Siemens SIPROTEC 5 7SJ86 Relay: Line Backup Protection & Functions

Siemens SIPROTEC 5 7SJ86 Protection Relay: Line Backup Protection, Functions, Applications & DIGSI 5 Engineering

Introduction

The Siemens SIPROTEC 5 7SJ86 is a numerical protection relay designed for line backup protection and overcurrent protection applications in electrical power systems.

It belongs to the SIPROTEC 5 family of intelligent electronic devices (IEDs), which provide advanced protection, control, monitoring and communication capabilities for modern electrical substations.

The 7SJ86 is intended for applications where dependable backup protection and flexible integration into substation automation systems are required.

Using Siemens DIGSI 5 engineering software, protection engineers can configure the device, parameterize protection functions, develop logic schemes, configure communication and perform commissioning activities.

This article explains the main characteristics, protection functions, applications, engineering procedures and testing requirements of the SIPROTEC 5 7SJ86.

1. What Is the SIPROTEC 5 7SJ86?

The SIPROTEC 5 7SJ86 is a line protection device designed primarily for backup protection applications.

It can be used in electrical networks where overcurrent and associated protection functions are required to provide additional protection against faults.

Typical applications include:

  • High-voltage and medium-voltage line backup protection
  • Overhead line protection
  • Cable feeder protection
  • Transformer backup protection
  • Industrial power distribution
  • Utility substations
  • Distribution network protection

The device can be integrated into modern substation automation systems using its supported communication interfaces and protocols.

2. Main Characteristics of SIPROTEC 7SJ86

The 7SJ86 belongs to the modular SIPROTEC 5 platform.

Its main engineering characteristics include:

Numerical Protection

The device processes electrical measurements and evaluates protection conditions using configurable protection functions.

Modular Hardware

The SIPROTEC 5 platform provides configurable hardware arrangements according to the selected device variant.

DIGSI 5 Engineering

Protection settings, hardware configuration, logic engineering and communication configuration are performed using DIGSI 5.

Communication Integration

The device can exchange protection and operational information with other compatible IEDs and substation automation systems.

Monitoring and Diagnostics

Measurement values, device status and event information support troubleshooting and operational supervision.

3. Protection Functions of SIPROTEC 7SJ86

The actual protection function scope depends on the device variant, firmware and configured functional options.

3.1 Phase Overcurrent Protection – ANSI 50/51

Phase overcurrent protection detects excessive current caused by short circuits and other abnormal operating conditions.

The function includes two important operating principles.

Instantaneous Overcurrent Protection – ANSI 50

The relay operates when current exceeds a configured high-set threshold.

It is commonly used for fast fault clearance.

Time Overcurrent Protection – ANSI 51

The relay operates according to a configured time characteristic.

Possible characteristics include:

  • Definite time
  • Normal inverse
  • Very inverse
  • Extremely inverse

The selection depends on the protection coordination study.

3.2 Earth-Fault Protection – ANSI 50N/51N

Earth-fault protection detects residual current resulting from phase-to-earth faults.

Residual current can be calculated as:

3I₀ = Iₐ + Iᵦ + I꜀

The measurement can be obtained from phase CT summation or a dedicated residual CT, depending on the installation.

This function is essential for detecting ground faults in overhead lines and cable networks.

3.3 Directional Overcurrent Protection – ANSI 67

Directional overcurrent protection determines whether a fault is located in the forward or reverse direction.

It is particularly useful in:

  • Parallel transmission lines
  • Ring networks
  • Networks with multiple sources
  • Interconnected industrial power systems
  • Networks with distributed generation

The correct directional reference and polarization settings are essential for dependable operation.

3.4 Directional Earth-Fault Protection – ANSI 67N

Directional earth-fault protection determines the direction of earth faults using the configured residual measurement quantities.

It is useful in networks with:

  • Isolated neutral
  • Compensated neutral
  • Resistance-earthed neutral
  • Multiple interconnected sources

The correct operating principle must be selected according to the network earthing arrangement.

3.5 Thermal Overload Protection – ANSI 49

Thermal overload protection monitors the thermal stress caused by current loading.

It can be used to protect electrical equipment against prolonged overload conditions.

3.6 Negative-Sequence Overcurrent Protection – ANSI 46

Negative-sequence protection detects current unbalance.

Possible causes include:

  • Phase-to-phase faults
  • Open-phase conditions
  • Unbalanced loading
  • Incorrect phase connections

3.7 Circuit Breaker Failure Protection – ANSI 50BF

Circuit breaker failure protection supervises the successful interruption of fault current following a trip command.

If the circuit breaker fails to clear the fault, the protection scheme can initiate backup tripping.

3.8 Automatic Reclosing – ANSI 79

Automatic reclosing is particularly important for overhead transmission and distribution lines.

The function can initiate automatic circuit breaker closing after a configured dead time.

Important parameters include:

  • Dead time
  • Reclaim time
  • Number of shots
  • Reclosing sequence
  • Protection interaction
  • Synchronism supervision, where required

3.9 Voltage Protection – ANSI 27/59

Where the selected configuration provides the required voltage measurement and protection functions, the relay can supervise undervoltage and overvoltage conditions.

These functions can be used for network protection and automation.

4. Applications of SIPROTEC 7SJ86

4.1 Transmission Line Backup Protection

The 7SJ86 can be considered for backup protection of transmission and sub-transmission lines.

Backup protection is necessary to provide an additional protection layer if the primary protection system or associated circuit breaker fails.

The backup scheme must be coordinated with the main line protection, neighboring protection devices and the network fault-clearing philosophy.

4.2 Overhead Line Protection

The relay can be used in suitable overhead line protection applications requiring overcurrent and earth-fault protection.

Automatic reclosing may also be included where supported and required by the protection scheme.

4.3 Cable Feeder Protection

The 7SJ86 can provide overcurrent and earth-fault protection for suitable cable circuits.

Protection settings must consider:

  • Cable rated current
  • Short-circuit withstand capability
  • Minimum and maximum fault current
  • Cable charging current
  • Network earthing
  • Protection coordination

4.4 Transformer Backup Protection

The device can be used to provide backup overcurrent and earth-fault protection for transformers.

It should be coordinated with transformer differential protection and other associated protection functions.

4.5 Industrial Power Networks

Industrial power networks may contain multiple sources, transformers, feeders and interconnected distribution systems.

The relay can be applied in suitable protection schemes to improve fault detection and backup protection.

5. Line Backup Protection Principles

Backup protection is an important part of a dependable power system protection philosophy.

A typical line protection arrangement may include:

  • Main line differential protection
  • Main distance protection
  • Backup overcurrent protection
  • Circuit breaker failure protection
  • Automatic reclosing
  • Teleprotection, where applicable

The purpose of backup overcurrent protection is to clear faults when the primary protection does not operate or the associated circuit breaker fails.

5.1 Coordination with Distance Protection

When a distance relay is used as the main protection, backup overcurrent protection must be coordinated with the distance protection zones and neighboring protection systems.

Engineers should evaluate:

  • Maximum load current
  • Minimum fault current
  • Remote-end fault current
  • Maximum short-circuit current
  • Upstream and downstream operating times
  • Circuit breaker clearing time

5.2 Coordination with Line Differential Protection

Where line differential protection is used as the primary protection, overcurrent protection may provide an additional backup layer.

The backup settings must ensure that the relay does not operate unnecessarily for external faults or normal operating conditions.

6. SIPROTEC 7SJ86 Protection Settings

Protection settings must be calculated based on the actual network parameters.

6.1 CT Ratio Configuration

The current transformer ratio must be correctly entered in DIGSI 5.

Example:

  • CT primary current: 1000 A
  • CT secondary current: 1 A

Verify CT polarity, phase assignment and secondary wiring before commissioning.

6.2 Phase Overcurrent Pickup

Assume a maximum feeder current of 700 A.

An illustrative pickup factor of 1.2 gives:

Ipickup = 700 × 1.2 = 840 A

This value is only an example. The actual pickup must be checked against emergency loading, minimum fault current, CT performance and protection coordination requirements.

6.3 Earth-Fault Pickup

Earth-fault settings should consider:

  • Neutral earthing method
  • Minimum earth-fault current
  • Maximum normal residual current
  • CT sensitivity
  • Feeder characteristics
  • Required operating time

6.4 Time Delay and Curve Selection

The operating time must be coordinated with the main protection and neighboring backup protection devices.

Inverse-time characteristics may be appropriate for certain networks, while definite-time characteristics may be preferred in other applications.

6.5 Directional Settings

Where directional functions are used, engineers must verify:

  • Polarizing quantities
  • Current and voltage phase relationships
  • Forward and reverse direction
  • Directional characteristic
  • Pickup thresholds
  • Operating time

7. DIGSI 5 Configuration of SIPROTEC 7SJ86

DIGSI 5 is the primary engineering software for SIPROTEC 5 devices.

A typical configuration workflow includes the following steps.

Step 1: Create a DIGSI 5 Project

Create a new project and enter the relevant project information.

Step 2: Add the 7SJ86 Device

Select the correct 7SJ86 device variant and insert it into the project.

Verify that the selected device corresponds to the physical relay.

Step 3: Configure Hardware

Configure the available measurement inputs, binary inputs, binary outputs and communication interfaces.

Step 4: Enter CT and VT Parameters

Enter the transformer ratios and measurement configuration according to the electrical drawings.

Step 5: Configure Protection Functions

Enable the required protection functions and enter the approved settings.

Examples include:

  • Phase overcurrent protection
  • Earth-fault protection
  • Directional overcurrent protection
  • Negative-sequence protection
  • Thermal protection
  • Circuit breaker failure protection
  • Automatic reclosing

Step 6: Configure Logic

Develop the required trip, alarm, blocking and control logic.

CFC can be used for customized signal processing and automation functions.

Step 7: Configure IEC 61850

Configure communication parameters, logical nodes, reports and GOOSE messages according to the approved system architecture.

Step 8: Download and Verify

Validate the configuration and transfer it to the relay.

After downloading, verify the protection settings, signal mapping and device status.

8. IEC 61850 Communication

SIPROTEC 5 devices are designed for integration into modern substation automation architectures.

Depending on the 7SJ86 communication configuration, IEC 61850 engineering can include:

MMS Communication

For measurements, reporting, monitoring and control.

GOOSE Communication

For fast signal exchange between IEDs.

Typical applications include:

  • Breaker failure initiation
  • Protection blocking
  • Interlocking
  • Breaker status exchange
  • Trip-related signals

SCL Engineering

SCL files support the exchange of substation engineering information between compatible tools.

Time Synchronization

Time synchronization is important for event records and disturbance analysis.

9. Testing and Commissioning of SIPROTEC 7SJ86

Testing should cover the relay, its measurement circuits, output circuits and communication interfaces.

9.1 Hardware Inspection

Check:

  • Auxiliary supply
  • CT connections
  • VT connections, where applicable
  • Binary inputs
  • Binary outputs
  • Communication ports
  • Grounding

9.2 Secondary Injection Testing

Using a suitable protection test set, perform:

  • Phase overcurrent pickup tests
  • Operating time tests
  • Inverse-time characteristic tests
  • Earth-fault protection tests
  • Directional protection tests
  • Negative-sequence protection tests
  • Thermal overload tests

9.3 Circuit Breaker Failure Testing

Verify the breaker failure initiation and supervision logic.

Check that backup tripping occurs according to the approved protection philosophy.

9.4 Automatic Reclosing Tests

Where automatic reclosing is configured, test:

  • Initiation conditions
  • Dead time
  • Reclosing sequence
  • Reclaim time
  • Blocking conditions
  • Circuit breaker status supervision

9.5 IEC 61850 Testing

Verify MMS communication, GOOSE messages, reports, signal mapping and time synchronization.

9.6 Disturbance Record Analysis

Use SIGRA to analyze disturbance records and evaluate the relay response during test operations and actual system events.

Omicron CMC test equipment and Test Universe can support comprehensive secondary injection testing.

10. SIPROTEC 7SJ82 vs 7SJ85 vs 7SJ86

These devices belong to the SIPROTEC 5 feeder and overcurrent protection portfolio, but their application focus and hardware characteristics differ.

ModelGeneral application
7SJ82Compact feeder protection
7SJ85Modular feeder protection
7SJ86Line backup protection

Selection should be based on the required protection functions, hardware configuration, communication interfaces and project specifications.

Always check the official Siemens product documentation for the exact device variant.

11. Common Engineering and Commissioning Problems

Common issues include:

  1. Incorrect CT ratio.
  2. Wrong CT polarity.
  3. Incorrect phase sequence.
  4. Incorrect residual current measurement.
  5. Improper directional protection configuration.
  6. Poor backup protection coordination.
  7. Incorrect breaker failure logic.
  8. Incorrect automatic reclosing conditions.
  9. GOOSE communication errors.
  10. Incorrect binary signal assignment.
  11. Missing circuit breaker feedback.
  12. Incomplete commissioning tests.

A detailed protection philosophy, approved settings documentation and systematic testing are essential for reliable operation.

12. SIPROTEC 7SJ86 Training by Elec-Engg

Elec-Engg provides professional training in Siemens SIPROTEC 5 protection relays, DIGSI 5 engineering and substation automation.

Our training programs are designed for protection engineers, commissioning engineers, electrical maintenance professionals and substation automation specialists.

Training subjects include:

  • SIPROTEC 5 device architecture
  • 7SJ86 applications and configuration
  • DIGSI 5 project engineering
  • Overcurrent protection
  • Earth-fault protection
  • Directional protection
  • Protection coordination
  • Circuit breaker failure protection
  • Automatic reclosing
  • CFC logic engineering
  • IEC 61850 and GOOSE
  • Omicron relay testing
  • Commissioning and troubleshooting

Available Training Formats

Online Training: Structured technical courses with practical engineering demonstrations.

Self-Paced Training: Recorded lessons, technical documents, exercises and assessments.

Face-to-Face Training: Practical classroom training for engineering teams.

Customized In-House Training: Training programs tailored to company requirements, installed relay models and real project applications.

Visit Elec-Engg for more information:

https://elec-engg.com

Conclusion

The Siemens SIPROTEC 5 7SJ86 is part of the SIPROTEC 5 line protection portfolio and is intended for line backup and associated protection applications.

Its numerical protection capabilities, engineering flexibility and integration into substation automation systems make it relevant to utility and industrial power networks.

Understanding its protection functions, backup coordination, DIGSI 5 engineering, IEC 61850 communication and commissioning requirements is essential for protection engineers.