1. Introduction
Electrical power systems require reliable protection to detect abnormal operating conditions, isolate faulty equipment and maintain the stability and continuity of electrical networks.
Numerical protection relays play a fundamental role in modern power system protection. They continuously monitor electrical quantities, process measured signals, execute protection algorithms and initiate circuit breaker tripping when predefined protection criteria are satisfied.
GE Multilin protection relays are widely used in electrical utilities, power generation facilities, industrial plants, transmission networks and distribution substations.
The Multilin product portfolio includes protection and control solutions for:
- Power transformers
- Generators and synchronous machines
- Electric motors
- Transmission lines
- Distribution feeders
- Busbar systems
- Circuit breakers
- Capacitor banks
The GE Multilin portfolio is now part of GE Vernova’s Electrification business and includes several generations of protection relay platforms.
2. What Is a GE Multilin Protection Relay?
A GE Multilin protection relay is a microprocessor-based intelligent electronic device (IED) designed to perform electrical protection, monitoring, control and communication functions.
Unlike traditional electromechanical relays, numerical protection relays can integrate multiple protection functions into one device.
For example, a single feeder protection relay may provide:
- Phase overcurrent protection (50/51)
- Earth fault protection (50N/51N)
- Directional overcurrent protection (67)
- Undervoltage protection (27)
- Overvoltage protection (59)
- Frequency protection (81)
- Circuit breaker failure protection (50BF)
- Automatic reclosing (79)
- Fault recording and disturbance analysis
- Communication with SCADA systems
The actual functions available depend on the relay model, hardware configuration, firmware and enabled options.
3. GE Multilin Protection Relay Product Families
GE Multilin offers several product families designed for different protection applications.
3.1 Multilin UR Family
The Universal Relay (UR) family is a modular protection and control platform designed for demanding power system applications.
Its common platform architecture provides protection, monitoring, metering, programmable logic and communication capabilities.
Important UR relays include:
| Relay | Main application |
|---|---|
| T60 | Transformer protection |
| T35 | Transformer protection |
| D60 | Distance protection |
| D30 | Distance protection |
| L90 | Line differential protection |
| L60 | Phase comparison protection |
| G60 | Generator protection |
| G30 | Generator and transformer protection |
| F60 | Feeder protection |
| F35 | Multiple feeder protection |
| B90 | Busbar protection |
| B30 | Busbar protection |
| M60 | Motor protection |
| C60 | Breaker management |
| C30 | I/O and logic control |
| C70 | Capacitor bank protection |
3.2 Multilin 8 Series
The 8 Series is a modern protection and control platform designed for transformer, feeder, motor and generator applications.
Its main products include:
- 845 – Transformer Protection
- 850 – Feeder Protection
- 869 – Motor Protection
- 859 – Compact Motor Protection
- 889 – Generator Protection
These relays combine protection, control, monitoring and diagnostic capabilities.
3.3 Multilin Distribution and Industrial Relays
GE also offers protection devices for distribution networks and industrial applications.
Examples include:
- Multilin 350 – Feeder Protection
- Multilin 339 – Motor Protection
- Multilin 369 – Motor Protection
- Multilin 469 – Motor Protection
- Multilin 345 – Transformer Protection
- Multilin F650 – Feeder Protection and Automation
The selection of a relay depends on the electrical equipment, protection philosophy, required functions and project specifications.
4. Basic Architecture of a GE Numerical Protection Relay
Although hardware architecture differs between relay families, most numerical protection relays contain several common functional sections.
4.1 Current Transformer Inputs
Current transformer (CT) inputs provide the relay with scaled representations of primary system currents.
These measurements are used for:
- Overcurrent protection
- Differential protection
- Earth fault protection
- Negative sequence protection
- Thermal protection
- Metering and disturbance recording
Correct CT ratio, polarity, wiring and grounding are essential for reliable protection operation.
4.2 Voltage Transformer Inputs
Voltage transformer (VT) inputs provide voltage measurements required for voltage-dependent protection functions.
Applications include:
- Undervoltage protection
- Overvoltage protection
- Directional protection
- Distance protection
- Frequency protection
- Synchronism check
- Power measurement
4.3 Analog-to-Digital Conversion
The relay processes incoming analog current and voltage signals using internal signal conditioning and analog-to-digital conversion.
The numerical processing system uses sampled signals to calculate electrical quantities such as RMS values, phasors, frequency and impedance.
4.4 Protection Processing
The relay’s processor executes protection algorithms and evaluates the measured quantities against configured protection settings.
When an abnormal condition is detected, the relevant protection element may initiate an alarm, trip command or other programmed action.
4.5 Binary Inputs and Outputs
Binary inputs receive external signals such as:
- Circuit breaker auxiliary contacts
- Protection interlocks
- External trip signals
- Isolator status
- Alarm contacts
- Local and remote control signals
Binary outputs provide commands to external equipment, including:
- Circuit breaker trip coils
- Circuit breaker closing circuits
- Alarm systems
- Lockout relays
- External control systems
4.6 Communication Interfaces
Modern GE Multilin relays provide communication interfaces for engineering, monitoring and integration with automation systems.
Depending on the model, supported communication technologies may include:
- IEC 61850
- Modbus
- DNP3
- IEC 60870-5-103
- Ethernet communication
- Serial communication
The supported protocols and available communication options must always be verified against the specific relay documentation.
5. GE Multilin Protection Relay Applications
5.1 Transformer Protection
Transformer protection relays monitor transformer electrical conditions and detect internal and external faults.
Typical functions include:
- Transformer differential protection (87T)
- Restricted earth fault protection (64REF)
- Overcurrent protection (50/51)
- Earth fault protection (50N/51N)
- Thermal overload protection (49)
- Overexcitation protection (24)
GE Multilin T60 and 845 are examples of transformer protection solutions.
5.2 Generator Protection
Generators require comprehensive protection against electrical and abnormal operating conditions.
Typical protection functions include:
- Generator differential protection (87G)
- Stator earth fault protection (64G)
- Rotor earth fault protection
- Loss of excitation protection (40)
- Reverse power protection (32)
- Negative sequence protection (46)
- Overvoltage protection (59)
- Underfrequency protection (81U)
- Overfrequency protection (81O)
- Pole slip protection (78)
GE Multilin G60 and 889 are examples of generator protection relays.
5.3 Transmission Line Protection
Transmission line protection requires fast and selective fault detection to maintain power system stability.
Common protection functions include:
- Distance protection (21)
- Line differential protection (87L)
- Directional overcurrent protection (67)
- Power swing detection
- Auto-reclosing (79)
- Breaker failure protection (50BF)
GE Multilin D60 and L90 provide solutions for different transmission line protection philosophies.
5.4 Motor Protection
Industrial motors require protection against electrical and thermal stresses.
Typical functions include:
- Thermal overload protection (49)
- Short-circuit protection (50)
- Overcurrent protection (51)
- Locked rotor protection
- Stall protection
- Negative sequence protection (46)
- Undervoltage protection (27)
- Phase loss protection
- Starts-per-hour supervision
GE Multilin M60, 869, 469 and 369 are examples of motor protection products.
6. GE Multilin Engineering Software
Engineering software is an important part of configuring, testing and maintaining GE Multilin protection relays.
GE’s EnerVista software family provides tools for relay configuration, settings management, monitoring and disturbance analysis.
Depending on the relay family, engineers may use different software packages.
Important engineering activities include:
- Establishing communication with the relay.
- Reading the relay configuration.
- Uploading existing settings.
- Modifying protection parameters.
- Configuring logic and control functions.
- Configuring communication protocols.
- Downloading approved settings.
- Retrieving event records.
- Analysing oscillography.
- Backing up the final configuration.
The exact software package and supported version must be selected according to the relay model.
7. GE Multilin and IEC 61850
IEC 61850 is an important communication standard in modern digital substations.
GE Multilin relays with appropriate communication capabilities can exchange information with other IEDs and substation automation systems.
Important IEC 61850 engineering concepts include:
- Logical Nodes (LN)
- Data Objects (DO)
- Data Attributes (DA)
- MMS communication
- GOOSE messaging
- Report Control Blocks (RCB)
- DataSets
- ICD files
- CID files
- SCD files
GOOSE communication can be used for high-speed interlocking, protection signalling and communication between protection devices.
MMS communication provides client-server services for monitoring, reporting and control.
The actual IEC 61850 capabilities depend on the relay model and firmware.
8. Testing and Commissioning
Correct configuration alone does not guarantee reliable protection operation. Every protection scheme must be properly tested before being placed into service.
Typical commissioning activities include:
- Visual and mechanical inspection
- Verification of relay model and hardware
- CT circuit verification
- VT circuit verification
- Binary input testing
- Binary output testing
- Protection setting verification
- Secondary injection testing
- Trip circuit testing
- Communication testing
- GOOSE testing, where applicable
- Event and disturbance recording verification
- Final commissioning documentation
Testing equipment such as Omicron CMC test sets can be used to verify protection elements and complete protection schemes.
9. Conclusion
GE Multilin protection relays provide integrated protection, control, monitoring and communication solutions for a wide range of electrical power system applications.
Understanding the different relay families, hardware architecture, protection functions, engineering software and communication capabilities is essential for protection and commissioning engineers.
Practical knowledge of GE Multilin relays enables engineers to perform relay selection, configuration, protection coordination, testing, commissioning and troubleshooting more effectively.
In the following articles, we will examine the GE Multilin product families and individual relay models in greater technical detail.
Related topics: GE Multilin Protection Relays, GE UR Family, GE 8 Series, EnerVista Software, FlexLogic, Transformer Protection, Generator Protection, Motor Protection, Feeder Protection, IEC 61850, Relay Testing and Commissioning.