Siemens SIPROTEC 5 7SJ85 Feeder Protection Relay: Functions, Applications, Settings & DIGSI 5 Engineering
Introduction
The Siemens SIPROTEC 5 7SJ85 is a modular numerical protection relay designed for feeder protection, overcurrent protection and related protection and automation applications in electrical power systems.
As part of the Siemens SIPROTEC 5 family, the 7SJ85 provides configurable hardware, advanced protection functions, measurement capabilities, communication interfaces and integration with modern substation automation systems.
The relay is particularly relevant to medium-voltage distribution networks, industrial power systems and utility substations where flexible protection and control engineering is required.
Using Siemens DIGSI 5 engineering software, protection engineers can configure the device hardware, assign protection functions, enter relay settings, develop logic schemes, configure IEC 61850 communication and perform device diagnostics.
This article examines the SIPROTEC 5 7SJ85, including its applications, protection functions, engineering procedures, settings and commissioning requirements.
1. What Is the SIPROTEC 5 7SJ85?
The SIPROTEC 5 7SJ85 is a feeder protection IED with a modular hardware concept.
It is designed to provide protection, control, monitoring and communication functions for electrical distribution systems.
Its modular architecture allows the hardware configuration to be adapted to project requirements, subject to the available device variants and ordering options.
Typical applications include:
- Medium-voltage feeder protection
- Industrial distribution systems
- Incoming and outgoing feeder protection
- Cable and overhead line protection
- Transformer backup protection
- Distribution network protection
- Power plant auxiliary systems
- Substation protection and automation
The device can be integrated into conventional and IEC 61850-based substation automation architectures.
2. Main Features of SIPROTEC 7SJ85
The main engineering advantages of the 7SJ85 include:
Modular Hardware Architecture
The device offers a configurable hardware arrangement, allowing engineers to select suitable input/output and communication options for the intended application.
Numerical Protection Functions
The relay provides protection functions for detecting short circuits, earth faults, overloads and other abnormal operating conditions.
DIGSI 5 Engineering
All engineering activities are performed using DIGSI 5, including device configuration, protection parameterization and communication engineering.
Substation Automation Integration
The relay supports integration with substation automation systems using supported communication protocols and interfaces.
Logic Configuration
CFC engineering can be used to implement customized logic, interlocking, alarms and signal processing where supported.
Measurement and Event Recording
The relay provides measurement and event information to support operational supervision and fault analysis.
3. Protection Functions of SIPROTEC 7SJ85
The available protection functions depend on the device order variant, firmware and configured functional scope.
3.1 Phase Overcurrent Protection – ANSI 50/51
Phase overcurrent protection is a fundamental function in feeder protection applications.
The relay monitors phase currents and detects conditions where current exceeds the configured operating threshold.
Two main operating characteristics are used.
Instantaneous Overcurrent Protection (50)
The function operates when the current exceeds a predefined high-set threshold.
It is typically used for fast short-circuit protection.
Time Overcurrent Protection (51)
The relay operates with a configured time delay or inverse-time characteristic.
Common characteristic types include:
- Definite time
- Normal inverse
- Very inverse
- Extremely inverse
The correct characteristic is selected according to the network protection coordination study.
3.2 Earth-Fault Protection – ANSI 50N/51N
Earth-fault protection detects residual current caused by phase-to-earth faults.
The residual current is calculated as:
3I₀ = Iₐ + Iᵦ + I꜀
The measurement can be obtained through the summation of phase CT currents or a dedicated residual current transformer, depending on the installation.
Earth-fault settings must consider the network neutral earthing method and the minimum expected earth-fault current.
3.3 Directional Overcurrent Protection – ANSI 67
Directional overcurrent protection determines the direction of a fault in addition to measuring its current magnitude.
It is useful in:
- Parallel feeder networks
- Ring networks
- Networks with multiple sources
- Industrial interconnected systems
- Networks with distributed generation
Correct current and voltage reference configuration is essential for dependable directional operation.
3.4 Directional Earth-Fault Protection – ANSI 67N
Directional earth-fault protection helps identify the direction of ground faults.
It is particularly important in systems with isolated, compensated or resistance-earthed neutral arrangements.
Depending on the selected protection principle, the relay can use residual current, residual voltage and directional characteristics to determine the fault direction.
3.5 Thermal Overload Protection – ANSI 49
Thermal overload protection monitors the heating effect caused by prolonged current loading.
It can be applied to protect cables, feeders and other electrical equipment against excessive thermal stress.
The thermal model and equipment parameters must be configured according to the protected asset.
3.6 Negative-Sequence Protection – ANSI 46
Negative-sequence protection detects current unbalance in three-phase electrical systems.
Possible causes include:
- Phase-to-phase faults
- Open conductors
- Unbalanced loading
- Incorrect phase connections
It can provide additional protection and supervision for electrical equipment.
3.7 Circuit Breaker Failure Protection – ANSI 50BF
Circuit breaker failure protection supervises whether the circuit breaker successfully interrupts the fault current after a trip command.
If the fault current persists or the configured failure conditions are fulfilled, the relay can initiate backup tripping through the protection scheme.
3.8 Automatic Reclosing – ANSI 79
Automatic reclosing is commonly used on overhead distribution feeders.
It allows the circuit breaker to close automatically after a temporary fault has been cleared.
Important engineering parameters include:
- Dead time
- Reclaim time
- Number of shots
- Reclosing sequence
- Protection function interaction
- Synchronism and voltage supervision, where required
3.9 Voltage Protection – ANSI 27/59
Where the device configuration includes the required voltage measurement and functions, undervoltage and overvoltage protection can be applied.
These functions detect abnormal voltage conditions and can initiate alarms or trip commands according to the protection scheme.
4. Applications of SIPROTEC 7SJ85
4.1 Utility Distribution Substations
The 7SJ85 can be used in medium-voltage distribution substations to protect incoming and outgoing feeders.
The protection scheme may include phase overcurrent, earth-fault protection, directional elements and circuit breaker failure protection.
4.2 Industrial Power Systems
Industrial facilities require dependable protection for their internal electrical distribution networks.
The 7SJ85 can be applied to feeders supplying:
- Industrial transformers
- Motor control centers
- Distribution boards
- Production facilities
- Auxiliary electrical systems
4.3 Cable Protection
The relay can provide overcurrent and earth-fault protection for medium-voltage cable feeders.
Protection settings should consider cable ampacity, short-circuit withstand capability, fault current and upstream/downstream selectivity.
4.4 Overhead Line Protection
For suitable distribution line applications, the 7SJ85 can provide overcurrent and earth-fault protection, together with automatic reclosing where supported and configured.
4.5 Transformer Backup Protection
The relay can provide backup phase and earth-fault protection for transformers.
Coordination with transformer differential protection and downstream feeder protection is essential.
5. SIPROTEC 7SJ85 Protection Settings
Correct parameterization is essential for dependable operation.
Settings must be determined through an engineering study rather than copied from another installation.
5.1 Current Transformer Configuration
The first step is to enter the correct CT primary and secondary ratings.
Example:
- CT primary rating: 800 A
- CT secondary rating: 1 A
The configured ratio must correspond to the installed CT and the actual relay current input.
Engineers should also verify:
- CT polarity
- Phase identification
- Secondary wiring
- CT accuracy class
- CT saturation performance
5.2 Phase Overcurrent Pickup
Assume a feeder maximum operating current of 500 A.
If an illustrative pickup factor of 1.2 is selected:
Ipickup = 500 × 1.2 = 600 A
The final pickup must be checked against:
- Maximum load current
- Emergency loading conditions
- Minimum fault current
- CT characteristics
- Downstream protection settings
- Equipment thermal limits
5.3 Earth-Fault Pickup
Earth-fault pickup depends on the neutral earthing arrangement.
For example, a resistance-earthed network may have a limited earth-fault current, requiring more sensitive protection than a solidly earthed network.
The engineer must consider normal residual current, measurement sensitivity and fault clearance requirements.
5.4 Directional Protection Settings
Directional elements require correct configuration of:
- Directional reference quantities
- Polarization method
- Operating characteristic
- Forward and reverse direction
- Pickup current
- Operating time
The relay should be tested using suitable current and voltage injection before being placed into service.
5.5 Protection Coordination
The 7SJ85 must coordinate with other protection devices in the electrical network.
A coordination study should consider:
- Maximum and minimum fault levels
- Transformer impedance
- Feeder impedance
- CT ratios
- Circuit breaker clearing time
- Downstream protection characteristics
- Upstream backup protection
Time-current curves are important tools for verifying selectivity.
6. DIGSI 5 Engineering and Configuration
DIGSI 5 is Siemens’ engineering software for configuring SIPROTEC 5 protection devices.
A typical 7SJ85 engineering procedure includes the following activities.
Step 1: Create a Project
Open DIGSI 5 and create a new project.
Enter the relevant project identification and engineering information.
Step 2: Insert the 7SJ85
Select the appropriate 7SJ85 device and add it to the project.
Check the device variant against the actual hardware ordering information.
Step 3: Configure the Hardware
Configure the available hardware according to the project requirements.
This may include:
- Current inputs
- Voltage inputs
- Binary inputs
- Binary outputs
- Communication interfaces
- Additional hardware modules
Step 4: Configure Measurement Transformers
Enter CT and VT ratings where applicable.
Check the measurement connections and phase assignments.
Step 5: Configure Protection Functions
Enable the protection functions required by the approved protection philosophy.
Configure pickup levels, time delays, characteristics and associated parameters.
Step 6: Develop Protection and Control Logic
Use the available engineering functions to implement:
- Trip logic
- Blocking logic
- Alarm logic
- Circuit breaker control
- External interlocking
- Protection function interactions
CFC can be used for customized automation and protection logic.
Step 7: Configure Communication
Configure the required station communication and IEC 61850 functions.
This includes logical node mapping, reports, GOOSE datasets and communication parameters where applicable.
Step 8: Validate and Download
Check the project configuration and consistency before transferring it to the physical relay.
After downloading, verify the device configuration and perform the required functional tests.
7. IEC 61850 Communication in SIPROTEC 7SJ85
IEC 61850 is a key component of modern substation automation systems.
The 7SJ85 can be integrated into IEC 61850-based architectures according to its communication options and firmware capabilities.
Important communication services include:
IEC 61850 MMS
Used for monitoring, measurements, reports and control through compatible station-level clients.
GOOSE Messaging
Used for fast communication between protection and control IEDs.
Typical applications include:
- Circuit breaker interlocking
- Protection blocking
- Trip signal exchange
- Breaker status communication
- Automation logic
SCL Configuration
SCL files are used to exchange IEC 61850 engineering information between compatible engineering tools.
Time Synchronization
Accurate time synchronization supports event analysis and disturbance investigation.
8. SIPROTEC 7SJ85 Testing and Commissioning
A complete commissioning procedure should verify both the relay’s protection performance and the external electrical circuits.
8.1 Hardware Inspection
Verify:
- Relay model and configuration
- Auxiliary power supply
- CT connections
- VT connections, if used
- Binary input wiring
- Binary output wiring
- Communication connections
8.2 Secondary Injection Testing
Using an appropriate relay test set, perform tests such as:
- Phase overcurrent pickup
- Overcurrent operating time
- Inverse-time characteristic
- Earth-fault pickup
- Directional protection
- Negative-sequence protection
- Thermal protection
The tests should follow approved test plans and manufacturer guidance.
8.3 Binary Input and Output Tests
Check the response of all required signals.
Examples:
- Circuit breaker open status
- Circuit breaker closed status
- External blocking
- Protection trip
- Alarm outputs
- Interlocking signals
8.4 Trip Circuit Testing
Verify the complete trip chain from the relay output through the intermediate circuits to the circuit breaker trip coil.
Confirm correct breaker operation and feedback indication.
8.5 IEC 61850 Testing
Verify:
- MMS communication
- GOOSE publishing and subscription
- Report configuration
- Signal mapping
- Communication supervision
- Time synchronization
8.6 Disturbance Record Analysis
Retrieve and analyze disturbance records after testing.
SIGRA can be used to examine fault waveforms, current and voltage behavior and relay operation.
9. Difference Between SIPROTEC 7SJ82 and 7SJ85
Both relays belong to the SIPROTEC 5 feeder protection family, but their hardware and engineering characteristics differ.
| Feature | 7SJ82 | 7SJ85 |
|---|---|---|
| Platform | SIPROTEC 5 | SIPROTEC 5 |
| Main application | Feeder protection | Feeder protection |
| Hardware concept | Compact device configuration | Modular device configuration |
| Engineering | DIGSI 5 | DIGSI 5 |
| Protection functions | Feeder protection | Feeder protection |
| Expansion options | Device-specific | Modular options |
| Typical use | Distribution feeders | Flexible feeder protection applications |
The actual protection functions, hardware modules and communication options must be verified against the selected ordering variant and Siemens technical documentation.
10. Common Problems in 7SJ85 Engineering
Some problems encountered during configuration and commissioning include:
- Incorrect hardware configuration in DIGSI 5.
- CT ratio mismatch.
- Incorrect current transformer polarity.
- Incorrect phase sequence.
- Improper earth-fault measurement configuration.
- Incorrect directional protection settings.
- Protection coordination problems.
- Incorrect trip logic.
- Missing circuit breaker status feedback.
- Incorrect IEC 61850 GOOSE mapping.
- Communication configuration errors.
- Incomplete secondary injection testing.
Proper engineering documentation, systematic testing and detailed commissioning records help prevent these issues.
11. SIPROTEC 7SJ85 Training by Elec-Engg
Elec-Engg provides technical training in Siemens SIPROTEC 5 protection relays, DIGSI 5 engineering and substation automation.
Our training is designed for protection engineers, commissioning engineers, electrical maintenance engineers and substation automation specialists.
Training subjects include:
- SIPROTEC 5 hardware architecture
- 7SJ85 feeder protection
- DIGSI 5 project engineering
- Hardware and module configuration
- Overcurrent protection
- Earth-fault protection
- Directional protection
- Protection coordination
- CFC logic engineering
- IEC 61850 communication
- GOOSE engineering
- Secondary injection testing
- Omicron CMC and Test Universe
- Commissioning and troubleshooting
Training Formats
Online Training: Structured technical lessons and practical engineering demonstrations.
Self-Paced Training: Recorded courses, technical documents, exercises and assessments.
Face-to-Face Training: Practical classroom courses for engineering professionals.
Customized In-House Training: Tailored programs based on company requirements, installed devices and real project applications.
For Siemens SIPROTEC 5 training and technical courses, visit:
Conclusion
The Siemens SIPROTEC 5 7SJ85 is a modular feeder protection IED designed for flexible protection and automation applications in electrical distribution systems.
Its engineering capabilities, protection functions and integration into modern substation automation systems make it suitable for a range of utility and industrial applications.
For protection engineers, understanding the device architecture, protection settings, DIGSI 5 configuration, IEC 61850 communication and commissioning procedures is essential for reliable operation.