- 1. Introduction to SIPROTEC 5 7SS85
- 2. Main Features of SIPROTEC 5 7SS85
- 3. Busbar Protection Principles
- 4. Low-Impedance vs. High-Impedance Busbar Protection
- 5. Check-Zone and Selective Busbar Protection
- 6. Busbar Configurations Supported by 7SS85
- 7. Busbar Differential Protection Settings
- 8. Disconnector Image and Topology Processing
- 9. Circuit-Breaker Failure Protection – ANSI 50BF
- 10. Inherent Circuit-Breaker Failure Protection
- 11. Bus Coupler Differential Protection
- 12. End-Fault Protection
- 13. External Tripping of Busbar Sections
- 14. Centralized and Distributed Busbar Protection
- 15. SIPROTEC 5 7SS85 Hardware and I/O Configuration
- 16. DIGSI 5 Engineering for 7SS85
- 17. IEC 61850 Communication in 7SS85
- 18. Testing and Commissioning of SIPROTEC 5 7SS85
- 19. Omicron Testing of 7SS85
- 20. Common 7SS85 Engineering and Commissioning Problems
- 21. SIPROTEC 5 7SS85 vs. SIPROTEC 4 7SS52
- 22. Important Documents for a 7SS85 Project
- 23. Siemens SIPROTEC 5 7SS85 Training by Elec-Engg
- 24. Conclusion
Siemens SIPROTEC 5 7SS85 Busbar Protection Relay: Functions, Applications, DIGSI 5, Settings and Testing
1. Introduction to SIPROTEC 5 7SS85
Busbars are among the most critical components in electrical substations and power distribution systems. They collect and distribute electrical power between incoming feeders, outgoing feeders, transformers, generators and other electrical equipment.
A short circuit on a busbar can result in extremely high fault currents and serious equipment damage. Since several circuits may be connected to the same busbar, a busbar fault must be detected and cleared rapidly.
The Siemens SIPROTEC 5 7SS85 is a low-impedance numerical busbar protection relay designed to provide fast and selective protection for different busbar configurations.
The relay is suitable for:
- Medium-voltage switchgear.
- High-voltage substations.
- Extra-high-voltage substations.
- Single-busbar arrangements.
- Double-busbar arrangements.
- Multiple busbar sections.
- Busbar arrangements with bus couplers.
- Transfer busbar configurations.
- Complex switchgear with multiple disconnectors and circuit breakers.
The 7SS85 uses advanced differential protection algorithms and switchgear topology information to determine which busbar section is affected by a fault.
Engineering is performed using DIGSI 5, allowing the protection engineer to configure busbar sections, bays, current transformers, disconnectors, circuit breakers, protection functions and communication interfaces.
2. Main Features of SIPROTEC 5 7SS85
Important features include:
- Low-impedance busbar differential protection.
- Selective busbar section protection.
- Independent check-zone measurement.
- Differential and restraint current evaluation.
- CT saturation stabilization.
- Disconnector position evaluation.
- Dynamic busbar topology processing.
- Circuit-breaker failure protection.
- Inherent circuit-breaker failure protection.
- Bus coupler differential protection.
- End-fault protection.
- External tripping of busbar sections.
- Disconnector supervision.
- Flexible centralized and distributed protection architectures.
- IEC 61850 communication.
- GOOSE communication for distributed applications.
- DIGSI 5 engineering.
According to Siemens’ 7SS85 manual, the busbar differential protection has a typical operating time of approximately 7 ms under the specified operating conditions. Actual total fault-clearing time also depends on the protection output, circuit-breaker operating time and the complete tripping circuit.
3. Busbar Protection Principles
Busbar protection is generally based on the differential protection principle.
According to Kirchhoff’s current law, the sum of currents entering and leaving a protected electrical zone should be approximately zero under normal operating conditions and during external faults.
For an internal fault, the current balance changes and a differential current develops.
The basic differential current can be represented as:
[
I_{\mathrm{diff}}=\left|\sum_{k=1}^{n} I_k\right|
]
Where:
- (I_k) represents the current of each connected bay.
- (n) is the number of current measurement points.
- Current directions are defined according to the protection configuration.
The relay also calculates a restraint or stabilizing current. The differential protection characteristic compares the differential current against the restraint current.
This provides two important operating conditions:
External fault: The relay should remain stable even when high through-fault currents flow through the busbar.
Internal fault: The relay should detect the differential current and initiate tripping of the circuit breakers connected to the faulty busbar section.
4. Low-Impedance vs. High-Impedance Busbar Protection
Two common principles are used in busbar protection systems.
4.1 High-impedance differential protection
High-impedance protection uses a high-impedance measuring circuit, typically with matched CT requirements and a suitable stabilizing resistor.
The principle is based on the voltage developed across the high-impedance circuit during internal and external faults.
Important considerations include:
- CT characteristics.
- CT saturation behavior.
- Stabilizing resistor.
- Voltage-limiting equipment.
- CT secondary circuit design.
- Matching of CT ratios.
4.2 Low-impedance differential protection
Low-impedance protection uses numerical algorithms to calculate differential and restraint quantities.
The relay can accommodate different CT transformation ratios through engineering configuration and does not require interposing CTs solely to match all feeder CT ratios.
Important advantages include:
- Flexible busbar configuration.
- Numerical differential characteristics.
- Selective zone protection.
- CT saturation stabilization.
- Integration with switchgear topology.
- Advanced supervision and diagnostics.
- Flexible communication and automation.
The SIPROTEC 5 7SS85 is a low-impedance busbar protection solution.
5. Check-Zone and Selective Busbar Protection
One of the most important features of the 7SS85 is its use of two independent differential measurement systems.
5.1 Selective busbar zones
The selective busbar zones determine which particular busbar section is affected by a fault.
The current assignment to each busbar zone depends on the configured switchgear arrangement and actual disconnector positions.
For example, in a double-busbar substation, an outgoing feeder may be connected to Busbar 1 or Busbar 2.
The relay must know the actual switching configuration to assign the feeder current to the correct differential zone.
5.2 Check zone
The check zone provides an independent differential measurement that considers the overall protected busbar arrangement without relying on the selective disconnector image in the same way as the individual busbar zones.
Its purpose is to provide an additional verification of the internal fault condition.
The check-zone measurement improves security by helping prevent incorrect tripping caused by problems such as:
- Incorrect disconnector position information.
- Incorrect current assignment.
- Switching-state errors.
- Measurement problems.
- External fault conditions.
The exact operating logic and interaction between the check zone and selective busbar zones must be understood when engineering the protection.
5.3 Independent characteristics
The 7SS85 provides separately configurable operating characteristics for the check zone and busbar zones.
The selected characteristics and pickup settings must be coordinated with the CT characteristics, expected fault currents and system configuration.
6. Busbar Configurations Supported by 7SS85
The 7SS85 can be engineered for different busbar arrangements.
6.1 Single busbar
<escape> </escape>
A single busbar is the simplest arrangement.
Typical bays include:
- Incoming transformer feeders.
- Generator feeders.
- Outgoing feeders.
- Bus coupler or bus section arrangements, where applicable.
All connected circuits contribute to one main differential protection zone.
6.2 Single busbar with sectionalizer
A sectionalized busbar is divided into two or more sections using a bus section circuit breaker.
The bus sections can operate separately or be connected through the bus section breaker.
The 7SS85 must correctly identify the switching state and assign each feeder current to the appropriate protection zone.
6.3 Double busbar
A double-busbar arrangement allows feeders to be connected to either of two busbars through busbar disconnectors.
Typical equipment includes:
- Busbar 1.
- Busbar 2.
- Feeder circuit breakers.
- Busbar disconnectors.
- Bus coupler.
- Current transformers.
- Earthing switches.
The 7SS85 uses the disconnector image to determine the current assignment to the busbar protection zones.
6.4 Double busbar with transfer busbar
Some substations include a transfer busbar to support maintenance and switching operations.
The protection arrangement must correctly consider the transfer busbar and associated disconnectors.
Siemens documentation describes selective detection of short circuits on the transfer busbar, including tripping commands for the relevant circuit breakers at the opposite end where required by the application.
6.5 Multiple busbar arrangements
For more complex substations, the protection configuration may contain several busbar sections and additional bays.
The available number of bus zones and other function blocks depends on the selected centralized or distributed protection architecture and the configured device scope.
7. Busbar Differential Protection Settings
Correct busbar differential settings are essential for reliable protection.
Important settings include:
- Differential pickup threshold.
- Restraint current characteristic.
- Differential characteristic slope.
- High-set differential stage, where configured.
- Check-zone characteristic.
- Selective busbar-zone characteristic.
- CT saturation stabilization.
- Differential-current supervision.
- Zero-crossing supervision.
- Blocking and release conditions.
- Operating and supervision thresholds.
7.1 Differential current
The differential current represents the unbalanced current entering and leaving the protected zone.
For an internal fault, the differential current increases and may exceed the configured operating threshold.
7.2 Restraint current
The restraint current provides stability during external faults and high through-current conditions.
The relay evaluates the relationship between differential and restraint current using the configured characteristic.
7.3 CT saturation stability
External short circuits can produce very high currents.
During these conditions, one or more CTs may saturate, creating an apparent differential current.
The 7SS85 includes stabilization methods intended to maintain protection security during external faults and CT saturation.
Correct CT selection, wiring and commissioning remain essential.
7.4 CT ratio adaptation
A busbar protection system may include CTs with different transformation ratios.
The 7SS85 supports adaptation to different CT ratios through numerical configuration.
This reduces the need for interposing CTs solely for ratio matching.
The protection engineer must still verify CT performance, polarity, secondary wiring and suitability for the expected fault current.
8. Disconnector Image and Topology Processing
Disconnector position information is fundamental to selective busbar protection.
In a double-busbar substation, the relay must identify whether a feeder is connected to Busbar 1 or Busbar 2.
The 7SS85 uses the configured switchgear topology and actual switch positions to assign measured currents to the appropriate busbar zones.
8.1 Important signals
Typical signals include:
- Busbar disconnector open.
- Busbar disconnector closed.
- Transfer busbar disconnector position.
- Bus coupler disconnector position.
- Circuit-breaker open.
- Circuit-breaker closed.
- Disconnector intermediate position.
- Invalid or contradictory position indication.
8.2 Disconnector supervision
Disconnector supervision helps identify incorrect or inconsistent switching-state information.
Examples include:
- Both open and closed contacts active.
- Both contacts inactive when a valid position is expected.
- Incorrect position feedback.
- Discrepancy between expected and actual switching states.
Incorrect topology information can lead to incorrect current assignment. Therefore, disconnector signal engineering and testing are critical parts of commissioning.
8.3 DIGSI 5 Single-Line Editor
The Single-Line Editor (SLE) is an important engineering tool for configuring the busbar arrangement.
The engineer creates the busbar structure and connects the relevant bays and switching devices.
The resulting topology is used by the busbar protection function to determine the current assignment and selective tripping logic.
9. Circuit-Breaker Failure Protection – ANSI 50BF
Circuit-breaker failure protection is essential in busbar protection systems.
When a protection function issues a trip command, the circuit breaker should interrupt the fault current.
If the circuit breaker fails to open, the fault remains connected to the electrical system.
The circuit-breaker failure protection detects this condition and initiates backup tripping.
9.1 Operating principle
A typical circuit-breaker failure scheme includes:
- A protection function issues a trip command.
- The breaker failure function starts.
- Current flow is monitored.
- Breaker opening is evaluated.
- If the current remains above the configured threshold after the delay, backup tripping is initiated.
9.2 Busbar protection interaction
For a feeder fault, a failed circuit breaker may require tripping of the associated busbar section to clear the fault.
The protection scheme may also send an intertrip command to the remote line end.
For a busbar fault combined with circuit-breaker failure, the protection system must ensure that all necessary infeed sources are disconnected.
9.3 Important settings
- Breaker failure initiation.
- Current supervision threshold.
- Time delay.
- Backup trip output.
- Trip T2 logic.
- Remote intertrip.
- Busbar section trip assignment.
- Breaker status supervision.
Settings must be coordinated with the circuit-breaker operating time and the protection coordination philosophy.
10. Inherent Circuit-Breaker Failure Protection
The 7SS85 manual also describes an inherent circuit-breaker failure protection function.
This function monitors whether a circuit breaker has opened following a busbar protection trip or another relevant tripping command.
It uses current-flow supervision and a time delay to identify a breaker that has failed to interrupt the fault.
The function is important because a busbar fault must not remain connected through a failed circuit breaker after the other circuit breakers have opened.
For distributed applications, related functions can be implemented in the bay units or merging units as supported by the architecture.
11. Bus Coupler Differential Protection
A bus coupler connects two busbar sections.
In some arrangements, two current transformers are installed in the bus coupler bay.
The 7SS85 supports a bus coupler differential protection function for applicable configurations.
The section between the two current transformers is treated as a separate differential zone.
The function evaluates differential and restraint currents and can initiate operation of the bus coupler circuit breaker.
Important engineering considerations include:
- CT locations.
- CT ratios.
- CT polarity.
- Bus coupler circuit-breaker position.
- Differential characteristic.
- Trip output.
- Coordination with busbar protection.
- End-fault protection.
The bus coupler differential protection and end-fault protection must be engineered together where required by the switchgear arrangement.
12. End-Fault Protection
End-fault protection addresses faults in the section between a current transformer and an open circuit breaker.
This area can fall outside the normal protection zones depending on the location of the CT and circuit breaker.
End-fault protection evaluates the relevant breaker status and fault conditions to identify a fault in this section.
The function is particularly important in arrangements where the CT is located on the busbar side of the circuit breaker.
Important considerations include:
- CT location.
- Circuit-breaker position.
- Current measurement.
- Protection-zone boundaries.
- Trip logic.
- Busbar section assignment.
The 7SS85 manual describes end-fault protection for centralized and distributed busbar protection applications.
13. External Tripping of Busbar Sections
The 7SS85 supports external tripping functions that allow an external protection or control device to initiate tripping of a busbar section.
Typical applications include:
- External circuit-breaker failure protection.
- Backup protection.
- Protection system interlocking.
- External trip commands from bay devices.
The busbar protection evaluates the configured switchgear topology to determine which bays are connected to the affected busbar section.
The external trip command can be received through binary inputs or protection communication, depending on the application.
Proper supervision and release logic are necessary to avoid unwanted busbar tripping.
14. Centralized and Distributed Busbar Protection
The SIPROTEC 5 busbar protection architecture can be implemented in centralized or distributed arrangements.
14.1 Centralized busbar protection
In a centralized arrangement, the 7SS85 performs the main busbar differential protection calculations.
Current measurements and switching-state information are supplied from the relevant bays.
The central device evaluates:
- Busbar differential current.
- Restraint current.
- Check-zone measurements.
- Selective busbar zones.
- Disconnector positions.
- Circuit-breaker information.
- Tripping assignments.
This arrangement provides centralized protection engineering and topology processing.
14.2 Distributed busbar protection
A distributed arrangement uses a central unit together with bay units or merging units.
The central unit performs the busbar protection-specific functions, while selected bay-level functions are implemented in the distributed devices.
The architecture can use IEC 61850 communication for the exchange of information between the central unit and bay devices.
Important engineering tasks include:
- Device configuration.
- Bay assignment.
- Current measurement configuration.
- GOOSE communication.
- Central-unit configuration.
- Bay-to-central signal mapping.
- Communication supervision.
- Trip signal verification.
The exact device combination and functional allocation must follow Siemens’ supported architecture and documentation.
15. SIPROTEC 5 7SS85 Hardware and I/O Configuration
Hardware configuration depends on the selected 7SS85 device variant and protection architecture.
Typical hardware considerations include:
- Auxiliary power supply.
- Current measurement inputs.
- Binary inputs.
- Binary outputs.
- Communication interfaces.
- Ethernet ports.
- Additional I/O modules.
- Time synchronization interfaces.
The number and type of required inputs and outputs depend on the number of bays and the complexity of the switchgear.
A complete I/O list should be prepared before starting the DIGSI 5 engineering project.
Typical binary signals include:
- Circuit-breaker open.
- Circuit-breaker closed.
- Disconnector open.
- Disconnector closed.
- Trip circuit supervision.
- External trip.
- Breaker failure start.
- Protection blocking.
- Busbar trip.
- Alarm and device health.
16. DIGSI 5 Engineering for 7SS85
DIGSI 5 is the main engineering software used to configure SIPROTEC 5 devices.
The 7SS85 has a specialized engineering structure for busbar protection.
16.1 Create a new project
- Open DIGSI 5.
- Create a new project.
- Add the SIPROTEC 5 7SS85 device.
- Select the correct device variant.
- Check firmware compatibility.
- Select the busbar protection application template.
16.2 Configure the device
Configure the device hardware according to the selected order number.
Verify:
- Current inputs.
- Binary inputs.
- Binary outputs.
- Communication modules.
- Power supply.
- Installed hardware extensions.
16.3 Configure the busbar structure
Use the Single-Line Editor to create the actual switchgear arrangement.
Add:
- Busbar sections.
- Incoming bays.
- Outgoing bays.
- Bus coupler bays.
- Bus section breakers.
- Disconnectors.
- Circuit breakers.
- Current transformers.
The single-line configuration must reflect the real electrical arrangement.
16.4 Configure the bays
Each feeder, bus coupler or bus section disconnector is represented through the appropriate bay configuration.
The bay configuration includes the relevant function groups, such as:
- Circuit breaker.
- Disconnector.
- Current transformer.
- Other required protection and control functions.
16.5 Configure busbar protection zones
Create and configure the required busbar zones.
Important engineering parameters include:
- Number of busbar sections.
- Current measurement assignments.
- Check-zone configuration.
- Busbar-zone characteristics.
- Disconnector image.
- Bus coupler configuration.
- Circuit-breaker failure interaction.
- External trip logic.
16.6 Configure trip logic
The busbar protection must trip all circuit breakers connected to the faulty busbar section.
The trip assignment is determined by the switchgear topology.
The engineer must verify:
- Selective busbar tripping.
- Circuit-breaker outputs.
- Trip matrix.
- Bus coupler tripping.
- Breaker failure backup.
- Remote intertrip.
- External trip logic.
- Lockout and alarm signals.
16.7 Check and transfer the configuration
Before transferring the project to the relay:
- Check the device configuration.
- Review the single-line diagram.
- Verify the busbar zone assignments.
- Check the hardware configuration.
- Review communication settings.
- Validate trip logic.
- Document the final settings.
The downloaded project should be compared with the approved engineering documentation.
17. IEC 61850 Communication in 7SS85
IEC 61850 is important in modern busbar protection systems, particularly where protection information is exchanged between central and distributed devices.
Depending on the selected architecture, IEC 61850 communication can be used for:
- GOOSE messaging.
- MMS communication.
- Status exchange.
- Protection signals.
- Interlocking.
- Trip commands.
- Measurement information.
- Central-to-bay communication.
- Station-level integration.
17.1 GOOSE communication
GOOSE messaging provides fast peer-to-peer communication between IEDs.
Possible applications include:
- Transfer of bay information.
- Circuit-breaker status.
- Disconnector status.
- Protection blocking.
- Breaker failure signals.
- External trip signals.
- Trip commands.
In distributed busbar protection, communication engineering must be carefully coordinated with the central and bay devices.
17.2 SCL engineering
IEC 61850 SCL files describe the IED and substation communication configuration.
Common file types include:
- ICD – IED Capability Description.
- CID – Configured IED Description.
- SCD – Substation Configuration Description.
- IID – Instantiated IED Description.
The engineer must verify datasets, GOOSE control blocks, publisher/subscriber relationships and signal mapping.
17.3 Communication supervision
Important communication checks include:
- Ethernet connectivity.
- GOOSE publisher status.
- GOOSE subscriber status.
- Dataset mapping.
- VLAN configuration.
- Communication supervision.
- Time synchronization.
- Device health.
Tools such as IEDScout and Wireshark can help diagnose communication problems.
18. Testing and Commissioning of SIPROTEC 5 7SS85
Busbar protection commissioning is more complex than testing a conventional feeder protection relay because the protection depends on multiple CT circuits, switching-state information and selective trip logic.
A comprehensive commissioning plan should include hardware inspection, CT testing, topology verification, differential protection testing and complete trip circuit checks.
18.1 Hardware inspection
Verify:
- Relay model and order number.
- Auxiliary DC supply.
- Earthing.
- Current input wiring.
- Binary input wiring.
- Binary output wiring.
- Communication interfaces.
- Terminal connections.
- Device health indications.
18.2 CT circuit testing
Check:
- CT ratios.
- CT polarity.
- CT secondary grounding.
- CT circuit continuity.
- Current direction.
- Phase identification.
- Current measurement assignment.
- CT suitability for the application.
Incorrect CT polarity or current direction can produce unwanted differential current.
18.3 Differential protection testing
Testing should include:
- Balanced current conditions.
- External fault conditions.
- Internal fault conditions.
- Differential pickup.
- Restraint characteristic.
- CT saturation stability, using appropriate test methods.
- Check-zone operation.
- Selective busbar-zone operation.
- Alarm and trip signals.
18.4 Check-zone testing
The check zone must be tested independently to verify its measurement and operating characteristic.
The engineer should confirm that the check-zone logic interacts correctly with the selective busbar protection.
18.5 Disconnector image testing
This is one of the most important parts of commissioning.
Test different switching arrangements, including:
- Feeder connected to Busbar 1.
- Feeder connected to Busbar 2.
- Bus coupler open.
- Bus coupler closed.
- Transfer busbar in service.
- Busbar section disconnector open.
- Busbar section disconnector closed.
For each arrangement, verify the current assignment and the intended tripping behavior.
18.6 Circuit-breaker failure testing
Verify:
- Breaker failure initiation.
- Current supervision.
- Time delay.
- Backup trip.
- Trip T2.
- Remote intertrip.
- Busbar section tripping.
- Reset behavior.
18.7 End-fault protection testing
Test the relevant circuit-breaker and CT arrangement to verify detection of faults in the section between the CT and the open circuit breaker.
18.8 GOOSE and IEC 61850 testing
Check:
- GOOSE publisher.
- GOOSE subscriber.
- Dataset mapping.
- Signal exchange.
- Communication supervision.
- Blocking signals.
- External trip signals.
- Central and bay unit communication.
18.9 Complete scheme testing
The final test should verify the complete protection scheme from current measurement and switching-state information to the final circuit-breaker trip.
A successful relay injection test alone does not prove that the entire busbar protection system is correctly engineered.
19. Omicron Testing of 7SS85
Omicron CMC test equipment and Test Universe can be used for secondary injection testing of busbar protection functions.
Testing may include:
- Differential current injection.
- Restraint characteristic verification.
- Internal fault simulation.
- External fault simulation.
- Check-zone testing.
- Selective zone testing.
- CT polarity verification.
- Binary input/output testing.
- Circuit-breaker failure logic.
- Trip matrix verification.
For a multi-bay busbar protection scheme, the test plan must consider the complete measurement and switching configuration.
Multiple current injection channels and coordinated test equipment may be required depending on the test arrangement.
20. Common 7SS85 Engineering and Commissioning Problems
Incorrect CT polarity
Incorrect CT polarity can result in differential current during normal operation or external faults.
Incorrect CT ratio
An incorrect CT ratio or current scaling configuration can cause measurement imbalance.
Incorrect disconnector image
Incorrect switching-state configuration can assign feeder currents to the wrong busbar section.
Contradictory disconnector signals
Incorrect binary input wiring or contact logic can produce invalid topology information.
Incorrect busbar zone configuration
An incorrect number of busbar zones or incorrect bay assignment can affect selective tripping.
Check-zone mismatch
Incorrect measurement configuration or settings can cause disagreement between the check zone and selective zones.
Incorrect circuit-breaker failure settings
Incorrect current thresholds or time delays can lead to unwanted backup tripping or failure to clear a breaker-failure condition.
Incorrect trip matrix
The protection may identify the faulty busbar section but fail to trip all required circuit breakers because of incorrect output assignments.
GOOSE communication problems
Incorrect datasets, subscriptions, network configuration or communication supervision can affect distributed busbar protection.
Incorrect hardware configuration
A mismatch between the configured device and installed hardware can cause missing signals or unavailable functions.
21. SIPROTEC 5 7SS85 vs. SIPROTEC 4 7SS52
Siemens has offered different generations of busbar protection devices.
The SIPROTEC 4 7SS52 is a well-known numerical busbar protection system, while the SIPROTEC 5 7SS85 provides a newer engineering and hardware platform.
| Feature | SIPROTEC 4 7SS52 | SIPROTEC 5 7SS85 |
|---|---|---|
| Platform | SIPROTEC 4 | SIPROTEC 5 |
| Engineering software | DIGSI 4 | DIGSI 5 |
| Protection principle | Low-impedance differential | Low-impedance differential |
| Busbar topology | Configured busbar arrangements | Flexible topology engineering |
| Check zone | Available | Available |
| CT ratio adaptation | Numerical adaptation | Numerical adaptation |
| Engineering structure | SIPROTEC 4 architecture | Function-group-based architecture |
| IEC 61850 | Depends on device version and configuration | Supported according to selected architecture |
| Distributed protection | Device-specific architecture | Centralized and distributed applications |
Migration from 7SS52 to 7SS85 requires a complete engineering review. Existing CT assignments, topology logic, settings, trip circuits and communication configurations must be verified rather than transferred without modification.
22. Important Documents for a 7SS85 Project
A complete busbar protection project should include:
- Substation single-line diagram.
- Busbar arrangement drawings.
- CT data sheets.
- CT secondary circuit diagrams.
- Circuit-breaker drawings.
- Disconnector wiring diagrams.
- AC schematic diagrams.
- DC schematic diagrams.
- Protection philosophy.
- Busbar protection setting calculations.
- DIGSI 5 project.
- IEC 61850 SCL files.
- GOOSE signal list.
- I/O list.
- Trip matrix.
- Commissioning test procedure.
- Protection test reports.
- Final as-built documentation.
These documents are essential for engineering, commissioning, troubleshooting and future modification.
23. Siemens SIPROTEC 5 7SS85 Training by Elec-Engg
Elec-Engg provides practical training in power system protection and substation automation, including Siemens SIPROTEC protection relays and DIGSI 5 engineering.
Our busbar protection training focuses on the practical engineering and application of protection systems.
Training topics can include:
- Busbar protection principles.
- Low-impedance differential protection.
- Check-zone and selective-zone operation.
- CT selection and CT circuit engineering.
- Single-busbar and double-busbar arrangements.
- Bus coupler protection.
- Disconnector image configuration.
- Circuit-breaker failure protection.
- End-fault protection.
- DIGSI 5 project creation.
- Single-Line Editor engineering.
- Busbar zone configuration.
- Trip matrix and CFC logic.
- IEC 61850 and GOOSE engineering.
- Centralized and distributed busbar protection.
- Omicron CMC and Test Universe testing.
- Commissioning and troubleshooting.
Training formats include:
- Online training: Instructor-led technical courses.
- Structured self-paced training: Organized video lessons, practical exercises and learning materials.
- Face-to-face training: Classroom and practical engineering sessions.
- Customized in-house training: Training programs developed around company requirements, installed protection systems and project applications.
Our objective is to help protection, commissioning, operation and maintenance engineers develop the practical skills needed to configure, test and troubleshoot modern busbar protection systems.
Visit Elec-Engg.com to explore our power system protection and substation automation training programs or contact us to discuss customized training.
24. Conclusion
The Siemens SIPROTEC 5 7SS85 is a powerful low-impedance busbar protection solution for modern electrical substations.
Its combination of selective busbar differential protection, an independent check zone, dynamic topology processing, CT saturation stabilization and circuit-breaker failure protection provides a comprehensive approach to busbar protection.
Correct engineering of CT circuits, busbar topology, disconnector positions, protection zones, trip logic and IEC 61850 communication is essential for reliable operation.
For protection engineers, practical knowledge of DIGSI 5, busbar configuration, differential protection testing and commissioning is particularly important when working with complex substation arrangements.