COMTRADE is often used in relay disturbance records, fault investigations, oscillography, relay testing, and post-fault analysis, but engineers don’t always understand how the file is structured or why different COMTRADE versions have different file arrangements.
File Structure, Data Encoding, Standard Versions, Time Synchronization, and Disturbance Analysis
1. Introduction
COMTRADE stands for Common Format for Transient Data Exchange. It is a standardized file format used to exchange recorded electrical signals and event data from power systems.
COMTRADE files are commonly generated by:
- Protection relays and Intelligent Electronic Devices (IEDs)
- Digital Fault Recorders (DFRs)
- Power quality analyzers
- Substation automation systems
- Transient recording systems
- Protection relay test equipment
- Power system simulation software
The purpose of COMTRADE is to allow disturbance records produced by one manufacturer’s equipment to be analyzed using software from another manufacturer, without requiring proprietary data formats.
For example, during a fault on a transmission line, a protection relay may record:
- Three-phase currents
- Three-phase voltages
- Residual current
- Distance protection operating signals
- Line differential protection signals
- Breaker trip commands
- Breaker auxiliary contacts
- Protection element pickup signals
- Reclosing signals
- Fault detection and trip timestamps
These recorded quantities can be exported as COMTRADE files and analyzed later to investigate fault conditions, relay operation, breaker performance, and system behavior.
COMTRADE is particularly important in modern protection engineering because it allows engineers to reconstruct what happened before, during, and after a power system disturbance.
2. COMTRADE standards and their evolution
The COMTRADE format has evolved through several revisions. The major revisions encountered in practical engineering are 1991, 1999, and 2013.
2.1 IEEE C37.111-1991
The original COMTRADE standard was published in 1991.
It established a common method for exchanging transient data between power system recording devices and analysis systems.
The original version introduced the fundamental concept of separating:
- Configuration information
- Sampled data
- Descriptive information
The configuration file describes the recorded channels and how the data should be interpreted, while the data file contains the actual sampled values.
The 1991 format is relatively simple compared with later versions, but it remains relevant when working with older digital fault recorders, historical disturbance records, or legacy software.
2.2 IEEE C37.111-1999
The 1999 revision expanded and clarified the format, introducing additional information necessary for more reliable data exchange.
Important enhancements included:
- Explicit revision identification in the configuration file
- Analog channel scaling and conversion information
- CT and VT primary/secondary information
- Additional digital channel information
- Timestamp multiplication factor
- Improvements in data file encoding
- Additional metadata support through the INF file
- Improved support for different recording and sampling arrangements
The 1999 revision became widely used in protection and disturbance recording applications.
2.3 IEEE C37.111-2013 / IEC 60255-24:2013
The 2013 revision introduced several important enhancements to improve interoperability and timestamp handling.
The major additions included:
- Additional time-related information
- Time zone and time-quality information
- New binary data representations
- 32-bit integer binary data support
- 32-bit floating-point data support
- Combined File Format (CFF)
- Improved handling of time synchronization and data interpretation
This revision is jointly associated with IEEE C37.111-2013 and IEC 60255-24:2013.
The 2013 revision is especially important when analyzing modern disturbance records that require more precise timing, enhanced data encoding, and improved interoperability.
REFERENCE: IEEE C37.111 / IEC 60255-24
3. COMTRADE file structure
A traditional COMTRADE record consists of several files sharing the same base filename.
For example, a disturbance record may contain:
Example disturbance record
FAULT_001.cfg / Configuration file — channel definitions, sampling, scaling and time information
FAULT_001.dat / Data file — actual sampled analog and digital values
FAULT_001.hdr / Header file — optional descriptive text for engineers
FAULT_001.inf / Information file — optional supplementary metadata
The files are not independent. They work together as a single disturbance-record dataset.
The most important files for interpreting a record are the .CFG and .DAT files.
3.1 Configuration file (.CFG)
The configuration file is the main descriptive file of the COMTRADE record. It normally contains:
- Station name
- Recording device identification
- COMTRADE revision
- Total number of channels
- Analog channel count
- Digital channel count
- Channel identifiers
- Channel descriptions
- Phase identification
- Circuit identification
- Units
- Scaling coefficients
- Analog channel offset
- Channel skew
- Channel minimum and maximum
- Primary and secondary ratios
- Nominal system frequency
- Sampling rates
- Number of samples
- Start timestamp
- Trigger timestamp
- Data encoding type
- Time multiplier
- Time quality and synchronization information in supported versions
The CFG file is usually plain text and can be opened using Notepad or another text editor.
However, engineers should not assume that opening a CFG file is sufficient to interpret the record. The actual waveform values are stored in the DAT file, and their correct interpretation depends on the information in the CFG file.
3.2 Data file (.DAT)
The DAT file contains the sampled data recorded during the disturbance. Depending on the selected data format, it may be stored as:
- ASCII
- BINARY
- BINARY32
- FLOAT32
The DAT file may contain thousands or millions of sample values depending on the number of channels, sampling rate, and recording duration.
For each sample instant, the record contains information associated with the sample number, timestamp, analog channels, and digital channels.
The DAT file must be interpreted together with its CFG file.
3.3 Header file (.HDR)
The HDR file is an optional text file intended for descriptive information.
It may contain details such as:
- Substation name
- Bay name
- Equipment identification
- Fault description
- Recording conditions
- Engineering notes
- Additional information about the event
The HDR file is mainly intended for human-readable information rather than the core machine interpretation of the waveform.
3.4 Information file (.INF)
The INF file is an optional supplementary information file introduced in the 1999 revision.
It can contain additional structured information that may be relevant to the recording device or analysis application.
Its contents depend on the equipment and implementation. It is not normally the primary source of waveform sample data.
4. Understanding the differences between COMTRADE versions
One of the most important things for engineers is recognizing which COMTRADE revision they are dealing with.
Although the purpose of the format remains the same, the internal structure of the configuration file, supported data types, metadata, and timing information have changed.
4.1 Version comparison table
| Feature | 1991 | 1999 | 2013 |
|---|---|---|---|
| Revision identification | No explicit revision field on first line | Revision specified | Revision specified |
| CFG format | Basic structure | Expanded | Further expanded |
| Analog channel definitions | Basic | Enhanced | Enhanced |
| CT/VT ratio information | Not supported in the same manner | Added | Supported |
| Analog channel skew | Limited legacy structure | Supported | Supported |
| Digital channel descriptions | Basic | Expanded | Expanded |
| INF file | Not defined in original revision | Introduced | Supported |
| ASCII DAT | Supported | Supported | Supported |
| Binary DAT | Legacy binary format | Supported | Supported |
| BINARY32 | Not supported | Not supported | Supported |
| FLOAT32 | Not supported | Not supported | Supported |
| Time multiplier | — | Introduced | Supported |
| Time zone / time-code information | Not available | Not available | Added |
| Time quality information | Not available | Not available | Added |
| CFF single-file format | Not supported | Not supported | Introduced |
| Primary/secondary conversion metadata | Basic legacy structure | Added | Supported |
Summary of major changes. Specific supported fields and encodings must be interpreted according to the actual revision and implementation.
The main difference is not merely the filename extension. The later revisions contain additional fields that affect how the data is interpreted, converted, and synchronized.
5. How to identify the COMTRADE version
The easiest method is to open the CFG file using a text editor and inspect its first line.
Example: COMTRADE 1991
First line
STATION_A,RECORDER_01
The first line does not include a revision year, which is characteristic of the original 1991 format.
Example: COMTRADE 1999
STATION_A,RECORDER_01,1999
Example: COMTRADE 2013
STATION_A,RECORDER_01,2013
The revision identifier is a useful initial clue, but engineers should continue reading the configuration file to confirm the data type, channel definitions, and other fields.
Engineering note
Some software and equipment may identify or implement legacy variants differently. A file should not be classified only from its extension or from an assumed manufacturer’s convention. Check its internal configuration fields and validate the actual structure.
6. Anatomy of the COMTRADE configuration file
The CFG file is the most important file to understand when interpreting a COMTRADE dataset.
Its information is organized in a predefined sequence. The order of the lines is important because a software parser reads the file according to the structure defined by the standard.
The following is a simplified example of the structure.
Station_Name,Recorder_ID,2013 6,3A,3D 1,IA, A, BAY1, A, 1.0, 0.0, 0, -1000, 1000, 1000, 1, S 2,IB, B, BAY1, A, 1.0, 0.0, 0, -1000, 1000, 1000, 1, S 3,IC, C, BAY1, A, 1.0, 0.0, 0, -1000, 1000, 1000, 1, S 4,VA, A, BAY1, V, 1.0, 0.0, 0, -1000, 1000, 1000, 1, S 5,VB, B, BAY1, V, 1.0, 0.0, 0, -1000, 1000, 1000, 1, S 6,VC, C, BAY1, V, 1.0, 0.0, 0, -1000, 1000, 1000, 1, S 1,TRIP, A, BAY1 2,CB_OPEN, A, BAY1 3,CB_CLOSE, A, BAY1 50 1 10000,10000 2026/11/27,18:30:00.000000 2026/11/27,18:30:00.100000 ASCII 1 UTC,0
Illustrative example only — not a complete valid CFG for all COMTRADE revisions or equipment implementations.
The following sections explain the main blocks.
6.1 Station name and recorder identification
Station_Name,Recorder_ID,2013
This line identifies the station and the recording device and may contain the revision identifier.
| Field | Meaning |
|---|---|
| Station_Name | Name of the substation, station, or recording location |
| Recorder_ID | Recording device or recorder identification |
| Revision | Applicable COMTRADE revision, when specified |
6.2 Total channel count
6,3A,3D
This line indicates the number of channels in the dataset.
| Parameter | Meaning |
|---|---|
| 6 | Total channels |
| 3A | Three analog channels? No — here it means three analog channels |
| 3D | Three digital channels |
The total channel count is the sum of the analog and digital channels.
In this example:
- Analog channels = 3
- Digital channels = 3
- Total channels = 6
Note: This example is intended to demonstrate the counting format. The actual channel descriptions in a CFG must agree with the declared counts. In the sample above, the six analog definitions would therefore need to be reduced to three to make the file internally consistent.
6.3 Analog channel definition
Each analog channel is described using a record containing channel identification, phase, circuit information, units, scaling, offset, skew, limits, and ratio information, depending on the revision.
A simplified channel record:
1,IA,A,BAY1,A,1.0,0.0,0,-1000,1000,1000,1,S
| Parameter | Description |
|---|---|
| 1 | Channel index / sequence |
| IA | Channel identifier |
| A | Phase identifier |
| BAY1 | Circuit or monitored equipment identifier |
| A | Measurement unit |
| 1.0 | Scaling coefficient |
| 0.0 | Offset |
| 0 | Channel skew |
| -1000 | Minimum value |
| 1000 | Maximum value |
| 1000 | Primary ratio |
| 1 | Secondary ratio |
| S | Primary/secondary scaling flag |
The exact field interpretation and availability depend on the revision.
6.4 Digital channel definition
Digital channels represent binary or logical states rather than continuous measurements.
Example:
1,TRIP,A,BAY1
Possible digital signals in a protection system include:
- Relay trip output
- Breaker open status
- Breaker closed status
- Protection element pickup
- Protection element operation
- Reclosing active
- Reclosing blocked
- Teleprotection received
- Circuit breaker failure initiation
- Circuit breaker failure trip
- Interlocking permissive
- VT fuse failure alarm
- Protection scheme enabled
Digital channels are extremely useful during fault analysis because they allow engineers to correlate analog waveforms with the operation of protection functions and primary equipment.
7. Analog channel scaling: why raw data may not be the actual current or voltage
One of the most common mistakes in COMTRADE analysis is reading the values stored in the DAT file as if they were already the final engineering values.
In many COMTRADE formats, analog samples are stored as digital numbers (raw values). The CFG file contains the information required to convert these raw values into engineering quantities.
The general conversion equation is:
X=a⋅n+b
Where:
- X = converted engineering value
- n = raw sample value
- a = scaling coefficient
- b = offset
For example, assume an analog channel has:
a=0.1,b=0
and the recorded raw sample is:
n=250
Then:
X=0.1×250+0=25
The engineering value is 25 in the declared channel units, subject to any CT/VT ratio interpretation and primary/secondary selection.
7.1 Why scaling matters in protection analysis
Consider a recorded current waveform:
- Raw data = 1500
- Scaling factor = 0.01
The converted value is:
I=1500×0.01=15
If the analyst mistakenly interprets the raw number as 1500 A, the fault-current calculation will be incorrect by a factor of 100.
This can cause major errors in:
- Fault current calculations
- Relay pickup verification
- Differential current calculations
- Impedance calculations
- Distance protection analysis
- CT saturation analysis
- Protection coordination studies
Always verify the scaling coefficients and channel units before analyzing the waveform.
8. Analog channel information in more detail
The analog channel section is particularly important because different COMTRADE revisions provide different levels of measurement and conversion information.
8.1 Channel identifier
The channel identifier is the name of the recorded signal.
Examples:
| Channel name | Typical meaning |
|---|---|
| IA | Phase A current |
| IB | Phase B current |
| IC | Phase C current |
| IN | Neutral current |
| IG | Ground current |
| VA | Phase A voltage |
| VB | Phase B voltage |
| VC | Phase C voltage |
| VAB | Phase-to-phase voltage |
| VBC | Phase-to-phase voltage |
| VCA | Phase-to-phase voltage |
| 3I0 | Residual current |
| 3V0 | Residual voltage |
Channel names are determined by the recording device configuration. They are not always standardized across manufacturers, so the engineer should not rely only on the channel name.
8.2 Phase identification
Phase information may identify the phase associated with the channel, such as:
- A
- B
- C
- N
- Other applicable identifiers
This allows software to group and display the corresponding phase quantities.
8.3 Circuit identification
The circuit field may identify the monitored equipment or circuit.
Examples:
- LINE1
- TRANSFORMER1
- BUS1
- FEEDER05
- GENERATOR1
This information is particularly useful in multi-bay or multi-equipment disturbance records.
8.4 Units
Analog channels can use different units depending on the recorded quantity.
Typical units include:
| Quantity | Unit |
|---|---|
| Current | A |
| Voltage | V |
| Frequency | Hz |
| Active power | W |
| Reactive power | var |
| Temperature | °C |
| Other analog measurements | Equipment-defined |
Correct interpretation of the units is essential when comparing waveforms or performing engineering calculations.
9. Digital channel data and status interpretation
Unlike analog channels, digital channels have discrete states.
A digital channel generally represents a binary state, commonly interpreted as 0 or 1.
For example:
| Sample | Trip signal | CB closed | CB open |
|---|---|---|---|
| 1 | 0 | 1 | 0 |
| 2 | 0 | 1 | 0 |
| 3 | 1 | 1 | 0 |
| 4 | 1 | 0 | 1 |
The table illustrates how digital signals can help reconstruct the sequence of protection and breaker operations.
9.1 Digital channels in a disturbance record
A typical line protection disturbance record may contain:
- Distance protection start
- Zone 1 pickup
- Zone 2 pickup
- Trip command
- Breaker trip coil energized
- Breaker open indication
- Auto-reclose start
- Auto-reclose command
- Auto-reclose success
- Teleprotection send
- Teleprotection receive
- Carrier channel failure
- Breaker failure initiation
- Breaker failure operation
These signals allow engineers to understand the relay’s decision-making sequence and determine whether the protection scheme operated correctly.
9.2 Digital channels are not always self-explanatory
Engineers must be careful because:
- The signal name may be vendor-specific.
- A logical 1 may mean asserted, active, or another defined state.
- Some signals may be inverted.
- Contact status may be wired as normally open or normally closed.
- The channel may represent an internal relay logic state rather than an actual physical contact.
- The recording may include filtering or signal delay.
Therefore, digital channels should be interpreted using the relay logic, wiring diagrams, and recorder documentation whenever possible.
10. COMTRADE DAT file formats
The DAT file contains the actual recorded samples. One important difference between COMTRADE revisions is the supported data representation.
10.1 ASCII format
In ASCII format, the data is stored as readable text.
Example:
1,0,120,230,225,1,0,1 2,100,125,235,228,1,0,1 3,200,130,240,232,1,1,1 4,300,135,245,236,0,1,1
A simplified representation of the fields is:
| Column | Description |
|---|---|
| 1 | Sample number |
| 2 | Sample timestamp |
| 3 onwards | Analog channel samples followed by digital states |
The example is illustrative, not a complete dataset. The number of values and their interpretation depend on the channel counts and DAT format specified in the CFG.
Advantages of ASCII:
- Easy to open in a text editor
- Easy to inspect manually
- Convenient for troubleshooting
- Easy to convert into CSV or other formats
- Useful for educational demonstrations
Disadvantages:
- Larger file size
- Slower to load for large datasets
- More storage and processing overhead
- Less efficient for high-speed recording
10.2 BINARY format
Binary format stores data in a compact representation rather than as text.
Advantages include:
- Smaller file size
- Faster reading in suitable software
- Better efficiency for large disturbance records
- Reduced storage requirements
The disadvantage is that the file cannot be interpreted directly using a normal text editor.
The binary data must be decoded according to the COMTRADE standard and the file type declared in the CFG.
10.3 BINARY32 format
The 2013 revision supports BINARY32, a 32-bit integer data representation.
Compared with the older binary representation, this allows a wider range of integer values to be represented, which can be useful where higher-resolution or wider-range recording is required.
10.4 FLOAT32 format
FLOAT32 stores analog values using 32-bit floating-point representation.
This allows samples to be represented directly as floating-point values rather than relying only on integer samples with scaling coefficients.
This is useful in applications where:
- Data is generated by simulation software
- The recording system uses floating-point measurements
- Values may include fractional quantities
- Conversion from integer raw values is not desirable
Important: BINARY32 and FLOAT32 are different. BINARY32 uses 32-bit integer samples, while FLOAT32 uses 32-bit floating-point samples. A parser must not treat these two data types as interchangeable.
10.5 DAT encoding comparison
| Format | Sample representation | Main characteristic |
|---|---|---|
| ASCII | Text numbers | Readable, larger files |
| BINARY | Legacy integer binary | Compact, efficient |
| BINARY32 | 32-bit integer binary | Wider integer representation |
| FLOAT32 | 32-bit floating-point | Fractional real-valued samples |
The availability of a specific data encoding depends on the COMTRADE revision and implementation.
11. Sampling rate and sample timestamps
Sampling information is one of the most critical parts of a disturbance record.
A waveform cannot be analyzed correctly without understanding the relationship between the samples and time.
11.1 What is sampling rate?
Sampling rate represents the number of samples captured per second.
For example:
| Sampling rate | Sampling interval |
|---|---|
| 1,000 samples/s | 1 ms |
| 2,000 samples/s | 500 µs |
| 4,000 samples/s | 250 µs |
| 10,000 samples/s | 100 µs |
| 20,000 samples/s | 50 µs |
The relationship is:
Ts=fs1
Where:
- Ts = sampling interval
- fs = sampling frequency
11.2 Example: 4 kHz sampling
If a recorder samples at 4,000 samples per second:
Ts=40001=0.00025 s
Therefore:
Ts=250 μs
If the record contains 4,000 samples, the duration represented by 4,000 sampling intervals is approximately one second.
11.3 Multiple sampling rates
COMTRADE supports records that may contain multiple sampling-rate sections.
This is important when recording devices use different sampling arrangements or rates across a recording.
For example, a record may have:
| Section | Sampling rate | Number of samples |
|---|---|---|
| Section 1 | 1,000 Hz | 2,000 |
| Section 2 | 4,000 Hz | 8,000 |
A reader must correctly interpret the sampling-rate information and the sample counts associated with each section.
Incorrect interpretation of multiple rates can result in:
- Incorrect waveform duration
- Incorrect time axis
- Distorted waveform display
- Incorrect frequency analysis
- Incorrect calculation of operating times
11.4 Sample number versus timestamp
The sample number is an index that identifies the sample sequence.
The timestamp identifies the time associated with the sample.
These are not interchangeable.
A sample number alone cannot establish absolute time unless the sampling interval and time reference are known.
12. Time information in COMTRADE files
Time information is essential for analyzing power system disturbances. A COMTRADE file may contain both the start time of the record and the trigger time.
12.1 Start time
The start time indicates when the recording began.
The record may include pre-fault samples before the disturbance. This is essential because engineers need to observe the normal operating condition before the fault.
12.2 Trigger time
The trigger time indicates when the recording system triggered the disturbance record.
The trigger is not necessarily the exact instant of fault inception. Depending on the recorder settings, it may be associated with a threshold crossing, protection operation, digital event, or other recording trigger condition.
12.3 Pre-trigger and post-trigger data
A disturbance record typically contains both pre-trigger and post-trigger data.
| Period | Engineering purpose |
|---|---|
| Pre-fault | Determine normal system conditions |
| Fault inception | Observe transient response and fault initiation |
| During fault | Analyze current, voltage, and protection behavior |
| Protection operation | Identify relay trip and output timing |
| Breaker operation | Analyze interruption and current extinction |
| Post-fault | Confirm recovery, reclosing, or abnormal conditions |
The pre-fault portion is particularly useful for calculating load current, voltage, power, and system operating conditions before the fault.
13. Why the 2013 revision improved time information
Older COMTRADE records may provide timestamps without sufficient information to consistently interpret the time reference and synchronization quality across different recording systems.
The 2013 revision introduced additional fields for time-code information, local time offset, time quality, and leap-second information.
These fields help improve the interpretation of timestamps, especially when records from different IEDs or substations must be compared.
13.1 Time zone
Time zone information helps determine whether a timestamp is expressed relative to UTC or local time and how the time offset should be interpreted.
Without appropriate time-zone information, engineers may see different timestamps for the same physical event when comparing records from different devices.
13.2 Time quality
Time quality information provides additional context about the quality or status of the recorded time reference.
It is particularly relevant when comparing events recorded by:
- Different protection relays
- Different disturbance recorders
- Different substations
- GPS-synchronized equipment
- PTP-synchronized systems
- Systems using different time sources
13.3 Time synchronization and fault investigation
Imagine that a fault occurs on a transmission line connected to two substations.
Substation A records:
- Phase A current increase
- Distance protection Zone 1 pickup
- Trip command
- Breaker opening
Substation B records:
- Phase A current increase
- Remote protection operation
- Teleprotection received
- Breaker opening
To investigate the event, the engineer needs to compare the timestamps of both records.
If the recording systems are not properly synchronized, it may be difficult to determine:
- Which protection operated first
- Whether teleprotection was received before the local trip
- The actual sequence of breaker operations
- The time difference between remote and local events
- Whether the protection system behaved as expected
COMTRADE timestamps alone do not guarantee accurate synchronization. The actual quality of the time source and the recorder implementation must also be evaluated.
14. COMTRADE Combined File Format (CFF)
One of the important additions in the 2013 revision is the Combined File Format, with the .CFF extension.
Traditional COMTRADE records use separate files, such as:
- CFG
- DAT
- HDR
- INF
The CFF format combines the contents of the applicable sections into one file.
14.1 Traditional file arrangement
FAULT_001.cfg FAULT_001.dat FAULT_001.hdr FAULT_001.inf
The files are stored separately but share the same base name.
14.2 Combined file arrangement
FAULT_001.cff
The CFF file contains the relevant sections of information corresponding to the traditional files.
The section structure uses identifiers and separators to distinguish the embedded information. The DAT section can use ASCII or an applicable binary encoding.
14.3 Advantages of CFF
- Simplified file management
- Easier sharing of a complete record as one file
- Reduced risk of losing an associated CFG or DAT file
- Convenient transfer through email or document systems
- Easier organization of disturbance records
- Less chance of mismatched filenames
14.4 Limitations
- Older software may not support CFF.
- A CFF file cannot be assumed to be a normal text file throughout.
- The embedded binary data still requires proper decoding.
- Compatibility depends on the software supporting the relevant COMTRADE revision and encoding.
The CFF format does not replace the traditional separate-file arrangement in all systems. Both approaches remain encountered in practical engineering.
15. How a COMTRADE reader interprets the files
A COMTRADE analysis application does not simply open a waveform file and plot the numbers. It must first decode the dataset.
The process can be summarized as follows:
1. Load the COMTRADE datasetCFG + DAT or CFF
2. Identify the COMTRADE revision1991, 1999, or 2013
3. Read the channel configurationAnalog and digital channels, scaling, units and ratios
4. Decode the DAT formatASCII, BINARY, BINARY32, or FLOAT32
5. Convert samples and construct the time axisScaling, offsets, sample rates and timestamps
6. Display and analyze the recordWaveforms, digital signals, phasors and event timing
15.1 Typical waveform processing
The software generally performs the following operations:
- Read the CFG file.
- Identify the number of analog and digital channels.
- Determine the data encoding declared in the configuration.
- Read the DAT file using the appropriate decoder.
- Unpack the analog and digital sample values.
- Apply analog conversion information where applicable.
- Construct the sample time axis.
- Interpret timestamp and synchronization information.
- Display waveforms and digital states.
- Provide tools for waveform analysis, calculations, and exporting.
A mistake in any of these steps can result in an incorrect waveform or incorrect engineering conclusions.
16. Practical example: analyzing a COMTRADE record from a line protection relay
Assume that a transmission line protection relay records the following channels during a fault:
| Channel | Type | Description |
|---|---|---|
| IA | Analog | Phase A current |
| IB | Analog | Phase B current |
| IC | Analog | Phase C current |
| VA | Analog | Phase A voltage |
| VB | Analog | Phase B voltage |
| VC | Analog | Phase C voltage |
| DIST_START | Digital | Distance protection start |
| Z1_TRIP | Digital | Zone 1 trip |
| CB_OPEN | Digital | Breaker open indication |
The engineer receives the COMTRADE files after the event.
Step 1 — Verify the file set
Confirm that the CFG and DAT files are present and correspond to the same record. If a CFF is provided, confirm that the analysis software supports it.
Step 2 — Identify the revision
Check the configuration file for the declared revision.
This is important because the file’s structure and supported data types may differ between revisions.
Step 3 — Verify channel names and units
Confirm that:
- IA, IB, and IC are current channels.
- VA, VB, and VC are voltage channels.
- Digital channels correspond to the expected protection signals.
- The units and conversion factors are correct.
Step 4 — Verify the time axis
Confirm:
- Sampling frequency
- Number of samples
- Start timestamp
- Trigger timestamp
- Time multiplier where applicable
- Any additional time-quality information
Step 5 — Plot analog waveforms
Display the three-phase current and voltage waveforms.
Look for:
- Fault inception
- Current increase
- Voltage depression
- Phase involvement
- Ground fault indications
- DC offset
- Current asymmetry
- Fault clearing
- Post-fault recovery
Step 6 — Compare digital signals
Correlate the analog waveforms with:
- Distance protection start
- Zone 1 trip
- Trip output
- Breaker opening
Step 7 — Evaluate the operation
Determine whether the recorded sequence is consistent with the protection philosophy and expected operating times.
This example illustrates how COMTRADE is used as an engineering tool rather than simply a file format.
17. COMTRADE and protection relay testing
COMTRADE is also widely used during relay testing and commissioning.
An engineer may export a fault record from a simulation, convert or prepare it in a suitable waveform format, and replay the waveforms through a relay test set.
A typical workflow is:
- Obtain or create a COMTRADE disturbance record.
- Verify the channel scaling and units.
- Confirm the time axis and sampling arrangement.
- Check the waveform and digital states.
- Import the file into compatible relay test software.
- Assign the current and voltage channels to test-set outputs.
- Configure the test-set output magnitudes, phase relationships, and replay behavior as supported by the software.
- Replay the waveform into the protection relay.
- Observe protection element response.
- Compare the relay response with the expected operation.
This application is particularly useful for:
- Distance protection testing
- Differential protection testing
- Overcurrent protection testing
- Power swing and out-of-step analysis
- Fault waveform replay
- Protection logic testing
- End-to-end protection investigations
- Post-fault reproduction and troubleshooting
The replay process depends on the capabilities of the test equipment and the selected test software. Not every COMTRADE record can be replayed directly without conversion, channel mapping, or validation.
18. Common COMTRADE problems and mistakes
COMTRADE records may contain errors, inconsistencies, or implementation differences that make analysis difficult.
18.1 Missing files
A traditional COMTRADE record may be incomplete if its CFG or DAT file is missing.
Without the CFG file, the engineer may not have the required information to correctly decode and interpret the DAT samples.
18.2 Incorrect channel scaling
The waveform may look reasonable but have incorrect magnitudes because:
- Scaling coefficient is incorrect
- Offset is incorrect
- Primary/secondary interpretation is wrong
- CT or VT ratio has been applied twice
- The channel unit is misunderstood
18.3 Incorrect sampling-rate interpretation
A wrong sampling rate can make the waveform appear stretched or compressed along the time axis.
This can affect:
- Frequency calculations
- Fault duration
- Relay operating time
- Transient analysis
- Sequence-of-events investigation
18.4 Incorrect timestamp interpretation
Time-related problems may occur because of:
- Unsynchronized clocks
- Incorrect time zone interpretation
- Different time sources
- Incorrect local/UTC conversion
- Time-quality information being ignored
- Incorrect handling of timestamp multipliers
18.5 Unsupported COMTRADE revision
Some older applications may not support all features of the 2013 revision.
For example, a software package may support legacy integer binary data but may not support FLOAT32, BINARY32, or CFF.
18.6 Inconsistent CFG and DAT files
The CFG and DAT files may not belong to the same record.
Possible consequences include:
- Wrong channel values
- Incorrect channel count
- Unexpected sample count
- Invalid timestamps
- Parsing errors
- Misleading waveform display
18.7 Incorrect digital signal interpretation
A digital channel may be interpreted incorrectly because of:
- Inverted logic
- Normally closed contacts
- Incorrect signal naming
- Incorrect wiring
- Internal relay logic versus external contact status
Engineers should always validate important signals against the protection logic and circuit diagrams.
19. COMTRADE format selection: ASCII or Binary?
When exporting a disturbance record, the choice of data format may depend on the intended application.
| Requirement | Recommended consideration |
|---|---|
| Manually inspect file contents | ASCII |
| Share with engineers for troubleshooting | ASCII may be convenient |
| Large disturbance records | Binary may be more efficient |
| High-resolution modern recordings | Consider supported 2013 formats |
| Floating-point simulation data | FLOAT32, if supported |
| Legacy analysis software | Verify compatibility first |
| File transfer and record archiving | Validate the complete dataset |
| Test-set waveform replay | Confirm import and channel compatibility |
There is no universally best option for every application. The most important considerations are interoperability, data integrity, supported revisions, and the requirements of the receiving software.
20. COMTRADE files in modern substation engineering
COMTRADE remains an important engineering format across several areas.
Fault analysisAnalyze fault currents, voltages and fault clearance.
Relay testingReplay recorded waveforms into protection devices.
CommissioningVerify protection behavior and signal timing.
Disturbance investigationReconstruct events and identify abnormal behavior.
COMTRADE files help engineers exchange information between different manufacturers, software platforms, and engineering teams.
This is particularly valuable in multi-vendor substations where protection relays, fault recorders, test systems, and analysis tools may come from different suppliers.
21. Engineering checklist for COMTRADE analysis
Before starting a disturbance investigation, use this checklist.
COMTRADE record verificationConfirm CFG and DAT files belong to the same recordIdentify the COMTRADE revisionConfirm the data encoding typeVerify analog and digital channel countsCheck channel names and descriptionsVerify channel units and scaling coefficientsConfirm CT/VT primary and secondary interpretationCheck sampling rate and sample countVerify start time and trigger timeReview time multiplier and synchronization informationConfirm digital channel polarity and meaningValidate waveform magnitudes before calculationsCheck compatibility with the analysis softwareDocument any assumptions or data inconsistencies
22. Recommended software for COMTRADE analysis
COMTRADE files can be analyzed using different engineering software packages, depending on the application.
Common software and tools
- SIGRA — analysis of fault records and disturbance waveforms.
- OMICRON Test Universe — relay testing and disturbance replay with supported test equipment.
- OMICRON TransView — disturbance record analysis and visualization.
- Wavewin — oscillography and power system fault analysis.
- MATLAB — customized signal processing and waveform analysis.
- Python-based COMTRADE parsers — automated data extraction, conversion, and analysis.
The software selected should be capable of interpreting the required COMTRADE revision and data encoding correctly.
23. Summary: what every protection engineer should know about COMTRADE
COMTRADE is more than a waveform file. It is a standardized structure that combines configuration information, sampled data, timing information, and optional descriptive metadata.
An engineer working with disturbance records should understand the following:
- COMTRADE is used to exchange transient and disturbance data between power system devices and engineering software.
- The traditional dataset consists primarily of a CFG file and a DAT file, with optional HDR and INF files.
- The CFG file defines how the data should be interpreted.
- The DAT file contains the actual sampled data.
- Analog samples may require scaling and conversion.
- Digital channels represent recorded logical states.
- COMTRADE has several revisions, most notably 1991, 1999, and 2013.
- The 2013 revision introduced important enhancements, including additional time information, new data encodings, and CFF.
- ASCII and binary files are not interchangeable without a decoder.
- Sampling rate, sample timestamps, and synchronization are critical to correct analysis.
- COMTRADE records are essential for protection testing, fault analysis, commissioning, and event investigation.
A protection engineer who understands the COMTRADE structure can more effectively investigate relay operations, validate recorded data, replay disturbance waveforms, and perform accurate post-fault analysis.
24. References and further reading
- IEEE C37.111-1999 — Common Format for Transient Data Exchange
- IEC 60255-24:2013 — COMTRADE Standard
- Summary of Changes in the 2013 COMTRADE Standard
- Python COMTRADE parser reference and implementation
25. Elec-Engg: Practical training and technical resources
Understanding the COMTRADE format is an essential skill for engineers working in power system protection, relay testing, commissioning, fault analysis, and substation automation.