IEC 61850 MMS Communication in MiCOM Relays – Architecture, Data Access, Reporting, Controls and Configuration

Introduction

IEC 61850 MMS (Manufacturing Message Specification) is one of the fundamental communication services used in modern substation automation systems. It enables protection relays, bay controllers, SCADA systems and substation computers to exchange monitoring, control and configuration-related information over Ethernet networks.

MiCOM protection relays equipped with IEC 61850 communication capabilities can operate as server devices, providing information to external IEC 61850 clients.

Through MMS communication, engineers can access relay measurements, protection indications, equipment status, alarms and event information without requiring individual hardwired connections for every monitoring signal.

MMS is particularly important in MiCOM P40 Agile protection relays because it enables integration with substation automation systems, including multi-vendor architectures.

This article explains the architecture, communication principles, data models, reporting mechanisms, control services and practical engineering considerations associated with IEC 61850 MMS in MiCOM protection relays.

1. What Is MMS in IEC 61850?

MMS stands for Manufacturing Message Specification and is defined in ISO 9506.

IEC 61850 uses MMS as its application-layer communication protocol for client-server communication.

In a typical substation application:

  • The MiCOM protection relay operates as an MMS server.
  • The SCADA system or station controller operates as an MMS client.
  • Ethernet provides the communication medium.
  • TCP/IP provides the transport and network services.

The client establishes a communication association with the relay and accesses the information exposed through its IEC 61850 data model.

For example, a SCADA system can read the phase currents measured by a MiCOM feeder protection relay, monitor circuit breaker status and receive protection operation indications.

MMS supports both monitoring and control services, subject to the functions implemented and enabled in the particular relay.

2. MMS Communication Architecture in MiCOM Relays

A typical MMS architecture consists of three main elements.

1. MMS Client

The client is an external system that requests information or performs supported operations.

Examples include:

  • SCADA master stations.
  • SICAM PAS.
  • Substation HMI systems.
  • IEC 61850 engineering and diagnostic tools.
  • Station controllers.

2. MMS Server

The MiCOM relay provides the server functionality.

It exposes its IEC 61850 logical devices, logical nodes, data objects and supported communication services.

3. Ethernet Communication Network

The communication network connects the client and server devices.

The network normally includes industrial Ethernet switches, fiber-optic connections and appropriate network security equipment.

3. How MMS Communication Works

MMS communication involves several stages.

Step 1: Establishing Ethernet Connectivity

The MiCOM relay must have a correctly configured Ethernet interface.

Engineers configure the required network parameters, such as:

  • IP address.
  • Subnet mask.
  • Default gateway, where applicable.
  • Ethernet communication settings.

The client and relay must have appropriate network connectivity.

Step 2: Establishing TCP Communication

MMS communication typically uses TCP port 102.

The client establishes a TCP connection with the relay.

TCP provides reliable transport between the two devices.

Step 3: Establishing the MMS Association

After establishing TCP connectivity, the client and server perform the necessary protocol association procedures.

The IEC 61850 communication stack uses the relevant application and presentation-layer services to establish the association.

Step 4: Accessing the IEC 61850 Data Model

Once the association is established, the client can access the data model exposed by the MiCOM relay.

Typical information includes:

  • Protection status.
  • Current and voltage measurements.
  • Circuit breaker position.
  • Protection alarms.
  • Relay health information.
  • Operational indications.

Step 5: Reading and Monitoring Information

The client can read available data attributes and subscribe to supported reporting services.

This enables continuous monitoring of the protection system.

4. IEC 61850 Data Model Used by MiCOM MMS

IEC 61850 defines a standardized hierarchical data model.

The structure includes:

  1. Physical IED.
  2. Logical devices.
  3. Logical nodes.
  4. Data objects.
  5. Data attributes.

For example, a MiCOM relay may expose measurement information through an MMXU logical node.

Consider the following conceptual example:

LevelExample
IEDMiCOM_P143
Logical DevicePROT
Logical NodeMMXU1
Data ObjectA
Data AttributephsA.cVal.mag.f

This example represents a possible IEC 61850 path for a phase current magnitude.

The exact logical device names, logical node instances and data object paths depend on the MiCOM model and its implemented data model.

5. Important Logical Nodes for MMS Communication

Several IEC 61850 logical nodes are commonly used when integrating MiCOM protection relays.

Logical nodeFunction
LLN0Logical device common information
LPHDPhysical device information
MMXUMeasurements
PTOCTime overcurrent protection
PIOCInstantaneous overcurrent protection
PDIFDifferential protection
PDISDistance protection
XCBRCircuit breaker
XSWICircuit switch
PTRCProtection trip conditioning
GGIOGeneric input/output
RRECAutoreclosing

These logical nodes provide standardized representations of protection, measurement and control functions.

For example, the MMXU logical node can expose electrical measurements, while XCBR represents circuit breaker-related information.

Not every logical node is necessarily available in every MiCOM relay.

6. MMS Data Access Services

IEC 61850 defines several services that allow clients to access server information.

Important services include:

Read

Allows the client to retrieve the current value of a data attribute.

Example: Reading phase A current from a MiCOM feeder relay.

Write

Allows writing to supported data attributes, subject to the relay’s implementation and access permissions.

GetNameList

Allows a client to discover available names and objects within the server data model.

GetVariableAccessAttributes

Provides information about the attributes of a specified variable.

GetDataValues

Allows retrieval of the values associated with specified variables.

These services help external systems interact with the MiCOM relay’s IEC 61850 data model.

7. IEC 61850 Reporting in MiCOM Relays

Reporting is one of the most important MMS functions.

Instead of continuously polling every measurement and indication, an MMS client can configure reporting services to receive information when relevant changes occur.

IEC 61850 defines two principal reporting mechanisms:

  • Buffered Report Control Blocks (BRCB).
  • Unbuffered Report Control Blocks (URCB).

7.1 Buffered Reporting – BRCB

Buffered reporting stores report information for subsequent delivery.

If the communication connection is interrupted, supported buffered reports can retain events and deliver them after communication is restored.

This is particularly useful for event monitoring and maintaining an event sequence during temporary communication interruptions.

7.2 Unbuffered Reporting – URCB

Unbuffered reporting provides reports while the client association is available.

Reports that cannot be delivered during a communication interruption are generally not retained for later transmission.

7.3 Important Report Control Parameters

ParameterDescription
RptIDReport identifier
DatSetAssociated dataset
ConfRevDataset configuration revision
TrgOpsReport trigger options
OptFldsOptional report fields
BufTmBuffer time
IntgPdIntegrity period
GIGeneral interrogation
SqNumSequence number

Engineers should understand these parameters when integrating MiCOM relays with SCADA and station-level systems.

8. Data Sets in MiCOM IEC 61850 Communication

A dataset is a collection of data attributes selected for monitoring or reporting.

For example, an engineer may configure a dataset containing:

  • Phase A current.
  • Phase B current.
  • Phase C current.
  • Circuit breaker position.
  • Overcurrent protection start.
  • Overcurrent protection trip.
  • Relay health status.

The client can then receive information associated with this dataset through a configured reporting mechanism.

Datasets are also fundamental to GOOSE communication, although their configuration and transmission mechanisms differ from MMS reporting.

9. MMS Control Services in MiCOM Relays

IEC 61850 MMS can also support control operations.

For example, an external client may issue a supported command to operate a circuit breaker through a MiCOM relay.

IEC 61850 defines several control models:

Control modelDescription
Direct OperateDirect control operation
SBOSelect Before Operate
SBOwSelect Before Operate with enhanced security

The exact control models supported by a MiCOM relay depend on its implementation.

In a typical breaker control application, the client selects the required control object, performs the necessary checks and executes the command.

The relay may also apply local and remote control permissions, interlocking logic and command validation.

Important: IEC 61850 control should always be commissioned with appropriate operational safety measures. A successful communication command does not automatically prove that the breaker operating circuit and associated interlocking are functioning correctly.

10. MMS Communication in SICAM PAS and MiCOM Systems

SICAM PAS can be used as an IEC 61850 client in substation automation applications.

A typical architecture includes multiple MiCOM protection relays connected to an Ethernet network and communicating with SICAM PAS.

The integration process generally involves:

  1. Preparing the MiCOM relay IEC 61850 configuration.
  2. Obtaining the appropriate IED description file.
  3. Importing the IED into the system engineering environment.
  4. Establishing the communication configuration.
  5. Selecting the required measurements and indications.
  6. Configuring reporting.
  7. Mapping information to the station-level database.
  8. Testing communication and signal behavior.

This architecture allows information from multiple MiCOM relays to be collected and presented through a centralized substation automation system.

11. Testing MMS Communication Using Wireshark

Wireshark is a valuable diagnostic tool for IEC 61850 commissioning and troubleshooting.

Engineers can use it to capture and inspect Ethernet communication between a MiCOM relay and an IEC 61850 client.

Important checks include:

  • TCP connection establishment.
  • TCP port 102 communication.
  • MMS association establishment.
  • MMS Read requests and responses.
  • Report transmission.
  • MMS control requests.
  • Communication termination.
  • TCP retransmissions and connection resets.

A useful Wireshark display filter is:

tcp.port == 102

This filter displays TCP traffic using the standard MMS port.

Where protocol dissection is supported, engineers can inspect decoded MMS messages to investigate communication behavior.

For GOOSE traffic, a separate filter can be used:

goose

12. Common MMS Communication Problems in MiCOM Relays

Several problems can occur during IEC 61850 integration.

ProblemPossible cause
Relay not reachableIncorrect IP configuration
TCP connection failureNetwork or firewall restriction
MMS association failureProtocol or configuration mismatch
Missing measurementsIncorrect data model mapping
Reports not receivedIncorrect RCB configuration
Missing eventsTrigger or dataset configuration
Control command rejectedAccess permission or control model
Intermittent communicationNetwork instability
Incorrect indicationWrong signal mapping or polarity

A systematic troubleshooting process should begin with physical connectivity and proceed through IP networking, TCP communication, MMS association, data model access and application-level configuration.

13. MMS Security Considerations

IEC 61850 communication networks must be designed with cybersecurity in mind.

Important considerations include:

  • Restricting access to relay communication interfaces.
  • Network segmentation.
  • Firewall configuration.
  • Role-based access control where supported.
  • Secure engineering workstation access.
  • Controlled remote access.
  • Configuration backups.
  • Monitoring communication events.
  • Applying relevant IEC 62351 security mechanisms where supported.

Not all MiCOM generations support the same cybersecurity features. Engineers must consult the relevant product documentation before designing a security architecture.

14. MMS vs GOOSE Communication

MMS and GOOSE are both important IEC 61850 communication mechanisms, but they serve different purposes.

FeatureMMSGOOSE
Communication typeClient-serverPublisher-subscriber
Main purposeMonitoring and controlFast event exchange
TransportTCP/IPEthernet multicast
Standard portTCP 102Ethernet EtherType 0x88B8
Communication modelRequest/response and reportingEvent-based publishing
Typical applicationSCADA monitoringInterlocking and protection signals
Data transmissionOn request or through reportsPeriodic retransmission and event-driven updates

Both communication mechanisms can operate simultaneously in the same MiCOM IEC 61850 substation network.

15. Practical Engineering Checklist

Before commissioning MMS communication with a MiCOM relay, verify the following:

  • Confirm that the relay supports IEC 61850 MMS.
  • Verify the relay hardware and firmware.
  • Check the Ethernet configuration.
  • Confirm IP connectivity.
  • Verify TCP port 102 accessibility.
  • Establish the MMS association.
  • Inspect the available logical devices and nodes.
  • Verify measurement values.
  • Configure the required datasets.
  • Configure report control blocks.
  • Verify buffered and unbuffered reporting as applicable.
  • Test supported control operations.
  • Inspect communication using Wireshark.
  • Save and document the final configuration.

16. Conclusion

MMS communication is a fundamental component of IEC 61850 implementation in MiCOM protection relays.

It enables standardized monitoring, data access, event reporting and supported control operations between protection IEDs and substation automation systems.

For protection and commissioning engineers, understanding MMS communication is essential when integrating MiCOM relays into SCADA systems, SICAM PAS and multi-vendor substation automation architectures.

A good understanding of logical nodes, datasets, report control blocks and MMS services helps engineers configure and troubleshoot communication systems more efficiently.

IEC 61850 and MiCOM Training by Elec-Engg

Elec-Engg provides practical training in MiCOM protection relays, IEC 61850 communication and substation automation.

Our training covers:

  • MiCOM relay configuration and engineering.
  • IEC 61850 MMS and GOOSE communication.
  • Logical nodes and data models.
  • SCL file engineering.
  • Report control blocks and datasets.
  • GOOSE publisher and subscriber configuration.
  • SICAM PAS integration.
  • IEC 61850 testing and troubleshooting using practical engineering examples.