- 1. Introduction
- 2. Understanding Generator Excitation
- 3. Causes of Loss of Excitation
- 4. What Happens When a Generator Loses Excitation?
- 5. Effects of Loss of Excitation on the Generator
- 6. ANSI 40 Loss-of-Excitation Protection Principle
- 7. Impedance Characteristics for Loss-of-Excitation Protection
- 8. Generator Capability Curve and Underexcitation Limits
- 9. Coordination with the AVR and Underexcitation Limiter
- 10. Single-Zone and Multi-Zone Protection Approaches
- 11. Practical Engineering Example: Generator Rating and Impedance Base
- 12. CT and VT Configuration for ANSI 40
- 13. GE Multilin Relays and Loss-of-Excitation Applications
- 14. Generic GE Multilin EnerVista Configuration Workflow
- 15. Testing and Commissioning of ANSI 40
- 16. Common Problems and Troubleshooting
- 17. Practical Commissioning Checklist
- 18. Important Engineering Recommendations
- 19. Training on GE Multilin Protection Relays by Elec-Engg
- 20. Frequently Asked Questions
- What is ANSI 40 protection?
- Why does a generator absorb reactive power after losing excitation?
- How does impedance-based loss-of-excitation protection work?
- What is an offset mho characteristic?
- What is the difference between ANSI 40 and the underexcitation limiter?
- Can loss-of-excitation protection operate during normal underexcited operation?
- Which GE Multilin relays can provide ANSI 40 protection?
- How is ANSI 40 tested?
- Does loss of excitation always cause immediate generator tripping?
- 21. Conclusion
1. Introduction
Loss-of-excitation protection is one of the most important protection functions for synchronous generators. It detects abnormal reduction or complete loss of the generator field current and helps prevent damage to the machine and instability in the power system.
When a synchronous generator loses its excitation, it may continue operating temporarily while drawing reactive power from the connected electrical network. This operating condition is known as generator underexcitation or, in more severe cases, generator motoring-like asynchronous operation.
The consequences can include:
- Excessive reactive power absorption from the grid.
- Rotor and stator end-region heating.
- Reduced synchronizing torque.
- Loss of synchronism and pole slipping.
- Voltage instability in the surrounding network.
- Mechanical and thermal stress on the generator.
GE Multilin generator protection platforms, including certain G60, G30 and 889 configurations, may provide loss-of-excitation protection capabilities. The exact implementation, measuring quantities, characteristics and available settings depend on the relay model, firmware and enabled functions.
This article explains the engineering principles of ANSI 40 protection, impedance-based detection, generator capability curves, setting considerations, configuration and commissioning.
2. Understanding Generator Excitation
A synchronous generator requires a DC magnetic field in its rotor to establish the magnetic flux necessary for generating electrical power.
The excitation system supplies field current to the rotor winding. Depending on the generator design, the excitation system may include:
- Automatic voltage regulator (AVR).
- Exciter.
- Rectifier or rotating diode system.
- Field winding.
- Field breaker or field-discharge circuit.
- Excitation transformers and associated equipment.
- Excitation control and monitoring circuits.
The AVR continuously adjusts the field current to regulate generator terminal voltage and reactive power output.
When excitation is reduced, the generator’s internal generated voltage decreases. The machine may then absorb reactive power from the power system to maintain its electromagnetic operating condition.
This is why a generator that has lost excitation can remain connected to the grid for a limited period while operating abnormally.
3. Causes of Loss of Excitation
Loss of excitation can occur due to electrical, mechanical, control-system or operational failures.
3.1 Field breaker opening
An unintended opening of the generator field breaker interrupts the field current. Depending on the excitation system and protection arrangement, this may result in a rapid reduction in excitation.
3.2 AVR failure
An AVR malfunction can cause the excitation system to reduce field current below the required operating level.
Possible causes include:
- Control electronics failure.
- Incorrect voltage feedback.
- Defective control signals.
- Loss of auxiliary supply.
- Incorrect AVR configuration.
- Failure of excitation control components.
3.3 Exciter failure
The exciter may fail to provide the required excitation power. The consequences depend on whether the system uses static or brushless excitation.
3.4 Rotor field circuit problems
Open circuits, loose connections, damaged insulation or other rotor circuit problems can interrupt or reduce field current.
3.5 Rotating diode failure
In brushless excitation systems, rotating rectifier faults can reduce or interrupt the DC field supply.
3.6 Incorrect operation or maintenance
Human errors during maintenance, testing or excitation-system switching can also contribute to loss of excitation.
A complete loss of excitation is not the only concern. Partial loss or severe underexcitation can also cause operation outside the generator’s permitted capability.
4. What Happens When a Generator Loses Excitation?
Consider a synchronous generator operating in parallel with a strong electrical network.
Under normal conditions, the excitation system establishes the rotor magnetic field, while the generator supplies active and reactive power according to its operating point.
If excitation is lost:
- The internal generated voltage decreases.
- The generator’s reactive power output reduces.
- The machine may begin absorbing reactive power from the network.
- The apparent impedance measured at the generator terminals changes.
- The operating point may move outside the permitted capability curve.
- Rotor-angle stability may deteriorate.
- The generator may eventually lose synchronism.
The exact dynamic response depends on generator construction, network strength, loading, excitation-system design and the operating condition before the fault.
4.1 Reactive power absorption
A generator normally supplies or absorbs reactive power depending on its excitation level.
- Overexcited generator: generally supplies reactive power.
- Normally excited generator: operates near its intended voltage and reactive power target.
- Underexcited generator: absorbs reactive power.
- Severe loss of excitation: may lead to instability and asynchronous operation.
The direction of reactive power should always be interpreted using the plant’s metering convention and relay configuration.
5. Effects of Loss of Excitation on the Generator
5.1 Rotor heating
Loss of synchronism and asynchronous operation can produce induced currents in rotor components. These currents may cause significant rotor heating.
5.2 Stator end-region heating
Underexcited operation can increase flux concentrations and heating in the stator end regions. The permissible operating limit depends on generator design.
5.3 Reactive power demand
The generator may absorb substantial reactive power from the connected network, potentially affecting voltage stability and other connected equipment.
5.4 Stability problems
The generator may lose synchronism with the power system. Pole slipping can produce severe electrical and mechanical disturbances.
5.5 Network voltage instability
A generator absorbing reactive power during a system disturbance can worsen voltage conditions, especially in a weak network.
Loss-of-excitation protection therefore protects both the generator and the wider power system.
6. ANSI 40 Loss-of-Excitation Protection Principle
ANSI device number 40 identifies loss-of-field or loss-of-excitation protection.
One widely used detection method is based on measuring the apparent impedance at the generator terminals.
The relay measures generator voltage and current and calculates the apparent impedance:
[
Z=\frac{V}{I}
]
For three-phase protection applications, the relay uses its configured voltage and current measuring quantities and the applicable impedance calculation.
The apparent impedance changes as the generator moves from normal operation toward underexcited or loss-of-excitation conditions.
The relay evaluates the measured impedance against configured operating characteristics.
When the impedance enters a defined protection region for the required time, the relay can initiate an alarm or trip, depending on the protection design.
Important: Not every GE Multilin generator relay implements ANSI 40 using an identical impedance algorithm or characteristic. The actual measuring method and available settings must be checked in the relevant model and firmware documentation.
7. Impedance Characteristics for Loss-of-Excitation Protection
Loss-of-excitation protection is commonly implemented using impedance characteristics in the R-X plane.
The horizontal axis represents resistance, while the vertical axis represents reactance.
The protection characteristic may use an offset mho circle or another manufacturer-defined operating region.
7.1 Offset mho characteristic
An offset mho characteristic is commonly used for detecting loss of excitation.
Its geometry is selected to cover the expected impedance trajectory associated with underexcited generator operation while maintaining security during normal operating conditions.
A simplified representation of a circular characteristic is:
[
(R-R_c)^2+(X-X_c)^2=r^2
]
Where:
- (R) = measured resistance.
- (X) = measured reactance.
- (R_c) = circle centre resistance.
- (X_c) = circle centre reactance.
- (r) = circle radius.
The actual characteristic used by a relay may differ from this simplified mathematical representation.
7.2 Why an offset characteristic is used
The characteristic must distinguish between:
- Normal generator operation.
- Permitted underexcited operation.
- Abnormal underexcitation.
- Loss-of-excitation conditions.
- External faults and other disturbances.
An offset characteristic can provide coverage of the expected loss-of-excitation impedance region while helping avoid operation during normal load changes.
7.3 Impedance trajectory
During a loss-of-excitation event, the apparent impedance trajectory may move into the relay’s defined operating region.
The trajectory depends on:
- Generator synchronous reactances.
- Generator loading before excitation loss.
- Network impedance.
- Generator terminal voltage.
- Active power output.
- Reactive power exchange.
- Fault and disturbance conditions.
For this reason, the protection characteristic should be engineered using the generator parameters and system studies rather than copied from another installation.
8. Generator Capability Curve and Underexcitation Limits
The generator capability curve defines the permitted operating region of the machine in terms of active and reactive power.
It is one of the most important documents for engineering loss-of-excitation protection.
The capability curve normally considers:
- Stator current heating limit.
- Rotor field current heating limit.
- Underexcitation limit.
- Stability limit.
- Prime mover limitations.
- Generator terminal voltage.
8.1 Active and reactive power
Generator apparent power is:
[
S=\sqrt{P^2+Q^2}
]
Where:
- (S) = apparent power in MVA.
- (P) = active power in MW.
- (Q) = reactive power in MVAr.
The relationship can also be expressed as:
[
Q=\pm\sqrt{S^2-P^2}
]
The sign depends on whether the generator supplies or absorbs reactive power under the selected convention.
8.2 Underexcitation region
The underexcitation region represents operating points where the generator absorbs reactive power.
Although some underexcited operation may be permitted, the generator must not exceed its manufacturer-defined operating limits.
The underexcitation limiter (UEL) in the excitation control system helps prevent the generator from operating beyond these limits.
However, the UEL is a control function, not a replacement for independent generator protection.
9. Coordination with the AVR and Underexcitation Limiter
Loss-of-excitation protection must be coordinated with the excitation control system.
The principal systems involved are:
- Automatic voltage regulator (AVR).
- Underexcitation limiter (UEL).
- Generator capability limits.
- ANSI 40 protection.
- Generator trip logic.
The UEL should normally prevent the generator from entering prohibited underexcited operating conditions during normal operation.
ANSI 40 provides protection when the excitation condition becomes abnormal and cannot be corrected by the control system.
The coordination study should consider:
- The generator capability curve.
- The UEL operating boundary.
- The expected impedance trajectory.
- The loss-of-excitation protection characteristic.
- The required operating time.
- Stability and system-security requirements.
- Generator manufacturer recommendations.
The protection should not unnecessarily trip the generator during acceptable transient or steady-state operation.
At the same time, it must detect genuine loss-of-excitation events quickly enough to protect the machine and system.
10. Single-Zone and Multi-Zone Protection Approaches
Depending on the relay and protection philosophy, loss-of-excitation protection may use one or more operating zones.
10.1 Single-zone approach
A single operating zone provides a defined impedance boundary and associated operating delay.
It may be suitable for some generator applications, depending on the machine characteristics and system study.
10.2 Two-zone approach
Some protection designs use two operating zones with different reaches and time delays.
A simplified philosophy may include:
- A more sensitive zone with a longer delay.
- A faster zone for more severe loss-of-excitation conditions.
This approach can improve coverage and coordination.
However, the number of zones, their geometry and timing are relay-specific. Do not assume that every GE Multilin model provides the same arrangement.
11. Practical Engineering Example: Generator Rating and Impedance Base
Consider a hypothetical synchronous generator with the following ratings:
- Rated apparent power: 100 MVA.
- Rated voltage: 13.8 kV.
- Frequency: 50 Hz.
The generator impedance base is:
[
Z_{base}=\frac{V_{LL}^{2}}{S_{3\phi}}
]
Substituting:
[
Z_{base}=\frac{13.8^2}{100}
]
[
Z_{base}=1.9044\ \Omega
]
Therefore:
[
1\ pu=1.9044\ \Omega
]
If a study identifies an impedance value of 0.8 pu, its corresponding primary impedance magnitude on this base is:
[
Z=0.8\times1.9044
]
[
Z=1.5235\ \Omega
]
This calculation establishes the impedance base for engineering analysis.
It does not determine the loss-of-excitation relay reach. Actual zone settings require the generator reactances, capability curve, CT/VT ratios, network equivalent and the relay manufacturer’s characteristic definition.
12. CT and VT Configuration for ANSI 40
Accurate voltage and current measurement is essential for impedance-based protection.
12.1 Current transformer configuration
Verify:
- CT primary rating.
- CT secondary rating.
- CT polarity.
- Phase assignment.
- Connection arrangement.
- Correct relay current input selection.
- CT circuit integrity.
Incorrect CT polarity or phase assignment can cause erroneous impedance measurement.
12.2 Voltage transformer configuration
Verify:
- VT primary voltage.
- VT secondary voltage.
- Phase-to-phase or phase-to-neutral measurement.
- Phase sequence.
- VT polarity.
- Connection arrangement.
- Fuse supervision or VT failure detection, where available.
12.3 Impedance conversion
The relay may use secondary impedance quantities internally.
The conversion between primary and secondary impedance depends on the CT and VT ratios.
A commonly used relationship is:
[
Z_{secondary}=Z_{primary}
\times\frac{CTR}{VTR}
]
Where:
- (CTR) = CT ratio.
- (VTR) = VT ratio.
The engineer must confirm how the specific relay defines its ratios and impedance base before entering settings.
13. GE Multilin Relays and Loss-of-Excitation Applications
GE Multilin generator protection platforms may provide ANSI 40 functionality depending on the specific model, hardware, firmware and enabled options.
Relevant platforms to investigate include:
13.1 GE Multilin G60
The G60 generator protection system is designed for comprehensive generator protection applications. Its available loss-of-excitation functions and implementation must be confirmed against the exact product and firmware documentation.
13.2 GE Multilin G30
The G30 generator protection platform may be used in generator protection schemes. Verify the exact ANSI 40 functionality and available settings for the installed version.
13.3 GE Multilin 889
The 889 generator protection system is another platform to consider when reviewing generator protection applications. Confirm the specific protection functions and configuration options for the ordered device.
Do not assume that the three relays have identical ANSI 40 characteristics, settings names or engineering procedures.
14. Generic GE Multilin EnerVista Configuration Workflow
The following is a general engineering workflow. Actual menus, parameter names and available settings depend on the relay model and firmware.
Step 1: Identify the relay
Record:
- Exact relay model.
- Product order code.
- Firmware revision.
- Hardware configuration.
- Enabled protection functions.
Step 2: Establish the generator data
Collect:
- Generator rated MVA.
- Rated voltage.
- Rated current.
- Power factor.
- Synchronous reactance.
- Transient and subtransient reactances, as required by the study.
- Generator capability curve.
- Manufacturer underexcitation limits.
Step 3: Verify CT and VT settings
Check the current and voltage transformer ratios, polarity, phase assignment and measuring configuration.
Step 4: Review the loss-of-excitation function
Confirm whether ANSI 40 is available and identify:
- Operating characteristic.
- Zone configuration.
- Reach parameters.
- Directional or supervising quantities, where applicable.
- Time delays.
- Alarm and trip outputs.
Step 5: Enter approved settings
Use the approved protection study and generator manufacturer information.
Do not copy settings from another generator simply because it uses the same relay family.
Step 6: Configure output logic
Determine whether the protection should initiate:
- Alarm.
- Generator breaker trip.
- Field breaker trip.
- Turbine or prime mover shutdown.
- Lockout relay operation.
- Event recording.
The final logic must match the plant protection philosophy and approved trip matrix.
Step 7: Save and verify the configuration
After entering the settings:
- Save the project.
- Check for setting errors.
- Compare against the approved setting sheet.
- Record the firmware and settings revision.
- Confirm the final settings have been loaded into the correct relay.
15. Testing and Commissioning of ANSI 40
Loss-of-excitation protection testing must verify both the measuring characteristic and the complete trip logic.
Testing should be performed by qualified personnel using approved procedures and suitable secondary injection equipment.
15.1 Preparation
Before testing:
- Review the approved protection settings.
- Obtain the generator data and capability curve.
- Review the relay manual.
- Identify the protection output and trip path.
- Apply the approved isolation and safety procedures.
- Prevent unintended generator or breaker operation.
15.2 CT and VT measurement verification
Inject balanced voltage and current signals and verify:
- Measured phase voltages.
- Measured phase currents.
- Phase sequence.
- Voltage-current phase relationship.
- Calculated impedance.
- Power and reactive power direction, where available.
15.3 Impedance characteristic testing
Use a suitable relay test set to inject voltage and current combinations representing points in the R-X plane.
Test points should include:
- Points safely outside the operating region.
- Points near the characteristic boundary.
- Points inside the operating region.
- Points in any configured restraint or blocking regions.
Verify that the relay responds according to the approved characteristic and tolerances.
15.4 Timing test
For each applicable operating zone:
- Apply the test condition inside the operating region.
- Measure the time from application of the test quantity to relay operation.
- Compare the result with the approved delay and manufacturer’s tolerance.
- Repeat at relevant test points.
15.5 Alarm and trip logic test
Verify the complete logic path, including:
- ANSI 40 pickup.
- Alarm output.
- Trip output.
- Lockout relay.
- Breaker trip circuit.
- Field breaker trip, if included.
- Event and disturbance records.
15.6 Stability and security tests
Test representative conditions outside the operating region to confirm that the protection remains stable.
Where required by the protection study, test interactions with:
- VT failure supervision.
- Generator differential protection.
- Stator earth-fault protection.
- Power swing or out-of-step protection.
- Generator shutdown logic.
15.7 End-to-end functional verification
Where the commissioning scope requires it, verify the complete chain from simulated loss-of-excitation conditions through relay operation to the designated output and trip equipment.
A secondary injection test alone does not prove the complete field circuit or excitation system response.
16. Common Problems and Troubleshooting
Problem 1: Incorrect impedance measurement
Possible causes:
- Incorrect CT ratio.
- Incorrect VT ratio.
- Reversed CT polarity.
- Incorrect phase assignment.
- Wrong voltage connection.
- Incorrect phase sequence.
Recommended action: Verify the complete CT and VT circuits and compare relay measurements with an independent test instrument.
Problem 2: Unwanted ANSI 40 operation
Possible causes:
- Incorrect characteristic reach.
- Incorrect impedance base.
- Incorrect CT/VT scaling.
- Poor coordination with the capability curve.
- Incorrect measuring configuration.
- Unconsidered system disturbances.
Recommended action: Review the disturbance record, measured impedance trajectory, generator operating point and approved protection study.
Problem 3: Protection fails to operate during testing
Possible causes:
- Function disabled.
- Incorrect test quantities.
- Wrong operating region.
- Incorrect voltage/current phase relationship.
- Incorrect timing expectations.
- Output logic not configured.
Recommended action: Check the relay’s function status, characteristic settings, test-set configuration and trip matrix.
Problem 4: UEL and ANSI 40 coordination problems
Possible causes:
- Inconsistent capability-curve data.
- Incorrect UEL settings.
- Incorrect protection characteristic.
- Insufficient operating margin.
- Changes to generator or excitation-system parameters.
Recommended action: Coordinate the generator manufacturer, excitation-system engineer and protection engineer to review the complete operating limits.
Problem 5: Incorrect reactive power direction
Possible causes:
- CT polarity errors.
- VT polarity errors.
- Incorrect phase mapping.
- Different sign conventions between instruments and relay.
Recommended action: Verify the three-phase measuring circuits and establish the plant’s import/export convention.
17. Practical Commissioning Checklist
Before returning the generator to service, verify the following:
- Correct GE Multilin relay model and firmware identified.
- ANSI 40 function availability confirmed.
- Generator rated data verified.
- Generator capability curve reviewed.
- CT ratios and polarity checked.
- VT ratios and polarity checked.
- Phase sequence and phase assignment verified.
- Impedance base confirmed.
- Protection characteristic checked against the study.
- UEL and AVR coordination reviewed.
- Zone settings and time delays verified, where applicable.
- Alarm and trip logic tested.
- Breaker and field trip circuits verified.
- Stability tests completed.
- Event records and disturbance recording checked.
- Final settings backed up.
- Test report completed and approved.
18. Important Engineering Recommendations
- Always use the generator manufacturer’s capability curve when engineering loss-of-excitation protection.
- Do not select ANSI 40 settings solely from a generic example or another generator installation.
- Confirm the exact impedance characteristic implemented by the installed relay.
- Check the CT and VT ratios carefully because impedance protection depends on both quantities.
- Coordinate the protection with the AVR and UEL.
- Consider generator loading and network strength when studying loss-of-excitation behaviour.
- Test both operation and stability.
- Verify the complete trip logic, not only the relay element.
- Review disturbance records after any unexpected operation.
- Record the exact relay model, firmware and setting revision in commissioning documentation.
19. Training on GE Multilin Protection Relays by Elec-Engg
Understanding ANSI 40 requires more than knowing the protection function. Engineers must understand synchronous generator operation, excitation systems, impedance characteristics, generator capability curves, CT/VT circuits, relay settings and practical testing procedures.
Elec-Engg provides practical technical training by Dr Saeed Roostaee (Electrical Engineering) for engineers working in power system protection, commissioning, operation and maintenance.
Relevant training subjects include:
- GE Multilin generator protection.
- Generator loss-of-excitation protection (ANSI 40).
- Generator differential protection (ANSI 87G).
- Generator stator and rotor earth-fault protection.
- Reverse power protection (ANSI 32).
- Negative-sequence protection (ANSI 46).
- Overvoltage, undervoltage and frequency protection.
- Generator protection coordination.
- GE Multilin EnerVista configuration and troubleshooting.
- Secondary injection testing and commissioning.
Training delivery options include:
- Pre-recorded technical video courses.
- Structured self-paced training.
- Live online technical training.
- Face-to-face training.
- Customized in-house training for utilities, power plants and industrial companies.
The training emphasizes practical engineering procedures, relay configuration, protection logic, testing methods and troubleshooting rather than relying only on theoretical descriptions.
Visit Elec-Engg for available courses and technical training:
Website: https://elec-engg.com/
Training enquiries: https://elec-engg.com/contact/
20. Frequently Asked Questions
What is ANSI 40 protection?
ANSI 40 is loss-of-field or loss-of-excitation protection for synchronous machines. It detects abnormal loss or reduction of excitation and helps protect the generator against damaging underexcited or asynchronous operation.
Why does a generator absorb reactive power after losing excitation?
When the rotor field weakens, the generator may no longer maintain its normal reactive power output. It can begin drawing reactive power from the connected electrical network, depending on the operating condition and system characteristics.
How does impedance-based loss-of-excitation protection work?
The relay measures generator voltage and current, calculates apparent impedance and compares the result with a defined operating characteristic. Entry into the configured operating region for the required time can initiate an alarm or trip.
What is an offset mho characteristic?
It is an impedance-based protection characteristic commonly used for loss-of-excitation detection. Its offset and reach are selected to cover the expected abnormal operating region while maintaining stability during permitted operation.
What is the difference between ANSI 40 and the underexcitation limiter?
The UEL is part of the excitation control system and helps keep the generator within its permitted operating region. ANSI 40 is a protection function intended to detect abnormal loss-of-excitation conditions and initiate protective action.
Can loss-of-excitation protection operate during normal underexcited operation?
Properly engineered protection should remain stable during permitted underexcited operation. The characteristic must be coordinated with the generator capability curve, UEL and system studies.
Which GE Multilin relays can provide ANSI 40 protection?
Potential generator protection platforms include the G60, G30 and 889. Exact function availability and implementation must be verified against the installed relay model, firmware and order configuration.
How is ANSI 40 tested?
Testing typically includes verification of CT/VT measurements, impedance characteristic testing, operating-time measurement, stability tests and complete alarm/trip logic verification.
Does loss of excitation always cause immediate generator tripping?
Not necessarily. The protection response depends on the severity of the condition, operating zones, time delays and plant protection philosophy. The approved protection design determines the required action.
21. Conclusion
Loss-of-excitation protection is essential for protecting synchronous generators against abnormal underexcited operation, excessive reactive power absorption, rotor heating and loss of synchronism.
ANSI 40 protection commonly uses impedance-based characteristics to identify the abnormal operating condition. Correct engineering requires a detailed understanding of generator parameters, capability curves, CT/VT circuits, excitation-system behaviour and power-system stability.
For GE Multilin generator protection systems, engineers must verify the exact functionality and configuration of the installed relay rather than assume that all models use identical characteristics.
A properly engineered, configured and tested ANSI 40 scheme contributes significantly to generator protection and overall power-system reliability.
Related GE Multilin articles:
- GE Multilin Generator Protection: ANSI 87G, 40, 32, 46, 49, 27/59 and 81.
- GE Multilin Reverse Power Protection (ANSI 32).
- GE Multilin Negative-Sequence Protection (ANSI 46).
- GE Multilin Overexcitation Protection (ANSI 24).
- GE Multilin Protection Relay Testing and Commissioning.
- GE Multilin EnerVista Software: Relay Configuration and Troubleshooting.