SEL-700GW Wind Generator Protection Relay: Functions, Settings and Testing

The SEL-700GW Wind Generator Protection Relay is a numerical protection relay manufactured by Schweitzer Engineering Laboratories (SEL). It is designed for wind-generator applications where two independent sets of feeder overcurrent protection are required.

Unlike comprehensive generator protection relays, which may include generator differential, loss-of-field, voltage, frequency and synchronizing functions, the SEL-700GW focuses on protecting and isolating feeder faults. Its dual-feeder architecture helps improve wind turbine electrical system availability by allowing the relay to supervise two separate three-phase current circuits.

The SEL-700GW is particularly relevant to wind farms, distributed generation installations and applications where a single relay is required to provide protection and programmable control for two feeder circuits.

This guide explains the relay’s applications, protection functions, dual-feeder arrangement, configuration, communication capabilities and practical testing procedures.

SEL-700GW Wind Generator Protection Relay: Complete Guide to Applications, Protection Functions, Settings and Testing

Table Of Contents
  1. 1. What is the SEL-700GW relay?
  2. 2. Typical applications of the SEL-700GW
  3. 3. Understanding the dual-feeder protection arrangement
  4. 4. Main protection functions and ANSI numbers
  5. 5. Programmable logic and control capabilities
  6. 6. Communication and substation automation
  7. 7. Configuration using acSELerator QuickSet
  8. 8. Testing and commissioning of the SEL-700GW
  9. 9. SEL-700GW vs SEL-700GT vs SEL-700G
  10. 10. Common engineering mistakes
  11. 11. Frequently asked questions
  12. 12. Practical protection relay training by Elec-Engg
  13. 13. Official SEL documentation and references

1. What is the SEL-700GW relay?

The SEL-700GW is a wind-generator dual-feeder protection relay.

Its main purpose is to detect electrical faults on either of two protected feeder circuits and initiate the appropriate isolation operation.

The relay has two independent sets of three-phase current inputs:

  • Feeder X: IAX, IBX and ICX.
  • Feeder Y: IAY, IBY and ICY.

This arrangement allows the relay to supervise two three-phase current circuits.

The main protection functions include:

  • Phase overcurrent protection.
  • Ground overcurrent protection.
  • Negative-sequence overcurrent protection.
  • Instantaneous overcurrent protection.
  • Time-overcurrent protection.
  • Breaker failure protection.
  • RTD-based thermal monitoring.
  • Field-ground protection when the appropriate external equipment and options are provided.

The SEL-700GW also provides programmable logic, event recording, metering and communication capabilities.

2. Typical applications of the SEL-700GW

2.1 Wind turbine feeder protection

Wind turbines are connected to the wind farm electrical collection network through individual feeder circuits.

These circuits may connect the turbine generator, converter-associated equipment, step-up transformer and collection system, depending on the turbine architecture.

A fault on a feeder should be detected and isolated without unnecessarily interrupting healthy parts of the wind farm.

The SEL-700GW provides two sets of overcurrent protection elements, allowing the relay to protect two feeder circuits.

2.2 Wind farm electrical distribution

Wind farms typically contain multiple turbines connected through a medium-voltage collection network.

The collection network may use radial or other engineered arrangements, depending on the project.

The SEL-700GW can be applied where two feeder circuits require protection and control using a common relay.

The protection engineer must verify the feeder arrangement, fault-current contribution and required selectivity before selecting the relay.

2.3 Distributed generation

The relay can also be applied in distributed-generation installations where dual-feeder overcurrent protection is required.

Although its product designation refers to wind generation, the important engineering consideration is whether its protection functions, current inputs and control logic meet the actual application requirements.

2.4 Two-feeder protection and control

One of the important characteristics of the SEL-700GW is its ability to supervise two separate three-phase current circuits.

This can reduce the need for separate protection relays in suitable applications.

The two sets of protection elements must nevertheless be configured and tested independently.

3. Understanding the dual-feeder protection arrangement

The SEL-700GW provides six current inputs arranged into two three-phase groups.

Protection circuitCurrent inputs
Feeder XIAX, IBX, ICX
Feeder YIAY, IBY, ICY

Each group can be used to measure the three-phase current of its associated circuit.

The relay applies its configured phase, ground and negative-sequence overcurrent functions to the respective feeder.

For example, consider a wind turbine electrical installation with two protected feeder circuits.

If a phase-to-phase fault occurs on Feeder X, the corresponding overcurrent protection can detect the fault and initiate the configured trip logic.

If a separate fault occurs on Feeder Y, the protection elements associated with that circuit can detect and isolate it.

The objective is to isolate the faulty circuit while maintaining the availability of the healthy circuit, subject to the actual electrical arrangement and switching scheme.

Engineering note: Two sets of current inputs do not automatically mean that the relay provides two independent complete protection systems with separate breakers, trip circuits and control schemes. The trip matrix, binary inputs, output contacts and breaker arrangements must be engineered and tested for the specific installation.

4. Main protection functions and ANSI numbers

4.1 Phase instantaneous overcurrent – ANSI 50P

Phase instantaneous overcurrent protection detects high phase-current magnitudes.

The relay measures the phase currents and compares them with the configured pickup values.

When the measured current exceeds the applicable threshold and the operating conditions are satisfied, the element can initiate a trip.

Typical applications include:

  • Phase-to-phase faults.
  • Three-phase short circuits.
  • High-current feeder faults.
  • Backup protection for associated electrical equipment.

The pickup settings must be coordinated with downstream protection and the available fault current.

4.2 Phase time-overcurrent protection – ANSI 51P

Time-overcurrent protection provides coordination between protective devices.

The operating time depends on the magnitude of the measured current and the selected time-current characteristic.

Typical characteristics include inverse-time curves, depending on the available relay settings.

The engineer must consider:

  • Maximum load current.
  • Transformer inrush.
  • Motor starting current, where relevant.
  • Minimum and maximum fault currents.
  • Downstream fuse and relay coordination.
  • Upstream protection operating times.

The objective is to achieve selective fault isolation without unnecessary disconnection of healthy circuits.

4.3 Ground overcurrent protection – ANSI 50G/51G

Ground overcurrent protection detects earth-fault conditions.

The relay can use the configured ground or residual current measurement arrangement.

Possible fault conditions include:

  • Phase-to-earth faults.
  • Cable insulation failure.
  • Transformer or feeder earth faults.
  • Grounding-system abnormalities.

The engineer must verify the grounding arrangement and the method used to obtain the ground-current measurement.

For example, the residual current may be derived from the three phase currents or obtained using an appropriate core-balance CT arrangement, depending on the application and relay configuration.

Incorrect CT polarity or wiring can cause incorrect residual-current measurements.

4.4 Negative-sequence overcurrent – ANSI 50Q/51Q

Negative-sequence current is associated with unbalanced three-phase conditions.

It can be caused by:

  • Phase-to-phase faults.
  • Open conductors.
  • Unbalanced loads.
  • Unequal phase currents.
  • Abnormal switching conditions.

Negative-sequence overcurrent protection provides another method of detecting unbalanced current conditions.

For rotating machines, negative-sequence current can also produce additional rotor heating. The protection design should therefore consider the protected equipment’s withstand capability and the intended protection zone.

4.5 Breaker failure protection – ANSI 50BF

Breaker failure protection supervises the response of the circuit breaker following a trip command.

A typical sequence is:

  1. The relay detects a fault.
  2. The appropriate protection element initiates a trip.
  3. The relay supervises the breaker response.
  4. If the configured breaker-failure conditions remain satisfied after the timer expires, the relay initiates the backup trip logic.

Breaker failure protection is especially important where a failed breaker could leave a fault connected to the wind farm collection network.

The engineer must check the breaker auxiliary contacts, current supervision and backup trip arrangement.

4.6 RTD-based thermal monitoring – ANSI 49R

The SEL-700GW supports optional RTD-based thermal monitoring.

RTDs can be used to monitor equipment temperature and provide alarm or trip logic according to the application.

Typical monitored points may include:

  • Generator winding temperature.
  • Bearing temperature.
  • Transformer temperature.
  • Other equipment temperature points.

An external SEL-2600 RTD module or the applicable optional RTD input arrangement can be used.

The actual RTD input configuration and supported sensor types should be checked against the ordered hardware.

4.7 Field-ground protection – ANSI 64F

The SEL-700GW documentation identifies field-ground protection as an available option through an external SEL-2664 Field Ground Module.

Field-ground protection is relevant to synchronous generator rotor circuits.

A first field-ground fault may not immediately produce a severe fault current, depending on the excitation system and grounding arrangement. However, a second ground fault at a different location can create an undesirable current path and potentially cause serious rotor damage.

The SEL-2664 provides the external field-ground monitoring function where supported by the selected configuration.

Do not confuse this function with stator ground protection. They protect different parts of the generator.

4.8 Telemetering – ANSI 77

The SEL-700GW documentation identifies telemetering capability.

Telemetering and programmable logic can support remote monitoring and control applications.

Depending on the installed options and engineering configuration, the relay can exchange measurements and status information with external systems.

5. Programmable logic and control capabilities

The SEL-700GW is more than an overcurrent relay.

It includes advanced SELogic control equations that allow engineers to implement application-specific logic.

Typical applications include:

  • Trip and close logic.
  • Breaker status monitoring.
  • Alarm generation.
  • Interlocking.
  • Remote control.
  • Protection element supervision.
  • Event notification.
  • Indication and annunciation.

The relay also provides programmable front-panel LEDs and pushbuttons.

This allows the engineer to configure the front panel to display important operating conditions.

For example, LEDs can be assigned to indicate:

  • Feeder X trip.
  • Feeder Y trip.
  • Phase overcurrent pickup.
  • Ground overcurrent pickup.
  • Negative-sequence protection operation.
  • Breaker failure initiation.
  • Communication alarms.

The exact logic and indication assignments depend on the application.

6. Communication and substation automation

The SEL-700GW provides communication options for integration with wind farm SCADA and control systems.

The published SEL-700GW documentation lists communication capabilities including:

  • SEL ASCII.
  • SEL Mirrored Bits communications.
  • IEC 61850.
  • DNP3 serial.
  • DNP3 LAN/WAN.
  • Modbus RTU.
  • Modbus TCP.
  • SNTP.
  • Telnet.
  • FTP.
  • DeviceNet.
  • IEEE C37.118 synchrophasors.

The available communication media include serial and Ethernet options, with copper and fiber-optic configurations depending on the ordered hardware.

IEC 61850 integration

Where the required IEC 61850 option is installed, the relay can be integrated into a substation automation or wind farm control system.

Typical engineering tasks include:

  1. Confirming the relay’s supported IEC 61850 edition and firmware.
  2. Reviewing the available logical nodes and data objects.
  3. Configuring the communication parameters.
  4. Preparing the required SCL files.
  5. Integrating the relay into the station-level system.
  6. Testing indications and measurements.
  7. Verifying communication and control behavior.

The precise IEC 61850 implementation must be checked against the relay’s applicable documentation.

DNP3 and Modbus integration

DNP3 and Modbus can be used to exchange measurements, alarms and status information with supervisory systems.

The communication engineer should define the required data points, addressing, scaling and control permissions before commissioning.

Event reports and disturbance analysis

The SEL-700GW provides event reports and a Sequential Events Recorder (SER).

These records can help engineers investigate:

  • Feeder faults.
  • Protection element pickup.
  • Trip operations.
  • Breaker status changes.
  • Abnormal operating conditions.

Event reports can be retrieved and analyzed using compatible SEL software.

7. Configuration using acSELerator QuickSet

The SEL-700GW can be configured using acSELerator QuickSet SEL-5030.

QuickSet allows engineers to create, edit, retrieve and manage relay settings.

A typical configuration procedure includes the following steps.

Step 1 – Establish communication

Connect the engineering computer to the relay using an available serial or Ethernet communication port.

Confirm the communication parameters and relay access permissions.

Step 2 – Retrieve existing settings

Read the existing relay configuration and save a backup.

This is particularly important when working with an installed wind farm protection system.

Step 3 – Configure Feeder X

Enter the relevant settings for the first three-phase feeder circuit:

  • CT ratios.
  • Phase overcurrent pickup.
  • Instantaneous overcurrent pickup.
  • Ground overcurrent settings.
  • Negative-sequence overcurrent settings.
  • Time-current characteristics.
  • Operating delays.
  • Trip logic.

Step 4 – Configure Feeder Y

Repeat the engineering process for the second feeder circuit.

Do not assume that both feeders have identical CT ratios, fault levels or protection requirements.

Step 5 – Configure breaker failure logic

Review the breaker-failure initiation conditions, timers, current supervision and backup trip outputs.

Step 6 – Configure inputs and outputs

Assign the binary inputs and output contacts to the required protection and control functions.

Step 7 – Configure communication

Set the required communication protocol and data mapping for the wind farm SCADA system.

Step 8 – Validate the configuration

Review the settings, logic and protection coordination before downloading the final configuration to the relay.

Always retain the approved settings file and a record of the relay firmware revision.

8. Testing and commissioning of the SEL-700GW

Practical testing is essential to confirm that both feeder protection circuits operate correctly.

A suitable secondary-injection test set, such as an OMICRON CMC, can be used to test the configured overcurrent elements.

8.1 Initial inspection

Before injecting test quantities, verify:

  • Relay model and ordering code.
  • Auxiliary supply.
  • Current input wiring.
  • CT ratios.
  • CT polarity.
  • Binary input wiring.
  • Output contact wiring.
  • Breaker trip circuits.
  • Communication connections.
  • Relay settings.

8.2 Current measurement tests

Test Feeder X and Feeder Y separately.

For Feeder X, inject three-phase currents into IAX, IBX and ICX.

For Feeder Y, inject three-phase currents into IAY, IBY and ICY.

Check:

  • Phase current magnitude.
  • Phase identification.
  • Current polarity.
  • Phase sequence.
  • Metering accuracy.

The purpose is to verify that the relay measures the correct current on each protected circuit.

8.3 Phase overcurrent testing

Test the instantaneous and time-overcurrent elements for both feeders.

For each element:

  1. Apply a current below pickup.
  2. Increase the current gradually.
  3. Record the pickup value.
  4. Apply the specified test current.
  5. Measure the operating time.
  6. Verify the assigned trip output.
  7. Confirm reset behavior.

Compare the measured results with the approved relay settings and the manufacturer’s tolerances.

8.4 Ground overcurrent testing

Test the ground overcurrent elements using the actual configured measurement method.

If residual current is calculated from the phase CT inputs, inject the appropriate unbalanced current quantities.

If a separate ground CT input is used, inject the test current through the corresponding circuit.

Check pickup, operating time, reset and trip logic.

8.5 Negative-sequence protection testing

Apply unbalanced three-phase currents to produce the required negative-sequence current.

Verify the pickup threshold and operating time for the configured negative-sequence protection.

Testing should cover both Feeder X and Feeder Y.

8.6 Breaker failure testing

Simulate a trip command and the corresponding breaker response.

Verify:

  • Breaker failure initiation.
  • Current supervision.
  • Timer operation.
  • Reset conditions.
  • Backup trip output.

The complete breaker failure scheme should be tested, including external trip circuits where applicable.

8.7 RTD testing

If RTD inputs are installed, test the temperature measurement and associated alarm or trip logic.

Use suitable resistance simulation or an approved RTD test method.

Verify the scaling, sensor type and alarm thresholds.

8.8 Communication testing

Test the configured communication protocol and confirm that the control system receives the expected information.

Typical checks include:

  • Relay status.
  • Protection pickup indications.
  • Trip indications.
  • Measurements.
  • Alarm points.
  • Event information.
  • Communication failure alarms.

8.9 End-to-end trip testing

Finally, verify the complete protection chain.

A successful relay element test does not automatically confirm that the circuit breaker will trip correctly.

Check the complete sequence from current injection and protection operation through to the breaker trip coil and the corresponding status feedback.

9. SEL-700GW vs SEL-700GT vs SEL-700G

The three relays belong to the SEL-700G product family, but they are intended for different applications.

RelayMain application
SEL-700GSynchronous generator protection
SEL-700GTGenerator intertie protection
SEL-700GWWind generator dual-feeder overcurrent protection

SEL-700G

The SEL-700G is designed for comprehensive generator protection. Depending on the selected model and options, it provides functions such as generator differential protection, loss-of-field protection, voltage and frequency protection, power protection and autosynchronization.

SEL-700GT

The SEL-700GT is designed primarily for intertie protection between a generating facility and the utility network.

Its protection philosophy focuses on grid interconnection requirements and abnormal utility operating conditions.

SEL-700GW

The SEL-700GW focuses on dual-feeder overcurrent protection.

Its six current inputs are arranged as two three-phase groups, allowing the relay to supervise two feeder circuits.

The SEL-700GW should not be treated as a replacement for a comprehensive generator protection relay where functions such as generator differential, loss-of-field or stator ground protection are required.

10. Common engineering mistakes

When applying the SEL-700GW, engineers should pay attention to the following issues:

  1. Confusing the two feeder inputs: Verify the CT wiring and current assignment for Feeder X and Feeder Y.
  2. Using identical settings without assessment: The two feeders may have different fault levels and CT ratios.
  3. Incorrect CT polarity: This can affect measurements and residual-current calculations.
  4. Incorrect ground-current configuration: Confirm whether residual current is derived from phase CTs or measured through a dedicated ground CT arrangement.
  5. Poor protection coordination: Check downstream and upstream time-current characteristics.
  6. Incomplete breaker failure logic: Verify the actual breaker status and current supervision scheme.
  7. Assuming comprehensive generator protection: The SEL-700GW is primarily a dual-feeder overcurrent relay, not a full generator differential protection system.
  8. Assuming all communication options are standard: Confirm the ordered hardware and firmware.
  9. Testing only one feeder: Both three-phase current groups must be tested independently.
  10. Ignoring external equipment: RTD and field-ground functions may require additional hardware.

11. Frequently asked questions

What is the main application of the SEL-700GW?

The SEL-700GW is designed for wind-generator dual-feeder protection. It provides two sets of three-phase overcurrent protection elements to detect and isolate faults on two feeder circuits.

How many current inputs does the SEL-700GW have?

The relay has six current inputs arranged into two three-phase groups: Feeder X and Feeder Y.

Does the SEL-700GW provide differential protection?

The SEL-700GW’s principal published application is dual-feeder overcurrent protection. It should not be selected as a substitute for a dedicated generator differential protection relay without confirming the exact required functions and configuration.

Does the SEL-700GW support IEC 61850?

IEC 61850 is listed among its communication options. Availability depends on the ordered communication hardware and applicable firmware.

Can the SEL-700GW monitor generator temperature?

Yes. Optional RTD-based thermal monitoring is available through the appropriate RTD input arrangement or external SEL-2600 module.

Does the SEL-700GW provide field-ground protection?

Field-ground protection is identified as an option using the external SEL-2664 Field Ground Module. Verify the required hardware and configuration for the specific application.

Which software is used to configure the SEL-700GW?

The relay can be configured using acSELerator QuickSet SEL-5030.

Can the SEL-700GW be tested using OMICRON?

Yes. A suitable OMICRON CMC test set can be used for secondary-injection testing of the configured phase, ground and negative-sequence overcurrent elements, as well as associated control logic.

12. Practical protection relay training by Elec-Engg

At Elec-Engg, we provide practical training for engineers working in power system protection, relay testing and substation automation.

Our training topics include:

  • Protection relay fundamentals.
  • Feeder and generator protection.
  • Overcurrent and directional protection.
  • CT and VT circuits.
  • Relay settings and coordination.
  • Secondary injection testing using OMICRON CMC.
  • SEL relay configuration and commissioning.
  • IEC 61850 and substation automation.

Online training can be arranged based on the required subject and participants’ experience. Customized training for companies and engineering teams is also available.

For course information and training arrangements, visit:

Website: https://elec-engg.com/

Training: Contact Dr. Saeed Roostaee / Elec-Engg.

13. Official SEL documentation and references

For engineering and procurement, always use the applicable instruction manual, data sheet and ordering information for the exact relay revision.

Engineering note: Available protection functions, I/O cards, RTD options and communication protocols depend on the ordered hardware and firmware. Confirm the exact relay configuration before preparing protection settings or procurement specifications.