Siemens SIPROTEC 5 7SJ Series: Complete Feeder Protection Relay Guide

Table Of Contents
  1. Introduction to Siemens SIPROTEC 5 7SJ Series
  2. 1. Overview of SIPROTEC 5 7SJ Protection Relays
  3. 2. Siemens SIPROTEC 5 7SJ Models
  4. 3. Main Protection Functions of the 7SJ Series
  5. 4. Applications of Siemens 7SJ Protection Relays
  6. 5. Protection Settings and Coordination
  7. 6. DIGSI 5 Engineering for the 7SJ Series
  8. 7. IEC 61850 and GOOSE Communication
  9. 8. Testing and Commissioning of SIPROTEC 5 7SJ Relays
  10. 9. Comparison of SIPROTEC 5 7SJ Models
  11. 10. Common Problems in 7SJ Relay Engineering
  12. 11. SIPROTEC 5 7SJ Series Training by Elec-Engg
  13. Conclusion

Siemens SIPROTEC 5 7SJ Series: Complete Guide to Feeder Protection Relays – Models, Functions, Applications, Settings and DIGSI 5

Introduction to Siemens SIPROTEC 5 7SJ Series

The Siemens SIPROTEC 5 7SJ series comprises numerical protection relays designed primarily for feeder protection, overcurrent protection and related applications in medium-voltage and high-voltage electrical networks.

These relays are widely used in utility substations, industrial power distribution systems, power plants and electrical infrastructure requiring dependable protection against short circuits, earth faults and abnormal operating conditions.

The SIPROTEC 5 platform combines numerical protection functions, flexible engineering, communication capabilities and integration into modern substation automation systems.

Using Siemens DIGSI 5 engineering software, protection engineers can configure the 7SJ relays, calculate and enter protection settings, develop control logic, configure IEC 61850 communication and perform commissioning activities.

This guide provides an overview of the Siemens SIPROTEC 5 7SJ family, its models, protection functions, engineering principles, applications and differences between the available devices.

1. Overview of SIPROTEC 5 7SJ Protection Relays

The 7SJ family is intended for applications requiring feeder and overcurrent protection.

Depending on the device model and selected configuration, the relays provide functions such as:

  • Three-phase overcurrent protection
  • Earth-fault protection
  • Directional overcurrent protection
  • Directional earth-fault protection
  • Thermal overload protection
  • Negative-sequence protection
  • Voltage protection
  • Circuit breaker failure protection
  • Automatic reclosing
  • Circuit breaker control and monitoring
  • Measurement and event recording
  • IEC 61850 communication

The exact protection functions and hardware options depend on the individual device, firmware and ordering configuration.

2. Siemens SIPROTEC 5 7SJ Models

The SIPROTEC 5 7SJ portfolio includes different devices designed for specific feeder protection requirements.

2.1 SIPROTEC 5 7SJ81

The 7SJ81 is a feeder protection device within the SIPROTEC 5 platform.

It is intended for applications requiring feeder protection and associated overcurrent functions in electrical distribution systems.

Typical applications include:

  • Medium-voltage feeder protection
  • Industrial distribution networks
  • Overcurrent protection
  • Earth-fault protection
  • Electrical circuit monitoring

The exact functional scope should be checked against the relevant Siemens device documentation and ordering information.

2.2 SIPROTEC 5 7SJ82

The 7SJ82 is a compact numerical feeder protection relay.

It is designed for applications requiring dependable overcurrent and earth-fault protection with integration into substation automation systems.

Typical applications include:

  • Medium-voltage distribution feeders
  • Incoming and outgoing feeder protection
  • Cable feeder protection
  • Overhead line protection
  • Transformer backup protection
  • Industrial power distribution

The 7SJ82 can be engineered using DIGSI 5.

2.3 SIPROTEC 5 7SJ85

The 7SJ85 is a modular feeder protection IED designed for flexible protection and automation applications.

Its modular hardware architecture provides configuration flexibility for different project requirements.

Typical applications include:

  • Utility distribution substations
  • Industrial electrical networks
  • Feeder protection
  • Transformer backup protection
  • Cable and overhead line protection
  • Substation protection and control

The device can be integrated into IEC 61850-based substation automation systems according to its supported configuration.

2.4 SIPROTEC 5 7SJ86

The 7SJ86 is associated with line backup and overcurrent protection applications.

It can be used where additional protection is required alongside main line protection systems.

Typical applications include:

  • Line backup protection
  • Overhead line protection
  • Cable circuit protection
  • Transformer backup protection
  • Industrial power distribution

Protection coordination with the main line protection system is essential when applying the 7SJ86.

3. Main Protection Functions of the 7SJ Series

The 7SJ family provides a range of protection functions depending on the selected model and configuration.

3.1 Phase Overcurrent Protection – ANSI 50/51

Phase overcurrent protection is one of the fundamental protection functions of the 7SJ series.

It detects excessive current caused by short circuits or other abnormal electrical conditions.

Instantaneous Overcurrent Protection – ANSI 50

The relay operates when the measured current exceeds a predefined pickup threshold.

It is typically used for high-current faults requiring fast clearance.

Time Overcurrent Protection – ANSI 51

The relay operates according to a configured time characteristic.

Common characteristics include:

  • Definite time
  • Normal inverse
  • Very inverse
  • Extremely inverse

The selected characteristic must coordinate with the upstream and downstream protection devices.

3.2 Earth-Fault Protection – ANSI 50N/51N

Earth-fault protection detects residual current resulting from phase-to-earth faults.

The residual current is calculated as:

3I₀ = Iₐ + Iᵦ + I꜀

Earth-fault measurement may use phase CT summation or a dedicated core-balance current transformer.

The selected protection method depends on the network earthing arrangement and the required sensitivity.

3.3 Directional Overcurrent Protection – ANSI 67

Directional overcurrent protection determines the direction of the fault in addition to its current magnitude.

It is particularly useful in:

  • Parallel feeder systems
  • Ring distribution networks
  • Multiple-source networks
  • Interconnected industrial networks
  • Networks with distributed generation

The correct current and voltage reference configuration is essential for dependable operation.

3.4 Directional Earth-Fault Protection – ANSI 67N

Directional earth-fault protection identifies the direction of earth faults.

Applications include:

  • Isolated neutral networks
  • Compensated neutral networks
  • Resistance-earthed networks
  • Interconnected distribution systems

The directional characteristic and polarization principle must be selected according to the actual system configuration.

3.5 Thermal Overload Protection – ANSI 49

Thermal overload protection monitors the heating effect of electrical current.

It can protect cables, feeders and other equipment against prolonged overload conditions.

The thermal model must be configured according to the protected equipment and manufacturer requirements.

3.6 Negative-Sequence Protection – ANSI 46

Negative-sequence protection detects current unbalance in three-phase systems.

Possible causes include:

  • Phase-to-phase faults
  • Open conductors
  • Unbalanced loading
  • Incorrect phase connections

It can provide additional supervision and protection for electrical equipment.

3.7 Circuit Breaker Failure Protection – ANSI 50BF

Circuit breaker failure protection supervises whether a circuit breaker successfully interrupts the fault after receiving a trip command.

If the configured breaker failure conditions are fulfilled, the relay can initiate backup tripping of other circuit breakers.

3.8 Automatic Reclosing – ANSI 79

Automatic reclosing is commonly used for overhead line protection.

It allows a circuit breaker to close automatically after a temporary fault has been cleared.

Important parameters include:

  • Dead time
  • Reclaim time
  • Number of shots
  • Reclosing sequence
  • Protection function interaction
  • Synchronism supervision, where applicable

3.9 Undervoltage and Overvoltage Protection – ANSI 27/59

Where the selected device provides the required voltage measurement and functions, these elements supervise abnormal voltage conditions.

Undervoltage protection detects voltage reductions, while overvoltage protection detects excessive voltage.

4. Applications of Siemens 7SJ Protection Relays

4.1 Medium-Voltage Distribution Substations

The 7SJ family is commonly applied to outgoing and incoming feeder protection.

Typical protection arrangements include:

  • Phase overcurrent protection
  • Earth-fault protection
  • Directional protection
  • Circuit breaker failure protection
  • Automatic reclosing

4.2 Industrial Power Distribution

Industrial power systems contain transformers, motors, cables and multiple distribution feeders.

7SJ protection relays can be applied to suitable feeder circuits to improve fault detection and protection coordination.

4.3 Cable Feeder Protection

The relays can provide overcurrent and earth-fault protection for suitable medium-voltage cable circuits.

Settings should consider:

  • Cable rated current
  • Short-circuit withstand capability
  • Minimum fault current
  • Maximum fault current
  • CT performance
  • Protection coordination

4.4 Overhead Line Protection

For suitable overhead distribution and line applications, 7SJ relays can provide phase overcurrent and earth-fault protection.

Automatic reclosing can be included where supported by the selected device and protection scheme.

4.5 Transformer Backup Protection

The 7SJ series can provide backup overcurrent and earth-fault protection for transformers.

The backup functions must coordinate with:

  • Transformer differential protection
  • Restricted earth-fault protection
  • Downstream feeder protection
  • Upstream protection devices

5. Protection Settings and Coordination

Correct protection parameterization is essential for dependable operation.

Settings must be calculated based on the actual network design and approved protection coordination study.

5.1 CT Ratio Configuration

The CT primary and secondary ratings must be entered correctly in DIGSI 5.

Example:

  • CT primary rating: 800 A
  • CT secondary rating: 1 A

Engineers should verify:

  • CT ratio
  • CT polarity
  • Phase identification
  • Secondary wiring
  • CT accuracy
  • CT saturation performance

5.2 Overcurrent Pickup Calculation

Assume a feeder has a maximum operating current of 400 A.

An illustrative pickup factor of 1.25 gives:

Ipickup = 400 × 1.25 = 500 A

This is an example only. Final settings must account for emergency loading, minimum fault current, CT characteristics, equipment ratings and coordination requirements.

5.3 Earth-Fault Settings

Earth-fault settings depend on:

  • Neutral earthing method
  • Minimum earth-fault current
  • Maximum normal residual current
  • Measurement sensitivity
  • Feeder characteristics
  • Required fault clearance time

5.4 Time-Current Coordination

Protection engineers must coordinate the 7SJ relay with neighboring protection devices.

The study should consider:

  • Minimum and maximum short-circuit current
  • Transformer impedance
  • Feeder impedance
  • Circuit breaker clearing time
  • Downstream relay operating time
  • Upstream backup protection

Time-current characteristic curves should be reviewed to ensure selectivity and suitable backup protection.

6. DIGSI 5 Engineering for the 7SJ Series

DIGSI 5 is Siemens’ engineering software for configuring SIPROTEC 5 protection devices.

It provides the tools required for device parameterization, protection settings, logic engineering and communication configuration.

6.1 Project Creation

Create a new DIGSI 5 project and enter the project information.

6.2 Device Selection

Select the required 7SJ model and insert the device into the project.

Verify the exact hardware variant against the physical device.

6.3 Hardware Configuration

Configure the available:

  • Current measurement inputs
  • Voltage measurement inputs
  • Binary inputs
  • Binary outputs
  • Communication interfaces
  • Additional hardware modules

6.4 CT and VT Configuration

Enter the instrument transformer ratios and measurement parameters.

Verify phase assignment, polarity and wiring diagrams.

6.5 Protection Function Configuration

Enable the required protection functions and enter the approved settings.

These may include:

  • Phase overcurrent
  • Earth-fault protection
  • Directional protection
  • Thermal overload
  • Negative-sequence protection
  • Circuit breaker failure
  • Automatic reclosing

6.6 CFC Logic Engineering

Continuous Function Chart (CFC) provides tools for implementing customized protection and control logic.

Typical applications include:

  • Trip logic
  • Blocking logic
  • Alarm generation
  • Circuit breaker control
  • Interlocking
  • Signal processing
  • Protection function interactions

6.7 IEC 61850 Engineering

Configure the communication system according to the substation automation design.

This can include:

  • Logical nodes
  • Data objects
  • Reports
  • GOOSE datasets
  • GOOSE publishing and subscription
  • Station-level communication

6.8 Device Download and Diagnostics

After validating the project, transfer the configuration to the physical relay.

Verify the device settings, operational status and communication before commissioning.

7. IEC 61850 and GOOSE Communication

SIPROTEC 5 devices can be integrated into modern IEC 61850-based substation automation systems.

Important communication services include:

MMS Communication

Used for measurements, monitoring, reporting and control through compatible IEC 61850 clients.

GOOSE Messaging

Used for fast signal exchange between IEDs.

Typical applications include:

  • Circuit breaker interlocking
  • Protection blocking
  • Breaker status exchange
  • Trip-related signals
  • Automation functions

SCL Engineering

Substation Configuration Language supports engineering information exchange between compatible IEC 61850 tools.

Time Synchronization

Time synchronization is essential for accurate event records and disturbance analysis.

8. Testing and Commissioning of SIPROTEC 5 7SJ Relays

Commissioning must verify the complete protection and control system.

8.1 Hardware Inspection

Check:

  • Device identification
  • Auxiliary supply
  • CT connections
  • VT connections, where applicable
  • Binary inputs
  • Binary outputs
  • Communication interfaces
  • Grounding

8.2 Secondary Injection Testing

Using suitable protection test equipment, perform:

  • Phase overcurrent pickup tests
  • Operating time tests
  • Inverse-time characteristic tests
  • Earth-fault protection tests
  • Directional protection tests
  • Negative-sequence protection tests
  • Thermal overload tests

8.3 Binary Input and Output Testing

Verify:

  • Circuit breaker status
  • Protection trip signals
  • Alarm signals
  • External blocking signals
  • Interlocking signals
  • Control commands

8.4 Circuit Breaker Trip Testing

Verify the complete trip circuit, including relay output contacts, intermediate relays, wiring and circuit breaker trip coils.

8.5 Communication Testing

Check:

  • IEC 61850 MMS communication
  • GOOSE publishing
  • GOOSE subscription
  • Report configuration
  • Signal mapping
  • Communication supervision
  • Time synchronization

8.6 Disturbance Record Analysis

Retrieve disturbance records after testing or actual fault events.

SIGRA can be used to analyze current and voltage waveforms and investigate protection operation.

OMICRON CMC test equipment and Test Universe can be used for secondary injection testing and functional verification.

9. Comparison of SIPROTEC 5 7SJ Models

ModelGeneral application
7SJ81Feeder protection
7SJ82Compact feeder protection
7SJ85Modular feeder protection
7SJ86Line backup protection

The final device selection should consider:

  • Required protection functions
  • Hardware configuration
  • Number of measurement inputs
  • Binary input/output requirements
  • Communication interfaces
  • Substation automation architecture
  • Project specifications
  • Future expansion requirements

For exact technical specifications, ordering options and supported functions, engineers should consult the applicable Siemens product documentation.

10. Common Problems in 7SJ Relay Engineering

Common engineering and commissioning issues include:

  1. Incorrect CT ratio configuration.
  2. Incorrect CT polarity.
  3. Wrong phase sequence.
  4. Incorrect residual current measurement.
  5. Improper earth-fault pickup settings.
  6. Incorrect directional protection configuration.
  7. Poor time-current coordination.
  8. Incorrect circuit breaker trip logic.
  9. Missing circuit breaker feedback.
  10. Incorrect GOOSE signal mapping.
  11. Communication configuration errors.
  12. Incomplete secondary injection testing.

Proper engineering documentation and systematic commissioning procedures help prevent these problems.

11. SIPROTEC 5 7SJ Series Training by Elec-Engg

Elec-Engg provides practical training in Siemens SIPROTEC 5 protection relays, DIGSI 5 engineering and substation automation.

Our courses are designed for:

  • Protection engineers
  • Commissioning engineers
  • Electrical maintenance engineers
  • Substation automation engineers
  • Power system engineers
  • Industrial electrical engineers

Training topics include:

  • SIPROTEC 5 hardware architecture
  • 7SJ feeder protection relay family
  • DIGSI 5 project engineering
  • Overcurrent protection
  • Earth-fault protection
  • Directional protection
  • Protection coordination
  • Circuit breaker failure protection
  • Automatic reclosing
  • CFC logic programming
  • IEC 61850 communication
  • GOOSE engineering
  • Omicron CMC relay testing
  • Protection commissioning and troubleshooting

Available Training Formats

Online Training: Structured technical courses with practical demonstrations and engineering examples.

Self-Paced Training: Recorded technical lessons, exercises, documents and assessments with flexible access.

Face-to-Face Training: Practical classroom training for engineering professionals.

Customized In-House Training: Tailored programs based on company requirements, installed relay models and actual project applications.

For more information about our Siemens SIPROTEC 5 courses, visit:

https://elec-engg.com

Conclusion

The Siemens SIPROTEC 5 7SJ series provides numerical protection solutions for feeder and overcurrent protection applications in utility substations and industrial electrical networks.

The different 7SJ models offer application-specific hardware and protection capabilities for various distribution and line protection requirements.

Understanding their protection functions, current transformer configuration, protection coordination, DIGSI 5 engineering, IEC 61850 communication and commissioning procedures is essential for engineers working with Siemens protection systems.

Practical knowledge of these relays helps improve protection selectivity, fault clearance, system reliability and substation automation performance.

Leave a Comment

Your email address will not be published. Required fields are marked *

Scroll to Top