GE Multilin Motor Protection: 339, 369, 469 and 869 Relays – Protection Functions, Settings, Engineering and Commissioning

Table Of Contents
  1. 1. Introduction
  2. 2. GE Multilin Motor Protection Relay Families
  3. 3. Motor Protection Philosophy
  4. 4. Motor Nameplate Data and Relay Configuration
  5. 5. Thermal Overload Protection (ANSI 49)
  6. 6. Motor Starting and Acceleration Supervision
  7. 7. Starts-per-Hour Supervision (ANSI 66)
  8. 8. Phase Overcurrent Protection (ANSI 50/51)
  9. 9. Ground-Fault Protection
  10. 10. Phase Unbalance and Negative-Sequence Protection (ANSI 46)
  11. 11. Undercurrent and Loss-of-Load Protection (ANSI 37)
  12. 12. Undervoltage Protection (ANSI 27)
  13. 13. Overvoltage Protection (ANSI 59)
  14. 14. Motor Temperature Monitoring Using RTDs
  15. 15. Motor Protection for Different Starting Methods
  16. 16. Motor Protection Coordination
  17. 17. GE Multilin Motor Relay Configuration Using EnerVista
  18. 18. Testing GE Multilin Motor Protection Relays
  19. 19. Common GE Multilin Motor Protection Problems
  20. 20. Motor Protection Commissioning Checklist
  21. 21. Engineering Recommendations
  22. 22. Conclusion
  23. 23. Training on GE Multilin Motor Protection by Elec-Engg

1. Introduction

Electric motors are among the most important assets in industrial plants, power stations, water treatment facilities, oil and gas installations, and manufacturing industries. A motor failure can interrupt production, damage driven equipment, and cause significant financial losses.

Motor protection must address more than short circuits and overloads. A comprehensive motor protection scheme should consider thermal stress, locked rotor conditions, excessive starting time, phase unbalance, phase loss, ground faults, undercurrent, abnormal voltage, and mechanical operating conditions.

GE Multilin offers several motor protection relays for different motor applications, including the 339, 369, 469, and 869 families. Their features and protection functions depend on the exact model, firmware, hardware configuration, and installed options.

This article explains the practical engineering principles of GE Multilin motor protection, including motor data collection, CT and VT configuration, thermal modeling, starting supervision, protection settings, EnerVista engineering, secondary injection testing, and commissioning.

2. GE Multilin Motor Protection Relay Families

2.1 GE Multilin 339 Motor Protection Relay

The GE Multilin 339 is designed for motor protection applications, particularly in industrial motor installations.

Depending on the version and configuration, its protection and monitoring capabilities may include:

  • Thermal overload protection.
  • Phase overcurrent protection.
  • Ground-fault protection.
  • Current unbalance protection.
  • Starting supervision.
  • Locked rotor protection.
  • Motor operating measurements.
  • Programmable logic and output control.

The exact function list should be checked against the relay’s product documentation.

2.2 GE Multilin 369 Motor Management Relay

The GE Multilin 369 is a motor management relay used for protection and monitoring of industrial motors.

Its application may include:

  • Motor thermal protection.
  • Overload protection.
  • Short-circuit protection.
  • Ground-fault protection.
  • Phase unbalance protection.
  • Starting and acceleration supervision.
  • Motor operating information.
  • Alarm and trip management.

The relay is commonly associated with industrial motor protection applications where motor thermal condition and starting behavior are important.

2.3 GE Multilin 469 Motor Protection Relay

The GE Multilin 469 is a motor protection and management relay designed for more comprehensive motor protection applications.

Depending on its configuration, it may provide protection and monitoring functions such as:

  • Thermal overload protection.
  • Phase overcurrent.
  • Ground fault.
  • Negative-sequence protection.
  • Start supervision.
  • Locked rotor protection.
  • Undercurrent protection.
  • Voltage-related protection.
  • Motor temperature monitoring.
  • RTD-based thermal supervision.
  • Programmable control logic.

2.4 GE Multilin 869 Motor Protection Relay

The GE Multilin 869 is a motor protection relay designed for advanced motor protection applications.

Its available features depend on the product version and configuration. Engineering may include motor thermal protection, electrical fault protection, start supervision, monitoring, and communication functions.

2.5 Comparison of GE Multilin Motor Relays

RelayGeneral application
339Industrial motor protection
369Motor protection and management
469Comprehensive motor protection and monitoring
869Advanced motor protection applications

This is a general application comparison, not a complete feature comparison. Confirm the exact ordering code, hardware, firmware, and function list before selecting a relay.

3. Motor Protection Philosophy

Motor protection must be designed around the motor’s electrical characteristics, starting method, thermal limits, driven load, and operating environment.

Typical motor protection functions include:

Protection functionANSI number
Thermal overload49
Instantaneous overcurrent50
Time overcurrent51
Ground-fault protection50G/51G or 50N/51N
Negative-sequence protection46
Phase failure or unbalance46
Locked rotor protection48 or model-specific start supervision
Excessive starting time48
Undercurrent37
Undervoltage27
Overvoltage59
Undercurrent or loss of load37
Number of starts supervision66
Differential protection87M, where applied

ANSI designations and implementation vary by relay and protection scheme. A function may be implemented using a combination of elements rather than a single dedicated ANSI element.

4. Motor Nameplate Data and Relay Configuration

Before configuring a motor protection relay, the engineer must collect accurate motor data.

Typical information includes:

  • Rated output power.
  • Rated voltage.
  • Rated current.
  • Rated frequency.
  • Rated speed.
  • Power factor.
  • Efficiency.
  • Starting current.
  • Locked-rotor time.
  • Hot and cold thermal limits.
  • Service factor.
  • Insulation class.
  • Starting method.
  • Permitted starts per hour.
  • Cooling arrangement.
  • RTD sensor details, where fitted.

4.1 Rated Motor Current

For a three-phase motor, rated current can be estimated using:

[
I_n=\frac{P}{\sqrt{3}V_n\eta\cos\phi}
]

Where:

  • (P) is the rated mechanical output power in watts.
  • (V_n) is the rated line-to-line voltage.
  • (\eta) is motor efficiency.
  • (\cos\phi) is power factor.

Example

Consider a motor with:

  • Rated output: 500 kW.
  • Rated voltage: 6.6 kV.
  • Efficiency: 95%.
  • Power factor: 0.88.

[
I_n=\frac{500000}{\sqrt{3}\times6600\times0.95\times0.88}
]

[
I_n\approx52.5\text{ A}
]

This is an illustrative calculation. The actual rated current should be taken from the motor nameplate or manufacturer documentation.

4.2 CT Ratio Selection

The motor relay must be configured according to the installed CT ratio and relay current input rating.

For example, if the motor full-load current is approximately 52.5 A and the CT ratio is 100/1 A, the expected secondary current at rated motor load is:

[
I_s=\frac{52.5}{100}=0.525\text{ A}
]

The engineer must confirm that the relay’s selected input is compatible with the CT secondary rating.

5. Thermal Overload Protection (ANSI 49)

Thermal overload protection is one of the most important motor protection functions.

A motor can be damaged by excessive heating caused by:

  • Continuous overload.
  • Repeated starting.
  • Long acceleration time.
  • Locked rotor.
  • Cooling system failure.
  • High ambient temperature.
  • Excessive current unbalance.
  • Abnormal operating conditions.

5.1 Motor Thermal Model

A motor thermal model estimates the heating condition of the motor based on measured current and configured thermal parameters.

The relay may use thermal capacity, heating and cooling time constants, and other motor parameters to estimate the motor’s thermal state.

A simplified thermal relationship is:

[
\tau\frac{d\theta}{dt}+\theta=K I^2
]

Where:

  • (\theta) represents the thermal state.
  • (\tau) is a thermal time constant.
  • (I) is motor current.
  • (K) is a model-dependent coefficient.

This is a simplified representation. Actual relay thermal algorithms can be more complex and may include separate heating and cooling models.

5.2 Thermal Capacity

A motor protection relay may display thermal capacity used or remaining.

The engineer should verify:

  • Thermal overload pickup.
  • Thermal capacity alarm.
  • Thermal trip level.
  • Heating time constant.
  • Cooling time constant.
  • Hot and cold motor conditions.
  • Thermal memory behavior.
  • Restart inhibition.

5.3 Hot and Cold Motor Conditions

A motor starting from a cold condition can generally tolerate more starting thermal stress than a motor that has recently operated at full load.

The thermal model should account for the motor’s initial thermal condition.

Incorrect thermal parameters can result in unnecessary trips or inadequate motor protection.

6. Motor Starting and Acceleration Supervision

Motor starting is a critical operating condition because current can be several times the rated motor current.

During starting, the relay must distinguish normal starting current from a fault or abnormal acceleration condition.

6.1 Starting Current

The motor starting current depends on:

  • Motor design.
  • Supply voltage.
  • Starting method.
  • Driven load.
  • Motor impedance.
  • Starting system configuration.

A direct-on-line induction motor may draw several times its rated current during starting. The actual value must be obtained from the motor manufacturer’s data or measured during commissioning.

6.2 Starting Time

Starting time depends on motor inertia, driven-load inertia, load torque, and available accelerating torque.

The relay must allow sufficient time for normal acceleration while remaining capable of detecting an abnormal or stalled start.

6.3 Excessive Starting Time

Excessive starting time protection detects a motor that takes longer than the permitted acceleration time to reach normal operating conditions.

Possible causes include:

  • Excessive mechanical load.
  • Low supply voltage.
  • Incorrect motor design data.
  • Mechanical binding.
  • High load inertia.
  • Starting equipment malfunction.

6.4 Locked Rotor Protection

A locked rotor condition occurs when the motor cannot accelerate or the rotor becomes mechanically blocked.

The motor can draw high current while producing little or no useful mechanical output.

The protection setting must consider:

  • Locked-rotor current.
  • Hot and cold locked-rotor withstand times.
  • Normal acceleration time.
  • Starting method.
  • Thermal model.
  • Current measurement.

The relay must trip before the motor exceeds its thermal withstand limit.

7. Starts-per-Hour Supervision (ANSI 66)

Frequent motor starting can cause excessive thermal stress.

A motor manufacturer may specify:

  • Maximum starts per hour.
  • Maximum consecutive cold starts.
  • Maximum consecutive hot starts.
  • Minimum time between starts.

A starts-per-hour supervision function can prevent repeated starts when the motor has not cooled sufficiently.

The relay’s restart inhibition logic should be coordinated with the motor manufacturer’s starting limits and the plant operating requirements.

8. Phase Overcurrent Protection (ANSI 50/51)

Phase overcurrent protection provides protection against excessive motor current caused by faults and abnormal operating conditions.

8.1 Instantaneous Overcurrent (50)

Instantaneous overcurrent protection detects high current associated with severe short circuits.

The pickup must be selected to avoid operation during normal motor starting.

8.2 Time Overcurrent (51)

Time overcurrent protection can provide backup protection against sustained excessive current.

The engineer should consider:

  • Motor starting current.
  • Starting duration.
  • Motor thermal withstand.
  • Cable ampacity.
  • Contactor or circuit-breaker limits.
  • Upstream and downstream coordination.

8.3 Starting Current and Overcurrent Coordination

The overcurrent setting must allow normal starting while remaining sensitive to fault current.

A common engineering error is selecting a pickup that is too low and causes unwanted operation during motor acceleration.

Another error is selecting a pickup that is too high and reduces protection sensitivity.

The final setting should be based on motor data, fault calculations, CT performance, and coordination studies.

9. Ground-Fault Protection

Ground faults can occur in motor cables, terminal boxes, stator windings, and associated equipment.

Common protection arrangements include:

  • Residual current measurement from three phase CTs.
  • Core-balance CT measurement.
  • Neutral CT measurement, where applicable.

9.1 Residual Current

Residual current can be calculated as:

[
I_{\text{res}}=I_A+I_B+I_C
]

Under balanced conditions, the vector sum should be close to zero.

A ground fault can produce residual current depending on the system grounding arrangement and fault location.

9.2 Core-Balance CT

A core-balance CT measures the vector sum of the currents passing through the CT window.

It can provide sensitive earth-fault detection when properly installed and configured.

9.3 Grounding System Considerations

Ground-fault pickup depends on the plant grounding arrangement:

  • Solidly grounded.
  • Resistance grounded.
  • Reactance grounded.
  • Isolated or ungrounded.

The protection engineer must coordinate the relay with the expected ground-fault current and the plant’s earth-fault protection philosophy.

10. Phase Unbalance and Negative-Sequence Protection (ANSI 46)

Unbalanced phase currents create negative-sequence current.

Negative-sequence current produces additional heating in the motor rotor and can cause mechanical and thermal stress.

Possible causes include:

  • Single-phasing.
  • Unequal supply voltage.
  • Loose electrical connections.
  • Unbalanced loads.
  • Faults in the supply network.
  • CT measurement problems.

10.1 Negative-Sequence Current

The relay calculates negative-sequence current from the three phase current measurements.

A common thermal relationship is:

[
I_2^2t=K
]

Where:

  • (I_2) is negative-sequence current.
  • (t) is time.
  • (K) is a machine-dependent thermal constant.

The relay’s actual negative-sequence protection algorithm may differ from this simplified relationship.

10.2 Setting Considerations

The engineer should review:

  • Motor manufacturer limits.
  • Normal phase unbalance.
  • Starting current characteristics.
  • Negative-sequence pickup.
  • Time delay.
  • Thermal coordination.

11. Undercurrent and Loss-of-Load Protection (ANSI 37)

Undercurrent protection detects a reduction in motor current below a configured threshold.

This may indicate that the motor is no longer driving its intended load.

Typical applications include:

  • Pump dry running.
  • Broken coupling.
  • Loss of mechanical load.
  • Conveyor belt failure.
  • Loss of process material.
  • Pumping system malfunction.

Undercurrent protection should be supervised during starting and other conditions where low current is expected.

The pickup must distinguish normal low-load operation from a genuine loss-of-load condition.

12. Undervoltage Protection (ANSI 27)

Undervoltage can affect motor torque and acceleration.

For an induction motor, electromagnetic torque is approximately proportional to the square of the applied voltage under simplified operating assumptions:

[
T\propto V^2
]

A reduction in supply voltage can therefore reduce available torque and increase acceleration time or cause motor stalling.

Undervoltage protection may be required to:

  • Prevent prolonged operation at low voltage.
  • Protect motors during abnormal supply conditions.
  • Coordinate motor restart schemes.
  • Support load shedding and plant restoration.

Settings should consider motor starting requirements, process requirements, and the plant voltage protection philosophy.

13. Overvoltage Protection (ANSI 59)

Overvoltage can increase electrical stress on motor insulation and may cause abnormal operating conditions.

The protection engineer should consider:

  • Motor rated voltage.
  • Supply system voltage limits.
  • Switching events.
  • Transformer tap arrangements.
  • Voltage transients.
  • Coordination with plant voltage protection.

The availability of dedicated voltage protection elements depends on the relay model and its configured voltage measurement inputs.

14. Motor Temperature Monitoring Using RTDs

Some motor protection applications use resistance temperature detectors (RTDs) to monitor critical motor temperatures.

Possible measurement points include:

  • Stator windings.
  • Motor bearings.
  • Frame temperature.
  • Cooling air.
  • Cooling water.

RTD monitoring can provide additional protection beyond current-based thermal models.

14.1 RTD Configuration

The engineer must verify:

  • RTD type.
  • Sensor wiring.
  • Number of sensors.
  • Measurement range.
  • Input module compatibility.
  • Alarm threshold.
  • Trip threshold.
  • Sensor failure supervision.

RTD-based temperature protection must be coordinated with the motor manufacturer’s temperature limits.

15. Motor Protection for Different Starting Methods

Motor starting method has a significant impact on protection settings.

15.1 Direct-On-Line Starting

Direct-on-line starting applies full supply voltage to the motor.

The relay must allow the normal starting current and acceleration time while protecting the motor against a stalled start.

15.2 Star-Delta Starting

Star-delta starting initially connects the motor windings in star and then changes to delta.

The relay settings must account for the current transformation and the actual location of the CTs.

15.3 Autotransformer Starting

Autotransformer starting reduces the applied motor voltage during acceleration.

Protection settings should account for the reduced starting current and switching sequence.

15.4 Soft Starter

A soft starter controls the motor voltage during starting.

The relay must be coordinated with the soft starter’s starting profile, bypass contactor, and protection functions.

15.5 Variable Frequency Drive

A variable frequency drive controls motor speed and starting behavior through a power-electronic converter.

Motor protection arrangements may be divided between:

  • The VFD’s internal motor protection.
  • External motor protection relay.
  • Independent motor temperature monitoring.
  • Cable and feeder protection.

The engineer must consider the VFD output waveform, current measurement, motor cable arrangement, and the protection device’s suitability for the application.

16. Motor Protection Coordination

Motor protection must be coordinated with:

  • Motor thermal limits.
  • Cable thermal limits.
  • Transformer protection.
  • Upstream feeder protection.
  • Circuit-breaker characteristics.
  • Contactor withstand limits.
  • Starting current.
  • Locked-rotor current.
  • Earth-fault protection.

16.1 Illustrative Coordination Example

Consider a motor with:

  • Rated current: 100 A.
  • Starting current: 6 × rated current.
  • Starting time: 8 seconds.
  • CT ratio: 150/1 A.

The starting current is:

[
I_{\text{start}}=6\times100=600\text{ A}
]

The corresponding CT secondary current is:

[
I_{s,\text{start}}=\frac{600}{150}=4\text{ A}
]

The relay must be configured so that the normal starting profile does not cause an unwanted trip.

However, the thermal and locked-rotor protection must still operate within the motor’s permissible withstand limits.

This example illustrates current scaling only. Actual settings require the motor manufacturer’s starting and thermal data.

17. GE Multilin Motor Relay Configuration Using EnerVista

The applicable GE Multilin EnerVista software depends on the relay family and model.

A general engineering workflow is:

Step 1 – Identify the Relay

Confirm:

  • Relay model.
  • Product ordering code.
  • Firmware version.
  • Hardware modules.
  • Current input rating.
  • Voltage input availability.
  • Communication interfaces.

Step 2 – Collect Motor Data

Enter the motor nameplate and manufacturer information.

Confirm rated current, voltage, power, starting current, acceleration time, thermal limits, and permitted starts.

Step 3 – Configure CT and VT Inputs

Enter the installed CT ratio and verify the current input configuration.

If voltage-based protection is used, verify VT ratio and phase assignment.

Step 4 – Configure Thermal Protection

Review the thermal model parameters and ensure they match the motor data.

Step 5 – Configure Starting Supervision

Set the relevant starting and locked-rotor protection according to the motor starting profile.

Step 6 – Configure Electrical Protection

Configure the required elements, including:

  • Overcurrent.
  • Ground fault.
  • Negative sequence.
  • Undercurrent.
  • Undervoltage.
  • Overvoltage, where available.
  • Other required protection functions.

Step 7 – Configure Inputs, Outputs and Logic

Assign alarm and trip signals to the required output contacts.

Verify breaker trip, contactor control, restart inhibition, and external interlocks.

Step 8 – Save and Verify Settings

Compare the settings against the approved protection study.

Save the final settings file and maintain revision control.

18. Testing GE Multilin Motor Protection Relays

Motor protection testing should include individual protection elements and complete trip circuit verification.

18.1 CT Measurement Test

Inject known current values and verify:

  • Phase current measurements.
  • Current scaling.
  • Phase assignment.
  • Residual current.
  • Negative-sequence measurement.

18.2 Thermal Overload Test

Verify the thermal model response using an appropriate test procedure.

Check pickup, alarm, trip, thermal memory, and restart inhibition.

Do not assume that a simple single-point injection test validates the complete thermal model.

18.3 Starting Supervision Test

Simulate a motor start using the approved test method.

Verify starting detection, acceleration supervision, and excessive starting time logic.

18.4 Locked Rotor Test

Simulate the relevant current and timing conditions.

Verify that the relay identifies an abnormal starting or locked-rotor condition.

18.5 Overcurrent Test

Test instantaneous and time overcurrent elements.

Record pickup values and operating times.

18.6 Ground-Fault Test

Inject the appropriate residual or core-balance current signal.

Verify pickup, timing, alarm, and trip logic.

18.7 Negative-Sequence Test

Apply unbalanced phase currents and verify the negative-sequence measurement and protection response.

18.8 Undercurrent Test

Apply current below the configured threshold and verify the operating logic and any starting supervision.

18.9 RTD Test

Where RTD inputs are installed, use suitable resistance simulation equipment to verify temperature measurement, alarm, trip, and sensor failure supervision.

18.10 Trip Circuit Test

Verify the complete trip path:

Protection element → Relay logic → Output contact → Contactor or circuit breaker trip circuit

Confirm that external interlocks and emergency shutdown arrangements operate as intended.

19. Common GE Multilin Motor Protection Problems

Problem 1 – Motor Trips During Normal Starting

Possible causes:

  • Starting current exceeds the configured limit.
  • Starting time is set too short.
  • Incorrect CT ratio.
  • Incorrect thermal model.
  • Incorrect starting detection logic.

Recommended action: Compare measured starting current and acceleration time with the motor manufacturer’s data.

Problem 2 – Motor Thermal Protection Operates During Normal Loading

Possible causes:

  • Incorrect rated motor current.
  • Incorrect thermal time constants.
  • Incorrect CT scaling.
  • Excessive load.
  • Cooling problem.
  • Incorrect thermal memory configuration.

Recommended action: Verify motor data and compare actual current and temperature conditions with the manufacturer’s limits.

Problem 3 – Ground-Fault Protection Operates Incorrectly

Possible causes:

  • Incorrect CT polarity.
  • Incorrect residual wiring.
  • Core-balance CT installation problem.
  • Incorrect pickup.
  • Cable shielding or grounding arrangement issue.

Recommended action: Inspect the CT circuit and verify the grounding design.

Problem 4 – Negative-Sequence Protection Operates Frequently

Possible causes:

  • Supply voltage unbalance.
  • Single-phasing.
  • Loose connections.
  • CT measurement errors.
  • Incorrect phase assignment.

Recommended action: Analyze phase currents and voltages and verify the CT wiring.

Problem 5 – Motor Restart Is Blocked

Possible causes:

  • Thermal capacity remains high.
  • Starts-per-hour limit has been reached.
  • Minimum restart time has not elapsed.
  • External permissive is missing.
  • Restart inhibition logic is active.

Recommended action: Review relay thermal status, starting history, and external control logic before attempting another start.

20. Motor Protection Commissioning Checklist

  • Relay model and firmware verified.
  • Motor nameplate data collected.
  • Motor starting data reviewed.
  • CT ratio verified.
  • CT polarity and phase assignment checked.
  • VT configuration checked, where applicable.
  • Thermal overload settings reviewed.
  • Starting supervision tested.
  • Locked-rotor protection tested.
  • Starts-per-hour supervision checked.
  • Phase overcurrent tested.
  • Ground-fault protection tested.
  • Negative-sequence protection tested.
  • Undercurrent protection tested.
  • Voltage protection tested, where applicable.
  • RTD inputs tested, where installed.
  • Alarm and trip logic verified.
  • Contactor or breaker trip tested.
  • Restart inhibition checked.
  • Event records and measurements reviewed.
  • Final settings and test reports archived.

21. Engineering Recommendations

For reliable GE Multilin motor protection engineering:

  1. Use actual motor nameplate and manufacturer data.
  2. Confirm the CT ratio and relay input rating.
  3. Study the motor starting current and acceleration time.
  4. Coordinate thermal overload protection with the motor’s thermal limits.
  5. Verify hot and cold locked-rotor withstand times.
  6. Avoid setting instantaneous overcurrent protection too low.
  7. Coordinate ground-fault protection with the plant grounding system.
  8. Use negative-sequence limits specified by the motor manufacturer.
  9. Configure restart inhibition according to the motor’s permitted starting frequency.
  10. Consider RTD monitoring for critical motors where suitable.
  11. Coordinate protection with soft starters and variable frequency drives.
  12. Test the complete trip circuit, not only the relay protection elements.
  13. Archive settings, test reports, and event records.

22. Conclusion

GE Multilin 339, 369, 469, and 869 motor protection relays provide solutions for different industrial motor protection applications.

A dependable motor protection scheme requires correct configuration of thermal overload, starting supervision, locked-rotor protection, phase overcurrent, ground fault, negative sequence, undercurrent, voltage protection, and other functions required by the motor and plant design.

The most important engineering task is to coordinate relay settings with the motor manufacturer’s electrical and thermal limits. Incorrect motor data or CT configuration can lead to nuisance trips or inadequate protection.

Practical commissioning should verify current measurements, protection pickup and timing, thermal behavior, starting logic, alarm and trip outputs, and the complete motor control interface.

23. Training on GE Multilin Motor Protection by Elec-Engg

Elec-Engg provides practical technical training by Dr Saeed Roostaee (Electrical Engineering) for engineers involved in motor protection, industrial power systems, relay engineering, testing, and commissioning.

Relevant training topics include:

  • GE Multilin 339, 369, 469, and 869 motor protection relays.
  • Motor protection philosophy and ANSI functions.
  • Motor thermal overload protection (49).
  • Motor starting and acceleration supervision.
  • Locked-rotor protection.
  • Phase and ground overcurrent protection.
  • Negative-sequence protection (46).
  • Undercurrent and loss-of-load protection (37).
  • Starts-per-hour supervision (66).
  • CT and VT configuration.
  • Motor protection coordination.
  • EnerVista configuration and settings management.
  • Secondary injection testing and commissioning.
  • Practical fault analysis and troubleshooting.