ABB RET670 Transformer Protection Relay – Complete Technical Guide

Complete guide to ABB RET670 transformer protection relay, covering transformer differential protection, REF, CT compensation, inrush restraint, PCM600 configuration, IEC 61850 and commissioning.

Table Of Contents
  1. 1. Introduction to ABB RET670
  2. 2. Main Applications of ABB RET670
  3. 3. ABB RET670 Hardware and Application Configurations
  4. 4. Main Protection Functions of ABB RET670
  5. 5. Transformer Differential Protection – ANSI 87T
  6. 6. Restricted Earth-Fault Protection – ANSI 87N
  7. 7. High-Impedance Differential Protection
  8. 8. Phase Overcurrent Protection – ANSI 50/51
  9. 9. Earth-Fault Overcurrent Protection – ANSI 50N/51N
  10. 10. Distance Protection – ANSI 21
  11. 11. Thermal Overload Protection – ANSI 49
  12. 12. Overexcitation Protection – ANSI 24
  13. 13. Overvoltage and Undervoltage Protection – ANSI 59 and 27
  14. 14. Frequency Protection – ANSI 81
  15. 15. Circuit Breaker Failure Protection – ANSI 50BF
  16. 16. Transformer Tap Changer Control – ANSI 90
  17. 17. PCM600 Configuration of ABB RET670
  18. 18. IEC 61850 Communication in ABB RET670
  19. 19. Testing and Commissioning of ABB RET670
  20. 20. Common Problems and Troubleshooting
  21. 21. ABB RET670 Compared with Other Transformer Protection Relays
  22. 22. Frequently Asked Questions About ABB RET670
  23. 23. Conclusion

ABB RET670: Applications, Transformer Differential Protection, Restricted Earth-Fault Protection, PCM600 Configuration, IEC 61850 and Commissioning

ABB RET670 Transformer Protection Relay – Complete Technical Guide

1. Introduction to ABB RET670

The ABB RET670 is a numerical transformer protection and control intelligent electronic device (IED) belonging to ABB’s Relion 670 series.

It is designed to provide comprehensive protection, monitoring and control for power transformers, autotransformers, generator-transformer units and other transformer applications in electrical power systems.

Power transformers are among the most important and expensive components in transmission and distribution networks. Internal winding faults, insulation failures, earth faults, overloading and abnormal operating conditions can cause significant equipment damage and power system disturbances.

A reliable transformer protection system must detect internal faults quickly, distinguish between internal and external faults, remain stable during transformer energization and provide appropriate backup protection.

The ABB RET670 combines several protection functions in one numerical relay, including:

  • Transformer differential protection (87T).
  • Restricted earth-fault protection (87N).
  • High-impedance differential protection.
  • Phase and earth-fault overcurrent protection.
  • Distance protection.
  • Thermal overload protection.
  • Overexcitation protection (24).
  • Overvoltage and undervoltage protection.
  • Frequency protection.
  • Circuit breaker failure protection.
  • Transformer tap changer control.
  • IEC 61850 communication and substation automation.

The RET670 is suitable for different transformer configurations, including two-winding transformers, three-winding transformers, autotransformers and generator step-up transformers.

Its flexible protection functions and application logic allow engineers to implement different transformer protection philosophies according to system requirements.

2. Main Applications of ABB RET670

The RET670 is designed for transformer protection applications in different voltage levels and power system arrangements.

Typical applications include:

2.1 Two-Winding Transformer Protection

The relay can provide differential and backup protection for two-winding power transformers.

Typical applications include:

  • Transmission substations.
  • Distribution substations.
  • Industrial power systems.
  • Grid interconnection transformers.
  • Power plant auxiliary transformers, where the application is suitable.

2.2 Three-Winding Transformer Protection

Three-winding transformers are used in transmission networks, power plants and industrial installations.

RET670 supports three-winding transformer differential protection, allowing the currents from the three transformer sides to be evaluated within a common differential protection scheme.

2.3 Autotransformer Protection

Autotransformers are widely used in high-voltage transmission networks.

The RET670 can be engineered for autotransformer protection, including differential and earth-fault protection schemes, depending on the selected configuration.

2.4 Generator Step-Up Transformer Protection

Generator step-up transformers connect power plant generators to transmission networks.

RET670 can provide dedicated transformer protection, including differential protection, earth-fault protection, overcurrent backup and other functions.

2.5 Shunt Reactor Protection

The RET670 product family also supports protection applications for shunt reactors, subject to the applicable product configuration and engineering requirements.

3. ABB RET670 Hardware and Application Configurations

ABB provides different RET670 configurations for different transformer protection requirements.

The available functions depend on the selected hardware, software version, ordering code and preconfigured application.

The engineering requirements of a two-winding transformer differ from those of a three-winding transformer or autotransformer.

When selecting RET670, engineers should consider:

  • Number of transformer windings.
  • Transformer rated power.
  • Voltage levels.
  • CT ratios and connection arrangements.
  • Transformer vector group.
  • Neutral grounding arrangement.
  • Circuit breaker configuration.
  • Number of analog current and voltage inputs.
  • Required protection and control functions.
  • Communication architecture.
  • Redundancy requirements.

The actual ordering configuration must be checked against the applicable ABB product guide.

4. Main Protection Functions of ABB RET670

The RET670 provides a comprehensive protection function library.

Important functions include:

ANSI codeProtection functionApplication
87TTransformer differential protectionDetects internal transformer faults
87NRestricted earth-fault protectionDetects winding earth faults within a defined zone
50/51Phase overcurrent protectionShort-circuit and backup protection
50N/51NEarth-fault overcurrent protectionDetects earth faults
67/67NDirectional overcurrent protectionDirectional phase and earth-fault backup
21Distance protectionBackup protection for transformer and connected network faults
49Thermal overload protectionProtects against excessive thermal loading
24Overexcitation protectionDetects excessive V/Hz conditions
27Undervoltage protectionDetects low voltage
59Overvoltage protectionDetects excessive voltage
59NResidual overvoltage protectionDetects residual voltage conditions
81Frequency protectionDetects abnormal frequency
50BFCircuit breaker failure protectionDetects breaker failure
25SynchrocheckChecks synchronism before circuit breaker closing
79AutoreclosingProvides autoreclosing functionality where applicable
90Automatic voltage controlSupports transformer tap changer control

The actual availability and number of function instances depend on the selected RET670 product version and configuration.

5. Transformer Differential Protection – ANSI 87T

Transformer differential protection is the main protection function for detecting internal electrical faults in power transformers.

The RET670 provides transformer differential protection through dedicated functions:

  • T2WPDIF – Two-winding transformer differential protection.
  • T3WPDIF – Three-winding transformer differential protection.

5.1 Operating Principle

Transformer differential protection operates by comparing the currents measured on the different sides of a transformer.

Under normal operating conditions, the currents are compared after considering the transformer ratio and phase displacement.

For an external fault, the differential protection should remain stable.

For an internal fault inside the protected transformer zone, the differential current increases and the relay can initiate transformer tripping.

The simplified differential current principle is:

I_diff = |I_1 – I_2|

For a practical transformer differential relay, the measured currents must be compensated for:

  • Transformer transformation ratio.
  • Transformer vector group.
  • CT ratios.
  • Phase displacement.
  • Zero-sequence current effects, where applicable.
  • Transformer tap changer position and ratio variation.
  • CT errors and saturation.

The RET670 provides automatic CT ratio matching and vector group compensation in its differential protection application.

5.2 Transformer Differential Protection Characteristic

Modern transformer differential protection uses a biased or percentage differential characteristic.

The operating decision depends on both differential current and restraint current.

The restraint characteristic helps prevent unwanted operation during external faults and CT saturation.

Important settings include:

  • Differential pickup current.
  • Bias or restraint characteristic.
  • Slope settings.
  • Unrestrained differential stage.
  • Inrush restraint.
  • Overexcitation restraint.
  • Harmonic supervision.
  • CT configuration.

5.3 Transformer Magnetizing Inrush

When a transformer is energized, a high magnetizing inrush current may flow.

This current can be significantly higher than the normal magnetizing current and may cause an unwanted differential protection operation if not properly recognized.

The RET670 differential protection includes inrush restraint and blocking features.

Second-harmonic restraint is commonly used to identify transformer magnetizing inrush.

The relay also provides fifth-harmonic restraint for overexcitation-related conditions.

5.4 CT Saturation and External Fault Stability

During severe external faults, CT saturation can produce unequal secondary currents.

This may create an apparent differential current even though the fault is outside the transformer differential protection zone.

The differential protection characteristic and stabilization features must be engineered to ensure security during these conditions.

6. Restricted Earth-Fault Protection – ANSI 87N

Restricted earth-fault protection is a highly sensitive protection function used to detect earth faults within a defined transformer winding zone.

It is particularly important for detecting winding-to-earth faults that may not produce sufficient current for conventional transformer differential protection.

The RET670 supports restricted earth-fault protection using low-impedance and high-impedance principles, depending on the application.

6.1 Low-Impedance REF Protection

Low-impedance REF protection compares the residual current calculated from the phase CTs with the neutral CT current.

For a healthy condition or an external earth fault, the currents should balance within the protected zone.

For an internal earth fault, the differential quantity increases and the protection can operate.

Advantages include:

  • Sensitive earth-fault detection.
  • Flexible setting possibilities.
  • Suitable integration into numerical protection schemes.
  • Directional supervision options in applicable implementations.

6.2 High-Impedance REF Protection

High-impedance REF protection uses a high-impedance measuring circuit to detect internal earth faults.

The scheme generally requires carefully matched CTs and appropriate stabilizing components.

Important engineering considerations include:

  • CT class and characteristics.
  • CT secondary resistance.
  • Stabilizing resistor selection.
  • Nonlinear resistor requirements, where applicable.
  • Maximum external fault current.
  • CT saturation performance.
  • Wiring and polarity verification.

The selection between high-impedance and low-impedance REF must be based on the transformer protection design.

7. High-Impedance Differential Protection

In addition to transformer differential protection, RET670 offers high-impedance differential protection functions through HZPDIF.

This function can be used in several applications, depending on the protection scheme.

Examples include:

  • Restricted earth-fault protection.
  • Autotransformer differential protection arrangements.
  • Tertiary winding protection.
  • Tertiary reactor protection.
  • Transformer feeder differential protection.
  • Tertiary bus protection.

High-impedance protection requires careful CT selection and secondary circuit engineering.

The relay’s application documentation should be consulted to determine the correct arrangement and settings.

8. Phase Overcurrent Protection – ANSI 50/51

Phase overcurrent protection provides backup protection for transformer and connected power system faults.

The RET670 includes instantaneous and time-delayed phase overcurrent functions.

Typical applications include:

  • Backup protection for transformer differential protection.
  • Phase-to-phase fault protection.
  • Three-phase short-circuit protection.
  • Transformer incomer protection.
  • Backup protection for downstream feeders.

Depending on the selected function, directional and voltage-controlled characteristics may also be available.

Important setting considerations include:

  • Transformer rated current.
  • Maximum load current.
  • Transformer impedance.
  • Downstream protection coordination.
  • Maximum and minimum fault current.
  • Inrush current.
  • Time-current coordination.

9. Earth-Fault Overcurrent Protection – ANSI 50N/51N

Earth-fault overcurrent protection detects residual current associated with phase-to-earth faults.

The residual current can be calculated from the three phase currents or measured using a dedicated neutral or core-balance CT arrangement.

The RET670 provides instantaneous and time-delayed residual overcurrent protection.

Directional residual overcurrent protection can also be applied where the network grounding arrangement requires directional fault discrimination.

Important considerations include:

  • Transformer neutral grounding.
  • System zero-sequence impedance.
  • Earth-fault current magnitude.
  • CT arrangement.
  • Directional characteristic.
  • Coordination with downstream earth-fault protection.

10. Distance Protection – ANSI 21

Although transformer differential protection is the main protection for internal transformer faults, distance protection can provide supplementary backup protection.

The RET670 supports distance protection functions for phase-to-phase and phase-to-earth faults in applicable configurations.

Distance protection measures the apparent impedance between the relay location and the fault.

The measured impedance is evaluated against predefined protection zones.

Typical applications include:

  • Backup protection for transformer faults.
  • Backup protection for connected transmission lines.
  • Phase fault detection.
  • Earth-fault detection.
  • Protection of complex transformer and network arrangements.

Distance protection must be carefully coordinated with transformer impedance, connected network characteristics and other protection systems.

11. Thermal Overload Protection – ANSI 49

Transformer thermal overload protection monitors loading conditions and estimates thermal stress.

Transformers can operate above rated current for limited periods, depending on cooling conditions, ambient temperature and thermal characteristics.

Excessive loading can accelerate insulation ageing and reduce transformer lifetime.

The RET670 provides thermal overload protection functions that can be applied according to the selected configuration.

Important considerations include:

  • Transformer rated current.
  • Thermal time constants.
  • Cooling arrangement.
  • Ambient temperature.
  • Alarm and trip thresholds.
  • Transformer loading profile.

Thermal protection settings should be coordinated with the transformer manufacturer’s thermal capability information.

12. Overexcitation Protection – ANSI 24

Overexcitation occurs when the magnetic flux in a transformer core becomes excessive.

The main operating parameter is the voltage-to-frequency ratio (V/Hz).

A high V/Hz ratio may cause magnetic core saturation and excessive heating.

Overexcitation can occur due to:

  • Excessive voltage.
  • Reduced system frequency.
  • Incorrect voltage regulation.
  • Generator excitation problems.
  • Abnormal system operating conditions.

The RET670 provides overexcitation protection through the PVPH function.

The protection monitors the V/Hz ratio and can initiate alarm or trip signals according to the configured characteristic.

13. Overvoltage and Undervoltage Protection – ANSI 59 and 27

Voltage protection functions monitor abnormal transformer voltage conditions.

Overvoltage Protection

Overvoltage protection detects excessive voltage that may cause increased electrical stress on transformer insulation.

Undervoltage Protection

Undervoltage protection detects abnormal voltage reduction and can be used for system supervision and backup protection.

Residual Overvoltage Protection – ANSI 59N

Residual overvoltage protection can detect earth-fault-related voltage displacement in appropriate network arrangements.

The settings must consider system grounding, VT connections and the transformer protection philosophy.

14. Frequency Protection – ANSI 81

The RET670 supports frequency protection functions for detecting abnormal frequency conditions.

These functions can provide underfrequency and overfrequency protection.

Applications include:

  • Generator-transformer unit protection.
  • Power system frequency supervision.
  • Abnormal system operating condition detection.
  • Alarm and trip functions.

The protection settings must be coordinated with generator protection, load shedding and power system operational requirements.

15. Circuit Breaker Failure Protection – ANSI 50BF

Circuit breaker failure protection detects situations where a circuit breaker does not interrupt fault current after receiving a trip command.

For example, when transformer differential protection detects an internal fault, the relay issues a trip command to the associated circuit breakers.

If a breaker fails to open, breaker failure protection can initiate backup tripping of surrounding breakers.

The RET670 provides breaker failure protection for transformer breaker applications, subject to the selected configuration.

Important engineering considerations include:

  • Breaker failure initiation.
  • Current detection.
  • Breaker auxiliary contacts.
  • Retrip logic.
  • Backup trip logic.
  • Coordination time.
  • Multiple circuit breaker arrangements.

16. Transformer Tap Changer Control – ANSI 90

Some RET670 configurations support automatic voltage regulation and transformer tap changer control.

The purpose is to maintain the desired secondary voltage by adjusting the on-load tap changer position.

The automatic voltage control functions can be used in:

  • Single transformer applications.
  • Parallel transformer applications.
  • Voltage regulation schemes.
  • Substation automation systems.

Important parameters include:

  • Voltage setpoint.
  • Deadband.
  • Time delay.
  • Tap position limits.
  • Raise and lower commands.
  • Parallel transformer control philosophy.
  • Circulating current supervision, where applicable.

The available tap changer control functionality depends on the selected RET670 configuration and application engineering.

17. PCM600 Configuration of ABB RET670

PCM600 (Protection and Control IED Manager) is ABB’s engineering software for supported Relion protection and control IEDs.

It is used to configure, parameterize and manage the RET670.

Important PCM600 engineering activities include:

  1. Creating a new PCM600 project.
  2. Adding the RET670 IED.
  3. Selecting the correct product version.
  4. Installing the required connectivity package.
  5. Establishing communication with the relay.
  6. Reading and managing the IED configuration.
  7. Configuring transformer differential protection.
  8. Configuring REF and backup protection.
  9. Developing application logic.
  10. Configuring binary inputs and outputs.
  11. Engineering IEC 61850 communication.
  12. Downloading and verifying the configuration.

17.1 Creating a RET670 Project

The engineer first creates a new project in PCM600 and adds the appropriate RET670 IED.

The correct product version and connectivity package must be selected.

17.2 Transformer Differential Parameter Setting

The engineer configures the transformer differential protection according to the transformer nameplate and protection design.

Important data include:

  • Transformer rated power.
  • Primary and secondary rated voltage.
  • Tertiary voltage, if applicable.
  • Transformer vector group.
  • CT ratios.
  • Transformer winding configuration.
  • Neutral grounding arrangement.
  • Differential protection settings.

17.3 Application Configuration

The application configuration defines the interaction between protection functions, logic signals, binary inputs and outputs.

For example, transformer differential protection can be connected to:

  • Transformer lockout relay.
  • HV circuit breaker trip.
  • LV circuit breaker trip.
  • Tertiary circuit breaker trip.
  • Alarm indications.
  • Breaker failure initiation.
  • Disturbance recording.

The complete tripping logic must be verified before the IED is placed into service.

18. IEC 61850 Communication in ABB RET670

IEC 61850 is widely used for communication and engineering in modern digital substations.

The RET670 supports IEC 61850 communication for integration with other protection relays, bay controllers and station-level systems.

18.1 MMS Communication

MMS provides client-server communication between IEDs and supervisory systems.

Typical applications include:

  • Reading transformer measurements.
  • Monitoring protection status.
  • Receiving alarms and events.
  • Supervisory control.
  • Reporting information to SCADA systems.

18.2 GOOSE Communication

GOOSE provides fast peer-to-peer communication between IEDs.

Typical applications include:

  • Transformer interlocking.
  • Circuit breaker trip signals.
  • Breaker failure transfer signals.
  • Protection blocking.
  • Inter-IED protection logic.
  • Parallel transformer interlocking.

18.3 IEC 61850 SCL Engineering

Important SCL file types include:

  • ICD – IED Capability Description.
  • CID – Configured IED Description.
  • SCD – Substation Configuration Description.
  • SSD – System Specification Description.
  • IID – Instantiated IED Description.

The actual IEC 61850 edition and communication services must be checked against the particular RET670 hardware and firmware version.

19. Testing and Commissioning of ABB RET670

Testing and commissioning are essential before energizing a transformer protection system.

Protection engineers must verify the complete measurement, protection, control and tripping arrangements.

Typical commissioning activities include:

TestPurpose
Visual inspectionVerify relay installation and hardware
Auxiliary supply testVerify DC supply
CT circuit testVerify CT polarity, ratio and wiring
VT circuit testVerify voltage measurement
Differential protection testVerify 87T characteristic
Inrush restraint testVerify security during transformer energization
External fault stability testVerify differential protection stability
REF protection testVerify restricted earth-fault operation
Overcurrent testVerify phase and earth-fault protection
Distance protection testVerify backup distance characteristics
Thermal protection testVerify thermal overload function
Overexcitation testVerify V/Hz protection
Binary input testVerify external signals
Binary output testVerify alarm and trip contacts
Breaker failure testVerify 50BF logic
Tap changer testVerify raise/lower control, where applicable
IEC 61850 testVerify MMS and GOOSE communication
Trip circuit testVerify complete circuit breaker tripping

OMICRON CMC test equipment and Test Universe can be used for secondary injection testing and protection characteristic verification.

Transformer differential testing should include suitable tests for:

  • Differential pickup.
  • Biased differential characteristic.
  • CT ratio compensation.
  • Vector group compensation.
  • Inrush restraint.
  • Harmonic restraint.
  • External fault stability.

The final commissioning procedure must follow the approved protection design and applicable ABB documentation.

20. Common Problems and Troubleshooting

20.1 Incorrect Differential Current

Possible causes include:

  • Incorrect CT polarity.
  • Incorrect CT ratio.
  • Incorrect transformer vector group.
  • Incorrect phase mapping.
  • Wrong transformer rated data.
  • CT secondary wiring problems.
  • Incorrect configuration.

20.2 Unwanted Differential Operation During Transformer Energization

Possible causes include:

  • Incorrect inrush restraint settings.
  • Incorrect current measurement configuration.
  • Incorrect harmonic measurement.
  • CT circuit problems.
  • Incorrect application logic.

20.3 REF Protection Maloperation

Check:

  • Neutral CT polarity.
  • Phase CT residual connections.
  • CT ratio matching.
  • Stabilizing resistor arrangements for high-impedance schemes.
  • Earth-fault protection settings.
  • External fault stability.

20.4 Unexpected Overcurrent Operation

Review:

  • Actual measured current.
  • Protection pickup settings.
  • Time delays.
  • CT ratios.
  • Downstream protection coordination.
  • Transformer loading conditions.

20.5 Tap Changer Control Problems

Check:

  • Tap position feedback.
  • Raise and lower output signals.
  • Voltage measurement.
  • Voltage setpoint.
  • Deadband.
  • Time delay.
  • Tap changer interlocking.

20.6 PCM600 Communication Problems

Check:

  • Connectivity package compatibility.
  • IED product version.
  • Communication interface.
  • IP configuration.
  • Project configuration.
  • Firmware compatibility.

21. ABB RET670 Compared with Other Transformer Protection Relays

ABB offers several transformer protection products for different application requirements.

RelayGeneral application
RET670Comprehensive transformer protection and control
RET650Transformer protection in the Relion 650 family
RET620Transformer protection in the Relion 620 family
RET615Transformer protection in the Relion 615 family
REX640Modular protection and control platform

These products differ in hardware, protection function availability, engineering flexibility and application capabilities.

The selection must be based on transformer ratings, winding configuration, protection philosophy, communication requirements and project specifications.

22. Frequently Asked Questions About ABB RET670

What is ABB RET670 used for?

ABB RET670 is a numerical transformer protection and control relay designed for power transformers, autotransformers and generator-transformer units.

What is the main differential protection function in RET670?

The RET670 provides T2WPDIF for two-winding transformer differential protection and T3WPDIF for three-winding transformer differential protection.

Does RET670 support restricted earth-fault protection?

Yes. The RET670 supports low-impedance and high-impedance REF protection applications, depending on the selected configuration.

Does RET670 support transformer inrush restraint?

Yes. Its differential protection includes harmonic restraint and blocking features for transformer magnetizing inrush.

Can RET670 protect a three-winding transformer?

Yes. Three-winding transformer differential protection is supported through T3WPDIF in applicable configurations.

Which software is used to configure ABB RET670?

PCM600 is the engineering software used for supported RET670 product versions.

Does RET670 support IEC 61850?

Yes. RET670 supports IEC 61850 communication, including applicable MMS and GOOSE services.

Can RET670 control an on-load tap changer?

Yes. Automatic voltage control and tap changer control functions are available in applicable configurations.

Can RET670 be tested using OMICRON CMC?

Yes. OMICRON CMC test equipment can be used for secondary injection testing and verification of transformer protection functions.

23. Conclusion

The ABB RET670 is a comprehensive numerical transformer protection and control IED designed for modern transmission networks, power plants and industrial electrical systems.

Its transformer differential protection, restricted earth-fault protection, backup protection, monitoring, tap changer control and IEC 61850 communication capabilities make it suitable for a wide range of transformer protection applications.

For protection engineers, commissioning engineers and substation automation specialists, understanding RET670 requires knowledge of transformer differential protection principles, CT ratio and vector group compensation, REF protection, transformer inrush, backup protection, PCM600 engineering and IEC 61850 communication.

Elec-Engg provides practical technical training in power system protection, transformer protection, numerical protection relays, relay testing and substation automation.

Related Elec-Engg Topics:

  • Transformer Protection Fundamentals.
  • Transformer Differential Protection.
  • Restricted Earth-Fault Protection.
  • Transformer CT Selection and Ratio Matching.
  • ABB PCM600 Engineering.
  • IEC 61850 Engineering and Configuration.
  • Protection Relay Testing and Commissioning.

Technical references:

  • ABB Relion 670 Series – Transformer Protection RET670, Product Guide.
  • ABB RET670 Application Manual.
  • ABB RET670 Commissioning Manual.
  • ABB RET670 Technical Documentation and Available Functions.

Technical note: The availability of protection functions, hardware options and communication services depends on the ordered configuration and product revision. Always consult the applicable ABB documentation before engineering or commissioning an actual installation.