Siemens SIPROTEC 5 7UM85 Generator Protection Relay: Functions, Settings & Training

Table Of Contents
  1. 1. Introduction to the SIPROTEC 5 7UM85
  2. 2. Main Applications of the 7UM85
  3. 3. Generator Differential Protection (87G)
  4. 4. Stator Earth-Fault Protection
  5. 5. Rotor Earth-Fault Protection (64F)
  6. 6. Overexcitation Protection (24)
  7. 7. Underexcitation and Loss-of-Excitation Protection (40)
  8. 8. Reverse-Power Protection (32R)
  9. 9. Negative-Sequence and Unbalanced-Load Protection (46)
  10. 10. Overload Protection (49)
  11. 11. Overcurrent and Voltage-Dependent Overcurrent Protection
  12. 12. Voltage and Frequency Protection
  13. 13. Out-of-Step Protection (78)
  14. 14. Generator and Transformer Differential Protection
  15. 15. DIGSI 5 Engineering for the 7UM85
  16. 16. IEC 61850 Communication and Substation Automation
  17. 17. Testing and Commissioning of the 7UM85
  18. 18. Common Engineering and Commissioning Problems
  19. 19. 7UM85 Compared with Other SIPROTEC 5 Protection Relays
  20. 20. Why Learn Siemens SIPROTEC 5 7UM85?
  21. 21. Siemens SIPROTEC 5 7UM85 Training by Elec-Engg
  22. 22. Conclusion

Siemens SIPROTEC 5 7UM85 Generator Protection Relay: Complete Technical Guide

1. Introduction to the SIPROTEC 5 7UM85

The Siemens SIPROTEC 5 7UM85 is a modular generator protection relay designed to provide comprehensive protection, control, monitoring and automation for synchronous generators and power plant units.

Generator protection requires a coordinated combination of electrical protection functions. A generator can be exposed to internal stator faults, earth faults, rotor faults, abnormal excitation, unbalanced loading, overload, loss of synchronism, reverse power and abnormal voltage or frequency conditions.

The 7UM85 combines several generator-specific protection functions in one configurable device. Depending on the selected application, hardware, firmware and licensed functionality, it can also provide protection for associated transformers, auxiliary systems and busbar sections.

The relay is suitable for applications including:

  • Hydroelectric power plants
  • Thermal and conventional power plants
  • Industrial power generation
  • Generator-transformer units
  • Synchronous condensers
  • Generator applications requiring integrated protection and monitoring

The device is engineered using DIGSI 5, Siemens’ engineering software for the SIPROTEC 5 family.

2. Main Applications of the 7UM85

The 7UM85 can be configured for different generator arrangements and protection requirements.

2.1 Generator protection

The main application is the protection of synchronous generators against internal and external electrical faults and abnormal operating conditions.

Typical protection functions include:

  • Generator differential protection
  • Stator earth-fault protection
  • Rotor earth-fault protection
  • Overcurrent protection
  • Voltage-dependent overcurrent protection
  • Negative-sequence and unbalanced-load protection
  • Overload protection
  • Overexcitation protection
  • Underexcitation protection
  • Reverse-power protection
  • Overvoltage and undervoltage protection
  • Overfrequency and underfrequency protection
  • Out-of-step protection

The exact protection scope depends on the selected application template and configuration.

2.2 Generator-transformer unit protection

In a generator-transformer unit, the generator is connected to the transmission or distribution network through a step-up transformer.

The protection system must consider the generator, generator transformer, associated circuit breakers, current transformers, voltage transformers and neutral grounding arrangement.

The 7UM85 supports generator and transformer differential protection functions, subject to the selected function groups and configuration.

2.3 Hydroelectric power plants

The 7UM85 is suitable for hydroelectric generator applications. Its configurable protection and monitoring functions can be adapted to the operating requirements of hydro units.

A particularly useful application is protection of generators that may operate in both generator and motor modes, depending on the plant arrangement.

2.4 Synchronous condensers

Synchronous condensers are used for reactive-power support and voltage control. They require protection against abnormal operating conditions, including loss of excitation, unbalanced loading and electrical faults.

The 7UM85 can be applied to synchronous condenser installations where its configured functions meet the project protection requirements.

3. Generator Differential Protection (87G)

Generator differential protection is one of the most important protection functions for detecting internal phase-to-phase and phase-to-earth faults within the protected generator zone.

The 7UM85 includes a dedicated generator differential protection function.

3.1 Operating principle

Generator differential protection is based on Kirchhoff’s current law.

Current transformers are installed at the boundaries of the protected generator zone. Under normal operating conditions and for external faults, the currents entering and leaving the protected zone should balance after considering the configured CT ratios, polarities and measurement conventions.

The relay calculates the differential current and compares it with the restraint current.

A simplified representation is:

Differential current:

Idiff = |I1 + I2|

The actual calculation depends on the relay’s current reference directions and internal processing.

If the differential current exceeds the configured operating characteristic, the relay identifies an internal fault and initiates the configured trip logic.

3.2 Differential and restraint characteristics

A percentage-biased differential characteristic improves stability during external faults and measurement errors.

Important settings include:

  • Minimum differential operating current
  • Restraint-current characteristic
  • Bias or slope settings
  • Additional high-set differential stage, where configured
  • CT supervision and measurement checks
  • Trip and alarm routing

The characteristic must be selected with consideration of generator rated current, CT performance, maximum external fault current and expected CT saturation.

3.3 CT arrangement

Correct CT installation is essential for reliable generator differential protection.

The engineer must verify:

  • CT ratios
  • CT polarity
  • CT secondary ratings
  • CT accuracy and saturation characteristics
  • CT locations
  • Phase identification
  • Secondary wiring
  • Earthing of CT circuits
  • Current reference directions in DIGSI 5

Incorrect CT polarity or current assignment can cause differential current to appear during normal operation.

3.4 Generator differential protection zone

The protected zone is determined by the physical location of the CTs.

Depending on the generator arrangement, the zone may include the stator winding and associated conductors between the selected CT locations.

The protection engineer must ensure that the intended protected zone is correctly represented in the relay configuration and project drawings.

4. Stator Earth-Fault Protection

Stator earth faults are among the most important faults to detect in synchronous generators.

A stator earth fault can damage winding insulation, the stator core and other generator components. The protection method depends on the generator neutral grounding arrangement and the required fault coverage.

The 7UM85 provides several stator earth-fault protection approaches.

4.1 Stator earth-fault protection using residual voltage (59N)

Residual-voltage protection detects displacement of the generator neutral voltage during an earth fault.

The relay evaluates the zero-sequence or residual voltage, depending on the selected measurement arrangement.

Important considerations include:

  • Generator neutral grounding
  • Voltage transformer connection
  • Residual-voltage measurement
  • Voltage transformer ratio
  • Protection pickup threshold
  • Time delay
  • Coordination with other earth-fault protection

This method is commonly used for detecting stator earth faults, but its coverage depends on the grounding arrangement and the fault location.

4.2 Stator earth-fault protection using residual current

The 7UM85 also supports stator earth-fault protection approaches using zero-sequence current measurements.

The available methods include directional and non-directional stages.

The engineer must select the appropriate method according to the neutral grounding system, CT arrangement and sensitivity requirements.

4.3 100% stator earth-fault protection

Conventional neutral-voltage protection may not detect faults close to the generator neutral point because the available fault voltage becomes small.

For applications requiring protection of the entire stator winding, additional protection methods may be necessary.

The 7UM85 supports:

  • 100% stator ground-fault protection using 20 Hz injection
  • Stator ground-fault protection using third-harmonic quantities, where supported by the selected application and configuration

The 20 Hz injection method uses an external low-frequency injection system. The relay evaluates the injected voltage and resulting current to detect changes associated with an earth fault.

The complete arrangement must include the appropriate auxiliary equipment and wiring.

5. Rotor Earth-Fault Protection (64F)

The rotor field circuit is normally insulated from earth. An earth fault in the rotor circuit can create a dangerous operating condition.

A first rotor earth fault may not immediately produce a high fault current, but a second earth fault at another location can create a serious short-circuit path through part of the rotor winding.

The 7UM85 supports rotor ground-fault protection functions using appropriate measuring and injection arrangements.

Depending on the selected method, the available protection principles include:

  • Rotor ground-fault protection based on resistance measurement
  • Rotor ground-fault protection based on current measurement
  • Low-frequency injection methods, including the 1–3 Hz approach

The design must account for the excitation system, rotor circuit, auxiliary measuring equipment and the manufacturer’s recommended connection arrangement.

Important: Do not assume that the protection relay alone provides every part of the rotor earth-fault detection system. Certain applications require external auxiliary equipment.

6. Overexcitation Protection (24)

Overexcitation occurs when the magnetic flux in the generator or associated transformer exceeds the permitted operating level.

A common indicator is the ratio of voltage to frequency (V/Hz).

Overexcitation may result from:

  • Excessive terminal voltage
  • Reduced operating frequency
  • Incorrect excitation control
  • Abnormal system conditions
  • Improper voltage regulation

The 7UM85 provides overexcitation protection with thermal and independent characteristic stages.

Typical engineering considerations include:

  • Rated voltage
  • Rated frequency
  • V/Hz operating limit
  • Inverse-time or thermal characteristic
  • Definite-time stage
  • Alarm and trip thresholds
  • Coordination with generator and transformer withstand limits

The protection settings should be based on the generator and transformer capability curves and manufacturer data.

7. Underexcitation and Loss-of-Excitation Protection (40)

Loss of excitation can cause a synchronous generator to operate outside its permissible stability region.

Possible consequences include:

  • Increased reactive-power absorption
  • Rotor and stator heating
  • Instability
  • Pole slipping
  • Excessive current
  • Disturbances in the connected power system

Underexcitation protection monitors the generator operating point using electrical quantities, typically including voltage and current-derived impedance or power quantities.

The 7UM85 provides underexcitation protection with configurable characteristic curves.

Important engineering parameters include:

  • Generator capability curve
  • Underexcitation limit
  • Impedance or operating characteristic
  • Time delays
  • Power-system stability requirements
  • Coordination with excitation control
  • Alarm and trip stages

The protection characteristic should be coordinated with the generator manufacturer’s capability diagram rather than selected from generic values.

8. Reverse-Power Protection (32R)

Reverse-power protection detects when a generator begins absorbing active power from the electrical network instead of delivering power.

This condition can occur when the prime mover loses its mechanical input while the generator remains connected to the grid.

For example:

  • A steam turbine may lose steam supply.
  • A hydro turbine may experience loss of mechanical input.
  • A diesel engine may stop supplying sufficient torque.

The generator can then operate as a motor, potentially causing damage to the prime mover.

The 7UM85 provides reverse-power protection for generator applications.

Important settings include:

  • Reverse-power pickup
  • Operating direction
  • Time delay
  • Measurement supervision
  • Circuit-breaker trip logic
  • Coordination with turbine or engine protection

The setting must consider the minimum reverse power that can be reliably detected and the operating characteristics of the prime mover.

9. Negative-Sequence and Unbalanced-Load Protection (46)

Unbalanced three-phase currents produce negative-sequence current in the generator.

Negative-sequence current creates additional rotor heating because the resulting magnetic field rotates relative to the rotor.

Possible causes include:

  • Unbalanced system faults
  • Open phases
  • Unequal phase loading
  • Incorrect switching
  • Unbalanced network conditions

The 7UM85 includes unbalanced-load protection.

A common generator protection approach uses the negative-sequence current and its thermal withstand characteristic.

The engineer should consider:

  • Generator negative-sequence capability
  • Continuous negative-sequence current limit
  • Short-time withstand characteristic
  • Alarm and trip thresholds
  • Time-current coordination

The protection must be coordinated with the generator manufacturer’s negative-sequence withstand data.

10. Overload Protection (49)

Generator overload protection monitors thermal stress caused by excessive current.

Overload may result from:

  • Excessive active or reactive loading
  • Abnormal operating conditions
  • Cooling-system problems
  • Incorrect load sharing
  • Prolonged overcurrent

The 7UM85 provides overload protection functions for generator applications.

Depending on the selected configuration, thermal protection can be used to monitor heating and initiate an alarm or trip when the permitted thermal limit is exceeded.

Important settings include:

  • Rated current
  • Thermal time constant
  • Pickup current
  • Thermal alarm level
  • Thermal trip level
  • Cooling and reset assumptions

The settings must reflect the generator’s thermal capability and cooling arrangement.

11. Overcurrent and Voltage-Dependent Overcurrent Protection

Overcurrent protection provides backup protection for generator and connected-system faults.

The 7UM85 supports phase overcurrent protection and voltage-dependent overcurrent protection.

11.1 Phase overcurrent protection (50/51)

The relay can provide definite-time and inverse-time overcurrent stages, depending on the configured function.

Typical applications include:

  • Backup protection for external faults
  • Generator terminal fault backup
  • Transformer or auxiliary-system backup
  • Protection coordination with downstream devices

11.2 Voltage-dependent overcurrent protection (51V)

During a close-in short circuit, generator terminal voltage can fall significantly.

The generator fault current may also decrease as the generator’s internal electromagnetic conditions change.

Voltage-dependent overcurrent protection addresses this issue by adapting the overcurrent response according to voltage conditions.

The engineer must coordinate the current and voltage thresholds with the generator characteristics and system fault levels.

12. Voltage and Frequency Protection

Generator voltage and frequency must remain within acceptable operating limits.

The 7UM85 supports voltage and frequency protection functions for generator applications.

12.1 Overvoltage protection (59)

Overvoltage protection detects excessive generator terminal voltage.

Possible causes include:

  • Voltage regulator malfunction
  • Sudden load rejection
  • Excitation-system problems
  • Abnormal system operating conditions

Settings include pickup thresholds, time delays and alarm/trip routing.

12.2 Undervoltage protection (27)

Undervoltage protection monitors low generator terminal voltage.

It may be used for generator protection, operating supervision and interlocking applications, depending on the plant design.

12.3 Overfrequency protection (81O)

Overfrequency protection detects operation above the configured frequency limit.

It may be required following load rejection or abnormal system operating conditions.

12.4 Underfrequency protection (81U)

Underfrequency protection detects a reduction in system frequency.

The settings must consider the generator’s operating limits, turbine requirements and system protection philosophy.

13. Out-of-Step Protection (78)

Out-of-step conditions occur when a synchronous generator loses synchronism with the connected power system.

Such conditions may result from severe disturbances, unstable operating points or inadequate system stability.

Out-of-step protection evaluates the electrical quantities and operating characteristics associated with loss of synchronism.

The 7UM85 supports out-of-step protection, subject to the selected application and configuration.

Protection engineers should consider:

  • Generator stability limits
  • Power-system studies
  • Impedance measurement characteristics
  • Operating time
  • Trip strategy
  • Coordination with power-swing blocking and system protection

The settings must be based on system stability studies and generator operating requirements.

14. Generator and Transformer Differential Protection

A generator-transformer unit may require separate differential protection zones.

Typical protection functions include:

Protection functionANSI numberMain application
Generator differential87GInternal generator faults
Transformer differential87TInternal power-transformer faults
Restricted earth fault64REF / 87NSensitive earth-fault protection within a defined zone
Stator earth fault59N / 64GGenerator stator earth faults
Rotor earth fault64FRotor field circuit earth faults

The 7UM85 function library includes generator differential and transformer differential function groups, as well as restricted ground-fault protection.

The number of function groups and the practical application depend on the selected device configuration and available resources.

For a generator-transformer unit, the engineer must define the protection zones and CT locations carefully to avoid unprotected sections or overlapping protection arrangements that have not been properly coordinated.

15. DIGSI 5 Engineering for the 7UM85

The 7UM85 is engineered using Siemens DIGSI 5.

DIGSI 5 provides the tools required to configure the device, assign measuring points, activate protection functions, define logic and configure communication.

Typical engineering activities include:

15.1 Creating a new project

The engineer creates a DIGSI 5 project and adds the correct 7UM85 device.

The device order number, hardware configuration and firmware version must match the actual relay.

15.2 Selecting the application template

The appropriate generator application template is selected according to the generator and unit arrangement.

Templates provide a starting point for the function structure and configuration.

They must still be reviewed and adapted to the actual project.

15.3 Configuring measuring points

Current and voltage measuring points must be assigned correctly.

This includes:

  • Generator phase currents
  • Generator terminal voltages
  • Neutral current or residual current
  • Neutral voltage
  • Additional transformer-side measurements
  • Rotor ground-fault measuring inputs, where applicable

Correct assignment is essential because protection functions use specific measuring points and function groups.

15.4 Configuring function groups

The 7UM85 uses function groups to organize protection and measurement functions.

For generator differential protection, the relationship between the generator differential function group and the associated generator-side or generator-stator function groups must be configured correctly.

The engineer should verify all required interconnections before downloading the configuration.

15.5 Configuring protection settings

Protection settings are entered according to the approved protection study and generator data.

Typical data includes:

  • Generator rated power
  • Rated voltage
  • Rated current
  • Rated frequency
  • Power factor
  • CT ratios
  • VT ratios
  • Neutral grounding arrangement
  • Generator capability data
  • Thermal withstand limits
  • Differential protection settings
  • Voltage and frequency limits

15.6 CFC logic configuration

DIGSI 5 includes CFC engineering for implementing additional logic and automation functions.

CFC can be used for applications such as:

  • Alarm aggregation
  • Trip logic
  • Interlocking
  • Breaker status processing
  • Generator operating-state logic
  • External protection signal processing
  • Customized automation

CFC logic must be tested carefully, especially when it is connected to critical trip circuits.

16. IEC 61850 Communication and Substation Automation

The SIPROTEC 5 7UM85 supports IEC 61850 communication and can be integrated into modern substation automation systems.

Depending on the hardware, firmware and project configuration, the relay can exchange information with other protection devices, bay controllers, station controllers and SCADA systems.

16.1 IEC 61850 logical nodes

IEC 61850 uses logical nodes to organize protection, measurement, control and monitoring information.

The engineering process includes:

  • Selecting the required logical nodes
  • Configuring data objects
  • Defining reports
  • Configuring GOOSE communication
  • Engineering the station-level system
  • Validating the SCL files

16.2 GOOSE communication

GOOSE can be used for fast peer-to-peer communication between compatible IEDs.

Possible applications include:

  • Generator trip signals
  • Breaker status exchange
  • Interlocking
  • Protection blocking
  • Alarm and event exchange
  • Unit protection coordination

The engineer must verify the GOOSE publisher and subscriber configuration, dataset, control block, network settings and signal quality.

16.3 DIGSI 5 and IEC 61850 system engineering

A typical project may involve DIGSI 5 and an IEC 61850 system configuration tool.

The engineer must ensure that the device configuration and station-level SCL engineering remain consistent.

Communication testing should include checking the actual received and transmitted signals, not simply confirming that the Ethernet link is active.

17. Testing and Commissioning of the 7UM85

Testing and commissioning are essential to verify that the generator protection system operates correctly before the generator is placed into service.

Testing should follow the approved commissioning procedure, protection philosophy and manufacturer’s instructions.

17.1 Hardware and wiring inspection

Before secondary injection, inspect:

  • Auxiliary DC supply
  • CT secondary wiring
  • VT secondary wiring
  • Binary inputs
  • Binary outputs
  • Trip circuits
  • Alarm circuits
  • Communication connections
  • Earthing and shielding
  • Terminal tightness and identification

CT circuits must be handled safely. Never open an energized CT secondary circuit.

17.2 CT polarity and ratio testing

Verify CT ratio and polarity against the approved drawings.

Incorrect CT polarity can affect differential protection, directional functions and measurement accuracy.

Where required, perform primary injection or other approved tests to confirm the complete CT circuit.

17.3 Generator differential protection testing

Using a suitable relay test set, test the differential protection characteristic.

The test should verify:

  • Differential pickup
  • Restraint characteristic
  • Operating and restraint quantities
  • Stability for simulated external faults
  • Trip operation for simulated internal faults
  • Binary output assignment
  • Event and fault recording

17.4 Stator earth-fault protection testing

Test the configured stator earth-fault protection method.

Depending on the application, tests may include:

  • Residual-voltage injection
  • Residual-current injection
  • Directional measurement checks
  • 20 Hz injection-system testing
  • Third-harmonic protection checks, where configured

The test method must match the actual protection arrangement.

17.5 Rotor earth-fault protection testing

Rotor earth-fault protection must be tested using the appropriate auxiliary equipment and the manufacturer’s recommended test procedure.

Verify the measurement circuit, pickup thresholds, alarm and trip stages, and the associated logic.

17.6 Reverse-power protection testing

Inject voltage and current quantities with the appropriate phase relationship to simulate forward and reverse active power.

Verify:

  • Direction of power measurement
  • Reverse-power pickup
  • Time delay
  • Alarm indication
  • Trip output
  • Reset behavior

17.7 Voltage and frequency protection testing

Use a relay test set to simulate different voltage and frequency conditions.

Verify the configured stages, time delays, alarms and trip logic.

17.8 Trip circuit and breaker testing

Test the complete trip path from the protection function to the circuit-breaker trip coil.

Verify:

  • Trip output contact
  • Interposing relays, if used
  • DC supply
  • Circuit-breaker trip coil
  • Breaker auxiliary contacts
  • Breaker failure initiation
  • Trip circuit supervision

17.9 Disturbance recording and fault analysis

After functional testing, review the relay’s fault records and disturbance recordings.

SIGRA can be used to analyze disturbance records and understand the electrical behavior during simulated or actual events.

The final commissioning report should include test results, approved settings, deviations and outstanding issues.

18. Common Engineering and Commissioning Problems

Several problems can affect the performance of generator protection systems.

Incorrect CT polarity

Incorrect CT polarity can cause unwanted differential current or incorrect directional measurements.

Recommended action: Check the CT drawings, terminal markings, polarity and measured current phasors.

Incorrect generator rated data

Incorrect voltage, current, power or frequency data can affect protection thresholds and calculated quantities.

Recommended action: Compare DIGSI 5 settings with approved generator nameplate data and technical documentation.

Incorrect differential function-group configuration

Generator differential protection depends on correctly configured and interconnected function groups and measuring points.

Recommended action: Review the function-group structure, current assignments and differential protection settings in DIGSI 5.

Incorrect neutral grounding configuration

The selected stator earth-fault protection method must match the actual generator neutral grounding system.

Recommended action: Review the neutral grounding transformer, grounding resistor, VT arrangement and protection design.

Incorrect GOOSE configuration

GOOSE communication may fail because of mismatched datasets, control blocks, VLAN settings or signal assignments.

Recommended action: Check the SCL engineering, publisher/subscriber configuration, network settings and received signal quality.

Incorrect trip logic

A protection function may operate internally without producing the intended breaker trip if the trip routing or output assignment is incorrect.

Recommended action: Test the complete protection-to-breaker trip path, including CFC logic and binary outputs.

19. 7UM85 Compared with Other SIPROTEC 5 Protection Relays

The SIPROTEC 5 family includes different relays designed for specific protection applications.

RelayMain application
7UM85Generator protection
7UT82Transformer differential protection
7UT85Transformer differential protection
7UT86Transformer differential protection
7UT87Multi-winding transformer protection
7SJ82Feeder and overcurrent protection
7SJ85Feeder protection
7SA82Distance protection
7SA86Distance protection
7SD86Line differential protection
7SS85Busbar protection
7SK85Motor protection

The 7UM85 is specifically intended for generator protection applications, while the other devices address different protection requirements.

In a complete power plant protection system, these relays may operate together as part of an integrated protection and substation automation architecture.

20. Why Learn Siemens SIPROTEC 5 7UM85?

Engineers working with generator protection need more than a basic understanding of relay settings.

Practical knowledge should include:

  • Generator protection principles
  • Differential protection calculations
  • CT and VT circuit engineering
  • Stator and rotor earth-fault protection
  • Generator-transformer unit protection
  • Protection coordination
  • DIGSI 5 configuration
  • Function-group engineering
  • CFC logic
  • IEC 61850 and GOOSE
  • Relay testing and commissioning
  • Fault-record analysis

Understanding the relationship between the generator, protection relay, excitation system, circuit breaker and substation automation system is essential for reliable engineering.

21. Siemens SIPROTEC 5 7UM85 Training by Elec-Engg

Elec-Engg provides practical training in Siemens SIPROTEC 5 generator protection and related power system protection subjects.

Our training is designed for protection engineers, commissioning engineers, maintenance engineers and professionals working in power plants, substations and industrial electrical systems.

Training can be provided through:

  • Online training: Instructor-led technical training and practical engineering discussions.
  • Structured self-paced training: Organized lessons, exercises and assessments that engineers can complete at their own pace.
  • Face-to-face training: Practical classroom training for companies and engineering teams.
  • Customized in-house training: Training programs adapted to the client’s protection systems, relay models and project requirements.

Related training subjects include:

  • SIPROTEC 5 and DIGSI 5 engineering
  • Generator and transformer protection
  • Differential protection
  • CT and VT circuit analysis
  • IEC 61850 and GOOSE engineering
  • CFC logic configuration
  • Omicron CMC and Test Universe
  • Protection relay testing and commissioning
  • Fault-record analysis using SIGRA

Visit Elec-Engg to explore our power system protection and substation automation training programs.

22. Conclusion

The Siemens SIPROTEC 5 7UM85 is a flexible generator protection relay designed for comprehensive protection, monitoring and control of synchronous generators and power plant units.

Its protection functions include generator differential protection, stator and rotor earth-fault protection, overexcitation, underexcitation, reverse power, unbalanced-load protection, overload, voltage and frequency protection, and other generator-specific functions.

Correct application requires detailed knowledge of generator characteristics, CT and VT circuits, neutral grounding, protection settings, DIGSI 5 engineering and commissioning procedures.

For protection and commissioning engineers, understanding the complete 7UM85 application is an important step toward designing, configuring, testing and maintaining reliable generator protection systems.


Technical note: The available functions and application scope depend on the 7UM85 order number, hardware, firmware, application template and configured function points. Always verify the final project against the applicable Siemens manual and approved protection study.

Leave a Comment

Your email address will not be published. Required fields are marked *

Scroll to Top