Feeder Protection (ANSI 50/51, 50N/51N, 67, 67N, 79, 50BF)

Overcurrent Protection, Directional Protection, Earth Fault Protection, Auto-Reclosing, Coordination, Settings and Testing.

1. Introduction

Feeder protection is one of the fundamental areas of power system protection engineering.

Electrical feeders are used to transfer electrical energy between substations, transformers, generators, distribution networks, and industrial loads.

Feeders can operate at different voltage levels, including:

  • Low voltage (LV).
  • Medium voltage (MV).
  • High voltage (HV).
  • Extra-high voltage (EHV).

A feeder fault can interrupt power supply to customers, industrial processes, and other important electrical equipment.

The primary objective of feeder protection is to detect faults, identify the affected circuit, and isolate it as quickly and selectively as possible while maintaining the continuity of the remaining power system.

Common feeder protection functions include:

  • Instantaneous overcurrent protection (50).
  • Time overcurrent protection (51).
  • Earth fault protection (50N/51N).
  • Directional overcurrent protection (67).
  • Directional earth fault protection (67N).
  • Auto-reclosing (79).
  • Circuit breaker failure protection (50BF).
  • Negative sequence protection (46).
  • Undervoltage protection (27).
  • Overvoltage protection (59).
  • Thermal overload protection (49).
  • Sensitive earth fault protection.

Modern numerical feeder protection relays integrate these functions with measurement, disturbance recording, communication, and control capabilities.

Common manufacturers include Siemens, ABB/Hitachi Energy, Schneider Electric, GE Vernova, SEL, and NR Electric.

2. Typical Feeder Protection Scheme

A typical feeder protection scheme consists of:

  1. Current transformers (CTs).
  2. Voltage transformers (VTs).
  3. Numerical protection relay.
  4. Circuit breaker.
  5. Trip and close circuits.
  6. DC auxiliary supply.
  7. Communication interfaces.
  8. Busbar and feeder connections.

The CTs measure feeder current and provide secondary current signals to the protection relay.

The VTs provide voltage measurements when required by directional protection and other voltage-dependent functions.

The relay continuously evaluates electrical quantities and determines whether a fault condition exists.

When a protection element operates, the relay issues a trip command to the associated circuit breaker.

The circuit breaker interrupts the fault current and isolates the faulty feeder.

Feeder Protection (ANSI 50/51, 50N/51N, 67, 67N, 79, 50BF): Complete Engineering Guide to Overcurrent Protection, Directional Protection, Earth Fault Protection, Auto-Reclosing, Coordination, Settings and Testing

3. Types of Feeder Faults

Understanding feeder faults is essential for selecting and configuring the correct protection functions.

3.1 Three-Phase Fault

A three-phase fault occurs when all three phases become electrically connected through a fault path.

It generally produces high fault current and is considered a severe short-circuit condition.

3.2 Phase-to-Phase Fault

A phase-to-phase fault occurs when two phases become connected.

It can result from insulation failure, conductor contact, or equipment damage.

3.3 Single Phase-to-Earth Fault

A single phase-to-earth fault occurs when one phase comes into contact with earth or grounded equipment.

It is one of the most common faults in distribution networks.

3.4 Double Phase-to-Earth Fault

Two phases become connected to earth, creating an unbalanced fault current condition.

The magnitude of fault current depends on:

  • System voltage.
  • Source impedance.
  • Transformer impedance.
  • Feeder impedance.
  • Fault impedance.
  • System grounding arrangement.

4. Instantaneous Overcurrent Protection (ANSI 50)

Instantaneous overcurrent protection is one of the basic functions used in feeder protection.

It operates when the measured phase current exceeds a predefined threshold.

I>IpickupI>Ipickup​

The function operates without an intentional time delay, although the relay and circuit breaker have inherent operating times.

Typical applications include:

  • High-current feeder faults.
  • Close-in short circuits.
  • Transformer feeder protection.
  • Motor feeder protection.
  • Cable fault protection.

The pickup setting must be selected carefully to ensure that the relay does not operate for faults beyond its intended protection zone when selectivity is required.

Important considerations include:

  • Maximum load current.
  • Minimum fault current.
  • Maximum short-circuit current.
  • CT performance.
  • Downstream protection coordination.
  • Upstream protection coordination.

5. Time Overcurrent Protection (ANSI 51)

Time overcurrent protection operates when current exceeds a configured pickup threshold for a specified operating time.

It is widely used in radial distribution networks.

The relay may use different time-current characteristics.

Common characteristics include:

  • Definite time.
  • Standard inverse.
  • Very inverse.
  • Extremely inverse.
  • Long-time inverse.
2. 과전류계전기(OCR, Over Current Relay) 동작 특성 :: 코스모스

A commonly used IEC inverse-time equation is:

t=k×TMS(IIs)α−1t=(Is​I​)α−1k×TMS​

Where:

  • tt = Operating time.
  • II = Measured current.
  • IsIs​ = Pickup current.
  • TMS = Time multiplier setting.
  • kk and αα = Curve constants.

For example, for the standard inverse characteristic:

k=0.14k=0.14

α=0.02α=0.02

The relay operates faster at higher fault current levels.

The selection of the appropriate curve depends on the network configuration and coordination requirements.

6. Earth Fault Protection (ANSI 50N/51N)

Earth fault protection detects current flowing through an unintended earth fault path.

It is essential in distribution and industrial networks.

Earth fault protection can be implemented using several methods.

6.1 Residual Current Calculation

The relay calculates the residual current from the three phase currents.

I0=IA+IB+IC3I0​=3IA​+IB​+IC​​

The residual current is proportional to the zero-sequence current.

Depending on relay conventions, the measured residual quantity may be expressed as 3I03I0​.

6.2 Core Balance CT

A core balance CT surrounds all three phase conductors.

During normal operation, the magnetic fluxes produced by the phase currents cancel.

During an earth fault, residual current appears and the CT provides an output to the relay.

6.3 Neutral CT

In grounded systems, a CT may be installed in the transformer neutral grounding connection.

This arrangement measures neutral current and can provide sensitive earth fault protection.

6.4 Earth Fault Settings

Settings must consider:

  • Network grounding method.
  • Minimum earth fault current.
  • Maximum earth fault current.
  • Feeder capacitance.
  • CT characteristics.
  • Downstream coordination.
  • Sensitive earth fault requirements.

7. Directional Overcurrent Protection (ANSI 67)

Directional overcurrent protection is used when current can flow in more than one direction.

This is particularly important in:

  • Ring networks.
  • Parallel feeders.
  • Double-ended substations.
  • Networks with distributed generation.
  • Industrial systems with multiple power sources.
Negative Sequence Component for directional Overcurrent Protection

Unlike ordinary overcurrent protection, directional overcurrent protection evaluates both current magnitude and direction.

The relay uses:

  • Current measurement.
  • Voltage measurement.
  • Directional characteristic.
  • Polarizing quantity.
  • Operating angle.

7.1 Directional Principle

The relay determines whether the fault current flows in the configured forward or reverse direction.

A simplified representation is:

Trip=I>Ipickup∧Direction=ForwardTrip=I>Ipickup​∧Direction=Forward

If the current exceeds the pickup but flows in the reverse direction, the relay blocks the forward protection element.

7.2 Voltage Polarization

Directional elements generally use voltage as a reference to determine current direction.

Common polarizing methods include:

  • Phase-to-phase voltage polarization.
  • Positive-sequence voltage polarization.
  • Cross-polarization.
  • Memory voltage polarization.

Memory polarization is particularly useful for close-in faults where the measured voltage may collapse.

7.3 Maximum Torque Angle

The maximum torque angle (MTA), also known as the maximum sensitivity angle in certain relay implementations, defines the preferred angular relationship between the operating current and the polarizing voltage.

Incorrect MTA configuration can result in directional protection operating incorrectly.

Engineers must verify the manufacturer’s definition, phase convention, and current polarity before applying settings.

8. Directional Earth Fault Protection (ANSI 67N)

Directional earth fault protection identifies earth faults and determines their direction.

It is especially important in networks with multiple sources or complex grounding arrangements.

The protection generally evaluates:

  • Residual current 3I03I0​.
  • Residual voltage 3U03U0​.
  • Directional operating characteristic.
  • Polarization method.

Depending on the network, directional earth fault protection may use:

  • Zero-sequence voltage polarization.
  • Negative-sequence polarization.
  • Wattmetric directional elements.
  • Admittance-based directional elements.

The correct method depends on the network grounding arrangement and available zero-sequence quantities.

8.1 Applications

  • Isolated neutral systems.
  • Compensated networks.
  • Resistance-grounded systems.
  • Ring distribution networks.
  • Networks with multiple infeed sources.

Sensitive earth fault protection is particularly useful where earth fault currents are relatively small.

9. Auto-Reclosing Protection (ANSI 79)

Auto-reclosing is widely used in overhead transmission and distribution networks.

Many overhead line faults are temporary.

Examples include:

  • Lightning strikes.
  • Temporary conductor contact.
  • Bird-related faults.
  • Temporary insulation flashover.
  • Wind-related conductor movement.

When a fault occurs, the protection relay trips the circuit breaker.

After a configured dead time, the auto-reclosing function sends a closing command.

If the fault has disappeared, the line returns to normal service.

If the fault remains, the breaker trips again.

9.1 Auto-Reclosing Sequences

Common reclosing strategies include:

  • Single-shot auto-reclosing.
  • Multi-shot auto-reclosing.
  • High-speed auto-reclosing.
  • Delayed auto-reclosing.
  • Three-phase auto-reclosing.
  • Single-phase auto-reclosing.

9.2 Important Settings

ParameterDescription
Dead timeTime between trip and reclosing
Reclaim timeTime after successful closing before the sequence resets
Number of shotsMaximum reclosing attempts
Synchronism checkVerification before closing
Dead line/live bus checkVoltage condition supervision
Breaker readyCircuit breaker availability
LockoutPrevents further reclosing attempts

9.3 Auto-Reclosing Lockout

Auto-reclosing should generally be blocked for faults where automatic restoration is inappropriate.

Examples include:

  • Transformer internal faults.
  • Busbar faults.
  • Generator internal faults.
  • Cable faults where the protection philosophy prohibits reclosing.
  • Manual trip conditions.
  • Circuit breaker failure conditions.

The exact blocking logic must be established in the protection and control design.

10. Circuit Breaker Failure Protection (ANSI 50BF)

Circuit breaker failure protection is designed to detect situations where a circuit breaker fails to interrupt fault current after receiving a trip command.

Possible causes include:

  • Trip coil failure.
  • Mechanical failure.
  • DC supply failure.
  • Breaker mechanism problems.
  • Electrical defects.

A typical operating sequence is:

  1. Feeder protection detects a fault.
  2. A trip command is sent to the circuit breaker.
  3. Breaker failure logic is initiated.
  4. Current supervision checks whether current persists.
  5. The breaker failure timer expires.
  6. Backup tripping is initiated if the failure condition remains.

The backup trip may involve adjacent breakers or upstream circuit breakers, depending on the substation design.

Important settings include:

  • Breaker failure initiation.
  • Current supervision threshold.
  • Timer setting.
  • Breaker auxiliary contact supervision.
  • Backup trip matrix.
  • Reset conditions.

11. Negative Sequence Protection (ANSI 46)

Negative sequence protection detects unbalanced three-phase current conditions.

It is useful for identifying:

  • Open phase conditions.
  • Unbalanced faults.
  • Abnormal phase loading.
  • Conductor problems.
  • Certain asymmetrical fault conditions.

The relay calculates:

I2=13(IA+a2IB+aIC)I2​=31​(IA​+a2IB​+aIC​)

Where:

a=1∠120∘a=1∠120∘

This protection can be particularly important in feeders supplying large motors and other equipment sensitive to phase unbalance.

12. Voltage Protection (ANSI 27/59)

Voltage protection may be applied to feeders for monitoring abnormal supply conditions.

Undervoltage (27) detects low voltage.

Overvoltage (59) detects excessive voltage.

Typical applications include:

  • Industrial motor feeders.
  • Distribution feeders.
  • Capacitor bank feeders.
  • Generator-connected feeders.
  • Voltage-dependent load shedding.

The settings must be coordinated with equipment operating limits and system requirements.

13. Feeder Protection Coordination

Protection coordination is one of the most important aspects of feeder protection engineering.

The objective is to ensure that the protection closest to the fault operates first.

For a radial distribution network, consider:

  • Main incoming breaker.
  • Transformer feeder.
  • Distribution feeder.
  • Outgoing load feeder.

During a fault on the downstream feeder, the downstream relay should operate first.

The upstream relay acts as backup protection if the downstream protection or circuit breaker fails.

13.1 Grading Margin

A grading margin is maintained between upstream and downstream protection operating times.

It accounts for:

  • Relay operating time.
  • Circuit breaker interruption time.
  • CT errors.
  • Relay overshoot.
  • Safety margin.
  • Protection coordination philosophy.

The required margin depends on the relay and circuit breaker technology and the engineering standard being applied.

13.2 Time-Current Coordination Curves

Assessment and Commissioning of Electrical Substation Grid Testbed with a Real-Time Simulator and Protective Relays/Power Meters in the Loop

Time-current curves help engineers verify selectivity between:

  • Feeder relays.
  • Transformer protection.
  • Motor protection.
  • Fuses.
  • Upstream circuit breakers.

Coordination must be checked at both maximum and minimum fault current conditions.

14. Feeder Protection in Different Network Configurations

14.1 Radial Network

In a radial network, power normally flows from one source toward the load.

Non-directional overcurrent protection is often suitable.

14.2 Ring Network

In a ring network, fault current may flow from different directions.

Directional overcurrent protection is often required to achieve selectivity.

14.3 Parallel Feeders

Parallel feeders may be supplied from the same busbar or different sources.

Directional protection can help distinguish faults on individual feeders.

14.4 Networks with Distributed Generation

Solar plants, wind farms, battery energy storage systems, and other distributed generators can change the magnitude and direction of fault current.

Protection engineers must review:

  • Multiple fault infeed contributions.
  • Directional sensitivity.
  • Grid-forming and grid-following inverter behavior.
  • Protection coordination.
  • Islanding conditions.
  • Fault current limitations.

Conventional overcurrent settings may not be sufficient for every inverter-dominated network.

15. Numerical Feeder Protection Relays

Modern feeder protection relays combine protection, control, monitoring, and communication functions.

Siemens – SIPROTEC 5 7SJ85

Numerical feeder protection with overcurrent, earth fault, directional protection, auto-reclosing, breaker failure and other protection functions. Engineering through DIGSI 5.

ABB / Hitachi Energy – REF615

Feeder protection and control relay for distribution networks, including directional and non-directional overcurrent and earth fault functions.

Schneider Electric – MiCOM P12x Series

Feeder protection solutions with overcurrent and earth fault protection. Available functions depend on the specific model.

GE Vernova – Multilin F60

Feeder protection with advanced protection, monitoring, recording and communication functions.

SEL – SEL-751

Feeder protection and control with overcurrent, directional, earth fault, arc-flash detection and other application-dependent functions.

NR Electric – PCS Series

Numerical protection solutions for transmission and distribution feeder applications.

16. Feeder Protection Settings and Engineering Calculations

Feeder protection settings depend on the actual electrical network and fault study.

Important information includes:

  • Rated feeder current.
  • CT ratio.
  • VT ratio.
  • Maximum load current.
  • Maximum short-circuit current.
  • Minimum fault current.
  • Feeder impedance.
  • Network grounding method.
  • Downstream relay settings.
  • Upstream relay settings.
  • Circuit breaker characteristics.

Practical Example

Consider a 33 kV feeder with:

ParameterValue
Rated voltage33 kV
Maximum load10 MVA
CT ratio300/1 A
Frequency50 Hz
NetworkRadial
ProtectionNumerical feeder relay

Step 1 – Calculate feeder full-load current

I=S3VI=3​VS​

I=10×1063×33×103I=3​×33×10310×106​

I=174.95AI=174.95A​

Step 2 – Calculate CT secondary current at maximum load

Is=174.95300Is​=300174.95​

Is=0.583AIs​=0.583A​

Step 3 – Review overcurrent pickup

The overcurrent pickup must be above the maximum expected load current, considering permissible overload and operating conditions, while remaining sensitive to the minimum fault current.

Step 4 – Review earth fault protection

Determine the minimum and maximum earth fault current according to the system grounding arrangement.

Step 5 – Perform coordination

Check the relay characteristic against downstream and upstream protection curves.

These calculations are preliminary. Final settings require short-circuit studies, load-flow studies, and coordination analysis.

17. Feeder Protection Testing and Commissioning

A complete feeder protection commissioning program should verify both protection functions and circuit breaker control.

17.1 Initial Inspection

  • CT ratio verification.
  • CT polarity verification.
  • VT ratio verification.
  • Phase sequence verification.
  • Wiring inspection.
  • Binary input checks.
  • Binary output checks.
  • Circuit breaker trip circuit checks.

17.2 Overcurrent Tests

  • Phase overcurrent pickup.
  • Instantaneous overcurrent.
  • Definite-time operation.
  • Inverse-time characteristic.
  • Reset behavior.
  • Coordination verification.

17.3 Earth Fault Tests

  • Residual current measurement.
  • Core balance CT verification.
  • Earth fault pickup.
  • Earth fault time characteristic.
  • Sensitive earth fault operation.

17.4 Directional Protection Tests

  • Forward fault simulation.
  • Reverse fault simulation.
  • Directional characteristic.
  • Polarizing voltage verification.
  • Memory polarization.
  • Directional earth fault operation.

17.5 Auto-Reclosing Tests

  • Initiation.
  • Dead time.
  • Reclosing command.
  • Reclaim time.
  • Successful reclosing.
  • Unsuccessful reclosing.
  • Lockout.
  • Synchronism check.
  • Blocking conditions.

17.6 Breaker Failure Tests

  • Breaker failure initiation.
  • Current supervision.
  • Timer operation.
  • Backup tripping.
  • Reset logic.

17.7 Final Functional Tests

  • Circuit breaker trip.
  • Circuit breaker close.
  • Local and remote control.
  • Interlocking.
  • Alarm indication.
  • SCADA communication.
  • Disturbance recording.
  • Event recording.

18. IEC 61850 and Feeder Protection

Modern numerical feeder relays are increasingly integrated into IEC 61850-based Substation Automation Systems.

Important IEC 61850 applications include:

  • GOOSE trip signals.
  • Circuit breaker status.
  • Interlocking.
  • Auto-reclosing coordination.
  • Breaker failure initiation.
  • SCADA measurements.
  • Alarm and event reporting.

Typical logical node groups include:

Logical NodeFunction
PTOCTime overcurrent
PIOCInstantaneous overcurrent
PDIRDirectional protection
PTOFOverfrequency
PTUVUndervoltage
PTOVOvervoltage
RRECAuto-reclosing
RBRFBreaker failure
MMXUMeasurements
XCBRCircuit breaker
XSWISwitch/disconnector

The actual logical nodes and their allocation depend on the relay implementation and IEC 61850 model.

Engineers should understand GOOSE configuration, SCL files, signal mapping, and communication supervision when working with digital substations.

19. Common Feeder Protection Engineering Mistakes

Common mistakes include:

  1. Incorrect CT polarity.
  2. Incorrect CT ratio.
  3. Incorrect phase rotation.
  4. Incorrect current direction.
  5. Incorrect directional MTA.
  6. Wrong voltage polarization.
  7. Overcurrent pickup too high.
  8. Overcurrent pickup too low.
  9. Incorrect earth fault sensitivity.
  10. Incorrect time multiplier setting.
  11. Poor upstream/downstream coordination.
  12. Incorrect auto-reclosing dead time.
  13. Auto-reclosing enabled for unsuitable faults.
  14. Incorrect breaker failure logic.
  15. Incorrect GOOSE trip mapping.
  16. Failure to test reverse fault conditions.
  17. Failure to verify minimum fault sensitivity.

One of the most important commissioning requirements is to verify both forward and reverse fault operation when directional protection is used.

20. Conclusion

Feeder protection is a fundamental component of electrical power system protection.

A reliable feeder protection scheme must provide:

  • Fast fault detection.
  • Selective isolation.
  • Proper earth fault sensitivity.
  • Directional discrimination where required.
  • Correct protection coordination.
  • Reliable circuit breaker operation.
  • Appropriate automatic reclosing.
  • Backup protection through breaker failure logic.

Modern numerical feeder relays provide advanced protection, monitoring, recording, and communication functions.

However, successful implementation requires a thorough understanding of network configuration, CT and VT circuits, short-circuit calculations, protection coordination, relay settings, and commissioning procedures.

21. Practical Feeder Protection Training by Elec-Engg

At Elec-Engg, we provide practical training and engineering resources covering feeder protection, power system protection, numerical relays, and substation automation.

Our practical training covers:

  • Overcurrent protection.
  • Earth fault protection.
  • Directional overcurrent protection.
  • Directional earth fault protection.
  • Protection grading and coordination.
  • Auto-reclosing.
  • Circuit breaker failure.
  • CT and VT circuit verification.
  • Numerical relay configuration.
  • OMICRON relay testing.
  • IEC 61850 communication.

Practical relay applications include Siemens SIPROTEC, ABB Relion, Schneider MiCOM, GE Multilin, SEL, and other protection platforms.

Trainer: Dr. Saeed Roostaee – Electrical Engineering

Our objective is to help protection, commissioning, operation, and maintenance engineers develop practical knowledge that can be applied to real electrical projects.

Explore our technical resources and training programs:

https://elec-engg.com

  1. Feeder protection single-line diagram.
  2. Three-phase feeder fault diagrams.
  3. ANSI 50 instantaneous overcurrent characteristic.
  4. ANSI 51 inverse-time characteristics.
  5. Earth fault protection CT arrangement.
  6. Directional overcurrent forward/reverse diagram.
  7. Directional earth fault phasor diagram.
  8. Auto-reclosing sequence.
  9. Circuit breaker failure logic.
  10. Radial feeder protection coordination.
  11. Ring network directional protection.
  12. Time-current coordination curves.
  13. Siemens SIPROTEC 5 7SJ85.
  14. ABB REF615.
  15. GE Multilin F60.
  16. OMICRON feeder protection testing setup.
  17. IEC 61850 feeder protection architecture.