VAMP Protection Relay Product Portfolio

Table Of Contents
  1. 1. Introduction
  2. 2. Understanding the VAMP Product Portfolio
  3. 3. VAMP 50 Series — Feeder and Motor Protection
  4. 4. VAMP 200 Series — Protection and Control Managers
  5. 5. VAMP 300 Series — Application-Oriented Protection Managers
  6. 6. VAMP 57 — Intelligent Protection for Power Systems
  7. 7. VAMP Arc Protection Product Family
  8. 8. VAMP Measurement and Monitoring Units
  9. 9. VAMP Accessories and Supporting Components
  10. 10. VAMP Software and Engineering Tools
  11. 11. VAMP Product Family Comparison
  12. 12. How to Select a VAMP Relay for a Project
  13. 13. Common Mistakes When Identifying VAMP Relay Families
  14. 14. Conclusion

VAMP Protection Relay Product Portfolio and Relay Families

1. Introduction

Selecting the correct protection relay is one of the most important tasks in protection and control engineering. A protection relay must be capable of detecting the electrical faults relevant to the protected equipment, operating according to the protection philosophy, interfacing with the circuit breaker and control system, and providing the required monitoring and communication capabilities.

VAMP is a well-known name in the field of numerical protection relays and arc-fault protection systems. VAMP devices have been applied in industrial power systems, medium-voltage distribution networks, substations, power plants, motor installations, transformer feeders, and other electrical infrastructure.

However, the VAMP portfolio is not a single relay with identical capabilities. Different product families and models have been developed for different applications, hardware arrangements, protection requirements, and generations of technology.

For an engineer working with VAMP relays, understanding the product portfolio is important for:

  • Selecting the correct relay for a new project
  • Identifying installed relays in existing substations
  • Understanding model-specific protection functions
  • Finding the correct technical manual
  • Selecting compatible engineering software
  • Checking hardware and communication options
  • Planning relay testing and commissioning
  • Evaluating retrofit and replacement projects

This article provides a structured overview of VAMP protection relay families, their applications, the differences between application-specific relays and multifunction relays, and the engineering factors that must be considered when selecting a suitable VAMP device.

2. Understanding the VAMP Product Portfolio

The VAMP product portfolio includes several generations of numerical protection relays, multifunction protection devices, specialized protection equipment, arc-protection systems, measurement units, and supporting engineering tools.

The main product families engineers should recognize include:

VAMP 50 Series

Protection for LV and MV feeders and motors. A legacy family, now discontinued and replaced by the Easergy P3 range for designated models.

VAMP 200 Series

Multifunction protection and control managers for feeders, motors, capacitor banks and other power system applications.

VAMP 300 Series

Application-oriented protection and control managers for feeder, motor, generator and transformer applications.

VAMP 57

Intelligent protection for low- and medium-voltage power systems.

VAMP Arc Protection

Specialized arc-fault detection and protection equipment for electrical switchgear.

VAMP Arc Accessories

Sensors, accessories and components associated with arc-protection installations.

Schneider Electric’s official portfolio pages identify the VAMP 50, VAMP 200, VAMP 300, VAMP 57 and VAMP arc-protection families. The VAMP 50 series is marked as discontinued and replaced by the Easergy P3 range for specified models. Schneider Electric India+3

3. VAMP 50 Series — Feeder and Motor Protection

The VAMP 50 series was designed to provide protection solutions for low- and medium-voltage power systems.

Schneider Electric lists the following models in the family:

  • VAMP 50
  • VAMP 52
  • VAMP 55
  • VAMP 59

The product family offered modular protection functions covering overcurrent, earth fault, voltage, frequency, and line differential protection across its range. The actual functionality varies by model. Schneider Electric Nigeria+1

3.1 VAMP 50

The VAMP 50 is part of the feeder and motor protection relay family.

Its application and configuration should be assessed using the model-specific documentation, particularly when determining the available current-based protection functions, measurement capabilities, and inputs/outputs.

3.2 VAMP 52

The VAMP 52 is another relay in the 50 series.

Engineers should identify the supported protection functions and electrical measurement options before using it in feeder or motor protection schemes.

3.3 VAMP 55

The VAMP 55 is associated with voltage-related protection and power-system monitoring capabilities in the VAMP 50 family.

When applying voltage and frequency-based protection, engineers must verify the available voltage inputs, wiring arrangement, measurement configuration, and supported protection functions.

3.4 VAMP 59

The VAMP 59 belongs to the VAMP 50 family and has application-specific capabilities that must be checked against its technical documentation.

For this model, engineers should pay particular attention to supported protection schemes, communication features, hardware options, and engineering requirements before using it in a new project.

3.5 Lifecycle Status of VAMP 50

The VAMP 50 series is no longer commercialized by Schneider Electric. The official product information identifies the Easergy P3 range as its replacement and provides model-specific replacement guidance.

Examples of listed substitutions include:

Legacy relayListed replacement
VAMP 50Easergy P3U10 / P3U20
VAMP 52Easergy P3U10 / P3U20
VAMP 55Easergy P3U30
VAMP 59Easergy P3L30

These are manufacturer’s listed replacement recommendations, not guaranteed plug-and-play substitutions. The protection design and application must be reviewed before replacement. Schneider Electric

4. VAMP 200 Series — Protection and Control Managers

The VAMP 200 series is a major family of multifunction protection and control devices for medium-voltage power systems.

Schneider Electric describes the family as protection and control managers with measurement capabilities for feeders, motors, and capacitor banks. Listed models include VAMP 210, 230, 255, 257, 259, 265 and 265M. Some regional product listings include additional models such as VAMP 245, so the exact catalogue availability should be checked by region and product documentation. Schneider Electric India+1

4.1 Main Applications

VAMP 200-series relays can be applied to:

  • MV feeder protection
  • Motor protection
  • Capacitor bank protection
  • Distribution system protection
  • Electrical monitoring
  • Breaker control
  • Protection logic
  • SCADA integration

4.2 Fixed I/O and Flexible I/O

One of the important engineering considerations when comparing VAMP 200-series models is their hardware input/output arrangement.

Depending on the model, the relay may have fixed I/O configurations or expanded/flexible I/O capabilities.

This directly affects the design of:

  • Circuit breaker trip and close circuits
  • Alarm circuits
  • External protection inputs
  • Interlocking
  • Disconnector and earthing switch status
  • Control logic
  • SCADA signal mapping

Engineers should prepare a complete I/O list before selecting the relay.

4.3 VAMP 210

The VAMP 210 is listed within the VAMP 200 family. Product-family material associates it with applications such as generator, transformer, motor and differential protection, depending on the specific available functions.

It should not be assumed to be identical to feeder manager models. Its intended application, current and voltage inputs, and supported functions must be checked in the technical documentation.

4.4 VAMP 230

The VAMP 230 is a multifunction feeder and motor manager used in protection and control applications.

Depending on the configuration and supported functions, feeder applications may involve:

  • Phase overcurrent protection
  • Earth-fault protection
  • Directional protection
  • Thermal protection
  • Voltage protection
  • Frequency protection
  • Breaker control
  • Monitoring

The VAMP 230 is a model worth studying for practical feeder protection and coordination.

4.5 VAMP 255

The VAMP 255 is another feeder and motor manager in the VAMP 200 family.

Engineering studies should focus on the protection functions, measurements, logic, communication, and hardware capabilities actually supported by the model.

4.6 VAMP 257

The VAMP 257 is particularly relevant for applications requiring an extended number of binary inputs and outputs, including complex control and switchgear arrangements.

Manufacturer documentation describes applications involving double-busbar systems and configurations requiring more extensive I/O for primary equipment status and control.

Potential engineering subjects include:

  • Feeder protection
  • Busbar arrangement status
  • Breaker control
  • Disconnector status
  • Earthing switch status
  • Interlocking
  • Trip and close commands
  • Alarm processing
  • SCADA signal acquisition

The VAMP 257 feeder-manager documentation includes application examples for feeder, motor, capacitor-bank and switchgear control arrangements. acdc-bg.com

4.7 VAMP 259

The VAMP 259 is included in the VAMP 200-series product family.

Its selection should be based on the intended protection application, supported functions, hardware configuration, measurement requirements, communication interfaces and available documentation.

4.8 VAMP 265 and VAMP 265M

VAMP 265 and VAMP 265M are listed members of the VAMP 200 family.

These devices should be evaluated according to their model-specific protection and measurement functions, application requirements, I/O, and engineering capabilities.

Because model names can be similar while hardware and function availability differ, engineers should not transfer settings or assumptions from one model to another without verification.

5. VAMP 300 Series — Application-Oriented Protection Managers

Vamp 300 Series Efficient protection and control managers for power systems

The VAMP 300 series is another important family of numerical protection and control devices.

According to Schneider Electric, the VAMP 300 family provides protection and control managers with measurement capabilities for feeders, motors, generators, and transformers.

The product family includes:

  • VAMP 300F
  • VAMP 300M
  • VAMP 300G
  • VAMP 300T

These model names identify members of the family, but the protection functions, configuration requirements, and hardware options must be confirmed against each model’s technical documentation. Schneider Electric India+1

5.1 VAMP 300F

The VAMP 300F belongs to the VAMP 300 family and is associated with feeder-oriented protection applications.

Feeder protection engineering may require evaluation of:

  • Phase overcurrent protection
  • Earth-fault protection
  • Directional overcurrent
  • Directional earth fault
  • Voltage protection
  • Frequency protection
  • Automatic reclosing, if supported
  • Breaker control
  • Monitoring
  • Communication

The correct function availability and settings should be confirmed from the relay manual.

5.2 VAMP 300M

The VAMP 300M is the motor-oriented member of the VAMP 300 family.

Motor protection engineering requires consideration of the motor’s thermal characteristics, starting method, load, operating duty, fault levels, and system grounding.

Relevant protection topics include:

  • Thermal overload
  • Phase overcurrent
  • Short circuit
  • Earth fault
  • Negative sequence
  • Locked rotor
  • Excessive starting time
  • Starts-per-hour limitation
  • Undervoltage
  • Motor temperature monitoring, where supported

The motor relay must be selected according to the motor application and protection requirements.

5.3 VAMP 300G

The VAMP 300G belongs to the VAMP 300 family and is intended for generator protection applications.

Generator protection may require functions such as:

  • Overcurrent
  • Earth fault
  • Voltage protection
  • Frequency protection
  • Reverse power
  • Negative sequence
  • Thermal protection
  • Generator monitoring

The actual generator protection scheme depends on the machine size, grounding method, operating mode, connection to the power system, and protection philosophy.

5.4 VAMP 300T

The VAMP 300T is the transformer-oriented member of the VAMP 300 family.

Transformer protection engineering involves several important considerations:

  • Transformer rated power
  • Primary and secondary voltage
  • CT ratio and connection
  • Transformer vector group
  • Grounding method
  • Inrush current
  • Overload capability
  • Fault current
  • Backup protection
  • Protection coordination

Engineers should determine which transformer protection functions the VAMP 300T supports and whether additional dedicated protection devices are required.

5.5 Why Application-Oriented Relays Are Important

Application-oriented relays can provide protection features and configurations suited to a particular type of equipment.

This helps engineers avoid unnecessary configuration and supports more focused protection design.

However, application-oriented naming does not mean that a relay can automatically provide a complete protection scheme for every feeder, motor, generator, or transformer.

The protection engineer must still perform a protection study, verify function availability, calculate settings, design logic, and commission the complete system.

6. VAMP 57 — Intelligent Protection for Power Systems

VAMP 57 is listed by Schneider Electric within the VAMP protection portfolio as an intelligent protection device for low- and medium-voltage power systems. Schneider Electric India+1

When engineers encounter the VAMP 57, the relay should be studied as a separate product rather than assumed to be a direct extension of the VAMP 50, 200, or 300 series.

Engineering information to investigate

When preparing a VAMP 57 application, review:

  1. Product application and supported protection functions
  2. Nominal current and voltage input specifications
  3. CT and VT connection requirements
  4. Auxiliary power supply
  5. Binary input configuration
  6. Binary output configuration
  7. Measurement and monitoring
  8. Protection setting ranges
  9. Logic and control functions
  10. Communication protocols
  11. Configuration software compatibility
  12. Event and disturbance recording
  13. Testing and commissioning procedures

The exact features and engineering limitations must be established using the correct technical manual for the device.

7. VAMP Arc Protection Product Family

VAMP arc protection is a specialized product category within the VAMP portfolio.

Schneider Electric identifies the arc-protection relay system as a flexible solution for arc-flash detection and protection, with models including VAMP 120, VAMP 121, VAMP 221, and VAMP 321. Schneider Electric USA

Arc protection differs from conventional feeder, motor, and transformer protection because its primary objective is rapid detection of an internal arc event within protected switchgear zones.

7.1 VAMP 120

The VAMP 120 is a member of the VAMP arc-protection product family.

When evaluating the VAMP 120, engineers should review the device’s sensor compatibility, detection logic, trip outputs, installation requirements, and application limitations.

7.2 VAMP 121

The VAMP 121 is another device within the VAMP arc-protection portfolio.

Its use should be based on the manufacturer’s application and hardware documentation, including its supported sensor arrangements and protection architecture.

7.3 VAMP 221

The VAMP 221 belongs to the VAMP arc-protection family.

The engineering study should consider the switchgear configuration, arc zones, sensor coverage, trip logic, circuit breaker assignment, and integration with the existing protection system.

7.4 VAMP 321

The VAMP 321 is also listed within the VAMP arc-protection portfolio.

When selecting an arc-protection unit, the engineer must confirm that the device is suitable for the required switchgear architecture and that its sensors, outputs, and operating logic meet the protection design requirements.

7.5 Arc Protection System Components

A complete arc-protection installation may include:

  • Arc protection relay or central unit
  • Optical arc sensors
  • Fiber-optic sensor circuits
  • Current supervision inputs, where required
  • Trip outputs
  • Circuit breaker interfaces
  • DC auxiliary supply
  • Zone configuration
  • Sensor wiring
  • Alarm outputs
  • Communication interfaces, if available

The arc-protection system must be designed so that detection coverage and tripping actions are appropriate for the switchgear compartments and protection zones.

8. VAMP Measurement and Monitoring Units

The VAMP product portfolio also includes measurement and monitoring equipment.

Measurement devices and protection relays serve related but different purposes.

A protection relay is designed to detect abnormal electrical conditions and initiate a protective action according to the protection design.

A measurement and monitoring device may primarily provide electrical data, monitoring, alarms, communication, and operational information.

8.1 Typical Monitoring Requirements

Depending on the device, electrical monitoring may involve:

  • Phase current
  • Phase voltage
  • Frequency
  • Active power
  • Reactive power
  • Apparent power
  • Power factor
  • Energy
  • Voltage unbalance
  • Current unbalance
  • Demand
  • Electrical system status

8.2 Why Monitoring Is Important

Electrical measurements help engineers:

  • Assess system loading
  • Identify unbalanced conditions
  • Monitor power quality indicators
  • Investigate abnormal operating conditions
  • Analyze operational trends
  • Verify equipment performance
  • Support maintenance decisions
  • Integrate electrical data into SCADA and energy-management systems

Monitoring capability should not be confused with protection capability. A device that measures a quantity does not necessarily have the required protection function or trip output for that quantity.

9. VAMP Accessories and Supporting Components

A protection relay installation may require accessories or additional components to complete the protection and control scheme.

Depending on the relay family, the system may require:

  • Expansion I/O modules
  • Binary input modules
  • Binary output modules
  • Temperature measurement modules
  • Communication accessories
  • Optical arc sensors
  • Sensor cables
  • Mounting accessories
  • Connector kits
  • Programming or communication cables

9.1 Engineering Considerations

Before selecting accessories, engineers should verify:

  • Compatibility with the relay model
  • Hardware revision
  • Firmware requirements
  • Input voltage ratings
  • Output contact ratings
  • Wiring requirements
  • Communication compatibility
  • Installation limitations
  • Availability and lifecycle status

Incorrect accessory selection can result in configuration problems, unsupported functions, wiring incompatibility, or failure to achieve the intended protection scheme.

10. VAMP Software and Engineering Tools

Software is an essential part of numerical relay engineering.

Engineers may use dedicated configuration tools to connect to relays, read settings, modify parameters, configure protection functions, review logic, retrieve event records, and perform maintenance.

Software compatibility depends on the relay family, device model, firmware version, and supported communication interfaces.

10.1 Typical Engineering Software Tasks

  • Establish communication with the relay
  • Read the relay configuration
  • Retrieve protection settings
  • Configure protection functions
  • Adjust pickup values and time settings
  • Configure logic
  • Assign binary inputs
  • Assign binary outputs
  • Configure alarms
  • Review measurements
  • Retrieve event logs
  • Retrieve disturbance records
  • Save configuration backups
  • Restore approved configurations

10.2 Software Selection

A common mistake is assuming that a single VAMP engineering tool supports every VAMP product generation.

Before installing or using software, engineers should identify:

  • Exact relay model
  • Product generation
  • Firmware version
  • Supported configuration tool
  • Required communication cable or interface
  • Communication settings
  • PC operating system compatibility
  • Available software version

Legacy relays may require older software or operating environments. Software availability and support should be confirmed before planning a commissioning or maintenance task.

We will cover the VAMP configuration software and engineering workflow in a separate article series, with model-specific instructions wherever documentation is available.

11. VAMP Product Family Comparison

The following table is a high-level portfolio comparison. It is intended to help engineers identify which family to investigate, not to replace the technical specification or protection function list.

Product familyGeneral applicationEngineering focus
VAMP 50LV/MV feeders and motorsProtection functions, lifecycle and replacement
VAMP 200Feeder, motor, capacitor bank and other MV protectionMultifunction protection and control
VAMP 300Feeder, motor, generator and transformer applicationsApplication-oriented protection managers
VAMP 57LV/MV power system protectionModel-specific protection and engineering
VAMP ArcSwitchgear arc-fault protectionSensors, zones and trip logic
VAMP measurement/monitoringElectrical measurement and monitoringElectrical quantities, data and integration
VAMP accessoriesSupporting relay and protection system hardwareI/O, sensors, compatibility and installation

The product families and descriptions above are based on Schneider Electric’s published VAMP product portfolio. Schneider Electric India+3

12. How to Select a VAMP Relay for a Project

Relay selection must begin with the electrical application and protection requirements, not simply with the relay name or available product.

Step 1 — Identify the protected equipment

Determine whether the relay is required for:

  • Feeder
  • Motor
  • Transformer
  • Generator
  • Capacitor bank
  • Switchgear arc protection
  • General distribution protection

Step 2 — Define the required protection functions

Prepare a protection function list.

For example, an MV feeder may require:

  • Phase overcurrent
  • Earth fault
  • Directional overcurrent
  • Directional earth fault
  • Voltage protection
  • Frequency protection
  • Breaker failure
  • Automatic reclosing
  • Thermal protection

Not every application requires all functions.

Step 3 — Calculate the fault levels

Determine the maximum and minimum fault currents, load currents, grounding conditions, and other relevant system parameters.

These calculations are necessary to evaluate CT selection, relay pickup settings, sensitivity, selectivity, and coordination.

Step 4 — Verify CT and VT requirements

Confirm:

  • CT ratio
  • CT class
  • CT burden
  • CT core arrangement
  • VT ratio
  • VT connection
  • Input requirements of the relay
  • Required measurement accuracy

Step 5 — Check I/O requirements

Count the required binary inputs and outputs.

Include signals for:

  • Circuit breaker status
  • Trip circuit supervision
  • Local/remote status
  • External protection trips
  • Disconnector positions
  • Earthing switch positions
  • Alarms
  • Trip commands
  • Close commands
  • Interlocking
  • SCADA

Step 6 — Review communication requirements

Identify the required protocol and communication architecture.

Possible requirements may include Modbus, IEC 60870, IEC 61850, serial communication, Ethernet, or integration with a gateway.

The supported protocols must be verified for the specific relay.

Step 7 — Check software and lifecycle

Confirm that the device is available, supported, and suitable for the project lifecycle.

For legacy equipment, consider spare parts, configuration software, firmware, documentation, and replacement strategy.

Step 8 — Perform final technical evaluation

Compare the selected relay against the project specification and confirm that all protection, measurement, control, communication, installation, and testing requirements are satisfied.

13. Common Mistakes When Identifying VAMP Relay Families

Protection engineers and technicians sometimes make mistakes when identifying VAMP relays or selecting equipment for replacement projects.

Mistake 1 — Assuming all VAMP relays have the same functions

Different models have different protection functions, hardware arrangements, and measurement capabilities.

Correct practice: Always use the exact model’s function list and technical manual.

Mistake 2 — Selecting a relay based only on the name

The model name may indicate an application category, but it does not guarantee that every protection function required by the project is available.

Correct practice: Verify the protection functions, setting ranges, I/O and communication options.

Mistake 3 — Confusing VAMP 50, 200 and 300 series

These families belong to different product generations and application categories.

Correct practice: Identify the family and hardware revision before configuration, testing, or replacement.

Mistake 4 — Assuming a replacement relay is plug-and-play

A newer relay may have different terminal assignments, hardware, logic, communication, and protection characteristics.

Correct practice: Perform a complete retrofit engineering review and commissioning test.

Mistake 5 — Ignoring lifecycle status

Some VAMP product families are discontinued.

Correct practice: Check the manufacturer’s lifecycle status, replacement recommendations, software availability, and support options.

Mistake 6 — Confusing arc protection with conventional overcurrent protection

Arc detection and conventional overcurrent protection perform different functions and may have different operating criteria.

Correct practice: Design arc-protection coverage, detection logic, zones, and trip circuits according to the switchgear risk assessment and manufacturer’s instructions.

14. Conclusion

The VAMP protection relay portfolio includes different generations and categories of protection equipment designed for electrical distribution, industrial power systems, motor protection, feeder protection, transformer protection, generator protection, and arc-fault protection.

Understanding the product families is the first step toward successful VAMP relay engineering.

Engineers should be able to recognize the differences between the VAMP 50, VAMP 200, VAMP 300, VAMP 57, and VAMP arc-protection families and understand the intended application of each product.

The correct relay selection process involves much more than identifying the model. It requires a complete review of protection functions, fault levels, instrument transformer requirements, hardware I/O, logic, communication, software compatibility, lifecycle status, and commissioning requirements.

In the next articles of this series, we will move from product identification toward the internal architecture and hardware of VAMP numerical protection relays, examining the components that receive measurements, process signals, execute protection algorithms, and initiate protection and control actions.