suitable test plan should include the following areas.
13.1 Visual and Hardware Inspection
Check:
- Correct IED type and product version
- Hardware modules and slot positions
- Auxiliary DC supply
- CT and VT wiring
- Optical communication connections
- Earthing arrangements
- Binary input and output wiring
- Time-synchronisation connections
13.2 CT and VT Circuit Testing
Verify:
- CT ratio and polarity
- Phase identification
- VT ratio and polarity
- Phase rotation
- Voltage and current channel assignment
- Correct primary and secondary scaling
Incorrect polarity or phase assignment can produce incorrect phasor angles even when the measured magnitudes appear reasonable.
13.3 Time-Synchronisation Testing
Verify the selected GPS or IRIG-B source and confirm that the IED indicates a valid synchronisation status.
Check the behaviour of the device when the time reference is disconnected or becomes invalid.
The test should also verify that the receiving PMU application recognises the time-quality information correctly.
13.4 Phasor Measurement Testing
Use a suitable relay test set to inject known voltage and current signals.
Verify:
- Phase-to-neutral voltage magnitudes
- Phase-to-phase voltage magnitudes, where applicable
- Current magnitudes
- Phase angles
- Phase sequence
- Positive-sequence quantities
- Negative-sequence quantities
- Zero-sequence quantities
- Frequency measurements
Compare the measured results with the expected values.
13.5 IEEE C37.118 Communication Testing
Verify that the PMU can establish communication with the intended client or PDC.
Check:
- IP address and network configuration
- Port settings
- Device identification code
- Data-stream identification
- TCP or UDP connection
- Reporting rate
- Phasor configuration
- Data-frame reception
- Timestamp and data-quality information
A PMU connection tester or compatible PDC software can be used to verify the communication stream.
13.6 IEC 61850 Testing
Where IEC 61850 is used, verify:
- Station-bus connectivity
- MMS communication
- Report configuration
- GOOSE publishing and subscription
- Signal mapping
- SCL configuration consistency
- Communication supervision
13.7 Protection Function Testing
If protection functions are enabled, test them according to the approved protection test plan.
Verify pickup values, operating times, directional behaviour, blocking signals, trip logic and alarm indications as applicable.
13.8 Disturbance Recording and Event Testing
Verify the configured disturbance recording and event functions.
Check trigger conditions, recording channels, timestamps, event indications and retrieval of the recorded files.
14. Common RES670 Problems and Troubleshooting
Problem 1: No Synchrophasor Data Received by the PDC
Possible causes:
- Incorrect IP configuration
- Wrong communication port
- Incorrect device identification code
- TCP or UDP configuration mismatch
- Firewall or network routing issue
- Incorrect PMU data-stream configuration
Recommended checks:
- Verify the physical Ethernet connection.
- Check the IED IP address and subnet mask.
- Confirm the communication port.
- Verify the PDC configuration.
- Check the PMU communication status.
- Inspect the network using suitable diagnostic tools.
Problem 2: Incorrect Phase Angle Measurements
Possible causes:
- Incorrect CT polarity
- Incorrect VT polarity
- Wrong phase assignment
- Incorrect phase reference configuration
- Incorrect measurement-channel mapping
- Invalid time reference
Recommended checks:
- Verify CT and VT wiring diagrams.
- Confirm phase rotation.
- Check voltage and current channel assignments.
- Verify the time-synchronisation status.
- Compare injected values with the reported phasors.
Problem 3: Time Synchronisation Alarm
Possible causes:
- GPS antenna or receiver problem
- IRIG-B wiring issue
- Incorrect time-source selection
- Loss of timing signal
- Hardware interface problem
Check the time-source configuration, wiring, receiver status and IED time-synchronisation indications.
Problem 4: Missing Phasors in the Data Stream
Possible causes:
- Incorrect phasor selection
- Incomplete PMU reporting configuration
- Incorrect reporting-block connections
- Unsupported configuration
- Incorrect data-stream setup
Review the PMU configuration and the associated reporting blocks in the engineering project.
Problem 5: IEC 61850 Communication Failure
Possible causes:
- Incorrect IP settings
- Port allocation conflict
- Incorrect SCL file
- Incorrect GOOSE configuration
- Network or switch configuration problem
- Communication interface not enabled
Check the station communication settings and verify the configuration against the approved SCL engineering files.
15. RES670 Compared with Conventional Protection Relays
RES670 has a different primary purpose from conventional protection relays such as REG670, RET670 and REL670.
| Feature | RES670 | Conventional protection IED |
|---|---|---|
| Main purpose | Synchrophasor measurement and monitoring | Fault detection and protection |
| Time reference | Precise common time reference for synchrophasors | Time synchronisation for events and records |
| Phase-angle reporting | Central feature | Usually local measurement and protection |
| IEEE C37.118 | Key communication capability | Not normally a primary function |
| Wide-area monitoring | Designed for PMU applications | Usually supplementary |
| Protection functions | Selected backup functions | Application-specific primary protection |
| Typical integration | PMU/PDC/WAMS architecture | Protection and substation automation architecture |
RES670 and conventional protection relays can complement each other in a modern substation.
16. RES670 Compared with Other Relion 670 IEDs
| ABB IED | Main application |
|---|---|
| REG670 | Generator protection |
| RET670 | Transformer protection |
| RED670 | Line differential protection |
| REL670 | Distance protection |
| REB670 | Busbar protection |
| REC670 | Bay control and protection |
| RES670 | Phasor measurement unit |
RES670 is the specialised member of this product family for synchrophasor measurement and wide-area monitoring applications.
17. Important Engineering Considerations
When designing an RES670 application, engineers should consider the following points:
Measurement accuracy: CT and VT accuracy, wiring, scaling and phase identification directly affect measurement quality.
Time reference: All PMUs participating in a wide-area monitoring system should use an appropriate common time reference.
Communication network: The network must support the required data rate, latency, availability and redundancy.
PDC compatibility: The receiving PDC must be configured to recognise the PMU identification, data streams and reporting characteristics.
Cybersecurity: Network access, device configuration and communication paths should follow the organisation’s cybersecurity policy.
Protection coordination: Backup protection functions must be coordinated with the primary protection system and should not be enabled without an approved protection design.
Product version: Always confirm the exact RES670 product version, hardware configuration and supported functions using the relevant ABB product guide and manuals.
18. Frequently Asked Questions About ABB RES670
What is ABB RES670?
ABB RES670 is a Phasor Measurement Unit (PMU) from the Relion 670 series. It measures AC voltage and current phasors and provides synchronised measurement data for wide-area monitoring, protection and control applications.
What is the main function of RES670?
Its main function is to provide time-synchronised voltage and current phasor measurements for monitoring power-system conditions across geographically separated locations.
Does RES670 support IEEE C37.118?
Yes. RES670 supports synchrophasor communication based on IEEE C37.118. The supported standard revision and capabilities depend on the product version.
Does RES670 support IEC 61850?
Yes. RES670 supports IEC 61850 station communication, and applicable versions and configurations support IEC 61850-9-2 process-bus functionality.
How many phasors can RES670 report?
The product documentation describes configurations supporting up to 32 analog phasors in two data streams. Actual capacity depends on the selected configuration and version.
Does RES670 require GPS?
A precise common time reference is required for synchrophasor applications. RES670 documentation identifies GPS and IRIG-B as supported time-synchronisation sources, subject to the required hardware and configuration.
What is the difference between a PMU and a PDC?
A PMU measures and transmits time-synchronised phasor data. A Phasor Data Concentrator receives data from multiple PMUs, aligns the measurements by timestamp and forwards the data to monitoring applications.
Can RES670 provide protection?
Yes. RES670 includes selected protection and control functions from the Relion 670 platform. However, its primary purpose is synchrophasor measurement, and the suitability of its protection functions must be assessed for each application.
Which software is used to configure RES670?
ABB PCM600 is used for engineering, configuration and parameterisation of RES670.
Can RES670 be used in a digital substation?
Yes. Applicable hardware and product versions support integration with IEC 61850-based substation automation and process-bus architectures.
ABB RES670 Phasor Measurement

19. Conclusion
The ABB RES670 Phasor Measurement Unit is an important component of modern power-system monitoring infrastructure. Its ability to provide synchronised voltage and current phasors makes it suitable for wide-area monitoring, dynamic system analysis and advanced grid applications.
By combining synchrophasor measurement, IEEE C37.118 communication, IEC 61850 integration and selected protection functions, RES670 can help utilities improve their visibility of power-system operating conditions.
For protection engineers, commissioning engineers and substation automation specialists, understanding RES670 requires knowledge of CT and VT measurement circuits, time synchronisation, PMU configuration, IEEE C37.118 communication, IEC 61850 engineering and testing procedures.
Practical experience with PCM600, test equipment and PMU client or PDC software is particularly valuable when commissioning and troubleshooting an RES670 installation.
Technical note: Function availability, communication options and hardware arrangements are product-version and order-code dependent. Always refer to the applicable ABB/Hitachi Energy RES670 Product Guide, Application Manual, Technical Manual and Commissioning Manual for the installed IED.