IEC 61850 in MiCOM Relays – Complete Introduction, Architecture, Features and Applications

Introduction

IEC 61850 is an international communication standard widely used in modern electrical substations for protection, control, monitoring and automation. It provides a standardized method for exchanging information between Intelligent Electronic Devices (IEDs), including protection relays, bay controllers, substation computers and SCADA systems.

MiCOM protection relays, particularly the MiCOM P40 Agile family, support IEC 61850 communication in various models and hardware configurations. This allows MiCOM relays to exchange protection and control information with other substation IEDs without relying exclusively on conventional hardwired signals.

By implementing IEC 61850, engineers can develop advanced substation automation systems using Ethernet communication, MMS client-server services and GOOSE peer-to-peer messaging.

Understanding IEC 61850 in MiCOM relays is important for protection engineers, commissioning engineers and substation automation specialists involved in modernizing conventional substations or designing new digital substations.

1. What Is IEC 61850 in MiCOM Protection Relays?

IEC 61850 is more than a communication protocol. It defines a comprehensive framework for substation automation, including:

  • Standardized data models.
  • Logical nodes and logical devices.
  • Client-server communication using MMS.
  • Fast peer-to-peer communication using GOOSE.
  • Reporting and event notification.
  • Substation Configuration Language (SCL).
  • Time synchronization and system integration.

In a MiCOM protection relay, IEC 61850 provides an interface through which external systems can access measurements, indications, alarms, protection information and control functions, depending on the particular relay implementation.

For example, a MiCOM feeder protection relay can communicate the following information to a substation automation system:

  • Circuit breaker position.
  • Protection trip indication.
  • Phase overcurrent operation.
  • Earth fault protection operation.
  • Current and voltage measurements.
  • Protection alarms.
  • Relay health and device status.
  • Disturbance recording information.

The exact available information depends on the relay model, firmware, communication option and IEC 61850 implementation.

2. Which MiCOM Relays Support IEC 61850?

IEC 61850 is available in several MiCOM protection relay families.

Examples include:

MiCOM relayMain application
P141Feeder protection
P143Feeder protection
P145Feeder protection
P211Motor protection
P342Generator protection
P343Generator protection
P444Distance protection
P546Line differential protection
P643Transformer protection
P645Transformer protection

Important: This is an application-oriented list, not a guarantee that every hardware version supports IEC 61850. Engineers must check the relay order code, communication hardware, firmware and corresponding technical manual before designing an IEC 61850 system.

3. IEC 61850 Communication Architecture in MiCOM Relays

A typical IEC 61850 substation architecture consists of protection relays connected through Ethernet switches to a station-level computer or SCADA system.

The architecture generally includes the following components:

1. Protection IEDs

MiCOM relays perform protection, control and monitoring functions. They exchange information with other IEDs through IEC 61850 communication services.

2. Ethernet switches

Industrial Ethernet switches provide network connectivity between protection relays, bay controllers and station-level equipment.

3. Station-level computer

A substation automation computer collects information from multiple IEDs and provides centralized monitoring and control.

4. SCADA system

The SCADA system receives measurements, indications, alarms and events from the substation automation system or directly from protection IEDs.

5. Engineering workstation

Engineers use configuration and diagnostic software to configure IED communication, examine data models and troubleshoot network communication.

Two major communication mechanisms are particularly important in MiCOM IEC 61850 systems:

  • MMS communication.
  • GOOSE communication.

4. MMS Communication in MiCOM Relays

MMS stands for Manufacturing Message Specification.

It is an application-layer communication protocol used by IEC 61850 for client-server communication.

In a typical MiCOM application, the protection relay operates as an IEC 61850 server, while external equipment such as a station controller, HMI or SCADA gateway operates as a client.

MMS communication supports several functions:

  • Reading relay measurements.
  • Reading protection indications.
  • Monitoring equipment status.
  • Receiving event notifications.
  • Buffered and unbuffered reporting.
  • Executing supported control commands.
  • Retrieving disturbance records.

For example, a substation computer can communicate with a MiCOM P143 feeder protection relay and read its phase currents, breaker position and protection operation indications.

The communication is established over Ethernet using TCP/IP.

5. GOOSE Communication in MiCOM Relays

GOOSE stands for Generic Object Oriented Substation Event.

It is one of the most important features of IEC 61850 because it enables fast peer-to-peer communication between protection and control IEDs.

Unlike conventional MMS client-server communication, GOOSE uses Ethernet multicast messaging.

A GOOSE publisher transmits information to the network, and subscribed IEDs receive and process the information.

For example, consider a substation with two incoming feeders and a bus coupler.

When one feeder detects a fault, its protection relay can publish a GOOSE trip or blocking signal. Another MiCOM relay subscribed to that signal can receive the information and use it in its programmable logic.

Typical GOOSE applications include:

  • Circuit breaker interlocking.
  • Busbar protection signaling.
  • Breaker failure protection initiation.
  • Intertripping between protection relays.
  • Blocking and permissive protection schemes.
  • Transfer trip applications.
  • Automatic changeover schemes.

In MiCOM relays, received GOOSE signals can be mapped to virtual inputs and subsequently used within the Programmable Scheme Logic (PSL), subject to the relay’s supported signal types and configuration.

6. IEC 61850 Logical Nodes in MiCOM Relays

The IEC 61850 data model is based on logical devices, logical nodes, data objects and data attributes.

This standardized structure allows different IEDs to represent their information in a common format.

Some important logical nodes used in protection and substation automation include:

Logical nodeDescription
XCBRCircuit breaker
XSWICircuit switch
PTOCTime overcurrent protection
PIOCInstantaneous overcurrent protection
PDIFDifferential protection
PDISDistance protection
MMXUMeasurement functions
GGIOGeneric input/output
PTRCProtection trip conditioning
RRECAutoreclosing
LPHDPhysical device information
LLN0Logical device common information

For example, XCBR represents circuit breaker information, while MMXU is used for electrical measurements.

The actual logical nodes and data objects implemented in a MiCOM relay must be checked in its Model Implementation Conformance Statement (MICS).

7. IEC 61850 Configuration Software for MiCOM Relays

MiCOM IEC 61850 engineering is performed using the appropriate configuration tools for the particular relay generation.

Depending on the relay family and software version, engineers may use:

  • MiCOM S1 Agile.
  • MiCOM S1 Studio.
  • IEC 61850 IED Configurator.
  • IEC 61850 Configuration Editor.

The configuration process may include:

  1. Connecting to the MiCOM relay.
  2. Reading the existing device configuration.
  3. Configuring the Ethernet interface.
  4. Defining IEC 61850 communication parameters.
  5. Configuring GOOSE publishing.
  6. Configuring GOOSE subscriptions.
  7. Mapping received signals to virtual inputs.
  8. Generating or importing SCL files.
  9. Downloading the configuration.
  10. Testing the communication.

The exact workflow depends on the MiCOM relay model and the software version.

8. IEC 61850 SCL Files in MiCOM Systems

Substation Configuration Language (SCL) is an XML-based engineering language defined by IEC 61850.

It allows engineers to describe IED capabilities, communication configuration and substation automation architecture.

The main SCL file types include:

FileDescription
ICDIED Capability Description
CIDConfigured IED Description
IIDInstantiated IED Description
SCDSubstation Configuration Description
SSDSystem Specification Description

These files are essential when integrating MiCOM relays into a multi-vendor IEC 61850 substation.

For example, an SCD file can describe the complete substation configuration, including multiple protection IEDs, communication networks and GOOSE signal exchanges.

9. IEC 61850 Advantages for MiCOM Protection Systems

Implementing IEC 61850 in MiCOM protection systems offers several advantages.

Reduced hardwiring

GOOSE communication can replace selected conventional copper signal connections between protection relays.

Faster communication

GOOSE provides high-speed event communication suitable for protection and automation applications.

Interoperability

Standardized data models and communication services simplify integration between compatible IEDs from different manufacturers.

Centralized monitoring

Measurements, alarms and protection indications can be collected through a common communication network.

Flexible engineering

Changes to communication logic and signal assignments can be implemented through engineering configuration, reducing the need for physical wiring modifications.

Improved diagnostics

Communication monitoring and diagnostic tools help engineers investigate network and IED communication problems.

10. Important Considerations Before Using IEC 61850 in MiCOM Relays

IEC 61850 capabilities are not identical across all MiCOM relays.

Before implementing an IEC 61850 project, engineers should verify:

  • Supported IEC 61850 edition.
  • Available Ethernet communication hardware.
  • Supported MMS services.
  • GOOSE publisher and subscriber capabilities.
  • Available logical nodes and data objects.
  • Supported control models.
  • SCL compatibility.
  • Firmware and configuration software versions.
  • Network architecture and redundancy support.
  • Time synchronization capabilities.

Another important consideration is that IEC 61850 communication does not automatically mean that every relay setting can be changed through MMS. Some MiCOM implementations provide monitoring and control services but require dedicated engineering software for protection setting changes.

11. IEC 61850 Testing and Commissioning of MiCOM Relays

Testing is an essential part of every IEC 61850 implementation.

Commissioning engineers should verify both the communication configuration and the actual protection/control behavior.

Typical testing activities include:

  • Checking Ethernet connectivity.
  • Verifying IP address and network settings.
  • Reading the relay data model.
  • Checking MMS communication.
  • Verifying report generation.
  • Testing GOOSE publishing.
  • Testing GOOSE subscription.
  • Checking virtual input mapping.
  • Verifying PSL operation.
  • Testing circuit breaker interlocking.
  • Checking GOOSE supervision and communication failure indications.
  • Verifying disturbance record retrieval.

Tools such as Wireshark and IEC 61850 client applications can help engineers analyze MMS and GOOSE communication.

12. Practical Example: MiCOM GOOSE Communication Between Two Feeder Relays

Consider a substation with two outgoing feeders protected by MiCOM P143 relays.

The objective is to exchange a protection signal between the two relays using IEC 61850 GOOSE.

The basic operation is as follows:

  1. MiCOM Relay 1 detects a predefined protection or control condition.
  2. The relay publishes the configured signal through a GOOSE message.
  3. The Ethernet switch forwards the multicast message.
  4. MiCOM Relay 2 receives the GOOSE message.
  5. The received signal is mapped to an available virtual input.
  6. The virtual input is connected to the required PSL logic.
  7. The programmed logic performs the required control or protection-related action.

During commissioning, engineers must verify the complete signal path, including the publisher dataset, communication parameters, subscriber configuration, virtual input mapping and final PSL operation.

The actual protection application must also be assessed for communication failure behavior, GOOSE supervision, network availability and fail-safe design.

13. Conclusion

IEC 61850 significantly expands the communication and automation capabilities of MiCOM protection relays.

Through MMS, GOOSE, standardized logical nodes and SCL engineering, MiCOM IEDs can become integrated components of modern substation automation systems.

For protection and commissioning engineers, understanding the relationship between IEC 61850 communication, MiCOM configuration software, programmable logic and Ethernet network architecture is essential for successful project implementation.

Learning IEC 61850 through practical MiCOM engineering examples is particularly valuable because it connects theoretical communication concepts with real protection and control applications.

IEC 61850 and MiCOM Relay Training by Elec-Engg

At Elec-Engg, we provide practical technical training in power system protection, MiCOM protection relays and IEC 61850 substation automation.

Our training programs include:

  • MiCOM protection relay configuration and engineering.
  • IEC 61850 fundamentals and practical implementation.
  • MMS communication and reporting.
  • GOOSE publisher and subscriber configuration.
  • SCL file engineering.
  • GOOSE-based interlocking and protection schemes.
  • IEC 61850 testing and troubleshooting.
  • Integration of protection relays with SCADA and substation automation systems.

Training is available through:

  • Online technical training.
  • Structured self-paced training.
  • Face-to-face training.
  • Customized in-house training for utilities, industries and engineering companies.

Visit Elec-Engg: https://elec-engg.com/