Directional Overcurrent Protection (67/67N)

Directional overcurrent protection is an essential protection function in power systems where fault current can flow in more than one direction. While conventional overcurrent protection (50/51) detects excessive current, directional overcurrent protection (67/67N) additionally determines the direction of the fault, allowing the protection system to isolate only the faulted section with better selectivity.

This article explains the principles, applications, polarizing quantities, relay operation, directional characteristics, setting considerations, testing, and practical engineering applications of directional overcurrent protection.

1. Introduction

In simple radial distribution systems supplied from a single source, overcurrent protection can often be coordinated using current magnitude and time delay alone.

However, in more complex power systems, fault current may flow in different directions due to:

  • Multiple incoming sources
  • Parallel transformers
  • Ring networks
  • Distributed generation
  • Grid-connected renewable energy
  • Interconnected substations
  • Parallel feeders
  • Motor contribution to faults

In these situations, an overcurrent relay cannot always determine whether the fault is located in its forward or reverse direction based on current magnitude alone.

Directional overcurrent protection solves this problem by combining current measurement with a reference voltage or polarizing quantity to determine fault direction.

2. What Is Directional Overcurrent Protection?

Directional overcurrent protection is a protection function that operates when:

  1. The measured current exceeds a defined pickup value.
  2. The fault current is flowing in the permitted direction.
  3. Any required timing or operating conditions are satisfied.

The relay evaluates the relationship between current and voltage phasors to determine whether the fault is in the forward or reverse direction.

Negative Sequence Component for directional Overcurrent Protection

ANSI protection function numbers

ANSI codeFunction
50Instantaneous overcurrent
51Time overcurrent
67Directional overcurrent
67NDirectional earth/ground overcurrent
67GDirectional ground overcurrent (designation varies by relay/vendor)
directionalDirectional supervision of overcurrent elements

The exact naming of earth-fault directional elements may differ among manufacturers. Always verify the function designation in the relay manual.

3. Difference Between 50/51 and 67 Protection

The key difference is the direction decision.

Feature50/5167
Current measurementYesYes
Pickup thresholdYesYes
Time delayOptional or applicableOptional or applicable
Direction determinationNoYes
Voltage referenceGenerally not requiredUsually required for directional decision
Forward/reverse discriminationNoYes
Typical applicationRadial systemsRing and multi-source systems

Conventional overcurrent protection

A conventional relay operates based on the current magnitude and its time-current characteristic.

Directional overcurrent protection

A directional relay adds directional supervision. Even if the current exceeds the pickup value, the relay may restrain operation if the measured direction is reverse.

4. Why Directional Protection Is Required

Using IEC 61850 GOOSE Service for Adaptive ANSI 67/67N Protection in Ring Main Systems with Distributed Energy Resources
Electrical engineering Community - Newsletter 103

Consider a system with two sources supplying a network from different directions.

If a fault occurs between two substations, fault current may flow from both sources toward the fault.

A non-directional relay may see high current from either direction and trip unnecessarily, potentially disconnecting healthy sections.

Directional protection helps identify:

  • Faults in front of the relay
  • Faults behind the relay
  • Faults on adjacent feeders
  • Reverse fault current due to another source

Main objectives

  • Selective fault isolation
  • Improved protection coordination
  • Reduced unnecessary tripping
  • Reliable protection of interconnected systems
  • Better protection of parallel feeders

5. Basic Operating Principle

A directional overcurrent relay uses two major electrical quantities:

  • Operating quantity: current
  • Polarizing quantity: voltage or another reference quantity

The relay compares their phase relationship.

Electrical Friend: Directional Over Current Relay - Maximum Torque Angle

A simplified directional decision can be represented as:

Directional Decision=f(I,V,θ)Directional Decision=f(I,V,θ)

Where:

  • II = measured current
  • VV = polarizing voltage
  • θθ = phase angle between relevant quantities
  • ff = relay directional characteristic

If the directional decision indicates forward and the current element is picked up, the relay can proceed toward operation.

Simplified logic

Current exceeds pickup ──────┐ ├── AND ──> Trip decision Forward direction detected ─┘ │ Time delay / curve │ Circuit breaker

The actual relay logic can be more complex, including blocking signals, breaker status, multiple directional stages, and programmable logic.

6. Forward and Reverse Direction

Directional protection defines a reference direction based on the CT and VT polarity, relay wiring, and relay configuration.

Negative Sequence Component for directional Overcurrent Protection
Directional Elements In Power System Protection

Forward direction

The forward direction is the direction selected by the protection engineer as the protected direction of the circuit.

For example, a feeder relay may be configured to look from the busbar toward the feeder.

Reverse direction

Reverse direction is the opposite of the selected forward direction, generally looking from the feeder toward the busbar or source side.

Fault locationDirection seen by relayTypical response
On protected feederForwardOperate if pickup and timing conditions are met
Behind the relay toward bus/sourceReverseRestrain forward element
Outside protected forward zoneDepends on system configurationMay restrain or operate another element

Direction definitions are not universal physical labels. They depend on the relay’s configured reference direction.

7. Directional Measurement: Voltage and Current

Directional elements use current and voltage phasors to establish the direction of power or fault current.

The relay typically measures:

  • Phase currents IA,IB,ICIA​,IB​,IC​
  • Phase voltages VA,VB,VCVA​,VB​,VC​
  • Residual current 3I03I0​, where applicable
  • Residual or neutral voltage 3V03V0​, where applicable

The directional element calculates the relationship between the measured operating current and the polarizing voltage.

A simplified directional torque expression may be represented as:

T∝∣V∣∣I∣cos⁡(θ−τ)T∝∣V∣∣I∣cos(θ−τ)

Where:

  • TT = directional operating quantity (simplified torque analogy)
  • VV = polarizing voltage
  • II = operating current
  • θθ = phase relationship
  • ττ = characteristic angle or maximum torque angle

This is a conceptual representation. Numerical relays implement their directional algorithms using manufacturer-specific measurement and decision logic.

8. Directional Characteristic Angle (DCA / RCA)

The directional element has a characteristic angle that determines the phase relationship at which the relay has maximum directional sensitivity.

Different relay manufacturers may use different terms:

  • RCA – Relay Characteristic Angle
  • MTA – Maximum Torque Angle
  • DCA – Directional Characteristic Angle
  • Characteristic angle – used in directional algorithms

The characteristic angle is important because power system impedance affects the phase angle between current and voltage during faults.

Directional Relay: How to Better Understand?
The Relay Characteristic Angle (RCA) and the Maximum Torque Angle (MTA) are key parameters in the operation and configuration of directional relays. While they are related, they serve different… | Ahmed Osman Abdalla

Why is the angle important?

The relay must reliably distinguish between forward and reverse faults, including faults where voltage magnitude is reduced.

Incorrect characteristic angle selection can result in:

  • Incorrect directional decisions
  • Reduced sensitivity
  • Unwanted operation
  • Failure to operate for certain fault conditions

The appropriate characteristic angle depends on the protected network, fault type, relay algorithm, grounding method, and manufacturer recommendations.

9. Phase Directional Overcurrent Protection (67)

Phase directional overcurrent protection is used to detect phase faults in a defined direction.

Common faults include:

  • Three-phase faults
  • Phase-to-phase faults
  • Two-phase-to-ground faults

The directional elements may be configured separately for each phase or use a combined directional algorithm.

Applications

  • Parallel feeders
  • Ring distribution systems
  • Two-source networks
  • Transmission lines
  • Interconnected grids
  • Networks with distributed generation

Typical ANSI elements

ElementDescription
67PPhase directional overcurrent
67-1Directional stage 1 (manufacturer-dependent naming)
67-2Directional stage 2
67-3Additional directional stage where available

A relay may have multiple directional overcurrent stages with different pickups, operating curves, directionality, and logic.

10. Directional Earth-Fault Protection (67N / 67G)

Earth faults can be difficult to detect because their fault currents depend heavily on the grounding method and system capacitance.

Directional earth-fault protection determines whether the earth-fault current is flowing in the protected direction using residual current and a polarizing reference.

Residual current

Residual current can be calculated from the sum of three phase currents:

3I0=IA+IB+IC3I0​=IA​+IB​+IC​

Where:

  • IAIA​ = phase A current
  • IBIB​ = phase B current
  • ICIC​ = phase C current

Under balanced load conditions, the vector sum is approximately zero. During an earth fault, the residual current can become significant.

Polarizing quantities for 67N

Common methods include:

MethodPolarizing quantityApplication
Voltage polarizationResidual voltage 3V03V0​Grounded networks where residual voltage is available
Current polarizationNeutral or grounding currentNetworks with suitable grounding transformer
Dual polarizationVoltage and currentImproved directional reliability in selected systems
WattmetricActive power-related residual quantitiesCertain compensated or high-resistance grounded networks
Admittance-basedCalculated residual admittanceSpecialized earth-fault detection applications

The choice of method depends on the grounding arrangement and the relay’s supported directional algorithms.

11. Grounding System and Directional Earth-Fault Protection

Grounding has a major influence on earth-fault current and directional element behavior.

Grounding Studies for Industrial Applications
Grounding typeEarth-fault currentProtection consideration
Solid groundingGenerally highCurrent-based earth protection often feasible
Resistance groundingLimited by resistorPickup sensitivity and resistor rating
Reactance groundingLimited by reactorDirectional and coordination considerations
Isolated neutralMay be lowSensitive fault detection needed
Resonant grounding (Petersen coil)CompensatedSpecialized directional/admittance/wattmetric techniques

Directional earth-fault protection is especially valuable where fault current magnitude alone cannot reliably identify the faulted feeder.

12. CT and VT Requirements

Directional protection depends on correct current and voltage measurements.

Current transformers (CTs)

CTs supply the relay with current information. Correct CT polarity is essential for directional functions.

Voltage transformers (VTs / PTs)

VTs supply the relay with voltage reference information.

Important engineering checks

  • CT ratio is correctly selected.
  • CT polarity and terminal markings are verified.
  • VT phase sequence is correct.
  • Voltage and current inputs correspond to the correct phases.
  • Residual current measurement is correctly configured.
  • Residual voltage measurement is correctly connected or calculated.
  • CT secondary circuits are safely grounded at the intended point.
  • Wiring diagrams are reviewed before commissioning.

Incorrect phase mapping or polarity may cause a directional element to detect the wrong direction.

13. Directional Overcurrent in Parallel Feeders

Parallel feeders are a common application of directional overcurrent protection.

Suppose two feeders connect the same bus sections or supply a common load from separate sources.

When a fault occurs on one feeder, current from the healthy feeder may also contribute to the fault. This can cause non-directional protection to lose selectivity.

Directional protection allows relays to distinguish fault current flowing toward the faulted feeder from current flowing in the opposite direction.

Advantages

  • Improved discrimination between parallel paths
  • Reduced risk of tripping healthy feeders
  • Better coordination for multi-source faults
  • More flexibility in network operation

14. Directional Overcurrent in Ring Networks

Ring networks are used to improve reliability and supply continuity.

In a ring network, power may reach a load from different directions depending on switching configuration.

New Approach for Validation of a Directional Overcurrent Protection Scheme in a Ring Distribution Network with Integration of Distributed Energy Resources Using Digital Twins

A non-directional relay may not be able to coordinate reliably with neighboring relays in every operating configuration.

Directional overcurrent protection allows engineers to define forward and reverse protection zones and coordinate each relay with the appropriate adjacent protection.

Typical applications

  • Urban distribution networks
  • Industrial MV networks
  • Large campuses
  • Oil and gas facilities
  • Mining installations
  • Utility distribution rings

15. Directional Protection in Networks with Distributed Generation

Modern power systems increasingly include:

  • Solar PV
  • Wind generation
  • Battery energy storage
  • Cogeneration
  • Industrial generators
  • Inverter-based resources

These sources may change fault current direction and magnitude.

Traditional radial protection assumptions may no longer be valid after distributed generation is connected.

Directional protection may be required to:

  • Distinguish faults on the feeder from faults on the source side
  • Avoid unwanted trips
  • Improve protection coordination
  • Accommodate different network configurations
  • Support bidirectional power flow

However, inverter-based generation may contribute fault current differently from conventional synchronous generators. Protection engineers must consider inverter fault-current characteristics, current limiting, control response, and the utility’s interconnection requirements.

16. Directional Overcurrent Coordination

Protection coordination ensures that the relay closest to the fault operates first while upstream relays provide backup.

Directional coordination is particularly important where fault current can flow in multiple directions.

Coordination principles

  1. Identify the primary protection for each circuit section.
  2. Establish forward and reverse reference directions.
  3. Confirm directional elements correctly identify fault direction.
  4. Select pickup values appropriate for load and fault current.
  5. Select time curves and delays.
  6. Coordinate with downstream and upstream relays.
  7. Confirm backup protection operation.
  8. Review different network configurations.

Directional logic alone does not guarantee selectivity. Proper pickup settings, time coordination, breaker operating time, and system topology are also required.

17. Directional Protection Logic

A numerical relay may include several conditions before a trip output is generated.

Example simplified logic:

Phase current > Pickup │ ▼ Current element pickup │ ▼ Directional element │ ┌──────┴───────┐ │ │ Forward Reverse │ │ ▼ ▼ Timer Restraint │ ▼ Trip logic │ ▼ Circuit breaker trip output

The logic may additionally include:

  • Start signals
  • Blocking inputs
  • Breaker status
  • Directional memory
  • Voltage supervision
  • Logic coordination
  • Interlocking
  • Trip matrix

18. Directional Memory and Low-Voltage Fault Conditions

During close-in faults, voltage can collapse to a very low level. Since directional protection uses voltage as a reference, low voltage can make direction determination difficult.

Numerical relays may use memory voltage or other polarizing techniques to maintain reliable directional decisions during fault conditions.

Voltage memory polarization

The relay retains a reference voltage from before the fault, for a defined period, to help determine direction when the present fault voltage is weak.

This is particularly relevant for:

  • Close-in three-phase faults
  • Severe voltage dips
  • Faults where the polarizing voltage is significantly reduced

The relay’s memory polarization method, duration, and limitations must be reviewed in the relevant manufacturer’s documentation.

19. Directional Overcurrent Settings

Directional overcurrent protection typically requires several settings.

SettingPurpose
Pickup currentMinimum current required for operation
DirectionForward, reverse, or both
Characteristic angleDefines directional sensitivity
Curve typeDefinite time or inverse time
Time multiplierAdjusts operating time
Definite-time delayFixed delay before operation
Voltage polarizationDefines the voltage reference method
Residual current sourceDefines earth-fault measurement
Blocking logicPrevents unwanted operation
Trip outputAssigns the trip command

Setting names and available options vary between relay families.

Engineering considerations

Settings must be checked against:

  • Maximum load current
  • Minimum fault current
  • Maximum fault current
  • CT ratio and performance
  • System grounding
  • Network configuration
  • Breaker operating time
  • Coordination with adjacent protection
  • Generator and motor contributions
  • Protection sensitivity requirements

Settings should be based on a protection study rather than copied from another installation.

20. Practical Setting Example – Illustrative Only

Consider a feeder with the following assumed data:

ParameterValue
Nominal voltage11 kV
Maximum feeder load300 A
CT ratio400/1 A
DirectionForward toward feeder
RelayNumerical directional overcurrent relay
Protection67P + 51P

Step 1 – Determine secondary load current

For a 400/1 CT:

Isecondary=Iprimary400Isecondary​=400Iprimary​​

At maximum feeder load:

Isecondary=300400=0.75AIsecondary​=400300​=0.75A

The relay sees approximately 0.75 A secondary at the maximum primary load.

Step 2 – Select pickup

A pickup must be selected above expected load and permissible overload conditions while remaining sensitive to the minimum fault current.

The final pickup is not determined solely by multiplying maximum load by a generic margin. It must account for load growth, overload requirements, CT performance, relay tolerances, and downstream coordination.

Step 3 – Confirm direction

The directional element is configured to look forward from the bus toward the protected feeder.

Step 4 – Coordinate timing

The time delay or inverse curve is selected to coordinate with downstream feeder protection and provide appropriate backup.

Step 5 – Verify the result

The protection engineer must verify that:

  • The relay picks up for the intended fault range.
  • The directional element detects forward faults.
  • Reverse faults are restrained where required.
  • The circuit breaker operates within the protection scheme’s requirements.
  • Backup protection remains effective.

This is an educational example, not a final protection setting recommendation.

21. Directional Protection in Numerical Relays

Modern numerical relays combine directional elements with other protection functions.

Typical functions may include:

FunctionDescription
50/51Non-directional phase overcurrent
67Directional phase overcurrent
50N/51NNon-directional earth-fault overcurrent
67NDirectional earth-fault overcurrent
46Negative-sequence current protection
49Thermal protection
27/59Undervoltage/overvoltage
79Auto-reclosing
50BFBreaker failure
86Lockout

These functions can interact through configurable logic.

For example, directional overcurrent may initiate a trip, block an auto-reclosing operation under certain conditions, or participate in backup protection logic.

22. Directional Overcurrent in Different Manufacturers’ Relays

Directional overcurrent protection is available in many protection platforms.

ManufacturerRelay families / platforms
SiemensSIPROTEC 4 and SIPROTEC 5
Hitachi EnergyRelion 615, 620, 630, 650 and related platforms
Schneider ElectricEasergy protection relays
SELSEL-351, SEL-751 and other feeder relays
GE VernovaMultilin feeder and line protection platforms
NR ElectricPCS-series protection relays
ToshibaNumerical protection relay families
Mitsubishi ElectricNumerical protection platforms

The exact directional element implementation, polarizing methods, setting menus, curve types, and test requirements differ between manufacturers and models.

23. Directional Protection Testing and Commissioning

Testing directional protection is more complex than testing a conventional overcurrent element because both current magnitude and directional behavior must be verified.

23.1 Required equipment

  • Protection relay test set
  • OMICRON CMC series or equivalent
  • Relay test software, such as Test Universe
  • Test leads and binary input/output connections
  • Relay configuration software
  • Approved test procedure
  • Protection setting file

23.2 Testing steps

StepTest
1Review relay settings and drawings
2Verify CT/VT ratios and phase mapping
3Check current and voltage polarity
4Test phase overcurrent pickup
5Test earth-fault pickup
6Test forward directional decision
7Test reverse directional restraint
8Verify characteristic angle behavior
9Test operating time for selected curve
10Test trip output and circuit breaker trip path
11Verify blocking and interlocking logic
12Record and review results

23.3 Directional testing

Directional tests should include combinations of current and voltage phasors representing:

  • Forward fault conditions
  • Reverse fault conditions
  • Conditions near the directional boundary
  • Relevant fault types
  • Weak polarizing conditions, where supported by the test procedure

The test engineer should verify the operating and restraining regions against the relay manufacturer’s directional characteristic.

23.4 Timing tests

For inverse-time protection, test timing at several current multiples to confirm that the selected characteristic and time multiplier are behaving correctly.

23.5 End-to-end considerations

For schemes involving remote protection, communication-assisted protection, or intertripping, secondary injection alone may not verify the entire scheme.

Additional tests may be required to verify:

  • Communication channels
  • Remote signals
  • Permissive or blocking logic
  • Intertripping
  • End-to-end scheme operation

24. Common Engineering Mistakes

Common mistakes when applying directional overcurrent protection include:

  • Selecting the wrong forward direction.
  • Incorrect CT polarity.
  • Incorrect VT polarity.
  • Wrong phase-current and voltage mapping.
  • Selecting an unsuitable characteristic angle.
  • Using inappropriate polarizing quantities.
  • Ignoring minimum fault-current sensitivity.
  • Failing to coordinate directional elements between feeders.
  • Incorrect earth-fault residual-current configuration.
  • Ignoring network changes or distributed generation.
  • Testing only current pickup without testing direction.
  • Not testing reverse-direction restraint.
  • Copying settings from another installation without a protection study.

Directional protection is a protection function where configuration, wiring, and test results must all be verified together.

25. Practical Applications of Directional Overcurrent Protection

ApplicationWhy directional protection is useful
Parallel feedersDistinguishes fault current direction between parallel paths
Ring networksEnables selective fault isolation in interconnected paths
Two-source substationsIdentifies faults relative to each source
Industrial networksHandles multiple incoming supply connections
Distributed generationAccommodates bidirectional fault-current contributions
Transformer interconnectionsHelps coordinate protection around interconnected sources
Grid interconnectionsImproves fault discrimination and backup protection

26. Directional Overcurrent Protection vs. Other Protection Methods

ProtectionMain operating principleTypical application
50/51Current magnitude and timeRadial feeders
67Current magnitude + directionRing and multi-source networks
87Current comparisonTransformers, generators, busbars, lines
21Impedance measurementTransmission lines
67NEarth-fault current + directionGrounded or specialized distribution systems
67QDirectional negative-sequence overcurrentUnbalanced faults, depending on relay

Directional overcurrent is often used as primary or backup protection, depending on the system design. It is not necessarily a replacement for differential or distance protection.

27. Standards and Technical References

Relevant standards and reference documents may include:

  • IEC 60255 series – Measuring relays and protection equipment
  • IEC 60255-1 – Common requirements
  • IEC 60255-151 – Functional requirements for overcurrent protection
  • IEC 61850 – Communication networks and systems for power utility automation
  • IEEE C37.2 – Electrical power system device function numbers
  • IEEE C37.112 – Inverse-time characteristic guidance for overcurrent relays
  • IEEE C37.90 series – Relay testing and performance-related guidance, where applicable

Always check the applicable edition, scope, and requirements of each standard for the project.

28. Practical Training at Elec-Engg

Directional protection is one of the topics where understanding the theory alone is not enough. Engineers should be able to configure, test, troubleshoot, and verify directional elements in real protection relays.

At Elec-Engg, our practical protection training covers protection principles, relay configuration, fault analysis, relay testing, coordination, and commissioning.

Training subjects include:

  • Power system protection fundamentals
  • Overcurrent protection 50/51
  • Directional overcurrent protection 67/67N
  • Protection coordination and grading
  • CT/VT circuits and polarity verification
  • Numerical relay configuration
  • DIGSI 4 and DIGSI 5
  • ABB PCM600
  • Relay testing using OMICRON CMC and Test Universe
  • Practical troubleshooting and commissioning

Our objective is to help engineers understand not only how protection functions work, but also how they are applied and verified in real electrical power systems.

Explore the technical training and engineering resources available at Elec-Engg.com.

29. Conclusion

Directional overcurrent protection is a fundamental protection technique for power systems where fault current can flow in multiple directions.

Unlike conventional overcurrent protection, directional protection evaluates both current magnitude and direction, allowing engineers to achieve better selectivity in parallel feeders, ring networks, interconnected substations, and systems containing distributed generation.

Understanding the directional principle, polarizing quantities, characteristic angle, CT/VT connections, grounding methods, relay settings, and testing procedures is essential for protection engineers, commissioning engineers, and maintenance professionals.

Properly engineered directional protection improves reliability, reduces unnecessary outages, and helps maintain the continuity of healthy parts of the electrical network.