ABB REC670 Bay Control Unit – Complete Technical Guide

Table Of Contents
  1. 1. Introduction to ABB REC670
  2. 2. What Is a Bay Control Unit?
  3. 3. Main Applications of REC670
  4. 4. REC670 Preconfigured Applications
  5. 5. Circuit-Breaker Control
  6. 6. Disconnector and Earthing-Switch Control
  7. 7. Electrical Interlocking in REC670
  8. 8. REC670 Control Function Blocks
  9. 9. Synchrocheck and Energizing Check
  10. 10. Automatic Reclosing
  11. 11. Protection Functions Available in REC670
  12. 12. Capacitor Bank Protection Applications
  13. 13. Circuit-Breaker Failure Protection
  14. 14. Broken Conductor Detection
  15. 15. Voltage and Frequency Protection
  16. 16. IEC 61850 Communication in REC670
  17. 17. PCM600 Engineering and Configuration
  18. 18. Human-Machine Interface and Local Control
  19. 19. Testing and Commissioning of REC670
  20. 20. Common REC670 Problems and Troubleshooting
  21. 21. REC670 Compared with Other ABB Relays
  22. 22. Frequently Asked Questions About ABB REC670
  23. 23. Conclusion
  24. Related Articles

ABB REC670 Bay Control and Protection IED – Complete Technical Guide

1. Introduction to ABB REC670

The ABB REC670 is a numerical bay control IED from the ABB Relion 670 series. It is designed for control, monitoring, protection and automation applications in high-voltage substations.

A bay is the part of a substation associated with a particular circuit or electrical connection, such as a transmission line, transformer, bus coupler, bus section or capacitor bank.

REC670 provides an integrated solution for controlling and monitoring the primary equipment in a bay. It can also incorporate protection functions, communication facilities and programmable logic.

Its main applications include:

  • Circuit-breaker control
  • Disconnector and earthing-switch control
  • Electrical and mechanical interlocking
  • Bay-level monitoring
  • Synchrocheck and energizing check
  • Automatic reclosing
  • Circuit-breaker failure protection
  • Backup overcurrent and earth-fault protection
  • Capacitor bank protection
  • IEC 61850 substation communication
  • Integration with station-level SCADA systems

REC670 can be supplied as a preconfigured solution or as a customized IED. The available functions and control capacity depend on the selected product configuration and version.

2. What Is a Bay Control Unit?

A bay control unit is an IED responsible for controlling and monitoring the switching equipment associated with one or more substation bays.

Typical primary equipment includes:

  • Circuit-breakers
  • Busbar disconnectors
  • Line disconnectors
  • Earthing switches
  • Voltage transformers
  • Current transformers
  • Power transformers
  • Bus couplers
  • Bus section breakers

The bay control IED receives status information from the primary equipment and provides commands to operate the switching devices.

For example, an operator may issue a command from the station HMI to open a circuit-breaker.

The command is processed by the bay control system. Before the operation is executed, the interlocking logic checks whether the requested switching operation is permitted.

This prevents unsafe switching sequences, such as closing an earthing switch while the associated circuit is energized.

3. Main Applications of REC670

3.1 Transmission line bay control

REC670 can be used to control and monitor transmission line bays.

Typical functions include:

  • Circuit-breaker open and close commands
  • Line disconnector control
  • Busbar disconnector control
  • Earthing-switch control
  • Electrical interlocking
  • Circuit-breaker status monitoring
  • Auto-reclosing
  • Synchrocheck
  • Protection and alarm indication

3.2 Transformer bay control

In transformer bays, REC670 can be used for switching equipment control and monitoring.

Typical applications include:

  • Transformer circuit-breaker control
  • Disconnector control
  • Earthing-switch control
  • Interlocking
  • Transformer bay measurements
  • Backup protection functions
  • Communication with transformer protection IEDs

The main transformer differential protection is normally provided by a dedicated transformer protection IED, such as ABB RET670.

3.3 Bus coupler and bus section control

REC670 can also be applied to bus coupler and bus section bays.

Typical control functions include:

  • Bus coupler breaker control
  • Busbar disconnector control
  • Interlocking between switching devices
  • Busbar selection logic
  • Circuit-breaker monitoring
  • Status indication to the station HMI

3.4 One-and-a-half circuit-breaker arrangements

REC670 supports preconfigured applications for different switchgear arrangements, including one-and-a-half circuit-breaker applications.

In this arrangement, two circuits share three circuit-breakers.

The bay control system must correctly manage the switching equipment and interlocking conditions associated with the diameter.

The appropriate REC670 configuration depends on the number of controlled devices and the required application.

4. REC670 Preconfigured Applications

The REC670 Version 2.2 Product Guide describes several preconfigured applications.

ConfigurationGeneral application
REC670 A30Single circuit-breaker application
REC670 B30Double circuit-breaker application
REC670 C30One-and-a-half circuit-breaker application
REC670 D30Application for a complete one-and-a-half circuit-breaker diameter

The exact control and protection functions differ between configurations.

The product guide also describes customized REC670 applications, allowing the engineering team to select functions according to project requirements.

When selecting an IED, verify:

  • Number of circuit-breakers
  • Number of disconnectors
  • Number of earthing switches
  • Number of controlled objects
  • Binary input and output requirements
  • Interlocking requirements
  • Synchrocheck requirements
  • Protection functions
  • IEC 61850 communication requirements
  • Product version and ordering information

5. Circuit-Breaker Control

One of the most important functions of REC670 is circuit-breaker control.

A circuit-breaker is used to connect or disconnect an electrical circuit under normal operating conditions and to interrupt fault current when commanded by the protection system.

REC670 provides bay-level control functionality for circuit-breakers.

Typical commands include:

  • Open circuit-breaker
  • Close circuit-breaker
  • Local operation
  • Remote operation
  • Status monitoring
  • Command supervision
  • Operation indication
  • Control authority management

Circuit-breaker position indication

The IED receives auxiliary contact signals from the circuit-breaker.

Common indications include:

  • Circuit-breaker open
  • Circuit-breaker closed
  • Circuit-breaker intermediate position
  • Circuit-breaker discrepancy
  • Circuit-breaker operation not completed

The position information is used by the control and interlocking logic.

Circuit-breaker operation

A typical closing sequence is:

  1. The operator selects the circuit-breaker.
  2. The operator issues a close command.
  3. The IED checks the control authority.
  4. The interlocking logic checks the switching conditions.
  5. Synchrocheck or energizing check is evaluated where required.
  6. The close command is issued to the circuit-breaker.
  7. The auxiliary contacts confirm the new position.
  8. The updated status is communicated to the station HMI.

The exact sequence depends on the configured application.

6. Disconnector and Earthing-Switch Control

REC670 can control disconnectors and earthing switches as part of the bay control application.

Disconnector control

Disconnectors are used to isolate electrical equipment and provide visible isolation in suitable switchgear designs.

They are not intended to interrupt normal load current unless specifically designed and rated for that duty.

The bay control system must prevent unsafe disconnector operations.

For example, the control logic may prevent opening or closing a disconnector when the associated circuit-breaker is closed.

Earthing-switch control

Earthing switches are used to connect isolated equipment to earth for maintenance and safety purposes.

Before closing an earthing switch, the control system must verify the required isolation conditions.

Typical interlocking conditions include:

  • Associated circuit-breaker open
  • Relevant disconnector open
  • No conflicting switching operation
  • Required voltage absence condition satisfied, where applicable
  • Correct operating authority

The actual interlocking requirements must be determined from the substation design and approved switching philosophy.

7. Electrical Interlocking in REC670

Electrical interlocking is one of the most important bay control functions.

Its purpose is to prevent unsafe switching operations by checking the status of relevant switching devices and other permissive conditions.

Example: Circuit-breaker and disconnector interlocking

Consider a transmission line bay with:

  • One circuit-breaker
  • One busbar disconnector
  • One line disconnector
  • One line earthing switch

A typical switching philosophy may require the circuit-breaker to be open before operating the disconnectors.

The earthing switch may only be permitted to close when the line has been isolated and the required safety conditions have been satisfied.

Example interlocking conditions

OperationExample permissive condition
Close circuit-breakerRequired disconnectors in valid positions
Open circuit-breakerValid control authority
Operate busbar disconnectorCircuit-breaker open, where required
Operate line disconnectorCircuit-breaker open, where required
Close line earthing switchLine isolated and safety conditions satisfied
Open earthing switchNo conflicting operation

These are illustrative conditions. The actual interlocking matrix must be developed from the approved substation switching philosophy.

Interlocking types

Interlocking may be implemented using:

  • Local bay-level logic
  • Hardwired interlocking
  • Station-level interlocking
  • IEC 61850 GOOSE communication
  • Combination of hardwired and communication-based signals

The selected design must provide the required operational security and fail-safe behaviour.

8. REC670 Control Function Blocks

REC670 includes dedicated control function blocks for switching-device control.

The product documentation identifies the following control functions:

FunctionDescription
APC10Control functionality for a single bay, up to 10 objects
APC15Control functionality for a single bay, up to 15 objects
APC30Control functionality for up to six bays, up to 30 objects
SESRSYNSynchrocheck, energizing check and synchronizing
SMBRRECAuto-reclosing

The product guide also describes preconfigured control solutions for different circuit-breaker arrangements.

The exact object capacity and available functions must be checked against the selected configuration.

9. Synchrocheck and Energizing Check

The REC670 includes:

SESRSYN – Synchrocheck, Energizing Check and Synchronizing

This function is used to supervise circuit-breaker closing when connecting two electrical systems or energizing a de-energized circuit.

Closing a circuit-breaker between two energized systems under unsuitable conditions can create severe electrical and mechanical stresses.

Synchrocheck conditions

The function can evaluate:

  • Voltage magnitude difference
  • Phase angle difference
  • Frequency difference
  • Voltage availability
  • Live-bus and live-line conditions
  • Dead-bus and dead-line conditions

Example: Closing a bus coupler

Consider a substation with two energized busbar sections.

Before closing the bus coupler, the system should verify that the voltage magnitude, phase angle and frequency difference satisfy the configured limits.

The synchrocheck function provides the required supervision before issuing or permitting the closing command.

Energizing check

Energizing check is used when one side of the circuit-breaker is energized and the other side is de-energized.

The permissive conditions depend on the selected application and configured voltage supervision.

10. Automatic Reclosing

The REC670 supports automatic reclosing functionality through:

SMBRREC – Auto-Recloser

Auto-reclosing is widely used on overhead transmission lines because many faults are temporary.

After a protection trip, the auto-reclosing function can initiate a circuit-breaker closing operation after a configured dead time.

Important auto-reclosing parameters

  • Single-phase or three-phase reclosing
  • Dead time
  • Reclaim time
  • Reclosing shot sequence
  • Circuit-breaker readiness
  • Protection initiation
  • Reclosing blocking signals
  • Synchronism-check permission

Typical auto-reclosing sequence

  1. A line fault occurs.
  2. The line protection relay issues a trip command.
  3. The circuit-breaker opens.
  4. The auto-reclosing function starts its dead-time timer.
  5. The system checks the required permissive conditions.
  6. The circuit-breaker receives a closing command.
  7. The circuit-breaker closes.
  8. The system monitors whether the fault has cleared.

If the fault is permanent, the protection may trip again and the auto-reclosing sequence will follow its configured shot and lockout logic.

The complete sequence must be coordinated with the line protection IED and circuit-breaker characteristics.

11. Protection Functions Available in REC670

Although REC670 is primarily a bay control IED, it also supports a broad range of protection functions.

The available functions depend on the selected product configuration.

11.1 Current protection

FunctionDescription
PHPIOCInstantaneous phase overcurrent protection
OC4PTOCFour-step phase overcurrent protection
EFPIOCInstantaneous residual overcurrent protection
EF4PTOCFour-step residual overcurrent protection
NS4PTOCFour-step negative-sequence overcurrent protection
CCRBRFCircuit-breaker failure protection
BRCPTOCBroken conductor check
LCPTTR / LFPTTRThermal overload protection

11.2 Voltage protection

FunctionDescription
UV2PTUVTwo-step undervoltage protection
OV2PTOVTwo-step overvoltage protection
ROV2PTOVResidual overvoltage protection
VDCPTOVVoltage differential protection
LOVPTUVLoss-of-voltage check

11.3 Frequency protection

FunctionDescription
SAPTUFUnderfrequency protection
SAPTOFOverfrequency protection
SAPFRCRate-of-change-of-frequency protection
FTAQFVRFrequency time accumulation protection

11.4 Power protection

FunctionDescription
GOPPDOPDirectional overpower protection
GUPPDUPDirectional underpower protection

11.5 Capacitor bank protection

REC670 can also be configured for capacitor bank protection applications.

Relevant functions documented for the REC670 product family include:

  • CBPGAPC – Capacitor bank protection
  • SCUCPTOC – Current unbalance protection for shunt capacitor banks
  • SCPDPTOV – Phase voltage differential capacitor bank unbalance protection
  • SCUVPTOV – Voltage unbalance protection for shunt capacitor banks
  • SCCFPVOC – Cascading failure protection for shunt capacitor banks

The exact function availability depends on the product configuration.

12. Capacitor Bank Protection Applications

One important application of REC670 is protection and control of shunt capacitor banks.

Capacitor banks are installed in substations to provide reactive power compensation and improve voltage conditions.

However, capacitor banks can experience several abnormal operating conditions.

Examples include:

  • Capacitor unit failure
  • Internal capacitor element failure
  • Unbalance between capacitor groups
  • Overcurrent
  • Overvoltage
  • Excessive reactive power
  • Restrike conditions
  • Cascading capacitor failures

REC670 provides capacitor bank protection functions for suitable applications.

12.1 Capacitor bank overcurrent protection

Overcurrent protection detects excessive current flowing through the capacitor bank.

It can provide protection against abnormal current conditions and certain fault scenarios.

12.2 Capacitor bank unbalance protection

Capacitor bank unbalance can occur when one or more capacitor elements fail.

Depending on the bank arrangement, the protection may use current or voltage unbalance measurements.

12.3 Capacitor bank voltage differential protection

Voltage differential protection can be applied to suitable capacitor bank arrangements.

The function compares relevant voltage quantities to detect abnormal conditions.

12.4 Cascading failure protection

A capacitor unit failure can increase the electrical stress on the remaining healthy units.

If not detected, this may result in additional failures.

Cascading failure protection helps detect conditions associated with progressive capacitor bank deterioration.

The exact protection philosophy depends on the capacitor bank design, grounding arrangement and manufacturer recommendations.

13. Circuit-Breaker Failure Protection

REC670 includes circuit-breaker failure protection:

CCRBRF – Circuit-Breaker Failure Protection

The function detects situations where a circuit-breaker fails to interrupt fault current after receiving a trip command.

Typical applications include:

  • Line bay breaker-failure protection
  • Transformer bay breaker-failure protection
  • Bus coupler breaker-failure protection
  • Capacitor bank breaker-failure protection

Typical operating sequence

  1. A protection function issues a trip command.
  2. Circuit-breaker failure protection starts.
  3. The relay monitors the current and configured supervision signals.
  4. If the breaker fails to clear the fault within the set time, backup tripping is initiated.
  5. The relevant surrounding breakers are tripped according to the station breaker-failure philosophy.

Important settings include current thresholds, retrip time, backup trip time and initiation logic.

14. Broken Conductor Detection

REC670 includes:

BRCPTOC – Broken Conductor Check

A broken conductor is a series fault that may not produce sufficient fault current to operate conventional overcurrent protection.

The broken conductor function evaluates current unbalance between the phases.

It can provide an alarm or trip when the configured conditions indicate a broken conductor.

Important settings include:

  • Minimum phase current
  • Current unbalance threshold
  • Operating delay
  • Reset time
  • Load conditions
  • Normal system phase asymmetry

The settings must be selected to detect abnormal conductor conditions without operating during normal load imbalance.

15. Voltage and Frequency Protection

REC670 can also provide voltage and frequency protection functions.

These functions may be useful for monitoring and protecting the bay or associated equipment.

Undervoltage protection

UV2PTUV detects voltage below configured thresholds.

Possible applications include:

  • Loss of supply
  • Abnormal network voltage
  • Backup voltage protection
  • Load shedding schemes

Overvoltage protection

OV2PTOV detects excessive voltage.

It can provide protection against abnormal voltage conditions that may damage connected equipment.

Residual overvoltage protection

ROV2PTOV monitors residual voltage and can be used for earth-fault detection in suitable network grounding arrangements.

Underfrequency protection

SAPTUF detects system frequency below the configured threshold.

Overfrequency protection

SAPTOF detects system frequency above the configured threshold.

Rate-of-change-of-frequency protection

SAPFRC evaluates the rate at which system frequency changes.

It may be used in suitable load shedding, generation control or system protection applications.

16. IEC 61850 Communication in REC670

REC670 is designed for integration into IEC 61850-based substation automation systems.

IEC 61850 provides standardized communication between bay control IEDs, protection relays and station-level systems.

Typical communication capabilities include:

  • IEC 61850 MMS
  • IEC 61850 GOOSE
  • SCL engineering
  • Logical nodes and data objects
  • Event and alarm reporting
  • Remote monitoring and control
  • Interlocking signals
  • Circuit-breaker status exchange

16.1 IEC 61850 MMS

MMS communication is commonly used between REC670 and the station-level HMI or SCADA system.

Typical information includes:

  • Circuit-breaker position
  • Disconnector position
  • Earthing-switch position
  • Control commands
  • Protection alarms
  • Measurements
  • Event records
  • IED health status

16.2 IEC 61850 GOOSE

GOOSE provides fast peer-to-peer communication between IEDs.

In a substation, GOOSE can be used for:

  • Interlocking
  • Circuit-breaker status exchange
  • Protection signals
  • Blocking and permissive signals
  • Direct transfer signals
  • Bay-to-bay communication

The exact application depends on the station architecture and configured signals.

16.3 SCL engineering

Substation Configuration Language files are used to exchange IEC 61850 engineering information.

A typical engineering workflow includes:

  1. Configure the REC670 IED.
  2. Define the required IEC 61850 data.
  3. Export the SCL file.
  4. Integrate the IED into the station configuration.
  5. Configure GOOSE publishers and subscribers.
  6. Import updated configurations as required.
  7. Verify communication.
  8. Test the complete control and protection application.

17. PCM600 Engineering and Configuration

ABB PCM600 – Protection and Control IED Manager is used for engineering and configuration of compatible REC670 IEDs.

Typical engineering activities include:

  1. Create a new PCM600 project.
  2. Add the REC670 IED.
  3. Select the correct product version and connectivity package.
  4. Verify the hardware configuration.
  5. Configure analog inputs.
  6. Configure binary inputs and outputs.
  7. Configure circuit-breaker control.
  8. Configure disconnector control.
  9. Configure earthing-switch control.
  10. Develop electrical interlocking logic.
  11. Configure synchrocheck.
  12. Configure auto-reclosing.
  13. Configure protection functions.
  14. Configure IEC 61850 communication.
  15. Validate the application.
  16. Download the configuration to the IED.
  17. Perform functional tests.

Application configuration

Application configuration connects the control functions with the actual field signals.

For example, the circuit-breaker control logic must receive the appropriate position feedback and issue commands through the correct binary outputs.

The engineer should verify:

  • Open command
  • Close command
  • Open position feedback
  • Closed position feedback
  • Intermediate position
  • Command supervision
  • Interlocking conditions
  • Local and remote control authority

Incorrect signal mapping can cause control failures or unsafe switching operations.

18. Human-Machine Interface and Local Control

The REC670 platform supports local operation and monitoring according to the installed hardware and configuration.

The local HMI can provide access to information such as:

  • Single-line diagrams
  • Circuit-breaker status
  • Disconnector status
  • Earthing-switch status
  • Measurements
  • Alarms
  • Events
  • Protection indications
  • Control commands

The exact HMI functionality depends on the selected IED hardware and product configuration.

Local and remote control

A substation control system normally supports different operating levels.

Examples include:

  • Local control at the switchgear
  • Bay-level control
  • Station-level control
  • Remote control from a control centre

The control authority and selection logic must be clearly defined.

The operator should be able to determine which control level currently has authority.

19. Testing and Commissioning of REC670

REC670 commissioning must cover both control and protection functionality.

Testing only the protection functions is insufficient for a bay control IED.

19.1 Hardware and wiring inspection

Verify:

  • IED model and ordering information
  • Auxiliary DC supply
  • CT wiring
  • VT wiring
  • Binary input wiring
  • Binary output wiring
  • Circuit-breaker control circuits
  • Disconnector control circuits
  • Earthing-switch circuits
  • Communication connections
  • Panel grounding

19.2 Circuit-breaker control testing

Test the complete control sequence.

Verify:

  • Open command
  • Close command
  • Local control
  • Remote control
  • Open feedback
  • Closed feedback
  • Intermediate position
  • Command failure
  • Control authority

19.3 Disconnector and earthing-switch testing

Verify the control and feedback of each switching device.

Test the required interlocking conditions and ensure that unsafe operations are prevented.

19.4 Interlocking testing

Prepare an interlocking test matrix based on the approved substation switching philosophy.

For each switching device, verify the permissive and blocking conditions.

Examples include:

  • Circuit-breaker open before disconnector operation
  • Earthing switch operation only under approved isolation conditions
  • No conflicting switching commands
  • Correct busbar selection
  • Correct local and remote control authority

19.5 Synchrocheck testing

Using a suitable secondary injection test set, verify:

  • Voltage difference
  • Phase angle difference
  • Frequency difference
  • Live-bus and live-line conditions
  • Dead-bus and dead-line conditions
  • Closing permissive output

19.6 Auto-reclosing testing

Verify:

  • Initiation
  • Dead time
  • Reclaim time
  • Reclosing sequence
  • Blocking conditions
  • Circuit-breaker readiness
  • Synchronism-check permission
  • Final closing command

19.7 IEC 61850 testing

Verify:

  • MMS communication
  • GOOSE publishing
  • GOOSE subscription
  • Signal mapping
  • Communication supervision
  • Quality indications
  • Correct operation of interlocking and control logic

20. Common REC670 Problems and Troubleshooting

Problem 1: Circuit-breaker does not close

Possible causes:

  • Interlocking condition not satisfied
  • Incorrect circuit-breaker position feedback
  • Incorrect control authority
  • Missing close permissive
  • Synchrocheck not satisfied
  • Binary output configuration problem

Recommended checks: review the control logic, interlocking signals and circuit-breaker status feedback.

Problem 2: Disconnector operation is blocked

Possible causes:

  • Circuit-breaker not in the required position
  • Incorrect auxiliary contacts
  • Earthing-switch interlocking
  • Incorrect busbar selection
  • Missing permissive signal

Recommended checks: review the approved interlocking matrix and verify the field status signals.

Problem 3: Incorrect position indication

Possible causes:

  • Incorrect binary input assignment
  • Auxiliary contact wiring problems
  • Incorrect logic inversion
  • Intermediate position not handled correctly
  • Communication mapping errors

Recommended checks: compare field auxiliary contact states with the IED indications.

Problem 4: Synchrocheck does not permit closing

Possible causes:

  • Voltage difference outside the permitted range
  • Phase angle difference too high
  • Frequency difference too high
  • Incorrect voltage input configuration
  • Missing live-bus or live-line indication

Recommended checks: verify voltage measurements and the synchrocheck settings.

Problem 5: IEC 61850 control command fails

Possible causes:

  • Incorrect control model
  • Incorrect data mapping
  • Missing communication
  • Incorrect control authority
  • Command selection or execution problem
  • Incorrect GOOSE or MMS configuration

Recommended checks: inspect the IEC 61850 configuration and verify the complete command path.

21. REC670 Compared with Other ABB Relays

ABB offers several Relion IEDs designed for different substation applications.

RelayMain application
REG670Generator protection
RET670Transformer protection
RED670Line differential protection
REL670Line distance protection
REL650Line distance protection
REB670Busbar differential protection
REC670Bay control and protection

REC670 vs REB670

REC670 is primarily a bay control IED with additional protection capabilities.

REB670 is primarily a busbar differential protection IED.

They may be used together in the same substation.

For example, REB670 can protect the busbar, while REC670 controls the circuit-breakers and disconnectors associated with individual bays.

REC670 vs REC650

Both REC670 and REC650 are bay control products in the ABB Relion family.

Their control capacity, available configurations and application flexibility differ.

The selection should be based on the number of controlled objects, required interlocking, protection functions and project requirements.

22. Frequently Asked Questions About ABB REC670

What is ABB REC670 used for?

ABB REC670 is a bay control IED used for control, monitoring, interlocking and protection applications in high-voltage substations.

Is REC670 a protection relay or a bay control unit?

Its primary application is bay control, but it also supports a broad range of protection functions.

Can REC670 control circuit-breakers?

Yes. It supports circuit-breaker control and monitoring as part of its bay control functionality.

Can REC670 control disconnectors and earthing switches?

Yes. The bay control application can be configured for disconnector and earthing-switch control, including electrical interlocking.

Does REC670 support synchrocheck?

Yes. It includes the SESRSYN function for synchrocheck, energizing check and synchronizing applications.

Does REC670 support auto-reclosing?

Yes. The product documentation identifies the SMBRREC auto-recloser function.

Can REC670 be used for capacitor bank protection?

Yes. The REC670 product documentation includes capacitor bank protection and related unbalance protection functions for suitable configurations.

Which software is used to configure REC670?

ABB PCM600 is used for engineering and configuration of compatible REC670 IEDs.

Does REC670 support IEC 61850?

Yes. REC670 supports IEC 61850-based substation automation integration, subject to the installed product version and configuration.

Can REC670 be tested using OMICRON?

Yes. Suitable OMICRON CMC test equipment can be used for protection function testing, binary input and output testing, synchrocheck testing and other commissioning activities.

23. Conclusion

The ABB REC670 is an integrated bay control and protection IED designed for high-voltage substation applications.

Its main capabilities include circuit-breaker control, disconnector and earthing-switch control, electrical interlocking, synchrocheck, auto-reclosing, protection functions and IEC 61850 communication.

REC670 can be particularly useful in substations where bay-level control and protection functions need to be integrated into a common IED.

For protection engineers, commissioning engineers and substation automation specialists, understanding REC670 is important for PCM600 configuration, interlocking engineering, switching-device control, IEC 61850 integration and complete bay commissioning.

Elec-Engg – Practical Power System Protection and Substation Automation Training

Explore more technical articles and training resources covering ABB protection relays, bay control, PCM600, IEC 61850 and relay testing.


Related Articles

  • ABB REG670 Generator Protection Relay
  • ABB RET670 Transformer Protection Relay
  • ABB RED670 Line Differential Protection Relay
  • ABB REL670 Distance Protection Relay
  • ABB REL650 Line Distance Protection Relay
  • ABB REB670 Busbar Protection Relay
  • ABB PCM600 Engineering Software – Complete Guide
  • IEC 61850 GOOSE Communication in Substations
  • Substation Bay Control and Electrical Interlocking
  • Circuit-Breaker Control and Monitoring