GE Multilin 350 Feeder Protection Relay: Complete Technical Guide to Overcurrent Protection, Earth Fault, Directional Functions, Configuration and Testing

Table Of Contents
  1. 1. Introduction
  2. 2. GE Multilin 350 Relay Overview
  3. 3. Feeder Protection Philosophy
  4. 4. GE Multilin 350 Relay Architecture
  5. 5. CT Configuration and Current Scaling
  6. 6. Earth-Fault Current Measurement
  7. 7. Phase Overcurrent Protection – ANSI 50/51
  8. 8. Practical Overcurrent Example
  9. 9. Earth-Fault Protection – ANSI 50N/51N and 50G/51G
  10. 10. Directional Overcurrent Protection – ANSI 67/67N
  11. 11. Voltage and Frequency Protection
  12. 12. Protection Coordination
  13. 13. Circuit-Breaker Trip Logic
  14. 14. GE Multilin 350 Settings and Configuration Workflow
  15. 15. Communication and SCADA Integration
  16. 16. Testing and Commissioning
  17. 17. Common GE Multilin 350 Troubleshooting Problems
  18. 18. Practical Commissioning Checklist
  19. 19. GE Multilin 350 Compared with Other GE Multilin Feeder Relays
  20. 20. Training on GE Multilin Feeder Protection by Elec-Engg
  21. 21. Conclusion
  22. 22. Frequently Asked Questions

1. Introduction

The GE Multilin 350 is a numerical feeder protection relay designed for protection applications in electrical distribution systems. It is used to protect feeder circuits against abnormal operating conditions, particularly phase overcurrent and earth faults.

Feeder protection is a fundamental part of electrical power system protection. A feeder fault must be detected quickly and selectively so that the affected circuit can be isolated without unnecessarily interrupting the supply to healthy sections of the network.

In addition to protection, modern numerical relays provide measurement, event recording, programmable logic and communication capabilities. These functions help commissioning and maintenance engineers understand system behaviour and investigate protection operations.

This article provides a practical engineering guide to the GE Multilin 350, covering:

  • Relay architecture and applications
  • CT and VT configuration
  • Phase overcurrent protection (ANSI 50/51)
  • Earth-fault protection
  • Directional overcurrent principles
  • Voltage and frequency supervision
  • Protection coordination
  • Trip logic and binary inputs/outputs
  • Communication and SCADA integration
  • Settings and configuration
  • Secondary injection testing
  • Commissioning and troubleshooting

The precise functions available must be confirmed against the relay’s order code, hardware, firmware and applicable manufacturer documentation.

2. GE Multilin 350 Relay Overview

The GE Multilin 350 is part of GE’s feeder protection product range.

It is intended for feeder applications where dependable fault detection and circuit isolation are required.

Typical applications include:

  • Medium-voltage distribution feeders
  • Industrial distribution panels
  • Utility substations
  • Transformer outgoing feeders
  • Industrial incomers
  • Radial distribution systems
  • Selected interconnected feeder applications, where supported

A typical installation includes:

  1. Current transformers.
  2. Voltage transformers, where required.
  3. GE Multilin 350 relay.
  4. Circuit breaker.
  5. Breaker auxiliary contacts.
  6. Trip and close circuits.
  7. DC auxiliary supply.
  8. SCADA or communication network.

The relay receives electrical measurements from instrument transformers, processes the signals and evaluates the configured protection elements.

When an operating condition is detected, the relay initiates the configured alarm or trip response.

3. Feeder Protection Philosophy

The main objective of feeder protection is to identify faults within the protected circuit and isolate them selectively.

The protection design must consider:

  • Maximum load current
  • Emergency loading
  • Minimum fault current
  • Maximum fault current
  • Phase-to-phase faults
  • Three-phase faults
  • Single-phase earth faults
  • Double-phase earth faults
  • Motor starting current
  • Transformer inrush
  • Cable thermal withstand
  • Upstream and downstream protection
  • Circuit-breaker clearing time

For a radial feeder, non-directional overcurrent protection may be sufficient. For a network with multiple sources or parallel paths, directional protection may be required.

The protection philosophy should be based on short-circuit calculations and a coordination study rather than generic pickup recommendations.

4. GE Multilin 350 Relay Architecture

A numerical protection relay combines measurement inputs, processing, protection functions, logic, outputs and communication.

4.1 Current Inputs

CTs provide scaled current signals to the relay.

The relay uses these signals for:

  • Phase current measurement
  • Residual current calculation, where configured
  • Overcurrent protection
  • Ground-fault protection
  • Other supported current-based functions

The engineer must verify the CT ratio and secondary rating before configuring the relay.

4.2 Voltage Inputs

Where the installed hardware includes voltage measurement inputs, the relay may use voltage signals for applicable measurement and protection functions.

The exact voltage-dependent features must be confirmed from the installed product documentation.

4.3 Protection Processor

The relay evaluates measured quantities and compares them with configured operating thresholds.

Examples include:

  • Current pickup
  • Time delay
  • Protection curve
  • Earth-fault pickup
  • Directional decision, where supported
  • Alarm and trip logic

4.4 Binary Inputs

Binary inputs can receive external signals such as:

  • Circuit-breaker open
  • Circuit-breaker closed
  • External trip
  • External blocking
  • Local/remote selection
  • Protection permissive

4.5 Binary Outputs

Binary outputs can be assigned to functions such as:

  • Breaker trip
  • Alarm
  • External indication
  • Control operation
  • Other application-specific signals

The number of available inputs and outputs and their electrical ratings depend on the relay hardware.

4.6 Event Recording and Monitoring

Event and measurement information can help engineers investigate abnormal conditions.

Depending on the installed configuration, the relay may provide records such as:

  • Protection operation events
  • Alarm events
  • Breaker status changes
  • Measured current values
  • Disturbance records
  • Communication status

5. CT Configuration and Current Scaling

Correct CT configuration is essential for dependable protection.

Consider an 11 kV feeder with a maximum operating current of 180 A.

Assume a CT ratio of:

[
300/1\ A
]

The secondary current at maximum load is:

[
I_s=\frac{180}{300}
]

[
I_s=0.6\ A
]

The relay should measure approximately 0.6 A at the secondary input under ideal conditions.

5.1 CT Selection Considerations

CT selection should consider:

  • Rated primary current
  • Secondary rating
  • Accuracy class
  • Burden
  • Short-time thermal withstand
  • Dynamic withstand
  • Maximum fault current
  • CT saturation performance
  • Secondary cable resistance

5.2 CT Polarity

CT polarity must be verified against the approved schematic.

Incorrect polarity can affect:

  • Residual current calculation
  • Directional protection
  • Power measurement
  • Other schemes using phase relationships

5.3 CT Saturation

During high fault current, the CT core may saturate and produce a distorted secondary waveform.

The engineer should assess CT performance using the actual fault level, CT characteristics, burden and system X/R ratio.

6. Earth-Fault Current Measurement

Earth-fault protection can use residual current derived from phase CTs or a dedicated earth-fault CT arrangement.

6.1 Residual Current

The residual current is:

[
I_{\text{res}}=I_A+I_B+I_C
]

Under balanced conditions:

[
I_{\text{res}}\approx0
]

An earth fault produces a residual component that can be detected by the protection system.

6.2 Core-Balance CT

A core-balance CT surrounds all three phase conductors.

Under normal balanced operation, the magnetic flux produced by the phase currents approximately cancels.

During an earth fault, the residual current produces a net flux and a corresponding secondary signal.

This arrangement can be useful for sensitive earth-fault detection, depending on the relay input design.

6.3 Neutral Earthing

Earth-fault current depends strongly on the network neutral-earthing arrangement.

Common arrangements include:

  • Solid earthing
  • Resistance earthing
  • Reactance earthing
  • Isolated neutral
  • Resonant earthing

The protection engineer must determine the minimum and maximum earth-fault currents before selecting pickup and timing settings.

7. Phase Overcurrent Protection – ANSI 50/51

Phase overcurrent protection is a fundamental feeder protection function.

7.1 Instantaneous Overcurrent – ANSI 50

ANSI 50 detects current exceeding a configured high-set threshold.

It is commonly used for high-current faults close to the feeder source.

The setting must consider:

  • Maximum load current
  • Downstream fault current
  • Motor starting
  • Transformer inrush
  • Minimum fault current
  • Coordination with other devices

7.2 Time Overcurrent – ANSI 51

ANSI 51 provides time-delayed overcurrent protection.

Depending on the relay implementation, characteristics may include definite-time and inverse-time curves.

7.3 IEC Standard Inverse Characteristic

A commonly used IEC standard inverse equation is:

[
t=TMS\times\frac{0.14}{(I/I_s)^{0.02}-1}
]

Where:

  • (t) = operating time
  • (TMS) = time multiplier setting
  • (I) = measured current
  • (I_s) = pickup current

Always verify the actual curve equations and selectable characteristics in the relay’s documentation.

8. Practical Overcurrent Example

Consider an illustrative 11 kV feeder.

ParameterValue
System voltage11 kV
Maximum load current180 A
CT ratio300/1 A
Assumed pickup220 A
Maximum fault current5,000 A

The secondary pickup is:

[
I_s=\frac{220}{300}
]

[
I_s=0.733\ A
]

At a primary fault current of 5,000 A:

[
I_{\text{fault,secondary}}=\frac{5000}{300}
]

[
I_{\text{fault,secondary}}=16.67\ A
]

These values are ideal calculations and do not account for CT saturation or measurement tolerances.

The assumed 220 A pickup is illustrative only. The final setting must be checked against maximum load, emergency loading, minimum fault current and coordination requirements.

9. Earth-Fault Protection – ANSI 50N/51N and 50G/51G

Earth-fault protection detects abnormal current associated with a phase-to-earth fault.

Typical causes include:

  • Cable insulation failure
  • Damaged switchgear insulation
  • Moisture ingress
  • Mechanical cable damage
  • Contamination
  • Equipment insulation deterioration

9.1 Earth-Fault Pickup

The pickup setting must be:

  • Higher than expected normal residual current
  • Sensitive enough for the minimum fault current
  • Coordinated with downstream protection
  • Compatible with CT accuracy and measurement limits

9.2 Earth-Fault Time Delay

The operating time should provide selectivity with downstream protective devices while meeting the required equipment protection limits.

9.3 Sensitive Earth-Fault Protection

Where low earth-fault currents are expected, a suitable dedicated CT and protection input may be required.

The engineer must verify the actual ground-current measurement arrangement supported by the 350.

10. Directional Overcurrent Protection – ANSI 67/67N

Directional overcurrent protection determines whether a fault is in the defined forward or reverse direction.

It is important in networks where fault current can flow in more than one direction.

Applications may include:

  • Ring distribution networks
  • Parallel feeders
  • Multiple-source systems
  • Networks with embedded generation

10.1 Directional Operating Principle

The relay evaluates the relationship between operating current and a polarizing reference.

The directional element supervises the overcurrent element.

10.2 Engineering Requirements

Directional protection requires careful attention to:

  • CT polarity
  • VT polarity
  • Phase sequence
  • Current phase assignment
  • Voltage reference
  • Direction definition
  • Characteristic angle
  • Minimum operating quantities

10.3 Important Model Consideration

Do not assume that every directional function or polarizing method is available in every GE Multilin 350 configuration.

Confirm the exact directional protection capability in the applicable technical manual before including it in the protection design.

11. Voltage and Frequency Protection

Some feeder applications require voltage and frequency supervision.

Potential functions include:

  • Undervoltage – ANSI 27
  • Overvoltage – ANSI 59
  • Underfrequency – ANSI 81U
  • Overfrequency – ANSI 81O

These functions can be useful in industrial networks, load-shedding schemes and distribution systems with embedded generation.

However, their availability depends on the relay’s installed voltage measurement hardware and firmware.

Do not include voltage or frequency protection in the final scheme without confirming the required input configuration and supported elements.

12. Protection Coordination

Protection coordination ensures that the device closest to the fault operates first.

For a radial network, downstream protection normally clears the fault before upstream protection.

A simplified coordination relationship is:

[
t_{\text{upstream}}\geq t_{\text{downstream}}+CTI
]

Where CTI is the required coordination time interval.

12.1 Coordination Study

A practical study should include:

  • Maximum and minimum fault levels
  • Transformer impedance
  • Cable impedance
  • Feeder loading
  • CT ratios
  • Relay curves
  • Circuit-breaker clearing time
  • Downstream fuses
  • Motor starting characteristics
  • Upstream protection

12.2 Time-Current Curves

The engineer should plot the curves of all relevant protective devices.

Check coordination at both minimum and maximum fault current.

12.3 Sensitivity and Selectivity

A relay must be sensitive enough to detect the minimum fault current while remaining stable during permissible loading and transient conditions.

The final setting should satisfy both protection sensitivity and selectivity requirements.

13. Circuit-Breaker Trip Logic

A feeder relay normally initiates a breaker trip through configured output logic.

A simplified trip expression could be:

[
TRIP=50\ OR\ 51\ OR\ 50N\ OR\ 51N
]

This is an illustrative expression, not a statement of the relay’s default logic.

The actual trip scheme may include:

  • Phase overcurrent
  • Earth fault
  • External trip
  • Directional protection
  • Lockout
  • Breaker failure initiation
  • Interlocking
  • External blocking

The complete logic must be checked against the approved protection schematic.

13.1 Trip Circuit Supervision

Where trip-circuit supervision is implemented in the relay or external circuit, it can help identify:

  • Open trip-coil circuit
  • Loss of DC supply
  • Wiring problems
  • Auxiliary contact problems

Verify the actual supervision arrangement and alarm implementation.

14. GE Multilin 350 Settings and Configuration Workflow

The engineering software and supported configuration procedures depend on the exact relay version.

A general process is outlined below.

Step 1 – Identify the Relay

Record:

  • Model
  • Order code
  • Serial number
  • Firmware version
  • Hardware options
  • Input and output configuration

Step 2 – Retrieve Existing Settings

Connect using a supported interface.

Retrieve the existing configuration where possible and save an original backup.

Step 3 – Configure CT Inputs

Enter the correct CT ratio and secondary rating.

Verify phase assignment and polarity.

Step 4 – Configure Earth-Fault Measurement

Confirm whether the scheme uses residual current or a dedicated ground CT.

Verify the correct input and measurement scaling.

Step 5 – Configure Protection Settings

Enter approved values for the supported protection elements.

These may include:

  • Phase overcurrent pickup
  • Instantaneous overcurrent
  • Time multiplier
  • Curve selection
  • Earth-fault pickup
  • Earth-fault time delay
  • Other supported protection functions

Step 6 – Configure Logic and Outputs

Assign protection operation signals to the required outputs.

Verify alarm, trip, external blocking and breaker status logic.

Step 7 – Configure Communication

Where communication is required, configure the supported protocol and communication parameters.

Check SCADA mapping and time synchronization.

Step 8 – Validate and Save

Compare the final configuration against the approved settings schedule and wiring diagrams.

Save the final configuration with a revision identifier.

15. Communication and SCADA Integration

Feeder protection relays can provide operational information to supervisory systems.

The actual communication protocols and services available in the GE Multilin 350 depend on its hardware and firmware.

Typical information exchanged with SCADA may include:

  • Phase current measurements
  • Earth-fault measurements
  • Breaker status
  • Protection operation
  • Alarm indications
  • Device health
  • Control status

15.1 Communication Engineering

Verify:

  • Physical interface
  • Communication protocol
  • Addressing
  • Baud rate or network settings
  • Point mapping
  • Scaling
  • Time synchronization
  • Communication-loss alarm

15.2 IEC 61850 Considerations

Do not assume IEC 61850 MMS or GOOSE is available on every GE Multilin 350 version.

Where IEC 61850 is required, confirm support for the exact model and firmware before specifying the relay.

If the installed version does not support the required IEC 61850 services, an alternative communication architecture may be necessary.

16. Testing and Commissioning

Commissioning should verify the complete protection chain from measurement inputs to physical breaker operation.

16.1 Initial Inspection

Check:

  • Correct relay model
  • Auxiliary supply
  • CT wiring
  • VT wiring, where applicable
  • Binary input wiring
  • Binary output wiring
  • Communication connections
  • Earthing
  • Approved settings

16.2 Current Measurement Test

Inject balanced three-phase current.

Verify:

  • Phase A current
  • Phase B current
  • Phase C current
  • Current scaling
  • Phase sequence
  • Residual current

16.3 Overcurrent Testing

Test ANSI 50 and 51 elements.

Verify:

  • Pickup current
  • Operating time
  • Curve characteristic
  • Reset behaviour
  • Trip logic
  • Event indication

16.4 Earth-Fault Testing

Inject the required residual or dedicated ground current.

Verify:

  • Pickup
  • Operating time
  • Reset
  • Alarm output
  • Trip output

16.5 Directional Testing

Where directional protection is supported and configured, test both forward and reverse conditions.

Use controlled current and voltage phase relationships to verify the operating decision.

16.6 Binary Input and Output Testing

Test all configured binary inputs and outputs.

Verify each signal against the approved drawings and logic matrix.

16.7 Circuit-Breaker Trip Test

Verify:

  1. Protection element operation.
  2. Relay trip logic.
  3. Output contact operation.
  4. Trip circuit continuity.
  5. Trip coil operation.
  6. Breaker opening.
  7. Auxiliary contact feedback.
  8. Alarm and event recording.

16.8 Communication Test

Where communication is implemented, verify:

  • Device connectivity
  • Measurements
  • Status points
  • Alarms
  • Events
  • Remote control, where approved
  • Communication-loss indication
  • Time synchronization

All tests must be performed under approved isolation and safety procedures.

17. Common GE Multilin 350 Troubleshooting Problems

ProblemPossible causeRecommended check
Incorrect current readingCT ratio or wiring errorVerify ratio and phase assignment
Unexpected phase overcurrent tripIncorrect pickup or curveReview settings and coordination
Earth-fault operationResidual current or CT wiring issueCheck CT polarity and earthing
Incorrect directional decisionCT/VT polarity or phase referenceVerify measurement references
Relay does not trip breakerOutput logic or trip circuit faultTrace the complete trip path
Breaker status incorrectAuxiliary contact wiringCheck 52a/52b signals
SCADA values incorrectScaling or point mappingVerify communication configuration
Communication failurePhysical or protocol issueCheck interface and settings
Repeated alarmsIncorrect logic or external signalReview event records and input states

Avoid changing protection settings before identifying the actual cause of the problem.

18. Practical Commissioning Checklist

Hardware and wiring

  • Relay model and order code verified
  • Firmware version recorded
  • Auxiliary supply checked
  • CT ratios verified
  • CT polarity verified
  • VT configuration checked, where applicable
  • Binary inputs tested
  • Binary outputs tested

Protection

  • Phase overcurrent pickup tested
  • Phase overcurrent timing tested
  • Earth-fault pickup tested
  • Earth-fault timing tested
  • Directional elements tested, where supported
  • Voltage and frequency elements tested, where supported
  • Trip logic verified

Control and communication

  • Breaker trip circuit tested
  • Breaker status verified
  • Alarm outputs checked
  • SCADA measurements checked
  • Communication-loss alarm checked
  • Time synchronization checked

Documentation

  • Original settings backed up
  • Final settings saved
  • Test report completed
  • Drawings updated
  • Commissioning approval recorded

19. GE Multilin 350 Compared with Other GE Multilin Feeder Relays

RelayGeneral application
GE Multilin 350Feeder protection
GE Multilin 850Feeder protection platform with broader application capabilities
GE Multilin F650Feeder protection and bay control applications
GE Multilin UR familyApplication-specific protection platforms

The selection process should consider the required functions, hardware, communication, I/O capacity and project specifications.

The exact technical comparison should be made using the applicable product documentation and order codes.

20. Training on GE Multilin Feeder Protection by Elec-Engg

Understanding feeder protection requires practical knowledge of fault calculations, CT and VT circuits, protection settings, time-current coordination and secondary injection testing.

Elec-Engg provides practical technical training by Dr Saeed Roostaee (Electrical Engineering) for protection, commissioning, operation, maintenance and substation automation engineers.

Relevant training subjects include:

  • GE Multilin 350 feeder protection
  • GE Multilin 850 feeder protection
  • GE Multilin F650 protection and control
  • ANSI 50/51 overcurrent protection
  • Earth-fault protection
  • Directional overcurrent protection
  • CT and VT configuration
  • Protection coordination
  • Trip circuit engineering
  • EnerVista configuration
  • Relay testing and commissioning
  • SCADA communication
  • Practical troubleshooting

Training delivery options include:

  • Pre-recorded video courses
  • Structured self-paced training
  • Live online training
  • Face-to-face technical training
  • Customized in-house training for companies and utilities

The focus is on practical engineering applications, helping engineers understand how feeder protection systems are configured, tested and maintained in real installations.

Explore the training resources:

Elec-Engg website: https://elec-engg.com/

Contact and training enquiries: https://elec-engg.com/contact/

21. Conclusion

The GE Multilin 350 is a numerical feeder protection relay used to protect distribution and industrial feeder circuits.

Correct application requires accurate CT configuration, suitable phase overcurrent and earth-fault settings, proper coordination and dependable breaker trip logic.

Directional, voltage and frequency functions should only be included after confirming their availability in the exact installed configuration.

Commissioning must verify measurement accuracy, protection pickup and timing, binary inputs and outputs, trip circuit operation and communication.

A well-engineered feeder protection system helps minimize the impact of electrical faults, improve selectivity and maintain reliable operation of the distribution network.

22. Frequently Asked Questions

1. What is the GE Multilin 350 used for?

The GE Multilin 350 is a numerical feeder protection relay used in distribution and industrial power systems.

2. What is ANSI 50 protection?

ANSI 50 is instantaneous overcurrent protection. It operates when the measured current exceeds a configured high-set threshold.

3. What is ANSI 51 protection?

ANSI 51 is time overcurrent protection. It operates when current exceeds a pickup threshold for a defined period.

4. What is the difference between earth-fault and phase overcurrent protection?

Phase overcurrent protection detects excessive phase current, while earth-fault protection detects current associated with a phase-to-earth fault.

5. Does the GE Multilin 350 support directional protection?

Directional capability depends on the exact relay configuration and firmware. Verify the supported functions in the applicable manufacturer documentation.

6. Can the GE Multilin 350 communicate with SCADA?

Communication capability depends on the installed hardware and supported protocols. Confirm the exact interfaces and protocols before system integration.

7. Does the GE Multilin 350 support IEC 61850?

IEC 61850 support should not be assumed for every 350 version. Verify the exact product documentation and firmware capabilities.

8. How is the GE Multilin 350 tested?

Testing normally includes CT measurement checks, protection pickup and timing tests, earth-fault tests, binary I/O verification, trip circuit testing and communication checks where applicable.

9. What should be checked before changing relay settings?

Check the protection study, load current, fault levels, CT ratios, wiring, existing settings, event records and coordination requirements.

10. Where can engineers receive GE Multilin feeder protection training?

Elec-Engg provides practical technical training by Dr Saeed Roostaee (Electrical Engineering). Visit https://elec-engg.com/ or contact https://elec-engg.com/contact/.


Practical GE Multilin 350 guide covering feeder protection, ANSI 50/51, earth fault, directional protection, CT configuration, settings and commissioning.

GE Multilin 350, GE 350 Relay, Feeder Protection Relay, GE Feeder Protection, ANSI 50, ANSI 51, Overcurrent Protection, Earth Fault Protection, ANSI 50N, ANSI 51N, Directional Overcurrent, ANSI 67, CT Configuration, VT Configuration, Protection Coordination, EnerVista, Relay Settings, Secondary Injection Testing, Relay Commissioning, Power System Protection

Leave a Comment

Your email address will not be published. Required fields are marked *

Scroll to Top