ABB RED670 Line Differential Protection Relay – Complete Technical Guide

ABB RED670 Line Differential Protection Relay
Table Of Contents
  1. 1. Introduction to ABB RED670
  2. 2. Main Applications of ABB RED670
  3. 3. ABB RED670 Hardware and Preconfigured Applications
  4. 4. Main Protection Functions of ABB RED670
  5. 5. Line Differential Protection – ANSI 87L
  6. 6. Line Differential Protection Communication Channel
  7. 7. Distance Protection – ANSI 21
  8. 8. Earth-Fault Protection and Directional Overcurrent Protection
  9. 9. Phase Overcurrent Protection – ANSI 50/51
  10. 10. Autoreclosing – ANSI 79
  11. 11. Synchronism Check – ANSI 25
  12. 12. Breaker Failure Protection – ANSI 50BF
  13. 13. Power Swing Blocking and Out-of-Step Protection
  14. 14. Fault Locator and Disturbance Recording
  15. 15. PCM600 Configuration of ABB RED670
  16. 16. IEC 61850 Communication in ABB RED670
  17. 17. Testing and Commissioning of ABB RED670
  18. 18. Common Problems and Troubleshooting
  19. 19. ABB RED670 Compared with Other ABB Protection Relays
  20. 20. Frequently Asked Questions About ABB RED670
  21. 21. Conclusion

ABB RED670: Applications, Line Differential Protection, Distance Protection, Protection Functions, PCM600 Configuration, IEC 61850 and Commissioning

ABB RED670 Line Differential Protection Relay – Complete Technical Guide

1. Introduction to ABB RED670

The ABB RED670 is a numerical line differential protection and control intelligent electronic device (IED) belonging to ABB’s Relion 670 series.

It is designed primarily for the protection of overhead transmission lines and underground power cables in high-voltage and extra-high-voltage electrical networks.

Transmission lines are critical components of electrical power systems. Faults such as phase-to-phase faults, phase-to-earth faults and three-phase short circuits must be detected and cleared rapidly to maintain power system stability and minimize equipment damage.

Line differential protection is one of the most selective and reliable protection principles for transmission lines. It compares the currents measured at different ends of a protected line and determines whether a fault is located inside or outside the protection zone.

The ABB RED670 uses differential protection with communication between the line terminals to provide fast and selective fault detection.

Depending on the selected configuration, RED670 can also provide distance protection, overcurrent protection, earth-fault protection, autoreclosing, breaker failure protection, power swing detection and other supplementary protection functions.

Typical applications include:

  • High-voltage transmission lines.
  • Extra-high-voltage transmission lines.
  • Underground power cables.
  • Two-terminal transmission lines.
  • Three-terminal transmission lines.
  • Multi-terminal transmission systems.
  • Transmission lines with in-zone transformers.
  • Single-breaker and multi-breaker substation arrangements.

The RED670 is particularly suitable for applications where high-speed and selective line protection is required.

2. Main Applications of ABB RED670

The RED670 can be applied in different transmission network configurations.

2.1 Two-Terminal Transmission Lines

In a conventional two-terminal line, protection IEDs are installed at both ends of the transmission line.

Each RED670 measures the local three-phase currents and exchanges current information with the remote terminal through a communication channel.

The differential protection function compares the currents from both ends to determine whether a fault is inside the protected line section.

2.2 Three-Terminal Transmission Lines

Three-terminal lines have three connected electrical terminals.

A differential protection scheme must consider current contributions from all terminals.

RED670 supports multi-terminal line differential applications through the appropriate differential protection function and configuration.

2.3 Multi-Terminal Transmission Lines

Some transmission networks contain more than three line terminals.

The RED670 product documentation describes configurations supporting line differential protection with multiple CT sets and terminals, including applications with up to five line ends in the relevant six-CT arrangement.

The actual arrangement and supported topology must be verified against the ordered product version.

2.4 Underground Cable Protection

Line differential protection is also suitable for underground power cables.

Because the differential principle compares currents entering and leaving the protected cable zone, it provides selective protection for internal cable faults.

2.5 Transmission Lines with In-Zone Transformers

Some transmission line applications include transformers within the differential protection zone.

RED670 provides specific differential protection functions for these arrangements, with appropriate compensation for the transformer and protected-zone configuration.

3. ABB RED670 Hardware and Preconfigured Applications

ABB offers different preconfigured RED670 application packages.

The documented Relion 670 Version 2.2 configurations include:

A42 – Single Breaker Application

This configuration is intended for single-breaker arrangements and supports single-phase or three-phase tripping according to the selected application.

B33 – Multi-Breaker Application

This configuration is designed for multi-breaker arrangements, such as one-and-a-half breaker and ring-bus substations.

B42 – Multi-Breaker Application

This is another multi-breaker arrangement with associated breaker control and protection logic.

C42 – Single Breaker with Backup Distance Protection

This configuration includes backup distance protection in addition to line differential protection.

The actual configuration names, analog inputs, binary I/O and available functions must be checked against the relevant product guide and ordering code.

4. Main Protection Functions of ABB RED670

The RED670 includes several protection functions for line protection and backup applications.

Important functions include:

ANSI codeProtection functionDescription
87LLine differential protectionDetects internal faults within the transmission line zone
21Distance protectionDetects faults using measured impedance
50/51Phase overcurrent protectionProvides short-circuit backup protection
50N/51NEarth-fault overcurrent protectionDetects earth faults
67/67NDirectional overcurrent protectionProvides directional phase and earth-fault protection
79AutoreclosingAutomatically recloses circuit breakers
50BFBreaker failure protectionDetects failure of circuit breaker interruption
25Synchronism checkVerifies synchronism before closing
68Power swing blockingPrevents unwanted distance protection operation during power swings
78Out-of-step protectionDetects loss of synchronism
27Undervoltage protectionDetects low voltage
59Overvoltage protectionDetects excessive voltage
81Frequency protectionDetects abnormal frequency
85Teleprotection and scheme communicationSupports communication-assisted protection schemes
74Trip circuit supervisionMonitors circuit breaker trip circuit integrity

Not every function is available in every ordering configuration. Function quantities and features depend on the product version and selected application package.

5. Line Differential Protection – ANSI 87L

Line differential protection is the main protection function of ABB RED670.

The relay provides dedicated line differential protection functions, including:

  • L3CPDIF – Line differential protection using three CT sets, for two- or three-terminal applications.
  • L6CPDIF – Line differential protection using six CT sets, for multi-terminal applications.
  • LT3CPDIF – Line differential protection using three CT sets with in-zone transformers.
  • LT6CPDIF – Line differential protection using six CT sets with in-zone transformers.

The available alternatives depend on the product version and configuration.

5.1 Operating Principle

Line differential protection is based on Kirchhoff’s current law.

Under normal operating conditions, the vector sum of the currents entering and leaving the protected line zone should be approximately zero.

For an internal fault, the current balance is disturbed and the differential current increases.

A simplified differential current equation for a two-terminal line is:

I_diff = |I_A + I_B|

Here, the currents are expressed using a consistent reference direction, with currents entering the protected zone considered positive.

For an external fault, the current entering the zone should approximately equal the current leaving it.

For an internal fault, the difference between the terminal currents becomes significant.

The RED670 exchanges current information between the protection terminals and evaluates the differential protection characteristic.

5.2 Current Measurement and Synchronization

Accurate current measurement and correct alignment of terminal information are essential for line differential protection.

The relay must receive valid current information from the remote terminal.

Communication delays, channel failures and measurement errors must be supervised to maintain protection security.

5.3 Differential Restraint and Stability

The differential protection must remain stable during external faults, load conditions and communication disturbances.

The operating characteristic includes stabilization features to prevent unwanted operation caused by measurement errors and other non-fault conditions.

5.4 Multi-Terminal Line Differential Protection

In multi-terminal applications, current contributions from every connected terminal must be considered.

For a line with several terminals, the differential current is determined by the vector sum of all terminal currents.

This makes line differential protection suitable for complex transmission line arrangements when the communication and protection architecture are properly engineered.

6. Line Differential Protection Communication Channel

Communication is essential for line differential protection.

RED670 exchanges current measurement information with the remote protection IEDs through a suitable communication channel.

Typical communication arrangements include:

  • Direct fiber-optic connections.
  • Multiplexed telecommunication channels.
  • Optical communication networks.
  • Dedicated protection communication infrastructure.

The communication architecture must provide adequate bandwidth, low and predictable delay, availability and reliable channel supervision.

6.1 Fiber-Optic Communication

Fiber-optic communication is widely used in transmission line protection because it provides:

  • Electrical isolation.
  • Immunity to electromagnetic interference.
  • Long-distance communication capability.
  • High communication reliability.
  • Suitable bandwidth for protection applications.

6.2 Communication Channel Supervision

The RED670 supervises the communication channel used for differential protection.

If the communication channel becomes unavailable or unreliable, the protection system must respond according to the configured application philosophy.

Engineers should verify:

  • Communication channel availability.
  • Remote terminal identification.
  • Channel delay and asymmetry.
  • Communication errors.
  • Channel failure alarms.
  • Local and remote test modes.

7. Distance Protection – ANSI 21

In addition to line differential protection, RED670 supports distance protection functions in applicable configurations.

Distance protection is an important backup protection method for transmission lines.

It measures the apparent impedance between the relay location and the fault.

The basic impedance equation is:

Z = V / I

Where:

  • Z is measured impedance.
  • V is measured voltage.
  • I is measured current.

The relay evaluates the measured impedance against configured protection zones.

7.1 Distance Protection Zones

Typical distance protection arrangements include:

  • Zone 1 – Fast protection for a major part of the protected line.
  • Zone 2 – Time-delayed protection extending beyond the protected line.
  • Zone 3 – Remote backup protection for additional network sections.

The actual zone reach and timing must be calculated according to the line impedance, network topology and protection coordination requirements.

7.2 Distance Protection Characteristics

RED670 provides different distance protection characteristics depending on the selected functions and product configuration.

These can include:

  • Quadrilateral characteristics.
  • Mho characteristics.
  • Phase fault measuring elements.
  • Earth-fault measuring elements.
  • Series-compensated line applications.

Important engineering considerations include:

  • Line impedance.
  • Positive- and zero-sequence parameters.
  • Mutual coupling.
  • Load encroachment.
  • Power swing conditions.
  • Fault resistance.
  • Infeed and outfeed effects.

8. Earth-Fault Protection and Directional Overcurrent Protection

Earth faults are common transmission line faults.

The RED670 includes earth-fault protection functions that can provide backup and supplementary protection.

Directional earth-fault protection is particularly useful in networks where fault current direction must be determined.

Important considerations include:

  • Network grounding arrangement.
  • Zero-sequence current.
  • Residual voltage.
  • Polarizing quantities.
  • Directional characteristic.
  • Fault resistance.
  • Protection coordination.

The available functions and their application depend on the selected configuration.

9. Phase Overcurrent Protection – ANSI 50/51

Phase overcurrent protection provides backup protection for phase-to-phase and three-phase faults.

The RED670 can be configured with instantaneous and time-delayed overcurrent functions.

Typical applications include:

  • Backup protection for line differential protection.
  • Backup protection for distance protection.
  • Circuit breaker protection.
  • Short-circuit protection.
  • Protection coordination with adjacent feeders.

The settings must be coordinated with the network fault levels, CT ratios and downstream protection devices.

10. Autoreclosing – ANSI 79

Autoreclosing is widely used in overhead transmission line protection.

Many overhead line faults are temporary and may disappear after the circuit breaker opens.

Examples include:

  • Lightning-related flashovers.
  • Temporary conductor contact.
  • Transient insulation breakdown.
  • Temporary external interference.

Autoreclosing allows the circuit breaker to automatically close after a predefined dead time.

The RED670 provides autoreclosing functionality through the RREC function in applicable configurations.

10.1 Single-Phase Autoreclosing

Single-phase autoreclosing is commonly applied in transmission networks where single-phase tripping is supported.

Only the faulted phase is disconnected, while the healthy phases remain in service.

10.2 Three-Phase Autoreclosing

Three-phase autoreclosing disconnects all three phases and attempts to restore the line after the configured dead time.

10.3 Autoreclosing Coordination

Autoreclosing must be coordinated with:

  • Line differential protection.
  • Distance protection.
  • Circuit breaker operating times.
  • Synchronism check.
  • Dead-line and live-line conditions.
  • Permanent fault detection.
  • Protection trip logic.

11. Synchronism Check – ANSI 25

Synchronism check protection verifies electrical conditions before a circuit breaker is closed.

The purpose is to avoid closing a breaker when the voltage difference, phase angle or frequency difference between the two sides is outside acceptable limits.

The RED670 supports synchronism check functions through the appropriate application configuration.

Typical checks include:

  • Voltage difference.
  • Frequency difference.
  • Phase angle difference.
  • Live-bus and dead-line conditions.
  • Live-line and dead-bus conditions.

Synchronism check is especially important in autoreclosing applications and transmission network restoration.

12. Breaker Failure Protection – ANSI 50BF

Breaker failure protection detects unsuccessful circuit breaker interruption.

For example, when line differential protection detects an internal line fault, the relay sends a trip command to the circuit breaker.

If the breaker fails to interrupt the fault current, breaker failure protection initiates backup tripping.

The RED670 includes circuit breaker failure protection functions in applicable configurations.

Important settings include:

  • Breaker failure initiation.
  • Current detection.
  • Breaker auxiliary contact supervision.
  • Retrip logic.
  • Backup trip timing.
  • Busbar or adjacent breaker trip signals.

13. Power Swing Blocking and Out-of-Step Protection

Power swings can occur after disturbances such as:

  • Large generator outages.
  • Transmission line faults.
  • Loss of generation.
  • Major switching operations.
  • Severe power system disturbances.

During a power swing, the apparent impedance measured by distance protection may enter a protection zone even though no short-circuit fault exists.

Power swing blocking helps prevent unwanted distance protection operation during stable power swings.

RED670 provides power swing-related functions, including detection and blocking logic in applicable configurations.

Out-of-step protection can detect unstable power swings and initiate appropriate separation actions.

14. Fault Locator and Disturbance Recording

Fault location is an important feature for transmission line maintenance and restoration.

The RED670 provides fault location and disturbance recording capabilities in applicable configurations.

14.1 Fault Locator

The fault locator estimates the distance to the fault based on measured electrical quantities and line parameters.

This information can help maintenance teams identify the approximate fault location and reduce restoration time.

Important data include:

  • Line length.
  • Positive-sequence impedance.
  • Zero-sequence impedance.
  • Fault type.
  • Measured voltage.
  • Measured current.
  • System operating conditions.

14.2 Disturbance Recording

Disturbance recording captures electrical quantities and binary signals during system disturbances.

Engineers can use these records to investigate:

  • Fault current behavior.
  • Protection operation.
  • Breaker tripping.
  • Autoreclosing sequences.
  • Communication problems.
  • Unexpected protection operations.

Disturbance analysis is an important part of transmission protection engineering.

15. PCM600 Configuration of ABB RED670

PCM600 (Protection and Control IED Manager) is ABB’s engineering software for supported Relion protection and control IEDs.

It is used to configure and manage the RED670.

Important engineering activities include:

  1. Creating a new PCM600 project.
  2. Adding the RED670 IED.
  3. Selecting the correct product version.
  4. Installing the required connectivity package.
  5. Establishing communication with the relay.
  6. Reading and managing the IED configuration.
  7. Configuring line differential protection.
  8. Configuring distance protection.
  9. Configuring overcurrent and earth-fault protection.
  10. Configuring autoreclosing.
  11. Developing trip and interlocking logic.
  12. Engineering IEC 61850 communication.
  13. Downloading and verifying the configuration.

15.1 Line Differential Configuration

The engineer must configure the appropriate differential protection function according to the number of line terminals and the selected application.

Important engineering data include:

  • Number of line ends.
  • CT ratios.
  • Current measurement connections.
  • Remote terminal configuration.
  • Communication channel settings.
  • Differential protection parameters.
  • Protected zone arrangement.

15.2 Application Configuration

Application configuration defines the interaction between protection functions, communication signals, binary inputs and outputs.

For example, line differential protection can be connected to:

  • Local circuit breaker trip.
  • Remote trip logic, where required.
  • Breaker failure initiation.
  • Autoreclosing initiation.
  • Alarm signals.
  • Disturbance recording.

The complete logic must be verified before placing the protection system into service.

16. IEC 61850 Communication in ABB RED670

IEC 61850 is widely used in modern transmission substations.

The RED670 supports IEC 61850 communication for integration with other protection IEDs, bay controllers, station controllers and SCADA systems.

16.1 MMS Communication

MMS provides client-server communication for monitoring, reporting and control applications.

Typical uses include:

  • Monitoring line protection status.
  • Reading measurements.
  • Receiving alarms and events.
  • Supervisory control.
  • Retrieving disturbance information.

16.2 GOOSE Communication

GOOSE provides fast peer-to-peer communication between IEDs.

Typical applications include:

  • Breaker interlocking.
  • Protection trip signals.
  • Breaker failure transfer signals.
  • Blocking signals.
  • Inter-IED protection logic.
  • Substation automation.

16.3 IEC 61850 SCL Engineering

Important SCL file types include:

  • ICD – IED Capability Description.
  • CID – Configured IED Description.
  • SCD – Substation Configuration Description.
  • SSD – System Specification Description.
  • IID – Instantiated IED Description.

The actual IEC 61850 edition and communication services must be verified against the particular RED670 product version.

ABB RED670 Line Differential Protection Relay

17. Testing and Commissioning of ABB RED670

Testing and commissioning are essential before placing a transmission line protection system into service.

The engineer must verify the complete measurement, protection, communication and circuit breaker tripping arrangements.

Typical commissioning activities include:

TestPurpose
Visual inspectionVerify relay installation and hardware
Auxiliary supply testVerify DC supply and supervision
CT circuit testVerify CT ratio, polarity and wiring
VT circuit testVerify voltage measurement and phase sequence
Differential protection testVerify line differential characteristics
Communication channel testVerify local and remote communication
Remote terminal testVerify current exchange and terminal identification
Distance protection testVerify impedance characteristics
Overcurrent testVerify phase and earth-fault backup
Directional protection testVerify directional operation
Autoreclosing testVerify dead time and reclosing logic
Synchronism check testVerify voltage and phase-angle supervision
Breaker failure testVerify 50BF operation
Trip circuit testVerify complete circuit breaker tripping
IEC 61850 testVerify MMS and GOOSE communication
Disturbance recording testVerify fault recording

OMICRON CMC test equipment and Test Universe can be used for secondary injection testing and verification of protection characteristics.

For line differential protection, testing should also consider the remote terminal and communication channel.

The final test procedure must follow the approved protection design, ABB documentation and transmission system commissioning requirements.

18. Common Problems and Troubleshooting

18.1 Line Differential Protection Communication Failure

Possible causes:

  • Fiber-optic cable problems.
  • Incorrect communication channel configuration.
  • Communication equipment failure.
  • Incorrect remote terminal identification.
  • Excessive channel delay.
  • Incorrect communication interface configuration.

18.2 Incorrect Differential Current

Check:

  • CT polarity.
  • CT ratios.
  • Phase mapping.
  • Current measurement connections.
  • Remote terminal data.
  • Communication channel supervision.

18.3 Unexpected Differential Protection Operation

Investigate:

  • Disturbance records.
  • Differential current.
  • Restraint current.
  • CT saturation.
  • Communication errors.
  • Protection settings.
  • Application configuration.

18.4 Distance Protection Maloperation

Check:

  • Line impedance settings.
  • CT and VT ratios.
  • Voltage measurement.
  • Fault resistance.
  • Load encroachment.
  • Power swing conditions.
  • Directional supervision.
  • Protection zone reach.

18.5 Autoreclosing Problems

Check:

  • Autoreclosing initiation.
  • Circuit breaker status.
  • Dead time.
  • Synchronism check.
  • Dead-line and live-bus conditions.
  • Reclaim time.
  • Lockout conditions.

18.6 PCM600 Connectivity Problems

Check:

  • Correct connectivity package.
  • Product version.
  • Communication interface.
  • IP settings.
  • IED configuration.
  • Firmware compatibility.

19. ABB RED670 Compared with Other ABB Protection Relays

ABB provides different protection products for transmission line and feeder applications.

RelayGeneral application
RED670Comprehensive line differential protection
REL670Distance and line protection
REL650Line distance protection
RED650Line differential protection
REF615Feeder protection
REF620Feeder protection

The selection depends on the required protection principle, transmission line arrangement, number of terminals, communication infrastructure and project specifications.

RED670 is particularly relevant when line differential protection is required for high-voltage transmission applications.

20. Frequently Asked Questions About ABB RED670

What is ABB RED670 used for?

ABB RED670 is a numerical line differential protection and control relay used primarily for overhead transmission lines and underground cables.

What is the main protection function of RED670?

Its main protection function is line differential protection (ANSI 87L).

Does RED670 support multi-terminal line differential protection?

Yes. Depending on the selected differential function and configuration, RED670 supports multi-terminal applications, including arrangements with up to five line ends in the relevant product configuration.

Does RED670 support distance protection?

Yes. Distance protection is available in applicable configurations and can provide backup protection.

Does RED670 support autoreclosing?

Yes. Autoreclosing functionality is available through the RREC function in applicable configurations.

Does RED670 support IEC 61850?

Yes. RED670 supports IEC 61850 communication, including applicable MMS and GOOSE services.

Which software is used to configure ABB RED670?

PCM600 is the engineering software used for supported RED670 product versions.

Can RED670 protect underground cables?

Yes. Line differential protection can be applied to underground cables, subject to the selected protection configuration and communication architecture.

Can RED670 be tested using OMICRON CMC?

Yes. OMICRON CMC test equipment can be used for secondary injection testing and protection function verification. Line differential testing must also consider remote terminal and communication channel requirements.

21. Conclusion

The ABB RED670 is a comprehensive numerical line differential protection IED designed for high-voltage transmission lines and underground cable applications.

Its line differential protection, distance backup, overcurrent protection, autoreclosing, breaker failure protection, power swing functions and IEC 61850 communication capabilities make it suitable for a wide range of transmission network protection schemes.

For protection engineers, commissioning engineers and substation automation specialists, understanding RED670 requires knowledge of line differential protection, communication-assisted protection, distance protection, autoreclosing, CT and VT circuits, PCM600 engineering and IEC 61850 communication.

Elec-Engg provides practical technical training in power system protection, numerical protection relays, line protection, relay testing and substation automation.

Related Elec-Engg Topics:

  • Transmission Line Protection Fundamentals.
  • Line Differential Protection.
  • Distance Protection and Impedance Characteristics.
  • Autoreclosing and Synchronism Check.
  • ABB PCM600 Engineering.
  • IEC 61850 Engineering and Configuration.
  • Protection Relay Testing and Commissioning.

Technical references:

  • ABB Relion 670 Series – Line Differential Protection RED670, Product Guide, Version 2.2, document 1MRK 505 379-BEN.
  • ABB RED670 Application Manual.
  • ABB RED670 Commissioning Manual.
  • ABB RED670 Technical Reference Manual.

Technical note: Available functions, communication interfaces and hardware configurations depend on the ordered product version and application package. Always consult the applicable ABB documentation before engineering or commissioning an actual installation.

Leave a Comment

Your email address will not be published. Required fields are marked *

Scroll to Top