MiCOM P13x Protection Relays: Complete Guide to P130, P132 and P139

Introduction to MiCOM P13x Protection Relays

The MiCOM P13x family belongs to the numerical protection and control relay portfolio developed for electrical distribution and industrial power systems.

These relays are designed for feeder protection applications where reliable detection of phase faults, earth faults, overloads and other abnormal electrical conditions is required.

MiCOM P13x devices combine protection functions with measurement, monitoring, control and communication capabilities, depending on the individual model and hardware configuration.

They can be used in distribution substations, industrial switchgear, utility networks and other electrical installations.

This article introduces the MiCOM P130, P132 and P139 models, their applications, protection functions, engineering considerations and testing procedures.

1. Overview of MiCOM P13x Models

The P13x family includes different relay variants intended for feeder protection and related applications.

ModelGeneral application
P130Feeder protection and control
P132Numerical feeder protection
P139Feeder protection and management

The available protection functions, measurement facilities, communication interfaces and hardware options must be verified against the relevant model documentation.

2. Applications of MiCOM P13x Relays

MiCOM P13x relays can be applied in different electrical distribution systems.

Typical applications include:

  • Medium-voltage feeder protection.
  • Industrial distribution networks.
  • Transformer feeder protection.
  • Incoming feeder protection.
  • Outgoing feeder protection.
  • Utility distribution substations.
  • Electrical switchgear protection.
  • Backup protection for downstream equipment.

The protection scheme must be designed according to the network configuration, grounding arrangement, fault levels and equipment requirements.

3. Main Protection Functions

The exact functions depend on the individual relay variant.

3.1 Phase Overcurrent Protection – ANSI 50/51

Phase overcurrent protection detects excessive current in the three phases.

The relay compares measured current against configured pickup values and initiates the appropriate operation when the protection conditions are satisfied.

Typical applications include:

  • Phase-to-phase fault protection.
  • Three-phase short-circuit protection.
  • Feeder backup protection.
  • Overload protection.

Important parameters include pickup current, operating curve, time multiplier and definite-time delay.

3.2 Earth-Fault Protection – ANSI 50N/51N

Earth-fault protection detects current flowing through an unintended earth-fault path.

Residual current can be calculated from the phase currents:

\[ I_N=I_A+I_B+I_C \]

Alternatively, a dedicated earth-current CT may be used.

Applications include cable protection, feeder earth-fault protection and transformer feeder backup protection.

3.3 Directional Overcurrent Protection – ANSI 67

Directional overcurrent protection determines whether a fault is located in the forward or reverse direction.

It is particularly useful in:

  • Parallel feeder systems.
  • Ring distribution networks.
  • Multiple-source installations.
  • Networks with distributed generation.

The directional element uses voltage and current information to establish the direction of fault current.

Correct CT and VT connections are essential for reliable operation.

3.4 Directional Earth-Fault Protection – ANSI 67N

Directional earth-fault protection identifies earth faults according to their direction.

Depending on the relay design, the element may use residual current and residual voltage measurements.

Important engineering parameters include:

  • Residual current pickup.
  • Residual voltage threshold.
  • Directional characteristic angle.
  • Forward and reverse direction.
  • Operating time.

3.5 Thermal Overload Protection – ANSI 49

Thermal overload protection estimates the thermal condition of electrical equipment.

It helps prevent damage caused by excessive current over an extended period.

Applications include cable and feeder thermal supervision.

3.6 Negative-Sequence Protection – ANSI 46

Negative-sequence protection detects current unbalance in three-phase electrical systems.

It can identify abnormal operating conditions such as phase imbalance, asymmetrical faults and open-phase conditions.

3.7 Voltage Protection – ANSI 27/59

Where supported, voltage protection provides supervision against:

  • Undervoltage.
  • Overvoltage.
  • Abnormal supply voltage.
  • Voltage-related operating conditions.

3.8 Frequency Protection – ANSI 81

Frequency protection monitors system frequency and can detect abnormal underfrequency or overfrequency conditions.

This function is particularly relevant in industrial power systems and installations requiring load-shedding or frequency supervision.

3.9 Circuit Breaker Failure Protection – ANSI 50BF

Circuit breaker failure protection supervises the operation of the associated circuit breaker following a trip command.

If the breaker fails to interrupt the fault current within the configured time, the relay initiates a backup trip scheme where configured.

4. CT and VT Connections

Correct instrument transformer connections are essential for proper protection operation.

Current Transformer Circuits

Engineers should verify:

  • CT primary and secondary ratios.
  • CT polarity.
  • Phase identification.
  • Secondary circuit continuity.
  • Correct earthing arrangement.
  • Residual current measurement.
  • CT accuracy requirements.

Voltage Transformer Circuits

For relays equipped with voltage inputs, the following should be checked:

  • VT transformation ratio.
  • Phase sequence.
  • Phase-to-neutral or phase-to-phase connections.
  • Residual voltage arrangements.
  • Voltage circuit supervision, where supported.

Incorrect instrument transformer connections can affect directional, voltage and measurement functions.

5. MiCOM P13x Protection Settings

Protection settings should be calculated according to the electrical system study and protection coordination requirements.

Typical setting groups include:

Setting categoryMain parameters
CT configurationPrimary and secondary ratios
VT configurationVoltage transformation ratio
Phase overcurrentPickup, curve and time delay
Earth faultPickup and operating time
Directional protectionDirection and characteristic angle
Thermal protectionThermal parameters
Voltage protectionPickup and delay
Frequency protectionFrequency thresholds and delays
Breaker failureCurrent supervision and timer

The final settings should consider normal load current, minimum fault current, maximum fault current, equipment withstand limits and upstream/downstream protection coordination.

6. MiCOM S1 Studio Engineering

MiCOM S1 Studio is an engineering tool used with supported MiCOM protection relays.

Depending on the relay and software version, engineering activities include:

  1. Creating a relay project.
  2. Selecting the correct device model.
  3. Establishing communication.
  4. Reading existing settings.
  5. Modifying protection parameters.
  6. Configuring available logic functions.
  7. Downloading the configuration.
  8. Retrieving events and disturbance records.
  9. Saving the final engineering project.

Before connecting to an installed relay, engineers should verify software compatibility and maintain a backup of the existing configuration.

7. Programmable Scheme Logic (PSL)

Programmable Scheme Logic provides flexibility for implementing application-specific protection and control schemes in supported MiCOM devices.

Typical applications include:

  • External trip logic.
  • Protection blocking.
  • Alarm generation.
  • Circuit breaker interlocking.
  • Binary input processing.
  • Circuit breaker status supervision.
  • Trip output logic.

A typical feeder trip scheme may combine protection operation signals with external blocking and breaker supervision conditions.

The completed logic must be checked against the approved protection drawings and tested before commissioning.

8. Communication and Substation Automation

Communication facilities allow protection relays to exchange information with SCADA systems and other substation devices.

Depending on the model and installed options, communication may include:

  • Serial communication.
  • Ethernet communication.
  • Remote measurement retrieval.
  • Event and alarm reporting.
  • Relay configuration access.
  • SCADA integration.
  • IEC 61850 integration where supported.

Engineers should verify the exact protocol support for the selected relay rather than assuming that every P13x device has identical communication capabilities.

9. Testing and Commissioning of MiCOM P13x

Secondary injection testing is an important part of relay commissioning.

Omicron CMC test equipment and Test Universe can be used for testing compatible protection functions.

Typical tests include:

TestPurpose
Current measurementVerify CT input measurements
Voltage measurementVerify VT input measurements
Overcurrent pickupVerify pickup thresholds
Overcurrent timingVerify operating time
Earth-fault protectionVerify earth-fault operation
Directional protectionVerify forward/reverse operation
Thermal protectionVerify thermal response
Voltage protectionVerify voltage thresholds
Frequency protectionVerify frequency operation
Binary inputsCheck external signals
Binary outputsCheck relay contacts
Trip circuitVerify breaker trip operation
CommunicationVerify remote monitoring

The actual commissioning test plan must reflect the protection functions available in the installed model.

10. Common Problems and Troubleshooting

Incorrect Current Measurements

Possible causes:

  • Wrong CT ratio.
  • Incorrect phase wiring.
  • Reversed CT polarity.
  • Incorrect relay input configuration.

Unexpected Earth-Fault Operation

Possible causes:

  • Incorrect residual current measurement.
  • CT secondary wiring problems.
  • Incorrect pickup settings.
  • Incorrect grounding arrangement.

Directional Protection Problems

Possible causes:

  • Incorrect CT polarity.
  • Incorrect VT phase connections.
  • Wrong phase sequence.
  • Incorrect directional characteristic settings.

Communication Failure

Possible causes:

  • Incorrect communication parameters.
  • Wrong cable or interface.
  • Incompatible engineering software.
  • Incorrect protocol configuration.

Unwanted Tripping

Possible causes:

  • Incorrect protection coordination.
  • Incorrect binary input mapping.
  • Incorrect PSL configuration.
  • Incorrect pickup or time-delay settings.

Event records, disturbance records and relay measurements should be reviewed when investigating unwanted operations.

11. MiCOM P13x Training by Elec-Engg

Elec-Engg provides practical technical training in power system protection, numerical protection relays and substation automation.

Our programs are designed for engineers working in utilities, power plants, industrial facilities and electrical engineering companies.

Available training methods include:

  • Online technical training.
  • Structured self-paced training.
  • Face-to-face classroom training.
  • Customized in-house training.

Our technical subjects include:

  • MiCOM feeder protection.
  • Overcurrent and earth-fault protection.
  • Directional protection.
  • Protection settings and coordination.
  • MiCOM S1 Studio engineering.
  • Programmable Scheme Logic.
  • Omicron CMC relay testing.
  • IEC 61850 and substation automation.

Customized training can be developed according to the installed relay models, project requirements and experience level of participating engineers.

For more information about MiCOM relay training and technical courses, contact Elec-Engg.

Conclusion

The MiCOM P13x family provides numerical feeder protection and control solutions for electrical distribution systems.

Understanding the protection functions, relay settings, instrument transformer connections, engineering software and commissioning procedures is essential for engineers responsible for electrical power system protection.

Follow Elec-Engg for more technical articles covering MiCOM relays, their applications, configuration, protection settings, testing and troubleshooting.