- 1. Introduction
- 2. General Architecture of a GE Multilin Numerical Relay
- 3. Current Transformer Input Modules
- 4. Voltage Transformer Input Modules
- 5. Analog Signal Conditioning
- 6. Analog-to-Digital Conversion
- 7. Microprocessor and Protection Processing Unit
- 8. Memory and Data Storage
- 9. Binary Input Modules
- 10. Binary Output Modules
- 11. Communication Modules and Interfaces
- 12. Human-Machine Interface (HMI)
- 13. Power Supply Module
- 14. Internal Self-Supervision and Diagnostics
- 15. Practical Example: Complete Signal Flow in a GE Multilin Feeder Relay
- 16. Engineering and Commissioning Considerations
- 17. Training on GE Multilin Protection Relays by Elec-Engg
- 18. Conclusion
1. Introduction
Modern electrical power systems rely on numerical protection relays to detect faults, monitor electrical quantities, execute protection algorithms and initiate circuit breaker operations.
GE Multilin numerical protection relays use microprocessor-based architectures to combine protection, control, measurement, communication and disturbance recording within intelligent electronic devices (IEDs).
Understanding the internal architecture of these relays is essential for protection engineers, commissioning engineers and maintenance personnel.
This knowledge helps engineers understand how electrical signals travel from instrument transformers to the protection algorithms and how the relay generates trip commands to circuit breakers.
This article explains the fundamental architecture of GE Multilin numerical protection relays, including analog input circuits, signal conditioning, analog-to-digital conversion, processing units, binary inputs, binary outputs, communication interfaces and internal protection logic.
2. General Architecture of a GE Multilin Numerical Relay
Although the internal hardware differs between product families, most GE Multilin numerical protection relays contain the following functional sections:
- Analog current input circuits
- Analog voltage input circuits
- Signal conditioning circuits
- Analog-to-digital conversion
- Microprocessor and digital signal processing
- Memory and data storage
- Binary input circuits
- Binary output circuits
- Communication interfaces
- Power supply
- Human-machine interface (HMI)
- Internal monitoring and diagnostic circuits
The basic operating sequence is:
- CTs and VTs provide electrical measurements.
- The relay receives and conditions the analog signals.
- The analog signals are sampled and converted into digital data.
- The processor calculates electrical quantities.
- Protection algorithms evaluate the measured quantities.
- Internal logic determines whether an alarm or trip is required.
- Output contacts operate according to the configured logic.
- Communication and recording functions provide information to operators and other IEDs.
3. Current Transformer Input Modules
Current transformer inputs provide the relay with current signals representing the primary electrical system.
For example, a feeder protection relay may receive three-phase current signals from CTs installed in the switchgear.
Typical current measurements include:
- Phase A current
- Phase B current
- Phase C current
- Neutral current
- Residual current
- Additional current channels, depending on the application
3.1 CT Secondary Ratings
Common CT secondary ratings include:
- 1 A
- 5 A
The selected relay hardware must be compatible with the CT secondary rating.
The relay settings must also correctly reflect the CT primary and secondary ratios.
For example:
CT ratio = 1000/1 A
If the primary current is 500 A, the ideal secondary current is:
Isecondary = 500 / 1000 = 0.5 A
The relay uses this measured current to calculate the primary current and evaluate protection functions.
3.2 CT Polarity
CT polarity is particularly important in differential, directional and earth fault protection applications.
Incorrect CT polarity may result in:
- Incorrect differential current calculations
- Unwanted protection operation
- Incorrect directional measurements
- Measurement errors
During commissioning, CT polarity must be verified against the approved wiring diagrams and protection scheme.
3.3 CT Input Configuration
Depending on the GE Multilin model, current inputs can be assigned to different protection applications.
For example:
- Phase overcurrent protection
- Transformer differential protection
- Generator differential protection
- Motor differential protection
- Neutral overcurrent protection
- Restricted earth fault protection
The available channels and input configurations depend on the particular relay hardware.
4. Voltage Transformer Input Modules
Voltage transformer inputs provide the relay with voltage measurements.
Typical applications include:
- Overvoltage protection (59)
- Undervoltage protection (27)
- Directional overcurrent protection (67)
- Distance protection (21)
- Frequency protection (81)
- Synchronism check (25)
- Power and energy measurement
4.1 Three-Phase Voltage Measurements
A typical three-phase voltage measurement system includes:
- Phase A voltage
- Phase B voltage
- Phase C voltage
Some applications also require neutral or residual voltage measurements.
4.2 Voltage Input Configuration
Engineers must configure the relay according to the actual VT secondary arrangement.
Important parameters include:
- VT primary voltage
- VT secondary voltage
- Phase-to-phase or phase-to-neutral measurement
- VT connection
- Phase rotation
- Voltage input assignment
Incorrect VT configuration can affect directional protection, distance protection and other voltage-dependent functions.
5. Analog Signal Conditioning
The signals received from CT and VT circuits are processed by internal analog signal conditioning circuits.
These circuits prepare the incoming electrical signals for digital processing.
Depending on the relay design, signal conditioning may include:
- Signal scaling
- Filtering
- Isolation
- Surge protection
- Anti-aliasing filtering
The objective is to provide accurate and reliable measurement signals to the internal digital processing system.
6. Analog-to-Digital Conversion
Numerical protection relays cannot directly execute protection algorithms using analog electrical signals.
The analog signals must first be converted into digital samples.
This process is called analog-to-digital conversion (ADC).
The relay samples the incoming current and voltage waveforms and converts them into numerical values.
The processor then uses these values to calculate:
- RMS current
- RMS voltage
- Frequency
- Phase angle
- Active power
- Reactive power
- Apparent power
- Impedance
- Sequence components
These calculated quantities are used by protection elements and measurement functions.
6.1 Digital Signal Processing
Digital signal processing techniques are used to extract useful electrical information from sampled waveforms.
For example, a numerical overcurrent element evaluates the measured current against its configured pickup threshold.
A distance protection element uses voltage and current measurements to calculate apparent impedance.
A differential protection element compares the currents entering and leaving the protected equipment.
The specific algorithms and sampling characteristics vary between relay models.
7. Microprocessor and Protection Processing Unit
The processor is the central component responsible for executing the relay’s internal functions.
Its responsibilities include:
- Processing measured current and voltage samples
- Executing protection algorithms
- Evaluating protection settings
- Processing binary input signals
- Executing programmable logic
- Managing output operations
- Handling communication
- Managing event and fault records
- Performing internal diagnostics
7.1 Protection Processing
Consider a simple phase overcurrent protection function.
The relay continuously measures the phase currents.
When the measured current exceeds the configured pickup value, the protection element may start.
Depending on the selected characteristic and settings, the relay calculates the required operating time.
When the operating condition is satisfied, the protection element generates an internal trip signal.
The trip signal is then processed by the relay’s logic before being assigned to the required physical output.
7.2 Protection and Control Integration
Modern GE Multilin relays can integrate protection and control functions.
For example, a feeder relay may perform:
- Phase overcurrent protection
- Earth fault protection
- Circuit breaker status monitoring
- Local and remote control
- Interlocking
- Auto-reclosing
- Event recording
- SCADA communication
This integration can reduce the need for separate devices in certain applications.
8. Memory and Data Storage
Numerical protection relays require internal memory to store settings, configuration information and operational records.
Typical stored information includes:
- Protection settings
- System configuration
- Logic configuration
- Event records
- Fault records
- Oscillography
- Disturbance records
- Diagnostic information
The available storage capacity and recording features depend on the relay model.
8.1 Event Records
Event records provide a chronological history of important relay activities.
Examples include:
- Protection element pickup
- Protection element operation
- Circuit breaker status changes
- Binary input transitions
- Communication events
- Settings changes
8.2 Oscillography
Oscillography provides sampled current and voltage waveforms associated with disturbances.
Engineers can use disturbance records to investigate:
- Short-circuit faults
- Protection operation
- Incorrect tripping
- CT saturation
- Voltage disturbances
- Circuit breaker operating sequences
COMTRADE-compatible records can be analysed using suitable engineering software.
9. Binary Input Modules
Binary inputs allow the relay to receive external status and control signals.
These signals are commonly supplied by:
- Circuit breaker auxiliary contacts
- Isolator auxiliary contacts
- Protection lockout relays
- External trip circuits
- Control switches
- Interlocking circuits
- External protection devices
9.1 Typical Binary Input Applications
For example, a circuit breaker may provide two auxiliary contacts:
- 52a: Closed when the circuit breaker is closed.
- 52b: Closed when the circuit breaker is open.
These signals can be connected to relay binary inputs.
The relay can then use the information for:
- Breaker position monitoring
- Auto-reclosing logic
- Breaker failure protection
- Interlocking
- Trip circuit supervision
9.2 Binary Input Voltage
Binary input circuits must be compatible with the control voltage used in the installation.
Typical control voltages may include:
- 24 V DC
- 48 V DC
- 110 V DC
- 125 V DC
- 220 V DC
Not every relay supports every voltage range. The specific hardware manual must be checked before connecting external circuits.
10. Binary Output Modules
Binary outputs provide physical control signals from the relay to external equipment.
Typical applications include:
- Circuit breaker tripping
- Circuit breaker closing
- Alarm generation
- Lockout relay operation
- External annunciation
- Control system signalling
10.1 Trip Output
Consider a feeder protection application.
When the relay detects a phase-to-earth fault, the protection logic may generate a trip command.
The configured trip output contact operates and completes the external trip circuit.
This energizes the circuit breaker trip coil and causes the circuit breaker to interrupt the fault current.
10.2 Output Configuration
Engineers must configure the required output assignment according to the protection scheme.
For example:
| Protection function | Typical output assignment |
|---|---|
| Phase overcurrent | Trip output |
| Earth fault | Trip output |
| Breaker failure | Backup trip output |
| Protection alarm | Alarm output |
| Relay self-supervision | Watchdog or alarm output |
The actual output arrangement must be verified against the relay hardware and approved project drawings.
11. Communication Modules and Interfaces
Communication is an important part of modern numerical protection relay architecture.
GE Multilin relays may provide serial and Ethernet interfaces, depending on the model and installed hardware.
Common communication technologies include:
- IEC 61850
- Modbus RTU
- Modbus TCP
- DNP3
- IEC 60870-5-103
11.1 Serial Communication
Serial communication may be used for:
- Local engineering access
- Relay monitoring
- SCADA communication
- Data retrieval
11.2 Ethernet Communication
Ethernet interfaces provide communication capabilities for engineering and substation automation systems.
Applications may include:
- Remote relay configuration
- Monitoring and diagnostics
- MMS communication
- GOOSE messaging
- Event retrieval
- Integration with SCADA systems
The available services depend on the specific model and its communication configuration.
12. Human-Machine Interface (HMI)
The HMI allows engineers and operators to interact with the protection relay locally.
Depending on the model, it may include:
- LCD display
- Navigation keys
- Function keys
- LED indicators
- Local control interfaces
Typical information available through the HMI includes:
- Measured currents
- Measured voltages
- Protection status
- Active alarms
- Circuit breaker status
- Event information
- Relay configuration information
The HMI provides an important interface for local operation, troubleshooting and commissioning.
13. Power Supply Module
The power supply module provides the internal operating voltages required by the relay electronics.
Depending on the model, available supply options may include different AC or DC voltage ranges.
The power supply must be selected according to the station auxiliary supply system and the relay’s hardware specifications.
Engineers should verify:
- Nominal supply voltage
- Permitted voltage range
- Polarity
- Protective grounding
- Fuse and circuit protection requirements
- Auxiliary supply monitoring
An unreliable auxiliary supply can affect relay availability and protection system performance.
14. Internal Self-Supervision and Diagnostics
Modern numerical protection relays continuously monitor important internal functions.
Self-supervision may include:
- Processor monitoring
- Memory checks
- Power supply monitoring
- Internal hardware diagnostics
- Communication diagnostics
- Configuration monitoring
When an internal problem is detected, the relay may generate an alarm or indicate an unhealthy condition.
Protection engineers must understand the relay’s health indications and associated watchdog or alarm contacts.
15. Practical Example: Complete Signal Flow in a GE Multilin Feeder Relay
Consider a distribution feeder protected by a GE Multilin feeder relay.
The following sequence illustrates how the protection system operates.
Step 1 – Measurement
The CTs provide three-phase current signals to the relay.
Step 2 – Signal Processing
The relay conditions, samples and converts the incoming signals into digital values.
Step 3 – Protection Calculation
The processor calculates the phase currents and evaluates the overcurrent protection elements.
Step 4 – Fault Detection
A short circuit causes the measured current to exceed the configured pickup threshold.
Step 5 – Protection Operation
The protection element operates according to its configured time characteristic.
Step 6 – Logic Processing
The internal logic processes the protection operation signal and determines the required trip output.
Step 7 – Circuit Breaker Tripping
The output contact operates and energizes the circuit breaker trip circuit.
Step 8 – Event Recording
The relay stores the protection event and associated measurements.
Step 9 – Communication
The relay transmits the available event and status information to the substation automation or SCADA system.
This sequence illustrates the interaction between the relay’s analog inputs, processor, protection algorithms, internal logic, binary outputs and communication interfaces.
16. Engineering and Commissioning Considerations
When working with GE Multilin numerical protection relays, engineers should verify the following:
- Correct relay model and hardware configuration.
- Correct CT and VT input ratings.
- Correct CT ratios and polarity.
- Correct VT ratios and connections.
- Correct phase rotation.
- Correct binary input voltage.
- Correct binary output assignments.
- Correct protection settings.
- Correct programmable logic.
- Correct communication configuration.
- Correct circuit breaker trip and close interfaces.
- Correct auxiliary supply.
- Correct event and disturbance recording.
- Successful protection functional testing.
A complete commissioning process must verify both the internal relay configuration and the external electrical circuits.
17. Training on GE Multilin Protection Relays by Elec-Engg
Elec-Engg provides practical technical training in power system protection and substation automation by Dr Saeed Roostaee (Electrical Engineering).
Our training focuses on helping engineers understand numerical protection relay operation from the measurement circuits to the final circuit breaker trip command.
Relevant practical training topics include:
- Numerical protection relay architecture
- GE Multilin relay hardware and modules
- CT and VT circuit engineering
- Protection function configuration
- Binary inputs and outputs
- Protection logic and FlexLogic
- EnerVista engineering software
- Event and oscillography analysis
- IEC 61850 communication
- GOOSE engineering
- Secondary injection testing
- Protection relay commissioning and troubleshooting
Available Training Methods
- Video-based technical courses
- Structured self-paced training
- Live online training
- Face-to-face training
- Customized company and utility training
Training programs can be adapted to the requirements of protection, commissioning, operation and maintenance engineers.
Learn more about practical technical training:
Website: https://elec-engg.com/
Contact: https://elec-engg.com/contact/
18. Conclusion
The internal architecture of GE Multilin numerical protection relays consists of interconnected measurement, processing, protection, control, communication and diagnostic components.
Understanding the complete signal path from CT and VT inputs to protection algorithms and physical output contacts is fundamental to reliable protection engineering.
This knowledge is particularly important when configuring protection functions, troubleshooting incorrect relay operation, performing secondary injection tests and commissioning protection systems.
In the next article, we will examine GE Multilin protection functions and ANSI device numbers, explaining their applications and how they are implemented in numerical protection relays.
Related Topics: GE Multilin, Numerical Protection Relay Architecture, CT and VT Inputs, Analog-to-Digital Conversion, Binary Inputs and Outputs, FlexLogic, EnerVista, IEC 61850, Protection Relay Testing and Commissioning.
