SEL-700GT Intertie Protection Relay: Functions, Settings and Testing

The SEL-700GT Intertie Protection Relay is part of the SEL-700G family of generator and intertie protection relays manufactured by Schweitzer Engineering Laboratories (SEL). It is designed primarily to protect the electrical connection between a generator or generating facility and the utility power system.

The relay combines voltage, frequency, directional power, overcurrent, synchronism-check and islanding-detection functions. It is particularly relevant to industrial power plants, independent power producers, cogeneration facilities and distributed generation installations that operate in parallel with a utility network.

An important selection detail is that the SEL-700GT and SEL-700GT+ are not identical configurations. The SEL-700GT provides the intertie protection package, while the SEL-700GT+ adds basic generator-protection capabilities and generator synchronism and autosynchronism functions.

This guide explains the relay’s applications, ANSI protection functions, settings considerations, communication capabilities and commissioning tests.

SEL-700GT Intertie Protection Relay: Complete Guide to Applications, Protection Functions, Settings and Testing

Table Of Contents
  1. 1. What is the SEL-700GT relay?
  2. 2. Typical applications
  3. 3. SEL-700GT and SEL-700GT+: important differences
  4. 4. Main protection functions and ANSI numbers
  5. 5. Metering and monitoring
  6. 6. Communication and substation integration
  7. 7. Configuration and settings using SEL QuickSet
  8. 8. Testing and commissioning of the SEL-700GT
  9. 9. SEL-700GT vs SEL-700G vs SEL-400G
  10. 10. Common engineering mistakes
  11. 11. Frequently asked questions
  12. 12. Practical SEL relay training by Elec-Engg
  13. 13. Official SEL documentation and references

1. What is the SEL-700GT relay?

The SEL-700GT is an intertie protection relay intended to supervise and protect the electrical connection between a generator installation and the external power system.

An intertie is the electrical connection through which a generating facility exchanges power with a utility network. Depending on the operating arrangement, the generator may export power, import power, operate in parallel with the utility or disconnect and operate as an island.

The protection system must therefore detect abnormal operating conditions and separate the generating facility from the grid when required.

Typical protection requirements include:

  • Overvoltage and undervoltage protection.
  • Overfrequency and underfrequency protection.
  • Rate-of-change-of-frequency protection.
  • Directional power and reverse-power supervision.
  • Phase and negative-sequence overcurrent protection.
  • Ground-fault and residual-current protection.
  • Vector-shift islanding detection.
  • Breaker failure protection.
  • Tie-breaker synchronism checking.
  • Voltage transformer failure detection.

The SEL-700GT combines these functions in a compact numerical relay with metering, event reporting, programmable logic and communication capabilities.

2. Typical applications

2.1 Industrial generator interconnection

Industrial facilities frequently operate their own generators in parallel with the utility supply. Examples include refineries, petrochemical plants, steel plants, cement factories, mines and large manufacturing facilities.

The SEL-700GT can supervise the interconnection breaker and detect abnormal grid conditions that require the facility to disconnect from the utility.

2.2 Independent power producers (IPP)

Independent power producers export electrical energy to the transmission or distribution network.

Intertie protection is important because the generating plant must comply with the applicable grid connection requirements. These requirements may specify voltage and frequency operating limits, anti-islanding performance, directional power protection and disconnection times.

The actual settings must be based on the utility’s interconnection agreement and the applicable grid code.

2.3 Cogeneration and combined heat and power plants

Cogeneration plants produce electricity and useful heat for industrial processes.

The plant may operate in parallel with the utility while maintaining its own internal electrical distribution system. Intertie protection helps separate the plant from the utility when abnormal network conditions occur.

2.4 Distributed generation

Distributed generation installations may include synchronous generators connected to medium-voltage distribution networks.

The SEL-700GT can provide protection against abnormal voltage, frequency, power-flow and current conditions at the point of interconnection, subject to the project protection philosophy and local requirements.

2.5 Generator tie-breaker protection

The relay can also be applied to supervise a generator tie breaker or utility interconnection breaker. Its synchronism-check function helps prevent closing when the voltage conditions on the two sides of the breaker are outside the configured limits.

3. SEL-700GT and SEL-700GT+: important differences

One of the most important points when selecting this relay is understanding the difference between the standard intertie model and the plus configuration.

ModelMain application
SEL-700GTIntertie protection
SEL-700GT+Intertie protection plus basic generator protection

The standard SEL-700GT includes intertie protection functions such as directional power, voltage, frequency, overcurrent, vector shift, breaker failure and tie synchronism checking.

The SEL-700GT+ adds basic generator protection features based on the SEL-700G0 configuration. It also includes generator synchronism-check, synchroscope and autosynchronism capabilities.

Therefore, if the project requires generator protection in addition to intertie protection, the exact model and ordering code must be checked before procurement.

Important: The SEL-700GT should not be selected as a substitute for a dedicated generator-transformer differential protection relay. Its primary purpose is intertie protection. Transformer differential and comprehensive generator unit protection require an appropriately designed protection arrangement and suitable relay equipment.

4. Main protection functions and ANSI numbers

The following sections explain the principal protection functions associated with the SEL-700GT family. The actual available elements depend on the selected model, hardware and configuration.

4.1 Overvoltage and undervoltage protection – ANSI 27/59

Voltage protection is essential for generator interconnection applications.

The relay monitors the voltage at the interconnection and can detect abnormal voltage conditions.

ANSI 27 – Undervoltage protection

The undervoltage element detects when the measured voltage falls below a configured threshold.

Possible causes include:

  • Utility network faults.
  • Loss of an upstream supply.
  • Heavy system loading.
  • Voltage instability.
  • Abnormal network switching.

ANSI 59 – Overvoltage protection

The overvoltage element detects voltage above the configured operating limit.

Possible causes include:

  • Sudden load rejection.
  • Voltage regulator problems.
  • Abnormal network operating conditions.
  • Incorrect transformer tap or voltage control.

The engineer should coordinate the voltage settings with the utility requirements, generator capability and other plant protection functions.

4.2 Inverse-time voltage protection – ANSI 27I/59I

Inverse-time undervoltage and overvoltage functions provide time-dependent protection.

Instead of operating after a single fixed delay, the operating time varies according to the magnitude of the voltage deviation and the selected characteristic.

These elements can be useful when the interconnection agreement specifies different response times for different voltage ranges.

4.3 Overfrequency and underfrequency protection – ANSI 81O/81U

Frequency protection monitors the system frequency and identifies abnormal operating conditions.

ANSI 81U – Underfrequency

Underfrequency may occur following a generation deficit or a sudden increase in system demand.

ANSI 81O – Overfrequency

Overfrequency may occur following a significant load rejection or generation surplus.

Multiple frequency thresholds and time delays may be required to meet the applicable grid code.

The protection engineer must distinguish between normal frequency excursions, generator operating limits and conditions that require immediate disconnection.

4.4 Rate-of-change-of-frequency protection – ANSI 81R

Rate-of-change-of-frequency (ROCOF) protection measures how quickly the system frequency changes.

It is commonly used as an additional islanding-detection method.

A sudden frequency change may indicate that the generating facility has become electrically separated from the utility network.

ROCOF should not normally be treated as the only islanding-detection method. Its security and dependability must be evaluated under system disturbances, weak-grid conditions and power imbalance scenarios.

4.5 Directional power protection – ANSI 32

Directional power protection measures the direction and magnitude of active power flow.

This function is useful when the generating facility is expected to export power or maintain a defined power-flow condition at the point of interconnection.

Typical applications include:

  • Detecting reverse power flow.
  • Monitoring export and import conditions.
  • Detecting abnormal power exchange.
  • Implementing power-flow restrictions required by the utility.

The engineer must define the relay’s CT and VT polarities and the positive power-flow direction correctly. Incorrect polarity or reference direction can cause the element to operate in the wrong direction.

4.6 Phase overcurrent protection – ANSI 50P/51P

Phase overcurrent protection provides backup protection against excessive phase current.

  • 50P: Instantaneous phase overcurrent.
  • 51P: Time-overcurrent protection, where supported by the selected configuration.

These functions can provide backup protection for interconnection equipment and associated conductors.

The pickup and time-delay settings should be coordinated with downstream feeder protection, transformer protection and the utility protection scheme.

4.7 Negative-sequence overcurrent – ANSI 50Q/51Q

Negative-sequence current indicates unbalanced three-phase operating conditions.

Possible causes include:

  • Phase-to-phase faults.
  • Unbalanced loads.
  • Open conductors.
  • Abnormal switching conditions.
  • Unbalanced network faults.

Negative-sequence protection is important for detecting unbalanced current conditions that may not be adequately represented by positive-sequence measurements alone.

4.8 Ground and residual overcurrent protection – ANSI 50G/51G

Ground and residual overcurrent elements detect earth-fault conditions.

The relay uses the configured current inputs and protection logic to identify abnormal residual or ground current.

The engineer should confirm the grounding arrangement, CT connections and the intended residual-current measurement method before applying these elements.

4.9 Directional overcurrent protection – ANSI 67

Directional overcurrent protection combines current magnitude and direction information.

It is particularly useful in networks where fault current can flow from more than one source.

For example, an industrial facility may receive fault contribution from both the utility and its own generators. Directional protection helps distinguish faults in the intended protection direction from faults outside the protected zone.

4.10 Vector-shift islanding detection – ANSI 78VS

Vector-shift protection detects sudden changes in the phase angle of the measured voltage.

When a generator becomes separated from the utility, the voltage phase angle may change due to the mismatch between generation and load.

The relay can use this condition as an additional islanding-detection method.

Vector-shift settings require careful assessment because network faults, switching operations and other disturbances can also cause phase-angle changes.

4.11 Breaker failure protection – ANSI 50BF

Breaker failure protection supervises the operation of the interconnection circuit breaker.

If a trip command is issued but the breaker fails to interrupt the current within the configured time, the breaker failure logic can initiate an additional trip action.

A typical sequence is:

  1. The relay detects an abnormal condition.
  2. The relay issues a trip command to the interconnection breaker.
  3. The breaker failure logic supervises the breaker response.
  4. If current persists or the configured failure criteria are satisfied, the relay initiates the backup trip scheme.

The exact logic and trip matrix depend on the protection design and breaker arrangement.

4.12 Tie synchronism check – ANSI 25T

Synchronism checking is essential before closing a breaker that connects two energized electrical systems.

The relay checks relevant electrical quantities on both sides of the breaker, including:

  • Voltage magnitude.
  • Frequency difference.
  • Phase-angle difference.

The breaker closing permission is issued only when the configured synchronism conditions are satisfied.

For example, closing a generator intertie breaker without adequate synchronism checking can produce severe electrical and mechanical stresses.

The engineer must configure the voltage inputs and breaker-side measurements correctly.

5. Metering and monitoring

The SEL-700GT provides measurement and monitoring capabilities that support operation, commissioning and fault analysis.

Depending on the selected hardware and configuration, engineers can use the relay to monitor:

  • Phase currents.
  • Phase and system voltages.
  • Frequency.
  • Active power.
  • Reactive power.
  • Power factor.
  • Directional power quantities.
  • Protection element status.
  • Breaker and control status.

These measurements help engineers confirm that the relay is receiving correct CT and VT signals.

The phasor display is particularly useful during commissioning because it allows the engineer to verify current and voltage magnitude, phase angle, polarity and phase rotation.

6. Communication and substation integration

The SEL-700G family supports several communication options. The availability of a specific protocol depends on the ordered communication hardware and firmware.

Published family documentation lists options including:

  • IEC 61850 Edition 2.
  • DNP3 serial and DNP3 LAN/WAN.
  • Modbus RTU and Modbus TCP/IP.
  • IEC 60870-5-103.
  • EtherNet/IP.
  • IEEE 1588 Precision Time Protocol (PTP).
  • Simple Network Time Protocol (SNTP).
  • Parallel Redundancy Protocol (PRP).
  • Rapid Spanning Tree Protocol (RSTP).
  • SEL Mirrored Bits communications.

IEC 61850 integration

Where the appropriate IEC 61850 option is installed, the relay can be integrated into a substation automation system.

Typical engineering activities include:

  1. Reviewing the relay’s IEC 61850 capabilities.
  2. Configuring the required logical nodes and data objects.
  3. Defining the communication parameters.
  4. Preparing and validating the SCL configuration.
  5. Integrating the relay into the station-level system.
  6. Testing indications, measurements and control signals.
  7. Verifying the communication and protection behavior.

The exact logical-node implementation, reporting and control capabilities must be checked against the applicable IEC 61850 conformance documentation and the installed firmware.

7. Configuration and settings using SEL QuickSet

SEL acSELerator QuickSet is used to configure and manage settings for supported SEL protection relays.

A typical engineering workflow includes:

Step 1 – Establish communication

Connect to the relay using an available communication port and the appropriate communication settings.

Step 2 – Retrieve the relay configuration

Read the existing relay settings and save a backup before making changes.

Step 3 – Configure system parameters

Enter the required information, including:

  • Nominal frequency.
  • CT ratios.
  • VT ratios.
  • Phase rotation.
  • Current and voltage input assignments.
  • Breaker and interconnection information.

Step 4 – Configure protection elements

Set the pickup values, operating characteristics, time delays and directional references according to the approved protection study.

Step 5 – Configure control logic

Review the trip logic, breaker failure scheme, synchronism-check conditions, alarms and output contacts.

Step 6 – Verify communication

Configure the required protocols and communication parameters for the station control system.

Step 7 – Validate and document

Save the final settings, review the logic and prepare the approved settings file and commissioning documentation.

Always verify the relay’s actual model, firmware and available settings before applying a configuration prepared for another SEL-700G family model.

8. Testing and commissioning of the SEL-700GT

Testing is essential to confirm that the relay operates correctly and that the intertie protection scheme meets the project requirements.

OMICRON CMC test equipment and other suitable secondary-injection systems can be used to test the configured protection functions.

8.1 Initial inspection

Before testing, verify:

  • Relay model and ordering code.
  • Auxiliary supply voltage.
  • CT and VT wiring.
  • CT polarity and ratio.
  • VT polarity and phase sequence.
  • Binary input wiring.
  • Output contact wiring.
  • Communication connections.
  • Relay settings and firmware.

8.2 Current and voltage measurement tests

Inject balanced three-phase currents and voltages.

Check:

  • Current magnitude.
  • Voltage magnitude.
  • Phase sequence.
  • Phase angles.
  • Active and reactive power.
  • Power factor.
  • Direction of power flow.

Incorrect CT or VT polarity can cause serious problems in directional protection and synchronism-check applications.

8.3 Overvoltage and undervoltage tests

Test the configured voltage protection elements.

For each element:

  1. Apply nominal voltage.
  2. Reduce or increase the voltage gradually.
  3. Verify the pickup value.
  4. Measure the operating time.
  5. Check the output contact and event record.
  6. Confirm reset behavior.

8.4 Frequency protection tests

Use a test set capable of generating controlled frequency variations.

Test the configured underfrequency and overfrequency thresholds, operating delays and reset conditions.

For ROCOF protection, apply suitable frequency ramps and verify the measured rate of change.

8.5 Directional power tests

Directional power testing requires controlled voltage and current injection with appropriate phase-angle relationships.

Verify:

  • Forward power operation.
  • Reverse power operation.
  • Pickup and dropout.
  • Directional reference.
  • Operating time.
  • Output logic.

8.6 Overcurrent protection tests

Test the phase, negative-sequence and ground/residual overcurrent functions that are enabled in the application.

Check the pickup values and operating times against the approved settings.

8.7 Vector-shift tests

Apply a controlled phase-angle change to the voltage signals and verify the configured vector-shift element.

The test should also confirm that the element does not operate incorrectly under the expected normal operating conditions.

8.8 Synchronism-check tests

Synchronism-check testing should include different combinations of:

  • Voltage difference.
  • Frequency difference.
  • Phase-angle difference.

Verify that the relay permits closing only when the configured conditions are satisfied.

Also test the blocking conditions and the associated breaker-close logic.

8.9 Breaker failure tests

Simulate a breaker trip command while maintaining the relevant current or failure supervision conditions.

Confirm the breaker failure timer, initiation logic and backup trip output.

8.10 End-to-end scheme testing

For a complete interconnection scheme, testing should not stop at the relay terminals.

Verify the full trip path, including:

  • Relay trip output.
  • Interposing relays, if installed.
  • Circuit-breaker trip coil.
  • Breaker auxiliary contacts.
  • Breaker failure logic.
  • Alarm and annunciation circuits.
  • SCADA indications.

The final commissioning report should record the test conditions, injected quantities, pickup values, measured operating times and pass/fail results.

9. SEL-700GT vs SEL-700G vs SEL-400G

These relays belong to SEL’s generator protection portfolio, but they address different protection requirements.

RelayMain application
SEL-700GTGenerator intertie protection
SEL-700GT+Intertie plus basic generator protection
SEL-700GGenerator protection
SEL-400GAdvanced generator protection system

The SEL-700G is intended for comprehensive generator protection and offers options such as generator differential protection and autosynchronization.

The SEL-400G is a more advanced generator protection platform with extensive generator and generator step-up transformer protection capabilities.

The SEL-700GT is a better fit when the main requirement is protection of the utility interconnection rather than comprehensive generator unit protection.

The final selection should be based on a protection-function matrix, I/O requirements, communication requirements, redundancy philosophy and the applicable grid connection requirements.

10. Common engineering mistakes

When configuring and commissioning an intertie protection relay, engineers should pay particular attention to the following issues:

  1. Incorrect CT polarity: This can reverse the measured power direction and affect directional protection.
  2. Incorrect VT phase sequence: This can affect voltage measurement, power calculation and synchronism checking.
  3. Uncoordinated frequency settings: Frequency thresholds and delays must comply with the applicable grid code.
  4. Incorrect ROCOF settings: Poorly selected settings may cause unwanted operation during network disturbances.
  5. Insufficient islanding assessment: Vector shift and ROCOF should be evaluated for the actual grid strength and generation/load conditions.
  6. Incorrect breaker failure logic: The scheme must account for the actual breaker auxiliary contacts and current supervision.
  7. Assuming GT and GT+ are identical: Their protection functions are different.
  8. Assuming every communication protocol is standard: Hardware and firmware options must be checked.
  9. Incomplete trip-circuit testing: The complete trip path should be verified, not just the relay output.

11. Frequently asked questions

What is the main application of the SEL-700GT?

The SEL-700GT is primarily used for generator intertie protection. It supervises the electrical connection between a generating facility and the utility network.

What is the difference between SEL-700GT and SEL-700GT+?

The SEL-700GT provides the intertie protection package. The SEL-700GT+ adds basic generator protection functions and generator synchronism-check and autosynchronism capabilities.

Does the SEL-700GT provide generator differential protection?

The standard SEL-700GT intertie configuration should not be treated as a generator differential relay. If generator differential protection is required, check the SEL-700GT+ configuration and the applicable protection-function documentation carefully, or select a suitable dedicated generator protection relay.

Does the SEL-700GT support IEC 61850?

IEC 61850 is listed among the SEL-700G family communication options. Its availability depends on the ordered communication option and firmware. Verify the exact relay configuration and applicable conformance documents.

Can the SEL-700GT detect islanding?

Yes. The intertie protection package includes vector-shift and frequency-related protection functions that can support islanding detection. The complete anti-islanding scheme must be engineered to meet the utility’s requirements.

Can the SEL-700GT perform synchronism checking?

Yes. The intertie model includes tie synchronism-check functionality. The SEL-700GT+ also includes generator synchronism-check and autosynchronism functions.

Which software is used to configure the SEL-700GT?

SEL acSELerator QuickSet is used for relay settings and SELogic control configuration.

Can the SEL-700GT be tested using OMICRON?

Yes. Suitable OMICRON CMC test equipment can be used for secondary-injection testing of the configured protection functions, provided the test plan and test modules support the required elements.

12. Practical SEL relay training by Elec-Engg

Understanding a numerical protection relay requires more than knowing its ANSI function numbers. Engineers should understand the complete measurement, protection, logic, communication and circuit-breaker trip chain.

At Elec-Engg, practical training is available for engineers working with power system protection and substation automation.

Training topics include:

  • Protection relay fundamentals and applications.
  • CT and VT circuits and polarity verification.
  • Overcurrent and directional protection.
  • Generator and intertie protection.
  • Relay settings and coordination.
  • Secondary injection testing using OMICRON CMC.
  • SEL relay configuration and commissioning.
  • IEC 61850 and substation automation.

Online training can be arranged based on the required subject and the participants’ experience. Customized training can also be discussed for companies and engineering teams.

For course details and training arrangements, visit Elec-Engg or contact Dr. Saeed Roostaee.

Website: https://elec-engg.com/

13. Official SEL documentation and references

For detailed technical information, always refer to the official SEL documentation and the instruction manual for the exact relay revision.

Engineering note: Protection functions, communication protocols and hardware options can vary by model suffix, ordering code and firmware revision. Confirm the exact SEL-700GT or SEL-700GT+ configuration before preparing settings or a procurement specification.