GE Multilin CT and VT Configuration: CT Ratios, VT Ratios, Polarity, Phase Assignment and Practical Engineering

Table Of Contents
  1. 1. Introduction
  2. 2. Why CT and VT Configuration Is Important
  3. 3. Current Transformer Fundamentals
  4. 4. Configuring CT Primary and Secondary Ratios
  5. 5. CT Polarity and Current Direction
  6. 6. Phase Identification and Phase Sequence
  7. 7. CT Connections for Overcurrent and Earth Fault Protection
  8. 8. CT Configuration for Transformer Differential Protection
  9. 9. CT Saturation and Accuracy Considerations
  10. 10. Voltage Transformer Fundamentals
  11. 11. VT Connection Types
  12. 12. VT Polarity and Phase Assignment
  13. 13. CT and VT Configuration for Directional Overcurrent Protection
  14. 14. CT and VT Configuration for Distance Protection
  15. 15. VT Fuse Failure and Loss-of-Potential Supervision
  16. 16. Practical CT and VT Configuration Workflow Using GE EnerVista Software
  17. 17. CT and VT Commissioning Tests
  18. 18. Common CT and VT Configuration Mistakes
  19. 19. Practical Engineering Checklist
  20. 20. Conclusion
  21. 21. Training on GE Multilin Protection Relays by Elec-Engg
  22. 22. Related Articles in the GE Multilin Protection Relay Series

1. Introduction

Correct current transformer (CT) and voltage transformer (VT) configuration is one of the most important stages in engineering a GE Multilin numerical protection relay. Even when the protection settings are correctly calculated, incorrect CT or VT ratios, polarity, phase assignment, or connection configuration can cause inaccurate measurements, incorrect fault detection, unwanted protection operation, or failure to trip during an actual fault.

GE Multilin relays use measured current and voltage signals to perform protection functions such as overcurrent, earth fault, directional overcurrent, distance protection, transformer differential protection, generator protection, voltage protection, frequency protection, and synchronism checking.

The accuracy of these functions depends on the correct relationship between the primary power system quantities and the secondary signals supplied to the relay.

This article explains the practical engineering principles behind CT and VT configuration in GE Multilin protection relays, including ratio selection, polarity, phase assignment, connection types, differential protection considerations, commissioning checks, and common configuration mistakes.

The exact configuration parameters and available measurement options depend on the GE Multilin relay model, hardware configuration, firmware version, and application.

2. Why CT and VT Configuration Is Important

Protection relays do not normally measure the primary system current and voltage directly. Instead, instrument transformers reduce these quantities to levels suitable for protection and measurement equipment.

For example:

  • A CT with a ratio of 1000/1 A converts 1000 A primary current into 1 A secondary current.
  • A VT with a ratio of 11,000/110 V converts 11 kV primary voltage into 110 V secondary voltage.

The relay uses the secondary quantities and the configured transformer ratios to calculate primary system values.

Incorrect configuration can affect:

  • Primary current and voltage measurements.
  • Overcurrent pickup and operating time.
  • Directional protection decisions.
  • Distance protection impedance calculations.
  • Transformer differential protection.
  • Generator differential protection.
  • Power and energy calculations.
  • Synchronism-check functions.
  • Event records and disturbance analysis.

Important engineering principle: CT and VT configuration must agree with the actual instrument transformer nameplates, approved drawings, wiring diagrams, and the relay’s measurement input arrangement.

3. Current Transformer Fundamentals

A current transformer reproduces the primary current at a reduced secondary value.

The CT ratio is expressed as:

CT Primary Current / CT Secondary Current

Common secondary ratings include 1 A and 5 A, depending on the installation and relay input design.

3.1 CT Ratio Example

Consider a CT with the following nameplate rating:

  • Primary current: 1000 A
  • Secondary current: 1 A
  • CT ratio: 1000/1 A

If the primary current is 600 A, the ideal secondary current is:

Is = Ip × (1 / CT ratio)

Is = 600 × (1 / 1000)

Is = 0.6 A

The relay receives approximately 0.6 A at its current input, assuming ideal CT performance and correct wiring.

If the relay is configured to display primary current, it uses the configured ratio to scale the measured secondary current.

3.2 CT Secondary Rating: 1 A or 5 A

The relay’s physical current input rating must match the CT secondary circuit.

For example, a relay designed for a 1 A current input must not be connected to a 5 A CT secondary circuit unless the specific hardware input is explicitly rated for that arrangement.

The engineer should verify:

  • CT secondary rating.
  • Relay current input rating.
  • CT ratio.
  • CT accuracy class.
  • CT burden.
  • CT short-time thermal current.
  • CT dynamic withstand capability.
  • CT core allocation and intended protection duty.

Never assume that all GE Multilin models or input modules support both 1 A and 5 A inputs.

4. Configuring CT Primary and Secondary Ratios

The CT ratio entered into the relay must reflect the installed CT.

Example:

ParameterValue
CT primary rating800 A
CT secondary rating1 A
CT ratio800/1
Primary operating current400 A
Expected secondary current0.5 A

The relay’s scaling configuration must use the correct primary and secondary values where these parameters are separately available.

4.1 Practical Engineering Example

A feeder has three phase CTs rated 1200/1 A. The measured secondary current during normal operation is 0.75 A.

The corresponding primary current is:

Ip = 0.75 × 1200 = 900 A

If the relay is configured with an incorrect CT ratio of 1000/1 A, it may display:

Ip = 0.75 × 1000 = 750 A

The actual current is 900 A, but the displayed primary value is 750 A.

This error can affect engineering decisions and any protection settings or calculations that rely on incorrectly scaled quantities.

Practical lesson: Verify the CT ratio independently against the nameplate and approved drawings before entering it into the relay configuration.

5. CT Polarity and Current Direction

CT polarity is essential for correct protection operation, particularly in differential and directional protection schemes.

A CT normally has primary polarity markings P1 and P2, and secondary polarity markings S1 and S2. The exact terminal designations should be confirmed from the manufacturer’s documentation.

The polarity relationship establishes the direction of the secondary current relative to the primary current.

5.1 Why CT Polarity Matters

Incorrect CT polarity can cause:

  • Incorrect directional overcurrent operation.
  • Incorrect differential current calculation.
  • False differential current during normal load conditions.
  • Incorrect residual current calculations.
  • Incorrect phase-angle relationships.
  • Unwanted tripping or failure to operate.

5.2 CT Polarity Verification

CT polarity should be verified using suitable test equipment and approved procedures.

Typical checks include:

  1. Review the CT nameplate and terminal markings.
  2. Verify the primary conductor orientation.
  3. Confirm the secondary wiring against the schematic.
  4. Check the polarity of the current input at the relay.
  5. Perform an appropriate polarity test.
  6. Verify the measured current direction and phase relationship.
  7. Compare the results with the protection scheme design.

Never open-circuit an energized CT secondary circuit. Dangerous voltages can develop. Use approved shorting facilities and safe isolation procedures.

6. Phase Identification and Phase Sequence

The relay must receive the correct current and voltage signals for phases A, B, and C.

A typical three-phase arrangement includes:

  • IA: Phase A current.
  • IB: Phase B current.
  • IC: Phase C current.
  • VA: Phase A voltage.
  • VB: Phase B voltage.
  • VC: Phase C voltage.

The actual terminal labels and phase naming conventions may vary by relay model.

Incorrect phase assignment can affect directional protection, power measurement, phase comparison, distance protection, and other functions that depend on the relationship between current and voltage.

6.1 Phase Sequence

The phase sequence describes the order in which the three phase voltages reach their positive peaks.

Common designations include ABC and ACB.

The engineer should confirm:

  • The power system phase sequence.
  • The CT phase assignment.
  • The VT phase assignment.
  • The relay’s configured phase rotation, if applicable.
  • The phase relationships shown in the approved drawings.

A phase sequence error can produce misleading measurements and incorrect protection decisions.

7. CT Connections for Overcurrent and Earth Fault Protection

For conventional three-phase overcurrent protection, three phase CTs are commonly connected to the relay’s phase current inputs.

The relay uses these currents for functions such as:

  • Phase instantaneous overcurrent (50).
  • Phase time overcurrent (51).
  • Negative-sequence overcurrent (46), where supported.
  • Thermal overload functions using current measurements.

7.1 Residual Earth Fault Current

In a three-phase system, residual current can be calculated from the vector sum of the phase currents:

3I0 = IA + IB + IC

For a balanced healthy system, the vector sum should be approximately zero, subject to measurement errors and system conditions.

During an earth fault, residual current may become significant.

Depending on the relay model and application, earth fault protection may use:

  • Residual current calculated from the three phase CT inputs.
  • A separate neutral CT input.
  • A core-balance CT.
  • A dedicated ground-current input.

These methods are not interchangeable without checking the protection design and relay input capabilities.

7.2 Separate Neutral or Core-Balance CT

A core-balance CT surrounds all phase conductors and, where applicable, the neutral conductor. It measures the residual current directly.

This arrangement can provide sensitive earth fault detection, particularly in applications where phase CT residual measurement is not sufficiently sensitive.

The engineer must verify the CT ratio, wiring polarity, relay input rating, and the selected earth fault protection function.

8. CT Configuration for Transformer Differential Protection

Transformer differential protection is one of the most demanding applications for CT configuration.

A transformer differential relay compares current measurements from different sides of the protected transformer. Under normal load and external fault conditions, the currents should balance after accounting for transformer ratio, vector group, and other compensation requirements.

The differential protection function identifies an internal fault when the compensated currents do not balance within the configured operating characteristics.

8.1 Transformer Ratio Matching

Consider a power transformer with:

  • HV rated voltage: 132 kV
  • LV rated voltage: 33 kV
  • Transformer rating: 40 MVA

The CT ratios on the HV and LV sides must be selected and configured so that the relay can correctly compare the measured currents.

The actual current on each side depends on the transformer rating and voltage:

I = S / (√3 × V)

For the HV side:

I = 40 MVA / (√3 × 132 kV)

I ≈ 175 A

For the LV side:

I = 40 MVA / (√3 × 33 kV)

I ≈ 700 A

The relay must compensate for the different current magnitudes and transformer connections.

8.2 Transformer Vector Group Compensation

Transformer vector group affects the phase displacement between HV and LV currents.

For example, a Dyn11 transformer introduces a phase displacement that must be considered by the differential protection scheme.

Depending on the relay model and configuration, compensation may be implemented internally by the relay or through an external CT connection arrangement.

The engineer must follow the relay manufacturer’s application guidance and the approved protection design. Do not apply external CT compensation and internal relay compensation simultaneously unless the design explicitly requires it.

8.3 Zero-Sequence Compensation

Zero-sequence current behavior can differ between transformer windings, particularly when one winding is delta-connected and another is grounded-wye connected.

Differential protection may require zero-sequence compensation or elimination to maintain stability during external earth faults.

The available compensation methods and configuration parameters depend on the specific GE Multilin transformer protection relay.

8.4 Differential Protection Commissioning

Before energizing a transformer differential scheme, verify:

  • CT ratios on all transformer sides.
  • CT polarity.
  • Phase assignment.
  • Transformer vector group.
  • Rated voltage and power.
  • Relay compensation configuration.
  • Differential and restraint current measurements.
  • Stability under balanced load or suitable secondary injection.
  • Operation under simulated internal fault conditions, where required by the approved test plan.

A differential protection scheme should never be commissioned based only on the absence of an alarm. The engineer must confirm that the measured and calculated quantities behave as expected.

9. CT Saturation and Accuracy Considerations

CT saturation can distort the secondary current waveform and affect protection performance.

Saturation may occur during high-current faults, particularly when the CT burden is high or the CT core is unsuitable for the required protection duty.

Factors affecting CT performance include:

  • CT accuracy class.
  • CT knee-point voltage, where relevant.
  • Secondary winding resistance.
  • Cable resistance.
  • Relay input burden.
  • Fault current magnitude.
  • System X/R ratio.
  • Remanent flux.
  • CT core selection.

9.1 Protection CT Selection

Protection CTs must be selected according to the applicable protection application and standards.

Differential, distance, and high-set overcurrent protection may impose different CT performance requirements.

The engineer should not select CTs based solely on their primary and secondary current ratings. Accuracy and saturation performance must also be considered.

10. Voltage Transformer Fundamentals

A voltage transformer reduces the primary system voltage to a secondary value suitable for protection and measurement.

Example:

  • Primary voltage: 33 kV
  • Secondary voltage: 110 V
  • VT ratio: 33,000/110
  • Ratio: 300:1

If the primary voltage is 30 kV, the ideal secondary voltage is:

Vs = 30,000 / 300 = 100 V

The relay uses the configured voltage ratio to calculate primary voltage where primary scaling is available.

10.1 VT Ratio Configuration

The engineer must confirm whether the VT nameplate rating is expressed as:

  • Phase-to-phase voltage.
  • Phase-to-neutral voltage.
  • A winding ratio for a particular connection.

This distinction is important. A line-to-line voltage must not be entered as a phase-to-neutral voltage, or vice versa, without accounting for the actual VT connection and relay measurement arrangement.

11. VT Connection Types

Different VT connection arrangements are used depending on the power system earthing arrangement and protection requirements.

11.1 Three-Phase Grounded-Wye Connection

A grounded-wye VT secondary provides phase-to-neutral voltages and may also provide phase-to-phase voltage measurements.

It is commonly used for voltage measurement and protection functions.

The engineer must verify the neutral connection and grounding arrangement against the design.

11.2 Open-Delta or Broken-Delta Connection

An open-delta or broken-delta secondary arrangement can provide a residual voltage signal associated with zero-sequence voltage.

This signal can be used in suitable earth fault detection and voltage supervision schemes.

The actual application depends on the VT design, system earthing, relay input arrangement, and protection scheme.

11.3 Other VT Arrangements

Some installations use other voltage transformer arrangements, including phase-to-phase connections or single-phase VTs.

The relay’s voltage input configuration must match the installed wiring arrangement. Do not assume that every relay supports every VT connection type.

12. VT Polarity and Phase Assignment

Correct VT polarity is essential for protection functions that compare voltage and current phase angles.

These include:

  • Directional overcurrent protection (67/67N).
  • Distance protection (21).
  • Power protection (32).
  • Synchronism check (25).
  • Power factor and power measurement.
  • Other voltage-dependent protection functions.

Incorrect VT polarity or phase assignment can produce an incorrect directional decision or impedance calculation.

12.1 Practical Verification

The commissioning engineer should:

  1. Check VT nameplate polarity and terminal markings.
  2. Review the approved VT secondary wiring diagram.
  3. Verify phase identification at the relay terminals.
  4. Confirm the neutral and earth connections.
  5. Perform suitable voltage injection tests.
  6. Compare the measured phase sequence and phase angles with expected values.
  7. Verify the relationship between current and voltage for directional protection.

13. CT and VT Configuration for Directional Overcurrent Protection

Directional overcurrent protection determines whether a fault is in the forward or reverse direction relative to the relay’s configured reference.

It generally uses current and polarizing voltage quantities, with the exact method depending on the relay and protection function.

For example, a feeder relay may use phase current and an appropriate phase-to-phase or other polarizing voltage quantity.

Incorrect CT polarity, VT phase assignment, or phase rotation can cause the relay to interpret the direction incorrectly.

For commissioning, verify:

  • Correct phase current inputs.
  • Correct voltage inputs.
  • CT polarity.
  • VT polarity.
  • Phase sequence.
  • Directional characteristic and settings.
  • Forward and reverse operation using suitable test methods.

Do not assume that a correct overcurrent pickup test also proves correct directional operation.

14. CT and VT Configuration for Distance Protection

Distance protection calculates an apparent impedance using measured voltage and current.

A simplified relationship is:

Z = V / I

The relay compares the calculated impedance with the configured protection zones.

Incorrect CT or VT ratios can cause the relay to calculate an incorrect primary impedance. Incorrect phase assignment or polarity can also affect the measured quantities and protection behavior.

For a GE Multilin distance relay, such as a model in the D60 or D30 family, the engineer must verify the specific model’s measurement arrangement and configuration requirements.

Important checks include:

  • CT primary and secondary ratings.
  • VT primary and secondary ratings.
  • Phase assignment.
  • Phase rotation.
  • Ground compensation settings, where applicable.
  • Line impedance data.
  • Protection zone settings.
  • VT failure supervision, where supported.

The exact parameter names and implementation depend on the relay model and firmware.

15. VT Fuse Failure and Loss-of-Potential Supervision

Voltage transformer secondary circuit failures can cause incorrect voltage measurements.

Examples include:

  • Blown VT fuse.
  • Open secondary wiring.
  • Loss of one phase voltage.
  • Incorrect VT isolation.
  • Wiring or terminal failure.

If the relay continues to use invalid voltage measurements, voltage-dependent functions may operate incorrectly.

Some GE Multilin relay models provide VT fuse failure, loss-of-potential, or related supervision features. The engineer must check the applicable model manual to confirm the function and its operating principles.

Where available, supervision logic may be used to block or modify selected voltage-dependent protection functions during detected VT circuit failure.

Commissioning should include verification of the supervision logic and its interaction with directional, distance, and other voltage-dependent elements.

16. Practical CT and VT Configuration Workflow Using GE EnerVista Software

GE Multilin relays are engineered using the applicable EnerVista software for the specific relay family and model.

The exact screens, menus, and parameter names vary between products. The following is a general engineering workflow rather than a model-specific menu sequence.

Step 1 – Identify the Relay

Confirm:

  • Relay model.
  • Hardware order code.
  • Firmware version.
  • Current input rating.
  • Voltage input arrangement.
  • Available protection functions.

Step 2 – Collect Instrument Transformer Data

Obtain:

  • CT nameplate information.
  • VT nameplate information.
  • CT and VT connection diagrams.
  • Protection single-line diagram.
  • Secondary wiring drawings.
  • Transformer vector group, where applicable.

Step 3 – Review the Current and Voltage Input Wiring

Check that the installed wiring matches the approved design.

Verify phase identification, polarity, terminal assignment, neutral connections, and grounding.

Step 4 – Configure CT Ratios

Enter the correct CT ratio and associated current input information in the applicable relay settings.

Check whether the relay expects separate primary and secondary values or another ratio representation.

Step 5 – Configure VT Ratios

Enter the appropriate voltage transformer data and select the correct voltage connection arrangement, where configurable.

Confirm whether the values refer to phase-to-phase or phase-to-neutral quantities.

Step 6 – Configure Application-Specific Parameters

Depending on the protection application, configure the relevant parameters for:

  • Differential protection.
  • Directional overcurrent.
  • Distance protection.
  • Earth fault protection.
  • Generator protection.
  • Voltage and frequency protection.

Step 7 – Review and Save the Configuration

Review the settings for consistency with the approved engineering documents.

Save the project and follow the site’s document control procedure for revisions and backups.

Step 8 – Perform Testing

Use suitable secondary injection and commissioning test procedures to verify the relay’s current and voltage measurements and protection functions.

17. CT and VT Commissioning Tests

CT and VT commissioning should be performed by qualified personnel using approved test procedures and suitable equipment.

17.1 CT Checks

Typical checks include:

  • CT ratio verification.
  • Polarity verification.
  • Secondary continuity.
  • Insulation checks as appropriate.
  • Phase identification.
  • Secondary earthing verification.
  • Burden assessment where required.
  • Relay current measurement verification.

17.2 VT Checks

Typical checks include:

  • VT ratio verification.
  • Polarity verification.
  • Secondary wiring continuity.
  • Phase identification.
  • Phase sequence verification.
  • Neutral and earth connection checks.
  • Relay voltage measurement verification.

17.3 Relay Secondary Injection

A relay test set can inject controlled current and voltage signals into the relay.

The engineer can verify:

  • Measured phase currents.
  • Measured phase voltages.
  • Current and voltage scaling.
  • Phase angles.
  • Residual current calculations.
  • Directional protection behavior.
  • Differential protection measurements.
  • Voltage-dependent protection functions.

The test plan must reflect the specific relay model, protection scheme, and commissioning requirements.

18. Common CT and VT Configuration Mistakes

MistakePossible consequence
Incorrect CT ratioIncorrect current measurement and scaling
Incorrect VT ratioIncorrect voltage measurement and scaling
Wrong CT polarityIncorrect directional or differential behavior
Wrong VT polarityIncorrect phase-angle relationships
Phase A and Phase B interchangedIncorrect phase measurements and protection calculations
Incorrect phase sequenceIncorrect directional or voltage-dependent operation
Incorrect VT connection selectionIncorrect voltage quantities
Incorrect transformer vector groupDifferential protection instability or incorrect compensation
Wrong current input ratingMeasurement error or hardware incompatibility
Incorrect residual CT wiringIncorrect earth fault measurement
Missing VT failure supervision checksVoltage-dependent functions may respond incorrectly to VT circuit failures

19. Practical Engineering Checklist

Before commissioning a GE Multilin protection relay, verify the following:

CT configuration

  • CT primary rating verified.
  • CT secondary rating verified.
  • Relay current input rating confirmed.
  • CT ratio configured correctly.
  • CT polarity verified.
  • Phase assignment verified.
  • Neutral or residual CT wiring checked.
  • CT secondary grounding checked.
  • CT core allocation checked.

VT configuration

  • VT primary rating verified.
  • VT secondary rating verified.
  • Phase-to-phase or phase-to-neutral basis confirmed.
  • VT ratio configured correctly.
  • VT connection arrangement confirmed.
  • VT polarity verified.
  • Phase sequence verified.
  • Neutral and grounding arrangements checked.
  • VT fuse failure supervision reviewed, where supported.

Protection and commissioning

  • Protection settings reviewed.
  • Current measurements verified by injection.
  • Voltage measurements verified by injection.
  • Phase angles checked.
  • Directional elements tested where applicable.
  • Differential measurements and stability checked where applicable.
  • Test results documented.
  • Final settings file backed up.

20. Conclusion

Correct CT and VT configuration is fundamental to the reliable operation of GE Multilin protection relays.

The engineer must understand not only how to enter CT and VT ratios into the relay, but also how instrument transformer polarity, phase assignment, connection arrangements, accuracy, and application-specific compensation affect protection performance.

Particular attention is required for directional overcurrent, distance protection, transformer differential protection, and generator protection because these functions depend strongly on the correct relationship between measured current and voltage quantities.

A successful commissioning process combines drawing reviews, nameplate verification, wiring inspections, secondary injection testing, and functional protection tests.

21. Training on GE Multilin Protection Relays by Elec-Engg

Elec-Engg provides practical technical training in power system protection, protection relay engineering, substation automation, relay configuration, testing, and commissioning.

Training by Dr Saeed Roostaee (Electrical Engineering) focuses on practical engineering applications and the skills required by protection, commissioning, operation, and maintenance engineers.

Relevant training topics include:

  • GE Multilin protection relay architecture and configuration.
  • CT and VT engineering and relay measurement configuration.
  • Overcurrent and earth fault protection.
  • Directional overcurrent protection.
  • Transformer differential protection.
  • Generator and motor protection.
  • Protection settings and coordination.
  • Relay testing and commissioning using secondary injection.
  • Event records, disturbance analysis, and troubleshooting.
  • Communication and IEC 61850 engineering, where supported by the selected relay.

Training is available through pre-recorded video courses, structured self-paced training, live online sessions, face-to-face courses, and customized in-house training.

For more information:

Website: https://elec-engg.com/

Contact: https://elec-engg.com/contact/

22. Related Articles in the GE Multilin Protection Relay Series

  • Introduction to GE Multilin Protection Relays: Technology, Applications, Functions and Engineering
  • GE Multilin Protection Relay Product Families and Applications
  • GE Multilin Numerical Protection Relay Architecture
  • GE Multilin Protection Functions and ANSI Device Numbers
  • GE Multilin Protection Relay Hardware and Modules
  • GE Multilin CT and VT Configuration

The next articles will explore GE Multilin relay configuration, EnerVista software, protection settings, testing, commissioning, and practical applications of individual relay families.