micom-relay-firmware-upgrade-compatibility-testing

Table Of Contents
  1. Introduction
  2. 1. Understanding the S1 Agile Engineering Environment
  3. 2. Common Categories of S1 Agile Problems
  4. 3. S1 Agile Installation and Software Startup Problems
  5. 4. S1 Agile Cannot Connect to the MiCOM Relay
  6. 5. Troubleshooting Ethernet Connection Problems
  7. 6. S1 Agile Project Cannot Be Opened
  8. 7. Project Does Not Match the Connected Relay
  9. 8. Configuration Upload and Download Problems
  10. 9. Troubleshooting Protection Settings Problems
  11. 10. Troubleshooting IEC 61850 Configuration in S1 Agile
  12. 11. Troubleshooting MMS Communication
  13. 12. Troubleshooting GOOSE Communication
  14. 13. SCL File and IEC 61850 Interoperability Problems
  15. 14. Troubleshooting Time Synchronization
  16. 15. Practical Troubleshooting Example: MiCOM Relay and SICAM PAS
  17. 16. Practical Troubleshooting Example: GOOSE Interlocking Failure
  18. 17. Recommended S1 Agile Troubleshooting Workflow
  19. 18. Best Practices for S1 Agile Engineering
  20. 19. S1 Agile Troubleshooting Checklist
  21. 20. Training on MiCOM S1 Agile and IEC 61850 Engineering
  22. Conclusion

Introduction

S1 Agile is an important engineering tool for configuring, maintaining, and troubleshooting supported MiCOM protection relays. It allows protection engineers to work with device settings, configuration parameters, communication options, and other engineering functions according to the capabilities of the connected relay.

During engineering and commissioning, however, different problems may occur. S1 Agile may fail to connect to a relay, a project may not open correctly, configuration data may be unavailable, or communication settings may not match the actual device.

IEC 61850 engineering can introduce additional challenges, particularly when troubleshooting MMS communication, GOOSE messaging, device identification, and SCL file compatibility.

This article provides a practical troubleshooting guide for engineers working with S1 Agile and MiCOM P40 Agile protection relays.

The exact functions, menus, connection methods, and supported operations depend on the relay model, order code, firmware, communication hardware, and S1 Agile release. Always consult the relevant manufacturer documentation before changing device parameters.

1. Understanding the S1 Agile Engineering Environment

S1 Agile is used for engineering supported MiCOM protection and control devices.

Depending on the device and software release, engineering activities may include:

  • Connecting to a protection relay.
  • Identifying the connected device.
  • Retrieving or transferring configuration data.
  • Reviewing protection settings.
  • Modifying supported device parameters.
  • Managing communication settings.
  • Reviewing available IEC 61850 information.
  • Supporting device maintenance and commissioning.

Troubleshooting should begin by identifying which part of the engineering process is failing.

For example, a connection failure is different from a project compatibility problem. Likewise, successfully connecting to a relay does not prove that the correct configuration has been retrieved.

A systematic approach helps avoid unnecessary configuration changes.

2. Common Categories of S1 Agile Problems

S1 Agile problems can generally be divided into the following categories.

2.1 Software installation problems

Examples include:

  • S1 Agile does not start.
  • Installation fails.
  • Required components are missing.
  • Device support packages are unavailable.
  • The software behaves unexpectedly after an update.

2.2 Project and configuration problems

Examples include:

  • An engineering project cannot be opened.
  • A project does not match the connected relay.
  • Configuration data is missing.
  • Settings cannot be transferred.
  • Project revisions are inconsistent.

2.3 Device connection problems

Examples include:

  • The relay is not detected.
  • Communication cannot be established.
  • Connection is repeatedly interrupted.
  • The wrong communication interface is selected.
  • Access is denied.

2.4 Communication configuration problems

Examples include:

  • Incorrect Ethernet parameters.
  • IP address conflicts.
  • Incorrect communication settings.
  • MMS communication failure.
  • Incorrect IEC 61850 device identification.

2.5 IEC 61850 engineering problems

Examples include:

  • Missing logical nodes or data objects.
  • Incorrect datasets.
  • Report control block problems.
  • GOOSE publisher or subscriber mismatch.
  • SCL file incompatibility.

The following sections explain how to investigate these problems.

3. S1 Agile Installation and Software Startup Problems

Before troubleshooting the relay connection, confirm that the engineering software is installed and operating correctly.

3.1 S1 Agile does not start

Possible causes include:

  • Incomplete installation.
  • Missing software components.
  • Unsupported operating environment.
  • Insufficient user permissions.
  • Conflicts with existing software components.
  • Damaged installation files.

Recommended troubleshooting procedure:

  1. Confirm that the installation completed successfully.
  2. Check the software version.
  3. Verify the supported operating environment.
  4. Confirm that the required components are installed.
  5. Check the operating system’s application error information.
  6. Consult the manufacturer’s installation documentation.

Avoid deleting project folders or shared software components as an initial troubleshooting action.

3.2 Required device support is unavailable

An engineering software installation may not automatically include support for every MiCOM device.

Possible causes include:

  • Missing device support package.
  • Software release incompatibility.
  • Incorrect installation package.
  • Unsupported device generation.

Check whether the installed S1 Agile release supports the exact relay model and firmware.

Do not assume that support for one MiCOM model automatically provides support for all devices in the same family.

3.3 Software behaves differently after an update

After updating engineering software, engineers may encounter changes in project handling or device support.

Before using an updated release:

  • Review its release information.
  • Check supported relay models.
  • Verify project compatibility.
  • Preserve the original engineering project.
  • Test the updated software using an approved project copy where possible.

4. S1 Agile Cannot Connect to the MiCOM Relay

Device connection problems are among the most common engineering issues.

The first step is to identify the intended communication method.

Depending on the relay model and available hardware, connection may use a supported front communication interface or a rear communication interface.

Do not assume that all MiCOM relays use the same physical connection or communication settings.

4.1 Check the physical connection

Inspect:

  • Communication cable.
  • Connector condition.
  • Correct relay port.
  • Correct computer interface.
  • USB or serial adapter, where applicable.
  • Ethernet cable and switch connection, where applicable.

If a USB-to-serial adapter is used, confirm that the required driver is installed and the operating system recognizes the adapter.

4.2 Check the selected communication interface

Confirm that S1 Agile is configured to use the intended interface.

A common mistake is selecting an incorrect communication port or interface.

For serial connections, verify the available port and the communication parameters required by the relay.

For Ethernet connections, verify the network adapter and IP configuration.

4.3 Check relay availability

Confirm that:

  • The relay is powered.
  • The relay has completed its startup sequence.
  • The selected communication port is enabled.
  • No physical connection fault is present.
  • The relay is not displaying an unexpected hardware or communication alarm.

4.4 Check access permissions

Some device operations may require appropriate access rights.

Verify the configured access level and authorization procedure.

Do not attempt to bypass device security or use unauthorized access methods.

5. Troubleshooting Ethernet Connection Problems

Ethernet connectivity is important when engineering supported MiCOM devices through a network interface.

Incorrect network configuration can prevent S1 Agile or another engineering client from communicating with the relay.

5.1 Verify the relay IP address

Confirm the relay’s configured IP address using an approved device identification method.

For example:

  • Relay IP address: 192.168.10.20
  • Engineering computer: 192.168.10.50
  • Subnet mask: 255.255.255.0

These are illustrative values only.

Both devices must have compatible network settings and a valid communication path.

5.2 Check the computer IP configuration

On a Windows engineering computer, open Command Prompt and use:

ipconfig

Check the active network adapter.

Confirm:

  • IPv4 address.
  • Subnet mask.
  • Default gateway, if required.
  • Correct adapter selection.

5.3 Test basic network connectivity

Where ICMP is supported and permitted, use:

ping 192.168.10.20

Replace the example address with the actual relay IP address.

Interpret the result carefully.

A successful ping indicates basic IP reachability, but it does not prove that the required engineering or IEC 61850 services are operating.

A failed ping does not necessarily prove that the relay is unavailable because ICMP may be disabled or filtered.

5.4 Check IP address conflicts

Two devices using the same IP address can cause intermittent communication problems.

Check the network configuration and consult the responsible network engineer before changing an address.

5.5 Check network restrictions

Investigate:

  • Firewall rules.
  • VLAN configuration.
  • Network access restrictions.
  • Switch port configuration.
  • Routing.
  • Network segmentation.
  • Security policies.

Do not disable site security controls without authorization.

6. S1 Agile Project Cannot Be Opened

Project compatibility problems may occur when projects are transferred between computers or opened using different engineering software releases.

Possible causes include:

  • Different S1 Agile versions.
  • Missing device support packages.
  • Unsupported project format.
  • Damaged project files.
  • Incomplete project transfer.
  • Incorrect project association.

Recommended troubleshooting procedure

Step 1: Identify the S1 Agile version used to create the project.

Step 2: Check the version installed on the current computer.

Step 3: Confirm that the required device support is available.

Step 4: Check the project file and associated folders.

Step 5: Open a separate copy rather than modifying the original project.

Step 6: Consult the manufacturer’s compatibility information if the project cannot be opened.

Always preserve the original engineering project before attempting conversion or migration.

7. Project Does Not Match the Connected Relay

A project may open successfully but still be incompatible with the connected device.

This can happen when the project was created for a different relay variant.

Check the following information:

  • Model designation.
  • Complete order code.
  • Hardware revision.
  • Firmware version.
  • Installed communication options.
  • Supported protection functions.
  • Available device configuration.

For example, two relays with similar product names may have different hardware configurations or communication capabilities.

Do not assume that a project created for one device can be downloaded into another device simply because both belong to the same MiCOM family.

Recommended solution

  1. Identify the actual connected relay.
  2. Check the project device identification.
  3. Verify hardware and firmware compatibility.
  4. Check the relevant engineering software release.
  5. Obtain the correct project or follow the approved conversion procedure.

8. Configuration Upload and Download Problems

Engineers should distinguish between retrieving configuration from a relay and transferring configuration to a relay.

The two operations have different risks.

8.1 Configuration upload or retrieval fails

Possible causes include:

  • Communication interruption.
  • Insufficient access rights.
  • Unsupported device operation.
  • Project incompatibility.
  • Incorrect interface selection.
  • Device-specific restrictions.

Recommended actions:

  • Verify the connection.
  • Confirm the device identity.
  • Check access permissions.
  • Review software compatibility.
  • Consult the model-specific engineering instructions.

8.2 Configuration download fails

Possible causes include:

  • Incorrect target device.
  • Incompatible project.
  • Firmware restrictions.
  • Communication interruption.
  • Unsupported configuration elements.
  • Device access restrictions.

Before attempting another download, identify why the original operation failed.

Do not repeatedly attempt to download an unverified project.

8.3 Configuration is different after retrieval

The configuration stored in the relay may differ from the saved engineering project.

Possible reasons include:

  • Previous engineering changes.
  • Different project revision.
  • Changes made through another supported interface.
  • Firmware-related configuration differences.
  • Incomplete project synchronization.

Use the available comparison functions where supported and investigate the differences before applying changes.

9. Troubleshooting Protection Settings Problems

Protection setting problems require particular care because they can affect the operation of the power system.

Common issues include:

  • Incorrect CT ratio.
  • Incorrect VT ratio.
  • Wrong rated frequency.
  • Incorrect pickup current.
  • Incorrect time delay.
  • Incorrect directional settings.
  • Incorrect distance protection zone values.
  • Incorrect differential protection parameters.
  • Incorrect trip matrix.

Recommended checking procedure

  1. Confirm the correct relay model.
  2. Confirm the intended application.
  3. Compare the engineering project with the approved settings document.
  4. Verify the scaling and units of important parameters.
  5. Check the applicable protection logic.
  6. Review any parameter changes introduced by firmware updates.
  7. Obtain independent engineering verification.
  8. Perform the required secondary injection and functional tests.

Do not treat the absence of an S1 Agile error message as proof that the protection settings are correct.

10. Troubleshooting IEC 61850 Configuration in S1 Agile

IEC 61850 introduces additional engineering requirements because the relay’s communication configuration must be consistent with the wider substation automation system.

The following areas should be checked.

10.1 IEC 61850 support is unavailable

Possible causes:

  • The relay does not support the required IEC 61850 option.
  • The communication hardware is not installed.
  • The selected firmware does not provide the required implementation.
  • The engineering software does not support the relevant configuration.
  • The device variant is incorrect.

Check the exact model, order code, firmware, communication module, and manufacturer documentation.

10.2 Logical nodes are missing

Logical nodes represent standardized functional elements in the IEC 61850 data model.

Examples include:

Logical nodeGeneral purpose
PTOCTime overcurrent protection
PIOCInstantaneous overcurrent protection
PDISDistance protection
PDIFDifferential protection
PTRCProtection trip conditioning
XCBRCircuit-breaker function
MMXUMeasurement functions
LPHDPhysical device information
LLN0Logical device common functions

These are examples of IEC 61850 logical node classes, not a guarantee that every MiCOM relay implements all of them.

If expected logical nodes are missing:

  1. Confirm the relay model.
  2. Verify the installed firmware.
  3. Check the device’s supported IEC 61850 data model.
  4. Review the applicable ICD or other manufacturer-provided description.
  5. Confirm that the engineering project corresponds to the correct device.

10.3 Logical node references are incorrect

An IEC 61850 reference identifies a particular data object or attribute.

For example, an illustrative reference may look like:

IED1LD0/PTOC1.Str.general

The actual reference depends on the device’s logical device name, logical node instance, data object, and functional constraint.

Check that the references used by the SCADA system or other IEDs match the actual device data model.

11. Troubleshooting MMS Communication

MMS is commonly used for communication between an IEC 61850 IED and a client such as SICAM PAS or another SCADA gateway.

If the relay is visible on the Ethernet network but MMS communication fails, investigate the following.

11.1 Check IP connectivity

Confirm:

  • Relay IP address.
  • Subnet mask.
  • Routing.
  • Network accessibility.
  • Firewall configuration.

11.2 Check MMS service availability

Verify that the relay supports and has the required MMS communication service configured.

MMS over TCP commonly uses port 102.

A useful Wireshark filter is:

tcp.port == 102

Check whether the TCP connection is established and whether the expected application traffic is exchanged.

11.3 Check IED identification

Confirm that the client is communicating with the correct IED identity.

Review:

  • IED name.
  • Logical device names.
  • Logical node references.
  • Data object references.
  • Client configuration.

11.4 Check report configuration

If the MMS connection works but SCADA indications are not updated, inspect the report configuration.

Check:

  • Dataset membership.
  • Report control block.
  • Buffered or unbuffered reporting.
  • Trigger options.
  • Client association.
  • Integrity reporting.
  • General interrogation behavior where supported.

Do not assume that every relay supports identical report-control features.

11.5 Check data quality and timestamps

A SCADA point may be visible but still have invalid quality or unexpected timestamp information.

Check:

  • Validity.
  • Detail quality.
  • Source and timestamp information.
  • Substitution behavior.
  • Time synchronization.
  • Client-side processing.

12. Troubleshooting GOOSE Communication

GOOSE is used for fast peer-to-peer communication between IEC 61850 IEDs.

It is commonly applied to:

  • Interlocking.
  • Protection trips.
  • Blocking signals.
  • Breaker failure initiation.
  • Transfer trip schemes.
  • Other protection and control applications.

A GOOSE problem may originate in the publisher, network, subscriber, or application logic.

12.1 Publisher configuration problems

Check:

  • GOOSE control block.
  • Dataset.
  • Destination multicast address.
  • APPID.
  • VLAN configuration.
  • Configuration revision.
  • Transmission state.

12.2 Subscriber configuration problems

Check:

  • External references.
  • Publisher identity.
  • Dataset references.
  • Input mapping.
  • Expected data types.
  • Subscriber enablement.
  • Application logic.

12.3 Network problems

Check:

  • Ethernet switch configuration.
  • VLAN membership.
  • Multicast handling.
  • Network segmentation.
  • Port configuration.
  • Network redundancy, if implemented.

12.4 Analyze GOOSE packets

Useful Wireshark filters include:

goose
eth.type == 0x88b8

Inspect:

  • Source MAC address.
  • Destination MAC address.
  • APPID.
  • VLAN ID.
  • stNum.
  • sqNum.
  • timeAllowedToLive.
  • ConfRev.

Remember:

  • stNum changes when the published dataset state changes.
  • sqNum advances during retransmissions of the current state.
  • timeAllowedToLive provides supervision interval information.
  • ConfRev identifies the applicable GOOSE configuration revision, not the firmware version.

A packet appearing in Wireshark does not prove that the subscriber has correctly processed the signal. Always perform an end-to-end functional test.

13. SCL File and IEC 61850 Interoperability Problems

SCL files are used to exchange IEC 61850 engineering information.

Common file types include:

  • ICD: IED Capability Description.
  • CID: Configured IED Description.
  • IID: Instantiated IED Description.
  • SCD: Substation Configuration Description.
  • SSD: System Specification Description.

Problems may occur when exchanging files between different engineering tools.

Typical causes include:

  • Different SCL schema versions.
  • Unsupported extensions.
  • Incorrect IED names.
  • Missing communication information.
  • Inconsistent logical device references.
  • Incompatible datasets.
  • Unsupported control blocks.
  • Different manufacturer implementations.

Recommended troubleshooting procedure

  1. Identify the source engineering tool.
  2. Identify the destination engineering tool.
  3. Check the SCL edition and schema requirements.
  4. Validate the XML structure.
  5. Inspect the IED configuration.
  6. Compare logical device and logical node references.
  7. Check datasets and control blocks.
  8. Verify communication addressing.
  9. Test the resulting configuration with the actual devices.

S1 Agile is primarily a MiCOM device engineering tool. Full station-level SCL integration may require a separate IEC 61850 system configurator.

Successful XML validation does not prove that two devices or engineering tools are fully interoperable.

14. Troubleshooting Time Synchronization

Incorrect time synchronization can affect event analysis, disturbance investigation, and SCADA reporting.

Depending on the relay and installed options, supported time synchronization methods may include:

  • SNTP.
  • PTP.
  • IRIG-B.
  • Other supported synchronization interfaces.

Do not assume that every MiCOM relay supports all these methods.

When investigating incorrect timestamps, check:

  • Configured time source.
  • Time synchronization status.
  • Network accessibility.
  • Time server configuration.
  • Time zone and UTC handling.
  • Device clock.
  • SCADA timestamp interpretation.

For IEC 61850 systems, distinguish between the relay’s internal time source and the timestamp transmitted with a particular data attribute or report.

15. Practical Troubleshooting Example: MiCOM Relay and SICAM PAS

Consider a MiCOM feeder protection relay connected to Siemens SICAM PAS through IEC 61850.

The relay appears online on the Ethernet network, but the SCADA system does not receive the expected protection indications.

A systematic investigation can be performed as follows.

Step 1 – Check the relay

Confirm that the relay is healthy and that the expected protection indications are available locally.

Step 2 – Check the IP configuration

Verify the relay IP address, subnet mask, and network accessibility.

Step 3 – Check MMS communication

Use network diagnostics to determine whether the MMS connection is established.

Step 4 – Check the IEC 61850 data model

Verify that the expected logical device, logical nodes, and data objects exist.

Step 5 – Check datasets

Confirm that the required indications are included in the relevant dataset.

Step 6 – Check report control blocks

Verify the reporting configuration and client association.

Step 7 – Check SICAM PAS mapping

Confirm that the SCADA points refer to the correct IEC 61850 data objects and attributes.

Step 8 – Check quality and timestamps

Confirm that the received values have the expected quality and time information.

Step 9 – Perform a functional test

Operate the relevant test signal under an approved test procedure and verify the complete signal path.

This process helps identify whether the problem originates in the relay, network, IEC 61850 configuration, or SCADA mapping.

16. Practical Troubleshooting Example: GOOSE Interlocking Failure

Consider two IEDs communicating through GOOSE.

One MiCOM relay publishes a breaker-related signal, while another IED subscribes to that signal for an interlocking function.

After a configuration modification, the receiving IED no longer responds correctly.

The investigation should include:

  1. Verify the publisher’s operating state.
  2. Confirm that the GOOSE control block is enabled.
  3. Check the dataset.
  4. Verify the multicast destination address.
  5. Check APPID and VLAN settings.
  6. Inspect the transmitted packets.
  7. Compare ConfRev and the relevant SCL configuration.
  8. Verify the subscriber’s external references.
  9. Confirm the received data quality and state.
  10. Test the complete interlocking logic.

Never assume that the problem is caused by the Ethernet network alone. The publisher, subscriber, mapping, and application logic must all be investigated.

17. Recommended S1 Agile Troubleshooting Workflow

A structured approach reduces unnecessary changes and improves troubleshooting efficiency.

Use the following sequence:

1. Identify the problem

Determine whether it relates to software, project compatibility, device connection, protection settings, or IEC 61850 communication.

2. Collect device information

Record model, order code, serial number, firmware, hardware, and communication options.

3. Preserve the existing configuration

Back up the available engineering project and device configuration before making changes.

4. Check software compatibility

Verify the S1 Agile release and required device support.

5. Check physical and network connectivity

Confirm the selected interface, cables, IP parameters, and network path.

6. Verify device identification

Ensure that the correct relay is connected.

7. Compare project and device configuration

Investigate differences before downloading changes.

8. Analyze communication

For IEC 61850, check MMS, GOOSE, and other implemented services individually.

9. Perform functional testing

Verify the actual protection and automation application.

10. Document the solution

Record the cause, corrective action, project revision, and test results.

18. Best Practices for S1 Agile Engineering

The following practices are recommended for protection and commissioning engineers:

  1. Use an engineering software release compatible with the relay.
  2. Confirm the exact device model and order code.
  3. Maintain an approved project for each relay.
  4. Back up configurations before making changes.
  5. Record firmware and hardware revisions.
  6. Avoid changing several unrelated parameters during troubleshooting.
  7. Use controlled engineering computers and approved software packages.
  8. Verify protection settings against approved documents.
  9. Review IEC 61850 data models before changing SCADA mappings.
  10. Test MMS and GOOSE separately.
  11. Use Wireshark when packet-level analysis is required.
  12. Maintain consistent SCL file revisions.
  13. Follow site change-control and operational safety procedures.
  14. Obtain independent verification of protection-critical changes.
  15. Document every modification and final test result.

19. S1 Agile Troubleshooting Checklist

Software and project

  • S1 Agile installation verified.
  • Software version recorded.
  • Required device support available.
  • Project opens successfully.
  • Correct device selected.
  • Project revision recorded.

Device connection

  • Correct communication interface selected.
  • Cable and connectors checked.
  • Required drivers installed.
  • Relay powered and operational.
  • Communication parameters verified.
  • Device identification confirmed.
  • Access permissions checked.

Configuration

  • Existing configuration backed up.
  • Project and device configuration compared.
  • Protection settings reviewed.
  • Binary input/output assignments checked.
  • Programmable logic reviewed where applicable.
  • Approved changes downloaded using the correct procedure.

IEC 61850

  • IEC 61850 support confirmed.
  • IED name checked.
  • IP parameters checked.
  • Logical device and node references verified.
  • Dataset configuration reviewed.
  • Report control blocks checked.
  • GOOSE publisher verified.
  • GOOSE subscriber mapping checked.
  • MMS communication tested.
  • GOOSE communication tested.
  • SCL files checked for compatibility.

Final verification

  • Device health checked.
  • Protection functions tested as required.
  • SCADA indications verified.
  • Communication alarms checked.
  • Final project saved.
  • Troubleshooting results documented.
  • Operational approval obtained where required.

20. Training on MiCOM S1 Agile and IEC 61850 Engineering

Practical troubleshooting requires more than knowing how to open an engineering project. Protection engineers must understand the relay’s protection functions, communication architecture, configuration structure, and commissioning requirements.

Elec-Engg provides practical training covering:

  • MiCOM protection relays.
  • S1 Agile engineering.
  • Protection settings and configuration.
  • IEC 61850 logical nodes and data objects.
  • MMS communication and reporting.
  • GOOSE configuration and testing.
  • SCL file engineering.
  • SICAM PAS integration.
  • Wireshark network diagnostics.
  • Relay testing and commissioning.

Training is available through video courses, structured self-paced training, face-to-face courses, and customized in-house programs.

Practical courses by Dr Saeed Roostaee / Elec-Engg

Visit Elec-Engg for available protection and substation automation training.

Conclusion

Effective S1 Agile troubleshooting requires a systematic understanding of the engineering software, MiCOM device configuration, communication interfaces, firmware compatibility, and IEC 61850 architecture.

Engineers should identify the actual problem before changing settings or downloading a new configuration. Backups, device identification, compatibility checks, and controlled testing are essential throughout the troubleshooting process.

For IEC 61850 installations, MMS and GOOSE should be investigated separately, and the complete signal path must be verified rather than relying only on software status messages or network connectivity.

A structured troubleshooting process helps reduce commissioning delays, avoid unnecessary configuration changes, and maintain the reliability of protection and substation automation systems.