- 1. Introduction
- 2. What Are ANSI Device Numbers?
- 3. Overcurrent Protection – ANSI 50 and 51
- 4. Earth Fault Protection – ANSI 50N, 51N and 50G, 51G
- 5. Directional Overcurrent Protection – ANSI 67 and 67N
- 6. Distance Protection – ANSI 21
- 7. Differential Protection – ANSI 87
- 8. Restricted Earth Fault Protection – ANSI 64REF
- 9. Thermal Overload Protection – ANSI 49
- 10. Voltage Protection – ANSI 27 and 59
- 11. Frequency Protection – ANSI 81
- 12. Negative Sequence Protection – ANSI 46
- 13. Reverse Power Protection – ANSI 32
- 14. Loss of Excitation Protection – ANSI 40
- 15. Breaker Failure Protection – ANSI 50BF
- 16. Automatic Reclosing – ANSI 79
- 17. Synchronism Check – ANSI 25
- 18. Power Swing Detection and Out-of-Step Protection – ANSI 68 and 78
- 19. Motor Protection Functions
- 20. GE Multilin Protection Functions and Relay Selection
- 21. Practical Protection Engineering Considerations
- 22. Training on GE Multilin Protection Relays by Elec-Engg
- 23. Conclusion
1. Introduction
Protection functions are the foundation of every electrical power system protection scheme. Numerical protection relays continuously monitor electrical quantities, identify abnormal operating conditions and initiate appropriate control or tripping actions.
GE Multilin protection relays incorporate a wide range of protection functions designed for transformers, generators, motors, transmission lines, distribution feeders and busbar systems.
Understanding ANSI/IEEE device numbers is essential for protection engineers because these numbers provide a standardized way to identify protection and control functions in electrical drawings, relay settings, protection philosophies and commissioning documents.
This article explains the most important protection functions used in GE Multilin numerical relays, their ANSI device numbers, operating principles and practical applications.
2. What Are ANSI Device Numbers?
ANSI device numbers are standardized numerical identifiers used to describe electrical protection, control and switching functions.
They are commonly associated with IEEE C37.2, which defines standard device function numbers and contact designations.
For example:
- 50 – Instantaneous overcurrent protection
- 51 – Time overcurrent protection
- 21 – Distance protection
- 87 – Differential protection
- 27 – Undervoltage protection
- 59 – Overvoltage protection
- 67 – Directional overcurrent protection
- 79 – Automatic reclosing
These numbers are widely used in:
- Single-line diagrams
- Protection and control schematics
- Relay function lists
- Protection coordination studies
- Relay setting documents
- Commissioning reports
- Substation automation projects
A numerical protection relay may implement several ANSI functions within a single physical device.
The actual function names, implementation and available options depend on the specific GE Multilin model.
3. Overcurrent Protection – ANSI 50 and 51
Overcurrent protection is one of the most common protection functions in electrical power systems.
It detects current levels exceeding configured thresholds and initiates tripping when the operating criteria are satisfied.
3.1 Instantaneous Overcurrent Protection – 50
ANSI 50 operates when the measured current exceeds a predefined pickup threshold without an intentional inverse-time delay.
Applications include:
- Feeder short-circuit protection
- Transformer backup protection
- Motor short-circuit protection
- Busbar fault protection
- High-current fault detection
The pickup setting must be selected carefully to maintain selectivity and avoid unwanted operation during normal operating conditions or external faults.
3.2 Time Overcurrent Protection – 51
ANSI 51 operates according to a configured time-current characteristic.
Common characteristics include:
- Standard inverse
- Very inverse
- Extremely inverse
- Long-time inverse
- Definite-time overcurrent
The relay operating time depends on the measured current and selected characteristic.
A simplified inverse-time relationship is:
Operating time = f(Plug Setting Multiplier)
Where:
PSM = Fault current / Relay pickup current
The exact equation depends on the selected standard and curve.
3.3 GE Multilin Applications
Overcurrent protection is available across many GE Multilin feeder, transformer, motor and generator protection products.
Typical examples include the 350, 850, F60 and UR family relays.
4. Earth Fault Protection – ANSI 50N, 51N and 50G, 51G
Earth fault protection detects current flowing through an unintended path to ground.
It is essential for detecting phase-to-earth faults in electrical installations.
4.1 Neutral Overcurrent Protection
ANSI 50N and 51N are commonly used for neutral or residual overcurrent protection.
The residual current can be calculated as:
I0 = (IA + IB + IC) / 3
The residual current is:
3I0 = IA + IB + IC
Depending on the relay configuration, the measurement may be obtained from three phase CTs or a dedicated neutral CT.
4.2 Ground Overcurrent Protection
ANSI 50G and 51G are used for ground overcurrent applications.
The exact implementation and terminology can vary according to the relay and grounding arrangement.
4.3 Practical Applications
- Distribution feeder earth fault protection
- Transformer neutral protection
- Generator stator earth fault protection
- Industrial motor earth fault protection
- Backup earth fault protection
Correct CT configuration and grounding system analysis are essential for reliable earth fault detection.
5. Directional Overcurrent Protection – ANSI 67 and 67N
Directional overcurrent protection determines whether a fault is in the forward or reverse direction relative to the relay installation.
This function is particularly important in interconnected distribution systems, parallel feeders and networks with multiple sources.
The relay evaluates current and voltage quantities to determine the direction of fault current.
Applications
- Parallel transformer feeders
- Ring distribution networks
- Networks with distributed generation
- Transmission line backup protection
- Directional earth fault protection
ANSI 67 is generally used for directional phase overcurrent protection.
ANSI 67N is commonly used for directional neutral or earth fault protection.
6. Distance Protection – ANSI 21
Distance protection is widely used in transmission line protection.
The relay calculates the apparent impedance between its installation point and the fault location using measured voltage and current.
The basic relationship is:
Z = V / I
If the calculated impedance falls within a configured protection zone, the relay may initiate a trip command.
6.1 Distance Protection Zones
Typical distance protection schemes include:
- Zone 1 – High-speed primary protection
- Zone 2 – Extended protection and remote backup
- Zone 3 – Remote backup protection
The reach and time settings must be coordinated with adjacent protection systems and transmission network requirements.
6.2 GE Multilin Applications
GE Multilin D60 and D30 are examples of distance protection relays.
Their application requires appropriate engineering of:
- Line impedance
- Positive sequence impedance
- Zero sequence impedance
- CT and VT ratios
- Distance zone reach
- Directional characteristics
- Power swing blocking
- Fault resistance considerations
7. Differential Protection – ANSI 87
Differential protection is a highly selective protection principle used for critical electrical equipment.
It compares the currents entering and leaving a defined protection zone.
Under normal conditions and external faults, the compensated currents should balance within the relay’s operating criteria.
For an internal fault, the differential current increases and may cause the relay to trip.
7.1 Transformer Differential Protection – 87T
Transformer differential protection detects internal transformer faults.
Important engineering considerations include:
- Transformer vector group
- CT ratios
- CT connections
- Phase compensation
- Zero-sequence elimination
- Inrush current restraint
- Overexcitation restraint
- Differential pickup
- Percentage bias characteristics
GE Multilin T60 and 845 are examples of transformer protection products.
7.2 Generator Differential Protection – 87G
Generator differential protection detects internal faults within the generator stator winding protection zone.
GE Multilin G60 and 889 provide generator protection solutions.
7.3 Line Differential Protection – 87L
Line differential protection compares current measurements from both ends of a transmission line.
GE Multilin L90 is an example of a line differential protection relay.
7.4 Busbar Differential Protection – 87B
Busbar differential protection detects faults within the busbar protection zone.
GE Multilin B90 and B30 are examples of busbar protection solutions.
8. Restricted Earth Fault Protection – ANSI 64REF
Restricted earth fault protection is a sensitive protection function used to detect earth faults within a defined protection zone.
It is commonly applied to:
- Transformer windings
- Generator stator windings
- Other equipment with suitable neutral grounding arrangements
The protection scheme compares phase CT and neutral CT measurements.
Depending on the implementation, the relay may use high-impedance or low-impedance REF principles.
Important engineering considerations include:
- CT ratio matching
- CT polarity
- CT accuracy
- Neutral CT installation
- Stability during external faults
- Pickup sensitivity
- Operating time
REF protection is especially valuable when sensitive detection of winding-to-earth faults is required.
9. Thermal Overload Protection – ANSI 49
Thermal overload protection protects electrical equipment against excessive heating.
It is commonly applied to motors, transformers and generators.
The relay estimates thermal conditions using measured current and configured equipment characteristics.
Typical applications include:
- Motor thermal overload
- Transformer thermal protection
- Generator thermal monitoring
- Cable thermal protection
For motor applications, thermal protection may consider:
- Rated motor current
- Thermal capacity
- Heating time constant
- Cooling time constant
- Starting conditions
- Ambient temperature, where supported
GE Multilin 369 and 869 are examples of motor protection products.
10. Voltage Protection – ANSI 27 and 59
Voltage protection detects abnormal voltage conditions.
10.1 Undervoltage Protection – 27
Undervoltage protection operates when the measured voltage falls below a configured threshold.
Applications include:
- Motor protection
- Feeder protection
- Generator protection
- Load shedding
- Voltage supervision
10.2 Overvoltage Protection – 59
Overvoltage protection operates when the measured voltage exceeds the configured threshold.
Applications include:
- Transformer protection
- Generator protection
- Feeder protection
- Capacitor bank protection
Both functions may use definite-time or other supported operating characteristics.
11. Frequency Protection – ANSI 81
Frequency protection detects abnormal system frequency conditions.
11.1 Underfrequency – 81U
Underfrequency protection operates when system frequency falls below a configured threshold.
Typical applications include:
- Generator protection
- Load shedding
- Power system stability schemes
- Islanding detection schemes
11.2 Overfrequency – 81O
Overfrequency protection detects excessive system frequency.
It is commonly used in generator protection and power system control schemes.
12. Negative Sequence Protection – ANSI 46
Negative sequence protection detects unbalanced electrical conditions.
Unbalanced currents generate negative sequence components that can cause excessive heating in rotating machines.
This function is especially important for:
- Generators
- Motors
- Three-phase electrical equipment
The negative sequence current is commonly represented by I2.
Protection settings must consider the equipment’s permissible negative sequence withstand capability.
13. Reverse Power Protection – ANSI 32
Reverse power protection is commonly used in generator applications.
When a generator loses its prime mover input while remaining connected to the power system, it may begin importing active power from the network.
This condition can cause the generator to operate as a motor.
Reverse power protection detects the direction of active power flow and initiates the required action.
Applications include:
- Synchronous generators
- Turbine generators
- Diesel generator systems
- Generator protection schemes
14. Loss of Excitation Protection – ANSI 40
Loss of excitation protection detects abnormal reduction or loss of generator field excitation.
Loss of excitation can cause:
- Reactive power absorption
- Rotor heating
- Power system stability problems
- Abnormal generator operating conditions
The protection function generally evaluates generator electrical quantities and operating characteristics.
It is particularly important for large synchronous generators.
15. Breaker Failure Protection – ANSI 50BF
Breaker failure protection detects situations where a circuit breaker fails to interrupt fault current after receiving a trip command.
A typical scheme includes:
- Protection relay detects a fault.
- Trip command is issued.
- Breaker failure timer starts.
- Current or breaker status is monitored.
- If the breaker fails to clear the fault, backup tripping is initiated.
Applications include:
- Transmission substations
- Generator protection
- Transformer protection
- Busbar protection
- Distribution substations
16. Automatic Reclosing – ANSI 79
Automatic reclosing is used mainly in overhead transmission and distribution networks.
Many overhead line faults are temporary. Reclosing allows the circuit breaker to restore service after a predefined dead time.
Typical engineering parameters include:
- Reclosing initiation
- Dead time
- Reclaim time
- Number of shots
- Synchronism check
- Lockout conditions
- Protection initiation signals
The reclosing scheme must be coordinated with the network protection philosophy.
17. Synchronism Check – ANSI 25
Synchronism check verifies electrical conditions before connecting two electrical systems.
Typical parameters include:
- Voltage difference
- Frequency difference
- Phase angle difference
- Slip frequency
Applications include:
- Generator synchronization
- Busbar and feeder closing
- Interconnection of electrical networks
- Automatic transfer schemes
18. Power Swing Detection and Out-of-Step Protection – ANSI 68 and 78
Power swings can occur following disturbances in interconnected power systems.
They cause variations in apparent impedance measured by distance protection relays.
Power swing blocking helps prevent unwanted distance protection operation during stable power swings.
Out-of-step protection identifies unstable conditions where interconnected generators or power system areas lose synchronism.
These functions are particularly important in transmission networks and generator protection schemes.
19. Motor Protection Functions
Motor protection requires several functions working together to prevent electrical and thermal damage.
Important ANSI functions include:
| ANSI number | Protection function |
|---|---|
| 49 | Thermal overload |
| 50 | Instantaneous overcurrent |
| 51 | Time overcurrent |
| 46 | Negative sequence |
| 27 | Undervoltage |
| 48 | Incomplete sequence or starting supervision |
| 66 | Starts-per-hour supervision |
| 37 | Undercurrent or underpower |
| 50G/51G | Ground overcurrent |
The actual protection arrangement depends on the motor characteristics, starting method, driven equipment and process requirements.
20. GE Multilin Protection Functions and Relay Selection
Different GE Multilin models support different combinations of protection functions.
Some examples are:
| GE Multilin model | Main protection application |
|---|---|
| T60 | Transformer protection |
| 845 | Transformer protection |
| D60 | Distance protection |
| D30 | Distance protection |
| L90 | Line differential |
| G60 | Generator protection |
| 889 | Generator protection |
| B90 | Busbar protection |
| F60 | Feeder protection |
| 850 | Feeder protection |
| M60 | Motor protection |
| 869 | Motor protection |
| 369 | Motor protection |
| 469 | Motor protection |
This is an application overview, not a guarantee that every listed ANSI function is available in every hardware or firmware version.
21. Practical Protection Engineering Considerations
When configuring protection functions in GE Multilin relays, engineers should consider:
- Correct CT and VT ratios.
- Correct instrument transformer polarity.
- Correct system grounding arrangement.
- Protection pickup values.
- Operating time characteristics.
- Coordination with upstream and downstream relays.
- Circuit breaker operating time.
- Protection zone boundaries.
- Equipment thermal and short-circuit limits.
- Communication and interlocking requirements.
- Trip matrix and output assignment.
- Protection functional testing.
Protection settings should be based on approved engineering studies, equipment data and applicable protection standards.
22. Training on GE Multilin Protection Relays by Elec-Engg
Understanding ANSI protection functions is essential for engineers working with numerical protection relays.
However, effective protection engineering requires more than knowing device numbers. Engineers must understand the operating principles, setting calculations, relay configuration, coordination and practical testing of each protection function.
Elec-Engg offers practical technical training by Dr Saeed Roostaee (Electrical Engineering), focusing on power system protection and substation automation.
Our relevant training subjects include:
- Fundamentals of power system protection
- ANSI protection functions and applications
- Overcurrent protection and coordination
- Transformer differential protection
- Restricted earth fault protection
- Generator protection
- Motor protection
- Distance protection
- Feeder protection
- Numerical relay configuration
- FlexLogic and protection logic
- Relay testing using Omicron CMC
- IEC 61850 and GOOSE communication
- Protection commissioning and troubleshooting
Available Training Formats
- Pre-recorded technical video courses
- Structured self-paced training
- Live online technical training
- Face-to-face training
- Customized in-house training for utilities and companies
Training can be adapted to the experience level of engineers and the technical requirements of specific projects.
Explore technical training programs:
Contact us for customized training:
23. Conclusion
ANSI device numbers provide a standardized language for describing electrical protection and control functions.
GE Multilin numerical protection relays integrate many of these functions into flexible platforms designed for transformers, generators, motors, transmission lines, feeders and busbar systems.
Protection engineers must understand not only the meaning of each ANSI number but also its operating principle, application, setting requirements and coordination with other protection devices.
A strong understanding of these functions is fundamental to successful relay engineering, testing and commissioning.
In the next article, we will examine GE Multilin relay hardware in greater detail, including CPU modules, power supply modules, analog input modules, communication cards, binary inputs and outputs, and hardware configuration.