Siemens SIPROTEC 5 7SK82 & 7SK85 Motor Protection Relays: Functions, Settings & Training

Table Of Contents
  1. 1. Introduction to SIPROTEC 5 Motor Protection
  2. 2. Main Applications of 7SK82 and 7SK85
  3. 3. SIPROTEC 5 7SK82 vs. 7SK85
  4. 4. Overview of Motor Protection Functions
  5. 5. Motor Thermal Overload Protection – ANSI 49
  6. 6. Motor Starting Supervision – ANSI 48
  7. 7. Locked Rotor Protection – ANSI 14
  8. 8. Starts-per-Hour Supervision – ANSI 66
  9. 9. Negative-Sequence Protection – ANSI 46
  10. 10. Phase Overcurrent Protection – ANSI 50/51
  11. 11. Earth-Fault Protection – ANSI 50N/51N and 59N
  12. 12. Temperature Supervision – ANSI 38
  13. 13. Undercurrent Protection – ANSI 37
  14. 14. Undervoltage and Overvoltage Protection – ANSI 27 and 59
  15. 15. Motor Differential Protection – ANSI 87M
  16. 16. Motor Protection with Variable-Frequency Drives
  17. 17. DIGSI 5 Engineering for 7SK82 and 7SK85
  18. 18. CFC Logic and Motor Control
  19. 19. IEC 61850 Communication in 7SK82 and 7SK85
  20. 20. Testing and Commissioning of SIPROTEC 5 Motor Protection
  21. 21. Common Engineering and Commissioning Problems
  22. 22. 7SK82 and 7SK85 in Industrial Motor Protection Projects
  23. 23. SIPROTEC 5 7SK82 and 7SK85 Training by Elec-Engg
  24. 24. Conclusion

Siemens SIPROTEC 5 7SK82 and 7SK85 Motor Protection Relays: Functions, Settings, DIGSI 5, Applications and Testing

1. Introduction to SIPROTEC 5 Motor Protection

Electric motors are critical components in industrial plants, power stations, water treatment facilities, oil and gas installations, mining operations and manufacturing processes. An unexpected motor failure can result in production losses, equipment damage and operational interruptions.

Reliable motor protection requires more than conventional overcurrent protection. A complete motor protection scheme must consider thermal overload, short circuits, earth faults, locked rotor conditions, excessive starting time, unbalanced loading, abnormal voltage, phase failure and frequent starting.

Siemens offers two dedicated SIPROTEC 5 motor protection devices:

  • SIPROTEC 5 7SK82: Compact and cost-optimized motor protection, particularly suitable for small and medium-sized motors.
  • SIPROTEC 5 7SK85: Modular motor protection designed for motors of different sizes, with flexible hardware expansion and comprehensive protection, control and monitoring capabilities.

Both devices are engineered using DIGSI 5 and can be integrated into modern substation automation systems.

The exact functions depend on the selected device, application template, hardware, firmware and configured function scope.

2. Main Applications of 7SK82 and 7SK85

SIPROTEC 5 motor protection relays can be used in different industrial and power system applications.

Typical applications include:

  • Medium-voltage induction motors.
  • Large industrial motors.
  • Pumps and pumping stations.
  • Compressors.
  • Fans and blowers.
  • Conveyors and crushers.
  • Cooling-water systems.
  • Auxiliary motors in power plants.
  • Motors in oil and gas facilities.
  • Industrial process motors.
  • Motors with direct-on-line starting.
  • Motors with soft starters or variable-frequency drives, subject to the protection application and measurement arrangement.

The protection scheme must be selected according to motor power, rated voltage, starting method, thermal characteristics, CT arrangement, earthing system and operating requirements.

3. SIPROTEC 5 7SK82 vs. 7SK85

The 7SK82 and 7SK85 share the SIPROTEC 5 engineering platform but address different application requirements.

FeatureSIPROTEC 5 7SK82SIPROTEC 5 7SK85
Main applicationSmall and medium-sized motorsMotors of different sizes
Hardware conceptCompactModular
I/O expansionDepends on device variantFlexible modular expansion
Engineering softwareDIGSI 5DIGSI 5
Motor thermal protectionAvailable according to configurationAvailable according to configuration
Starting supervisionAvailable according to configurationAvailable according to configuration
Temperature measurementDepends on hardware and configurationSupports suitable temperature measurement arrangements
Motor differential protectionCheck device-specific functional scopeAvailable in applicable configurations
CommunicationDepends on selected interfacesDepends on selected interfaces
Application flexibilityCompact and cost-optimizedMore extensive modular flexibility

The 7SK85 is particularly useful where additional hardware flexibility, more complex motor protection arrangements or motor differential protection is required.

Siemens also offers ATEX-certified variants for relevant applications. Certification must be checked against the exact device order number and intended installation.

4. Overview of Motor Protection Functions

The following table summarizes important motor protection functions that may be used in SIPROTEC 5 motor protection applications.

ANSI codeProtection functionPurpose
14Underspeed / locked rotor-related protection, depending on implementationDetects abnormal motor speed or starting conditions
24Overexcitation protectionDetects excessive volts-per-hertz conditions where applicable
27Undervoltage protectionDetects low motor supply voltage
32Active/reactive power protectionMonitors abnormal power conditions
32RReverse-power protectionDetects reverse active power where applicable
37Undercurrent protectionDetects low motor current or loss of load
38Temperature supervisionMonitors motor temperature
46Negative-sequence protectionProtects against unbalanced current
47Negative-sequence voltage protectionDetects voltage unbalance
48Incomplete starting / excessive starting timeDetects unsuccessful or prolonged starting
49Thermal overload protectionProtects motor thermal condition
50/51Overcurrent protectionDetects phase overcurrent and short circuits
50N/51NEarth-fault overcurrentDetects earth-fault current
59Overvoltage protectionDetects excessive supply voltage
59NResidual-voltage protectionDetects earth faults using residual voltage
66Starts-per-hour supervisionLimits excessive motor starts
67NDirectional earth-fault protectionDetects directional earth faults where applicable
87MMotor differential protectionDetects internal motor winding faults in supported arrangements

Not all functions are available in every application template or device variant. The engineering scope should be checked in the applicable SIPROTEC 5 motor protection manual.

5. Motor Thermal Overload Protection – ANSI 49

Thermal overload protection is one of the most important functions in a motor protection relay.

An electric motor produces heat during operation. Under normal operating conditions, the motor cooling system removes this heat and maintains the winding temperature within permissible limits.

When a motor carries excessive current for a prolonged period, heat accumulates in the stator and rotor. This can damage winding insulation and shorten motor life.

The thermal protection function calculates the motor’s thermal condition using a thermal model.

5.1 Thermal model

The relay evaluates the motor current and applies configured thermal characteristics to estimate the motor’s heating condition.

Important parameters include:

  • Motor rated current.
  • Thermal time constant.
  • Permissible overload.
  • Thermal alarm threshold.
  • Thermal trip threshold.
  • Cooling time constant.
  • Thermal memory.
  • Motor starting characteristics.
  • Hot and cold operating conditions.

The thermal model should represent the motor manufacturer’s thermal capability.

5.2 Stator and rotor thermal protection

Motor thermal limits are not determined by stator current alone.

Depending on the protection configuration, separate thermal considerations can be applied to:

  • Stator winding heating.
  • Rotor heating.
  • Starting and acceleration conditions.
  • Repeated starting.
  • Cooling during operation and shutdown.

The 7SK85 documentation describes thermal protection arrangements for stator and rotor. The exact implementation and available settings must be checked for the selected application.

5.3 Thermal protection settings

A typical engineering process includes:

  1. Obtain the motor rated current and power.
  2. Obtain the motor thermal withstand information.
  3. Review the motor starting current and starting time.
  4. Determine the permissible hot and cold starting conditions.
  5. Enter the thermal time constants.
  6. Configure alarm and trip thresholds.
  7. Verify the thermal response using suitable test procedures.

Incorrect thermal settings can cause unnecessary tripping or insufficient motor protection.

6. Motor Starting Supervision – ANSI 48

Motor starting is a critical operating condition because the motor may draw several times its rated current during acceleration.

The starting current and acceleration time depend on:

  • Motor design.
  • Load torque.
  • Supply voltage.
  • Starting method.
  • Mechanical inertia.
  • Driven equipment.
  • System impedance.

The starting supervision function monitors the starting process and detects conditions such as excessive starting time or unsuccessful acceleration.

Important settings

  • Motor rated current.
  • Starting current threshold.
  • Maximum permissible starting time.
  • Motor starting detection threshold.
  • Starting supervision time.
  • Hot and cold starting limits, where applicable.

The starting time must be coordinated with the motor’s thermal withstand capability and the load characteristics.

Example

Consider an induction motor with:

  • Rated current: 120 A.
  • Starting current: 6 times rated current.
  • Starting time: 8 seconds.

The approximate starting current is:

[
I_{start}=6\times120=720\ A
]

The protection engineer must verify that the motor can withstand the starting current for the required acceleration time.

The actual relay settings must be based on the motor data and the selected starting method, not only on this simple calculation.

7. Locked Rotor Protection – ANSI 14

A locked rotor condition occurs when the motor rotor cannot accelerate or becomes mechanically blocked.

Possible causes include:

  • Mechanical jamming.
  • Pump blockage.
  • Compressor problems.
  • Bearing failure.
  • Excessive load torque.
  • Mechanical damage.
  • Failure of the driven equipment.

A locked rotor condition can result in very high current and rapid heating.

Locked rotor protection detects abnormal current and motor operating conditions associated with a blocked rotor.

Important engineering parameters include:

  • Locked rotor current.
  • Permissible locked rotor time.
  • Motor thermal withstand data.
  • Starting and running current thresholds.
  • Motor operating state.
  • Trip delay.

The protection must distinguish between normal starting and an abnormal locked rotor condition.

8. Starts-per-Hour Supervision – ANSI 66

Frequent motor starting can cause excessive thermal stress.

Every motor has limitations on the number of starts permitted within a specified period.

The starts-per-hour supervision function monitors the number and timing of motor starts.

Important settings include:

  • Permissible number of starts.
  • Monitoring period.
  • Starting counter.
  • Cooling or restart time.
  • Hot and cold starting limitations, where applicable.

This function is particularly useful for pumps, compressors and industrial motors that experience frequent operational switching.

9. Negative-Sequence Protection – ANSI 46

Voltage unbalance produces negative-sequence current in a three-phase induction motor.

Negative-sequence current produces additional rotor heating because the resulting magnetic field rotates in the opposite direction to the normal rotating field.

Possible causes include:

  • Phase loss.
  • Unbalanced supply voltage.
  • Loose connections.
  • Unequal phase impedances.
  • Faults in the supply network.
  • Fuse failure.

The 46 protection function evaluates negative-sequence current and can provide protection against excessive unbalanced loading.

Important settings include:

  • Negative-sequence pickup.
  • Thermal characteristic.
  • Alarm threshold.
  • Trip threshold.
  • Time delay.
  • Reset behavior.

The settings should be coordinated with the motor manufacturer’s permissible negative-sequence current and thermal withstand data.

10. Phase Overcurrent Protection – ANSI 50/51

Phase overcurrent protection provides backup protection against excessive motor current and phase-to-phase faults.

Two common stages are used:

ANSI 50 – Instantaneous overcurrent

The instantaneous stage operates when current exceeds a configured high threshold.

It is typically applied for fast short-circuit detection.

ANSI 51 – Time overcurrent

The time overcurrent stage operates according to a configured time characteristic.

It may be used for backup protection and coordination with upstream and downstream protection devices.

Important settings include:

  • Rated current.
  • Pickup current.
  • Definite-time or inverse-time characteristic.
  • Time multiplier.
  • High-set threshold.
  • Operating delay.
  • Coordination with upstream protection.

Motor starting current must be considered to prevent unwanted operation during normal acceleration.

11. Earth-Fault Protection – ANSI 50N/51N and 59N

Earth faults in motor stator windings and motor feeder cables can cause serious damage.

The appropriate earth-fault protection method depends on the system earthing arrangement.

Common arrangements include:

  • Solidly grounded systems.
  • Resistance-grounded systems.
  • Isolated-neutral systems.
  • Resonant-grounded systems.

11.1 Residual-current protection

Residual current can be calculated from the three phase currents:

[
I_0=\frac{I_A+I_B+I_C}{3}
]

The residual current is used to detect earth-fault conditions.

An external core-balance CT may also be used to measure the earth-fault current more sensitively, depending on the application.

11.2 Residual-voltage protection – 59N

Residual-voltage protection evaluates the zero-sequence voltage.

This method can be particularly useful in isolated or resonant-grounded networks.

11.3 Directional earth-fault protection

In compensated and isolated systems, directional earth-fault protection can help identify the faulted feeder.

Depending on the configured function, the relay may evaluate:

  • Residual current.
  • Residual voltage.
  • Phase relationship.
  • Active or reactive components.
  • Harmonic quantities.
  • Transient quantities.

The Siemens motor protection platform includes advanced earth-fault detection approaches for applicable network arrangements. The exact functions and settings must be verified in the device manual.

12. Temperature Supervision – ANSI 38

Motor temperature supervision provides additional protection by monitoring temperature sensors installed in the motor.

Typical sensor arrangements include:

  • RTDs.
  • Pt100 sensors.
  • Other supported temperature sensor types.

Temperature sensors may be installed in stator windings, bearings or other critical motor locations.

Temperature supervision can provide:

  • Temperature measurement.
  • High-temperature alarm.
  • High-high temperature trip.
  • Sensor failure detection.
  • Temperature monitoring for maintenance.

The availability of direct sensor connections depends on the relay hardware and configured analog or temperature measurement modules.

Where required, the relay can combine current-based thermal protection with direct temperature measurements to improve motor protection.

13. Undercurrent Protection – ANSI 37

Undercurrent protection detects situations where motor current falls below a configured threshold.

It is useful in applications where motor current reflects the mechanical load.

Examples include:

  • Pump dry-running conditions.
  • Loss of mechanical load.
  • Broken conveyor belts.
  • Coupling failure.
  • Loss of process material.

The protection can be configured with suitable pickup thresholds and time delays.

The engineer must consider normal variations in load current to prevent unnecessary operation.

14. Undervoltage and Overvoltage Protection – ANSI 27 and 59

Abnormal supply voltage can affect motor starting, torque, heating and operating stability.

Undervoltage protection

Low voltage can cause:

  • Reduced motor torque.
  • Increased current for certain operating conditions.
  • Motor stalling.
  • Failure to accelerate.
  • Unwanted operation of contactors.

Overvoltage protection

Excessive voltage can increase insulation stress and affect motor magnetic flux.

The 27 and 59 functions can provide alarm and trip stages according to the application.

The settings should consider:

  • Motor rated voltage.
  • Operating voltage range.
  • Starting conditions.
  • System disturbances.
  • Voltage-transformer accuracy.
  • Coordination with plant undervoltage schemes.

15. Motor Differential Protection – ANSI 87M

Motor differential protection detects internal faults in the protected motor winding zone.

It compares currents measured at different boundaries of the protected motor circuit.

During normal operation and external faults, the currents should balance after accounting for CT ratios, polarity and measurement direction.

An internal fault produces differential current and can cause the relay to operate.

15.1 Operating principle

The relay evaluates:

  • Differential current.
  • Restraint current.
  • Differential pickup.
  • Restraint characteristic.
  • CT measurement direction.
  • Fault conditions.

15.2 Application with 7SK85

The SIPROTEC 5 catalog describes motor differential protection arrangements using the 7SK85, including applications with multiple motor-side current measurement points.

This can be useful for motors requiring additional internal fault protection.

15.3 Important engineering considerations

  • CT ratio matching.
  • CT polarity.
  • Correct current measurement-point assignment.
  • Differential zone definition.
  • Motor connection arrangement.
  • Starting and operating conditions.
  • Trip matrix configuration.

Motor differential protection should be tested for both internal and external fault conditions.

16. Motor Protection with Variable-Frequency Drives

Motors supplied through variable-frequency drives require special consideration.

The current and voltage waveforms may differ from those of a motor connected directly to a conventional power supply.

Protection engineering should consider:

  • Drive output frequency.
  • Harmonic content.
  • Current measurement location.
  • Motor starting and acceleration profile.
  • Drive protection functions.
  • Motor thermal capability.
  • Grounding arrangement.
  • CT and sensor suitability.

The motor protection relay must be applied at a suitable measurement location and with functions appropriate to the drive arrangement.

Do not assume that every conventional motor protection function will operate correctly with every variable-frequency drive configuration.

17. DIGSI 5 Engineering for 7SK82 and 7SK85

DIGSI 5 is the engineering software used to configure SIPROTEC 5 motor protection relays.

A typical engineering workflow includes the following steps.

17.1 Create the project

  • Open DIGSI 5.
  • Create a new project.
  • Add the 7SK82 or 7SK85 device.
  • Select the correct device variant.
  • Verify firmware compatibility.
  • Select the appropriate motor protection application template.

17.2 Configure hardware

Configure the installed hardware according to the relay order number.

Typical items include:

  • Current transformer inputs.
  • Voltage transformer inputs.
  • Binary inputs.
  • Binary outputs.
  • Communication modules.
  • Temperature measurement interfaces.
  • Additional I/O modules.

The hardware configuration must match the actual device.

17.3 Configure motor data

Important motor parameters include:

  • Rated power.
  • Rated voltage.
  • Rated current.
  • Rated frequency.
  • Power factor.
  • Starting current.
  • Starting time.
  • Thermal time constants.
  • Locked rotor withstand time.
  • Permissible starts per hour.
  • CT and VT ratios.

The motor nameplate and manufacturer documentation should be used as the primary sources for these values.

17.4 Configure protection functions

Select and configure the functions required by the protection philosophy.

Typical functions include:

  • Thermal overload.
  • Starting supervision.
  • Locked rotor protection.
  • Starts-per-hour supervision.
  • Negative-sequence protection.
  • Phase overcurrent.
  • Earth-fault protection.
  • Temperature supervision.
  • Undervoltage and overvoltage.
  • Undercurrent.
  • Motor differential protection, where required and supported.

17.5 Configure trip logic

The protection functions must be connected to the correct trip outputs.

Typical trip destinations include:

  • Motor circuit breaker.
  • Contactor trip circuit.
  • Lockout relay.
  • Alarm system.
  • Plant control system.
  • Motor control center.

The final logic must follow the approved electrical drawings and motor control philosophy.

18. CFC Logic and Motor Control

CFC (Continuous Function Chart) is used in SIPROTEC 5 engineering to implement additional logic and signal processing.

Typical applications include:

  • Motor start permissive.
  • Motor running indication.
  • Starting supervision.
  • Alarm aggregation.
  • Interlocking.
  • Trip logic.
  • External protection signals.
  • Motor status indication.
  • Plant control interface.

For example, the motor start permissive may be designed to consider:

  • Circuit-breaker condition.
  • Protection lockout status.
  • Thermal capacity available.
  • Starts-per-hour limitation.
  • External process permissives.
  • Emergency stop status.

CFC logic must be documented and tested before being transferred to the operational relay.

19. IEC 61850 Communication in 7SK82 and 7SK85

SIPROTEC 5 motor protection relays can be integrated into IEC 61850-based substation and industrial automation systems, subject to the selected device communication configuration.

Typical communication applications include:

  • MMS communication.
  • GOOSE messaging.
  • Protection status transmission.
  • Motor operating status.
  • Alarm and trip information.
  • Measurement data.
  • Control commands.
  • Integration with station-level systems.

19.1 IEC 61850 logical nodes

IEC 61850 organizes protection and control information using logical nodes.

The relevant logical nodes and data objects depend on the device implementation and configured functions.

Engineers should review the 7SK82/7SK85 IEC 61850 documentation and exported SCL files when preparing the communication database.

19.2 GOOSE applications

GOOSE messaging can be used for fast communication between IEDs.

Possible applications include:

  • Interlocking.
  • Trip signal exchange.
  • Breaker status.
  • Motor start permissive.
  • Blocking signals.
  • External protection indications.

19.3 SCL engineering

SCL files are used to configure and describe IEC 61850 communication.

Common file types include:

  • ICD.
  • CID.
  • SCD.
  • IID.

Correct dataset mapping, GOOSE subscription and communication supervision are essential for reliable operation.

20. Testing and Commissioning of SIPROTEC 5 Motor Protection

A motor protection relay must be thoroughly tested before being placed into service.

Commissioning should cover hardware, measurement circuits, protection functions, logic, trip circuits and communication.

20.1 Hardware inspection

Check:

  • Device model and order number.
  • Auxiliary DC supply.
  • Earthing.
  • CT wiring.
  • VT wiring.
  • Binary inputs.
  • Binary outputs.
  • Temperature sensor connections.
  • Communication connections.
  • Terminal identification.

20.2 CT and VT testing

Verify:

  • CT ratios.
  • CT polarity.
  • CT secondary grounding.
  • CT circuit continuity.
  • VT ratio.
  • Phase sequence.
  • Correct measurement assignment in DIGSI 5.

20.3 Protection function testing

Typical secondary injection tests include:

  • Phase overcurrent.
  • Earth-fault overcurrent.
  • Negative-sequence protection.
  • Undervoltage and overvoltage.
  • Thermal overload.
  • Starting supervision.
  • Locked rotor protection.
  • Starts-per-hour supervision.
  • Undercurrent.
  • Motor differential protection, where configured.

20.4 Thermal protection testing

Thermal protection testing should verify:

  • Pickup behavior.
  • Thermal alarm.
  • Thermal trip.
  • Thermal memory.
  • Cooling behavior.
  • Hot and cold operating conditions.
  • Reset characteristics.

The test procedure must follow the configured thermal model and applicable Siemens documentation.

20.5 Motor starting simulation

Starting supervision can be tested by simulating suitable current and motor operating conditions.

The engineer should verify:

  • Starting detection.
  • Starting current threshold.
  • Starting time.
  • Acceleration supervision.
  • Locked rotor detection.
  • Successful start indication.
  • Trip operation for unsuccessful starting.

20.6 Omicron CMC and Test Universe

Omicron CMC test equipment can be used for secondary injection testing of motor protection functions.

Test Universe can support:

  • Overcurrent tests.
  • Earth-fault tests.
  • Voltage protection tests.
  • Negative-sequence tests.
  • Thermal protection tests.
  • Differential protection tests.
  • Timing tests.
  • Binary input/output tests.

The actual test modules and procedures should be selected according to the configured protection functions.

21. Common Engineering and Commissioning Problems

Incorrect motor rated current

Incorrect motor rated current affects thermal protection and other current-dependent functions.

Incorrect CT ratio

An incorrect CT ratio can result in incorrect measured current and protection pickup values.

Unwanted operation during motor starting

Incorrect starting supervision or overcurrent settings may cause tripping during normal acceleration.

Thermal overload trip after repeated starts

The thermal model may correctly identify accumulated heating, or the configured thermal data may not reflect the actual motor characteristics.

Incorrect starts-per-hour configuration

An incorrect monitoring period or start counter can prevent a motor from restarting when expected.

Incorrect earth-fault sensitivity

The earth-fault pickup must be coordinated with the system earthing method and expected fault current.

Incorrect temperature measurement

Incorrect sensor type, wiring or measurement configuration can produce false temperature indications.

Incorrect differential current measurement

Incorrect CT polarity, ratio or measurement-point assignment can cause unwanted differential operation.

Incorrect trip matrix

The protection function may detect a fault without operating the intended motor circuit breaker or contactor.

IEC 61850 communication problems

Incorrect GOOSE mapping, subscription or network configuration can prevent signals from reaching the intended IED.

22. 7SK82 and 7SK85 in Industrial Motor Protection Projects

A motor protection project should begin with a review of the motor and driven equipment.

Important documents include:

  • Motor data sheet.
  • Motor nameplate.
  • Motor starting study.
  • Motor thermal withstand data.
  • Single-line diagram.
  • CT and VT drawings.
  • Motor control schematic.
  • Motor control center drawings.
  • Protection coordination study.
  • Motor protection settings.
  • DIGSI 5 project.
  • IEC 61850 communication database.
  • Commissioning test procedures.
  • Final test reports.

The protection engineer should also review the process requirements, particularly for pumps, compressors and other critical equipment where an unexpected trip may affect the entire plant.

23. SIPROTEC 5 7SK82 and 7SK85 Training by Elec-Engg

Elec-Engg provides practical training in Siemens SIPROTEC protection relays, motor protection, power system protection and substation automation.

Our motor protection training focuses on the engineering and practical application of protection functions.

Training topics can include:

  • Motor protection principles.
  • Induction motor operating characteristics.
  • Motor starting and acceleration.
  • Thermal overload protection.
  • Locked rotor protection.
  • Starts-per-hour supervision.
  • Negative-sequence protection.
  • Phase overcurrent protection.
  • Earth-fault protection.
  • Motor differential protection.
  • DIGSI 5 project creation.
  • Hardware configuration.
  • Protection settings.
  • CFC logic and trip matrix.
  • IEC 61850 and GOOSE engineering.
  • Omicron CMC and Test Universe testing.
  • Commissioning and troubleshooting.

Training formats include:

  • Online training: Instructor-led technical courses.
  • Structured self-paced training: Organized video lessons, practical exercises and learning materials.
  • Face-to-face training: Classroom and practical engineering sessions.
  • Customized in-house training: Programs designed around the company’s installed protection systems, engineering requirements and project applications.

Our objective is to help protection, commissioning, operation and maintenance engineers develop practical skills for configuring, testing and troubleshooting motor protection systems.

Visit Elec-Engg.com to explore our power system protection and substation automation courses or contact us to discuss customized training.

24. Conclusion

The Siemens SIPROTEC 5 7SK82 and 7SK85 provide dedicated protection and control solutions for industrial motors.

The 7SK82 offers a compact and cost-optimized solution for small and medium-sized motors, while the modular 7SK85 provides greater hardware flexibility and supports more extensive motor protection arrangements.

Important functions include thermal overload protection, starting supervision, locked rotor protection, negative-sequence protection, overcurrent protection, earth-fault protection and temperature supervision. Motor differential protection is also available in applicable 7SK85 configurations.

Correct motor data, CT and VT configuration, protection settings, trip logic and commissioning tests are essential for reliable motor operation.

Engineers who understand motor characteristics and practical DIGSI 5 engineering can make better decisions when designing, commissioning and maintaining SIPROTEC 5 motor protection systems.