Sepam Protection Functions: Complete Technical Reference
- 1. Introduction to Sepam Protection Functions
- 2.1 Operating Principle
- 2.2 Instantaneous Overcurrent (50)
- 2.3 Time-Delayed Overcurrent (51)
- 2.4 Engineering Considerations
- 3.1 Operating Principle
- 3.2 Applications
- 3.3 Protection Setting Considerations
- 4.1 Why Directional Protection Is Required
- 4.2 Operating Principle
- 4.3 Typical Applications
- 4.4 Engineering Considerations
- 5.1 Operating Principle
- 5.2 Thermal State
- 5.3 Applications
- 5.4 Typical Setting Considerations
- 6.1 Operating Principle
- 6.2 Causes of Negative Sequence Current
- 6.3 Applications
- 6.4 Engineering Considerations
- 7.1 Operating Principle
- 7.2 Causes of Undervoltage
- 7.3 Applications
- 7.4 Setting Considerations
- 8.1 Operating Principle
- 8.2 Causes of Overvoltage
- 8.3 Applications
- 8.4 Engineering Considerations
- 9.1 Underfrequency Protection
- 9.2 Overfrequency Protection
- 9.3 Applications
- 9.4 Engineering Considerations
- 10.1 Operating Principle
- 10.2 Generator Applications
- 10.3 Applications
- 10.4 Setting Considerations
- 11.1 Operating Principle
- 11.2 Differential Protection Zones
- 11.3 Differential Protection Characteristics
- 11.4 Applications
- 11.5 Engineering Considerations
- 12.1 Operating Principle
- 12.2 Why REF Is Used
- 12.3 Applications
- 12.4 Engineering Considerations
- 13.1 Why Breaker Failure Protection Is Required
- 13.2 Operating Principle
- 13.3 Applications
- 13.4 Engineering Considerations
- 14.1 Why Synchronism Check Is Important
- 14.2 Operating Principle
- 14.3 Applications
- 14.4 Setting Considerations
- 15.1 Operating Principle
- 15.2 Reclosing Sequence Types
- 15.3 Applications
- 15.4 Engineering Considerations
- 16.1 What Is Cold Load Pickup?
- 16.2 Operating Principle
- 16.3 Applications
- 16.4 Engineering Considerations
- 17.1 Why Load Shedding Is Required
- 17.2 Load Shedding Methods
- 17.3 Load Priority
- 17.4 Engineering Considerations
- 18.1 Why Circuit Breaker Monitoring Is Important
- 18.2 Trip Circuit Supervision
- 18.3 Circuit Breaker Operating Time Monitoring
- 18.4 Switching Operation Counter
- 18.5 Breaker Wear and Interruption Duty
- 18.6 Applications
- 18.7 Engineering Considerations
- 19.1 Typical Function Coordination
This article provides a comprehensive technical overview of the major protection, control, monitoring, and automation functions used in Schneider Electric Sepam protection relays. It covers fundamental ANSI/IEEE protection functions, their operating principles, applications, typical setting considerations, coordination requirements, and practical engineering aspects for commissioning and troubleshooting.
Sepam protection relays are applied in industrial electrical networks, utilities, substations, motor feeders, transformers, generators, and other power system equipment. Depending on the Sepam model, hardware configuration, firmware, and application, different protection functions may be available.
The purpose of this guide is to help protection engineers, commissioning engineers, maintenance engineers, and electrical technicians understand how individual protection functions operate and how they work together in a coordinated protection scheme.
1. Introduction to Sepam Protection Functions
Sepam relays provide protection against electrical faults, abnormal operating conditions, equipment overloads, voltage disturbances, frequency deviations, and circuit breaker failures.
Protection functions are generally organized into several categories:
- Current-based protection
- Voltage-based protection
- Frequency-based protection
- Power-based protection
- Differential protection
- Circuit breaker protection and supervision
- System restoration and switching functions
- Load management and shedding
- Equipment monitoring and diagnostics
Each protection function detects a specific abnormal condition and initiates an appropriate response, such as alarm, trip, blocking, control action, or transfer of information to the substation automation system.
The available functions depend on the Sepam family and model, such as Sepam Series 20, Series 40, Series 60, Series 80, and specialized application models.
2. Phase Overcurrent Protection (50/51)
Phase overcurrent protection is one of the most fundamental protection functions used in electrical power systems. It detects excessive current flowing through the phase conductors due to overloads, short circuits, or other abnormal conditions.
ANSI functions:
- 50 — Instantaneous Overcurrent
- 51 — Time-Delayed Overcurrent
2.1 Operating Principle
The relay continuously measures the phase currents through connected current transformers (CTs).
When one or more phase currents exceed the configured pickup threshold, the relay starts the corresponding protection element.
Depending on the selected characteristic, the protection may operate:
- Immediately after pickup
- After a fixed delay
- According to an inverse-time characteristic
Instantaneous protection is generally used for high-current faults, while time-delayed protection provides coordination with downstream and upstream protective devices.
2.2 Instantaneous Overcurrent (50)
The instantaneous element operates when the measured current exceeds the configured threshold and any required operating conditions are satisfied.
Typical applications:
- High-current phase-to-phase faults
- Close-in feeder faults
- Short-circuit protection
- Fast fault clearance where selectivity is not compromised
2.3 Time-Delayed Overcurrent (51)
The time-delayed element operates after the current exceeds the pickup threshold for a defined operating time or calculated time according to a selected inverse characteristic.
Common curve families include:
- Definite Time
- Standard Inverse
- Very Inverse
- Extremely Inverse
- Other manufacturer-specific inverse curves
Inverse-time operation provides coordination between protection devices by allowing higher fault currents to be cleared faster while maintaining longer delays for lower fault currents.
2.4 Engineering Considerations
Important setting parameters include:
- Current pickup
- Time delay
- Curve selection
- Time multiplier or time dial
- Phase selection
- Reset characteristics
- Trip output assignment
- Coordination with upstream and downstream relays
Settings must account for maximum load current, minimum fault current, CT ratio, motor starting currents, transformer inrush, and network fault levels.
3. Earth Fault Protection (50N/51N)
Earth fault protection detects current flowing from a phase conductor to earth or through an unintended grounding path.
ANSI functions:
- 50N — Instantaneous Earth Fault
- 51N — Time-Delayed Earth Fault
Depending on the relay configuration, earth fault current may be measured using:
- Residual current calculated from three phase CTs
- Core-balance CT
- Neutral CT
- Dedicated earth fault CT
3.1 Operating Principle
The relay detects residual current:
\[ I_0 = I_A + I_B + I_C \]
The residual or zero-sequence current is normally close to zero under balanced conditions, depending on the measurement arrangement.
During an earth fault, the residual current increases and can initiate the earth fault protection element.
3.2 Applications
- Cable earth faults
- Feeder earth faults
- Transformer secondary earth faults
- Ground faults in industrial distribution networks
- Earth fault backup protection
3.3 Protection Setting Considerations
- Grounding system type
- Maximum normal residual current
- Minimum earth fault current
- Network capacitance
- CT arrangement and accuracy
- Sensitivity requirements
- Coordination with upstream earth fault protection
- Directional earth fault requirements
In resistance-grounded or isolated-neutral networks, conventional earth fault protection may require different sensitivity and operating characteristics compared with solidly grounded systems.
4. Directional Protection (67)
Directional overcurrent protection determines both the magnitude of current and the direction in which fault current flows.
ANSI function:
– 67 — Directional Overcurrent
It is particularly important in networks where fault current may flow from multiple sources.
4.1 Why Directional Protection Is Required
In a radial network with a single source, overcurrent protection may be sufficient for many applications.
In systems containing:
- Parallel feeders
- Ring networks
- Multiple transformers
- Generators
- Grid connections
- Distributed generation
- Multiple incoming supplies
fault current may flow in different directions.
A non-directional relay may trip unnecessarily for faults outside its intended protection zone.
Directional protection allows the relay to distinguish forward faults from reverse faults.
4.2 Operating Principle
Directional protection uses current and a polarizing voltage reference to determine the direction of fault current.
The relay evaluates the phase relationship between current and voltage, together with the configured directional characteristic.
Depending on the Sepam model, directional protection may support phase directional overcurrent and directional earth fault applications.
4.3 Typical Applications
- Ring distribution systems
- Parallel feeders
- Networks with multiple incomers
- Generator-connected networks
- Utility interconnections
- Directional earth fault protection
4.4 Engineering Considerations
- Voltage polarizing quantities
- Current polarizing quantities, where applicable
- Directional characteristic angle
- Forward and reverse definitions
- VT connections
- Phase rotation
- Minimum polarizing voltage
- Fault type
- Protection coordination
Incorrect voltage or CT polarity, phase sequence, or directional configuration can cause incorrect protection operation.
5. Thermal Overload Protection (49)
Thermal overload protection protects electrical equipment against overheating caused by excessive current or sustained overload conditions.
ANSI function:
– 49 — Thermal Overload
This function is widely used for motors, cables, transformers, and other equipment with thermal limitations.
5.1 Operating Principle
Thermal overload protection estimates the thermal condition of equipment using current measurements and a thermal model.
The relay calculates or estimates the accumulation of heating over time rather than responding only to instantaneous current magnitude.
The thermal model generally considers:
- Load current
- Heating characteristics
- Thermal time constants
- Thermal capacity
- Cooling characteristics
- Previous thermal state
- Alarm and trip thresholds
The protection may maintain a thermal memory, allowing the relay to consider previous heating even after current decreases.
5.2 Thermal State
A simplified thermal model can be expressed as:
\[ \frac{d\theta}{dt} = \frac{I^2}{I_{\mathrm{rated}}^2} – \frac{\theta}{\tau} \]
Where:
- \(\theta\) represents the normalized thermal state
- \(I\) is the measured current
- \(I_{\mathrm{rated}}\) is the reference current
- \(\tau\) is the thermal time constant
This simplified equation illustrates heating and cooling behavior. Actual Sepam thermal algorithms and setting parameters depend on the relay model and application.
5.3 Applications
- Motor thermal protection
- Cable overload protection
- Transformer thermal overload protection
- Equipment overheating prevention
- Alarm before thermal trip
5.4 Typical Setting Considerations
- Rated equipment current
- Thermal capacity
- Heating time constant
- Cooling time constant
- Alarm threshold
- Trip threshold
- Restart restrictions
- Cooling conditions
- Load profile
Thermal overload protection is particularly important where short periods of overload may be acceptable but sustained overload can damage insulation or shorten equipment life.
6. Negative Sequence Protection (46)
Negative sequence protection detects unbalanced phase currents caused by asymmetrical faults, abnormal phase loading, phase loss, or unbalanced operating conditions.
ANSI function:
– 46 — Negative Sequence Overcurrent
6.1 Operating Principle
In a balanced three-phase system, the phase currents are equal in magnitude and separated by 120 degrees. Under balanced conditions, negative sequence current is ideally zero.
When the system becomes unbalanced, negative sequence current appears.
The relay calculates the negative sequence component of the measured phase currents:
\[ I_2 = \frac{1}{3}\left(I_A+a^2 I_B+a I_C\right) \]
Where:
\[ a=e^{j120^\circ} \]
Negative sequence current can cause significant heating in rotating machines, particularly motors and generators.
6.2 Causes of Negative Sequence Current
- Phase-to-phase faults
- Phase-to-earth faults
- Unbalanced loads
- Open phase conditions
- Unequal phase currents
- Incorrect switching conditions
- CT measurement problems
6.3 Applications
- Motor protection
- Generator protection
- Phase imbalance detection
- Open-phase detection
- Backup protection for asymmetrical faults
6.4 Engineering Considerations
The pickup threshold must be selected according to equipment withstand capability and expected normal operating imbalance.
For motors and generators, negative sequence current produces rotor heating that may be substantially greater than the heating caused by balanced positive-sequence current.
The protection must therefore be coordinated with machine thermal limits and the characteristics of the protected equipment.
7. Undervoltage Protection (27)
Undervoltage protection detects when the system voltage falls below a configured threshold.
ANSI function:
– 27 — Undervoltage
7.1 Operating Principle
The relay continuously measures the phase-to-phase or phase-to-neutral voltages, depending on the VT configuration and protection application.
When voltage falls below the pickup threshold, the undervoltage element starts.
Depending on the settings, the relay may operate:
- After a definite time delay
- After a selected delay associated with the protection logic
- On one phase or multiple phases
- With additional supervision or blocking conditions
7.2 Causes of Undervoltage
- Short circuits
- System disturbances
- Overloaded feeders
- Motor starting
- Loss of upstream supply
- Transformer problems
- Voltage regulator failure
- Weak power systems
7.3 Applications
- Load shedding
- Motor protection
- Supply supervision
- Automatic transfer schemes
- Voltage quality monitoring
- Protection against abnormal operating conditions
7.4 Setting Considerations
- Minimum acceptable system voltage
- Normal voltage variation
- Motor starting voltage dips
- VT fuse failure detection
- Time delay
- Number of phases affected
- Load shedding requirements
- Coordination with automatic transfer systems
Undervoltage protection must be designed carefully to avoid unnecessary operation during normal voltage dips or transient disturbances.
8. Overvoltage Protection (59)
Overvoltage protection detects voltage levels exceeding the acceptable operating range of the system or equipment.
ANSI function:
– 59 — Overvoltage
8.1 Operating Principle
The relay measures voltage and compares it with a configured overvoltage threshold.
When voltage exceeds the threshold, the element starts and operates according to the selected delay.
Depending on the application, overvoltage protection may include one or more voltage thresholds with different operating times.
8.2 Causes of Overvoltage
- Sudden load rejection
- Incorrect voltage regulator operation
- Transformer tap changer malfunction
- Generator voltage control problems
- Capacitor switching
- Ground faults in certain system configurations
- Network resonance or transient disturbances
8.3 Applications
- Transformer protection
- Generator protection
- Bus voltage protection
- Capacitor bank applications
- Distribution network protection
- Voltage supervision and alarm
8.4 Engineering Considerations
- Nominal voltage
- VT ratio
- Phase-to-phase or phase-to-neutral measurement
- Pickup threshold
- Operating delay
- Temporary permissible overvoltage
- Equipment insulation capability
- Coordination with voltage control systems
Overvoltage protection settings should be consistent with the insulation withstand capability and the operating philosophy of the network.
9. Frequency Protection (81)
Frequency protection detects deviations from nominal system frequency.
ANSI function:
– 81 — Frequency Protection
Depending on the model and application, frequency protection may include:
- Underfrequency (81U)
- Overfrequency (81O)
- Rate-of-change-of-frequency functions, where supported
- Frequency-based load shedding or restoration logic
9.1 Underfrequency Protection
Underfrequency protection operates when the measured system frequency falls below a defined threshold.
It is commonly associated with generation-load imbalance, particularly when generation is insufficient to supply the connected load.
9.2 Overfrequency Protection
Overfrequency protection operates when system frequency exceeds the configured threshold.
It may indicate excess generation relative to load, islanding conditions, control problems, or other abnormal system conditions.
9.3 Applications
- Generator protection
- Grid interconnection protection
- Load shedding
- Islanding detection schemes
- Power system stability
- Automatic load restoration schemes
9.4 Engineering Considerations
- Nominal frequency
- Pickup thresholds
- Time delays
- Frequency measurement quality
- Voltage supervision
- Rate-of-change settings, if available
- Coordination with generator controls
- Coordination with underfrequency load shedding
Frequency protection should be coordinated with system operator requirements and the applicable grid code.
10. Reverse Power Protection (32)
Reverse power protection detects power flowing in an unintended direction.
ANSI function:
– 32 — Directional Power
This protection is commonly associated with generators, but can also be applied to other systems where the direction of active power flow is important.
10.1 Operating Principle
The relay calculates active power using measured current and voltage.
\[ P = \sum_{k=A,B,C} V_k I_k \cos(\phi_k) \]
The relay evaluates the sign and magnitude of active power according to its configured directional reference.
When the measured power enters the reverse-power region and remains there for the configured delay, the relay may issue an alarm or trip command.
10.2 Generator Applications
In generator applications, reverse power protection can detect motoring conditions.
A generator that loses its prime mover input may remain connected to the electrical system and begin absorbing active power from the network.
This condition may cause the machine to operate as a motor.
Reverse power protection helps prevent unwanted motoring and potential damage to the prime mover.
10.3 Applications
- Generator reverse power protection
- Grid-connected generator protection
- Power flow supervision
- Parallel source protection
- Interconnection protection
10.4 Setting Considerations
- Reverse power threshold
- Power direction convention
- VT and CT polarity
- Power measurement accuracy
- Time delay
- Minimum voltage
- Generator operating conditions
- Prime mover characteristics
Correct CT and VT polarity and phase relationships are essential for reliable directional power measurement.
11. Differential Protection (87)
Differential protection is a highly selective protection principle used to protect a defined zone of electrical equipment.
ANSI function:
– 87 — Differential Protection
Depending on the Sepam model and application, differential protection may be available for transformers, motors, generators, or other protected equipment.
11.1 Operating Principle
Differential protection compares current entering and leaving the protected zone.
Under normal operating conditions and external faults, the currents entering and leaving the zone should balance after compensation for applicable transformation ratios and measurement differences.
The differential current is calculated from the currents measured at the boundaries of the protected zone.
Conceptually:
\[ I_{\mathrm{diff}} = \left| I_1 + I_2 \right| \]
The sign convention and compensation depend on the protected equipment and relay configuration.
If the differential current exceeds the operating characteristic, the relay identifies a fault within the protection zone.
11.2 Differential Protection Zones
Differential protection may be applied to:
- Power transformers
- Generators
- Motors
- Busbars
- Cables
- Other equipment with appropriate differential measurement arrangements
11.3 Differential Protection Characteristics
Practical differential protection often uses a restrained or biased differential characteristic to maintain stability during:
- External faults
- CT saturation
- CT ratio mismatch
- Measurement errors
- Transformer magnetizing inrush
- Overexcitation, where applicable
The protection characteristic typically includes a differential pickup and restraint or bias components.
11.4 Applications
- Internal winding faults
- Phase-to-phase faults
- Internal earth faults, depending on the scheme
- Short circuits within the protected zone
- Rapid fault isolation
11.5 Engineering Considerations
- CT ratio and polarity
- Protected zone boundaries
- CT class and performance
- Differential pickup
- Bias/restraint characteristic
- Inrush restraint
- Harmonic restraint or blocking, where applicable
- External fault stability
- Trip circuit configuration
Differential protection is generally considered a primary protection function because it can provide fast and selective fault clearance within a defined zone.
12. Restricted Earth Fault Protection (64REF)
Restricted earth fault protection is a sensitive earth fault protection scheme designed to detect earth faults within a specific zone, commonly in transformer windings.
ANSI function:
– 64REF — Restricted Earth Fault
Depending on the relay nomenclature and standard adopted, REF may also be identified using related ANSI earth fault designations.
12.1 Operating Principle
Restricted earth fault protection compares residual current measured from the phase CTs with the current measured in the neutral CT.
Under normal conditions and external earth faults, the currents are expected to balance according to the scheme’s polarity and connection.
An internal earth fault within the protected zone produces an imbalance that causes REF operation.
12.2 Why REF Is Used
Transformer differential protection may not always provide the desired sensitivity for low-level earth faults near the neutral point, depending on transformer grounding and the protection scheme.
REF can provide more sensitive detection of internal earth faults within the defined winding zone.
12.3 Applications
- Transformer star-connected winding protection
- Generator winding protection, where applicable
- Grounded neutral systems
- Sensitive internal earth fault detection
12.4 Engineering Considerations
- Phase CT connections
- Neutral CT connection
- CT polarity
- CT ratio matching
- Protected zone definition
- REF sensitivity
- Stability for external earth faults
- Neutral grounding method
- Operating characteristic
REF protection requires careful CT wiring verification and commissioning testing because incorrect polarity or wiring can compromise both sensitivity and stability.
13. Breaker Failure Protection (50BF)
Breaker failure protection detects a situation in which a circuit breaker receives a trip command but fails to interrupt the fault current successfully.
ANSI function:
– 50BF — Breaker Failure Protection
13.1 Why Breaker Failure Protection Is Required
The primary protection relay may detect a fault and issue a trip command. However, the circuit breaker may fail due to:
- Mechanical failure
- Trip coil failure
- DC supply problems
- Failure of the operating mechanism
- Contact problems
- Incorrect breaker control wiring
- Failure of the trip circuit
If the breaker does not clear the fault, the fault remains connected to the electrical system and may cause extensive damage or threaten system stability.
13.2 Operating Principle
Breaker failure logic typically monitors:
- A protection trip initiation signal.
- The breaker trip command.
- Current or breaker status after the trip command.
- A configured breaker failure time delay.
- Conditions required to confirm failure.
If the breaker fails to interrupt the current within the expected time, the breaker failure function initiates backup tripping.
Depending on the scheme, backup tripping may operate:
- Adjacent circuit breakers
- Busbar breakers
- Upstream breakers
- Other breakers required to isolate the failed breaker and fault
13.3 Applications
- Transformer feeders
- Generator breakers
- Busbar protection schemes
- Transmission line protection
- Critical industrial substations
- Main and backup protection systems
13.4 Engineering Considerations
- Breaker failure initiation
- Current detection threshold
- Breaker auxiliary contact supervision
- Retrip logic
- Breaker failure timer
- Backup trip matrix
- Reset logic
- Coordination with busbar protection
- DC trip circuit integrity
Breaker failure protection is particularly important in substations where a breaker failure could prevent the normal protection system from clearing a fault.
14. Synchrocheck Protection (25)
Synchrocheck protection verifies that electrical conditions are suitable for connecting two energized electrical systems together.
ANSI function:
– 25 — Synchronism Check
14.1 Why Synchronism Check Is Important
Closing a circuit breaker between two energized systems without checking their electrical conditions can produce severe electrical and mechanical stresses.
The systems should be sufficiently compatible in terms of:
- Voltage magnitude
- Frequency
- Phase angle
- Phase sequence
Synchrocheck protection supervises breaker closing and allows the close command only when the configured conditions are satisfied.
14.2 Operating Principle
The relay measures voltage on both sides of the circuit breaker.
It evaluates the differences between the two systems:
- Voltage difference
- Frequency difference
- Phase-angle difference
If the conditions are within the configured permissive limits, the relay issues a synchronism-check permissive signal.
If the conditions are outside the limits, the close command is blocked.
14.3 Applications
- Generator synchronization
- Bus coupler breakers
- Incoming supply breakers
- Bus transfer schemes
- Parallel transformer operation
- Grid interconnection
14.4 Setting Considerations
- Voltage difference limit
- Frequency difference limit
- Phase-angle limit
- Synchronism window
- VT selection
- Dead-bus and live-bus conditions
- Closing time compensation, where applicable
- Breaker closing characteristics
- Closing permissive logic
Synchrocheck protection must be carefully integrated into the circuit breaker closing circuit and control logic.
15. Auto-Reclosing (79)
Auto-reclosing automatically recloses a circuit breaker following a protection trip when the scheme determines that reclosing is permitted.
ANSI function:
– 79 — Automatic Reclosing
Auto-reclosing is widely used on overhead distribution and transmission lines where many faults are temporary.
15.1 Operating Principle
Following a trip initiated by an eligible protection function, the auto-reclosing logic may:
- Detect the breaker trip.
- Identify the protection function that initiated the trip.
- Determine whether auto-reclosing is enabled for that trip.
- Start the dead time.
- Verify required conditions.
- Issue a breaker close command.
- Monitor whether the breaker successfully closes.
- Determine whether the fault has cleared or remains present.
If the fault remains, protection may trip again and the reclose scheme may proceed to lockout according to its configured sequence.
15.2 Reclosing Sequence Types
Depending on relay capability and application, auto-reclosing schemes may include:
- Single-shot reclosing
- Multiple-shot reclosing
- Fast reclosing
- Delayed reclosing
- Three-phase reclosing
- Single-phase reclosing, where supported
15.3 Applications
- Overhead transmission lines
- Distribution feeders
- Rural distribution networks
- Temporary fault restoration
- Network reliability improvement
15.4 Engineering Considerations
- Reclosing enable conditions
- Protection trip source
- Dead time
- Reclaim time
- Number of shots
- Breaker readiness
- Synchronism check
- Live/dead bus supervision
- Lockout conditions
- Coordination with downstream devices
Auto-reclosing should generally not be applied indiscriminately to all equipment. Transformer, cable, motor, and other equipment protection trips may require blocking auto-reclosing depending on the system design and fault type.
16. Cold Load Pickup
Cold load pickup is a protection adaptation feature used to avoid unwanted tripping when a feeder is energized following a prolonged outage.
Unlike the traditional ANSI protection elements listed above, cold load pickup is an adaptive protection function or setting strategy, depending on the relay model.
16.1 What Is Cold Load Pickup?
When a feeder is de-energized for a significant period, connected loads may behave differently when power is restored.
Examples include:
- Heating systems
- Refrigeration equipment
- Air-conditioning systems
- Motors
- Transformers
- Industrial processes
- Lighting loads
After supply restoration, many loads may draw elevated current simultaneously.
This temporary current increase may exceed the normal feeder loading and cause overcurrent protection to operate unnecessarily.
16.2 Operating Principle
Cold load pickup modifies selected protection settings or operating behavior temporarily following feeder energization.
Depending on the relay implementation, the function may use:
- Increased overcurrent thresholds
- Temporary time delays
- A predefined pickup profile
- Timer-based restoration of normal settings
- Breaker status and current supervision
- Other energization criteria
The relay returns to its normal protection settings after the configured cold load pickup period or when the defined conditions are met.
16.3 Applications
- Distribution feeder restoration
- Industrial feeder energization
- Load restoration after an outage
- Networks with high simultaneous load demand
- Systems containing many thermostatically controlled loads
16.4 Engineering Considerations
- Normal feeder load
- Expected restoration current
- Maximum permissible temporary loading
- Minimum fault current during cold load pickup
- Protection sensitivity during the temporary period
- Temporary setting duration
- Restoration sequence
- Coordination with load shedding
Cold load pickup must not compromise protection against genuine faults during the restoration period.
17. Load Shedding
Load shedding is a controlled protection and system management strategy used to disconnect selected loads when the electrical system cannot maintain acceptable operating conditions.
Load shedding is not always a single standalone relay function. Depending on the Sepam model and project, it may be implemented through protection elements, logic, external control systems, or a combination.
17.1 Why Load Shedding Is Required
Load shedding may be necessary when:
- Generation capacity is insufficient
- Frequency is falling
- Voltage is collapsing
- Transformer loading exceeds limits
- Network overload conditions occur
- An upstream supply is lost
- An emergency operating condition develops
The objective is to disconnect nonessential or lower-priority loads while maintaining supply to critical equipment.
17.2 Load Shedding Methods
Underfrequency Load Shedding
Loads are disconnected when system frequency falls below defined thresholds.
This helps restore generation-load balance.
Undervoltage Load Shedding
Loads are disconnected when voltage falls below configured thresholds and operating conditions indicate a system emergency.
Overload-Based Load Shedding
Selected loads may be disconnected when loading exceeds permissible limits for a defined period.
Logic-Based Load Shedding
A scheme may use combinations of:
- Breaker status
- Transformer loading
- Feeder current
- Power measurements
- Generator status
- Frequency
- Voltage
- Communication signals
- Plant operating conditions
17.3 Load Priority
A typical industrial load shedding philosophy may divide loads into priority levels.
| Priority | Load category | Typical action |
|---|---|---|
| Priority 1 | Critical loads | Maintain whenever possible |
| Priority 2 | Essential loads | Disconnect only during severe conditions |
| Priority 3 | Important but interruptible | Shed during moderate emergencies |
| Priority 4 | Nonessential loads | Shed first |
The exact classification must be determined by the plant operating philosophy and process requirements.
17.4 Engineering Considerations
- Load priority
- Trigger conditions
- Frequency and voltage thresholds
- Time delays
- Breaker selection
- Interlocking
- Restoration sequence
- Communication reliability
- Fail-safe logic
- Coordination with generator and plant controllers
Load shedding must be carefully engineered to avoid unnecessary loss of critical process equipment or cascading outages.
18. Circuit Breaker Monitoring
Circuit breaker monitoring supervises the operating condition, availability, and performance of circuit breakers used in protection and switching systems.
Unlike a primary fault protection function, breaker monitoring is generally a diagnostic and supervision function that helps identify problems before the breaker becomes unavailable when required to interrupt a fault.
18.1 Why Circuit Breaker Monitoring Is Important
Circuit breakers are critical components in electrical protection systems. A relay may operate correctly, but if the circuit breaker cannot open, the fault may remain connected.
Breaker monitoring can help identify:
- Trip circuit problems
- Loss of DC supply
- Breaker mechanism problems
- Excessive operating time
- Abnormal contact condition
- Excessive accumulated switching operations
- Abnormal current interruption duty
- Maintenance requirements
18.2 Trip Circuit Supervision
Trip circuit supervision monitors the integrity of the breaker trip circuit.
It may supervise:
- DC supply availability
- Trip coil continuity
- Auxiliary contacts
- Trip circuit wiring
- Circuit breaker position
- External trip circuit components
A trip circuit supervision alarm can alert maintenance personnel to a problem before a fault occurs.
18.3 Circuit Breaker Operating Time Monitoring
Breaker operating time monitoring evaluates the time required for the breaker to operate following a command.
Abnormal operating times may indicate:
- Mechanical deterioration
- Lubrication problems
- Operating mechanism problems
- Coil issues
- Control circuit problems
18.4 Switching Operation Counter
The breaker operation counter records the number of switching operations.
This information is useful for:
- Preventive maintenance
- Maintenance scheduling
- Equipment life assessment
- Operational history
- Condition-based maintenance
18.5 Breaker Wear and Interruption Duty
Depending on relay capability, breaker monitoring may evaluate accumulated interruption duty or other indicators associated with breaker wear.
This helps maintenance teams assess whether the breaker requires inspection, servicing, or replacement of components.
18.6 Applications
- MV switchgear
- Industrial substations
- Distribution substations
- Transformer feeders
- Motor feeders
- Generator breakers
- Critical power systems
18.7 Engineering Considerations
- Breaker auxiliary contacts
- Trip and close circuit supervision
- DC supply monitoring
- Breaker operating time
- Operation counter
- Maintenance alarm thresholds
- External alarm mapping
- SCADA communication
Breaker monitoring helps shift maintenance from purely periodic inspection toward condition-based maintenance when sufficient monitoring data is available.
19. Protection Function Coordination
Sepam protection functions should not be considered independently. A reliable protection system requires coordination between individual elements, primary protection, backup protection, circuit breakers, and the overall network topology.
For example, phase overcurrent protection, earth fault protection, directional protection, breaker failure protection, and auto-reclosing may interact within the same feeder protection scheme.
19.1 Typical Function Coordination
| Protection function | Main purpose | Typical coordination requirement |
|---|---|---|
| 50/51 | Phase short-circuit and overcurrent | Selectivity with downstream and upstream protection |
| 50N/51N | Earth fault detection | Grounding system and earth fault coordination |
| 67 | Directional overcurrent | Correct forward/reverse discrimination |
| 49 | Thermal overload | Equipment thermal withstand |
| 46 | Negative sequence | Machine unbalance withstand |
| 27 | Undervoltage | System voltage stability and restoration |
| 59 | Overvoltage | Insulation and operating voltage limits |
| 81 | Frequency | Grid code and system stability |
| 32 | Reverse power | Prime mover or power flow requirements |
| 87 | Differential | Stability for external faults and sensitivity for internal faults |
| 64REF | Sensitive internal earth fault | CT balance and external fault stability |
| 50BF | Breaker failure | Backup fault clearance |
| 25 | Synchronism check | Safe connection of energized systems |
| 79 | Auto-reclosing | Fault type and restoration philosophy |
| Cold load pickup | Restoration current management | Maintain fault protection sensitivity |
| Load shedding | Emergency load reduction | Load priority and system stability |
| Breaker monitoring | Breaker condition supervision | Alarm and maintenance philosophy |
20. Sepam Protection Configuration and Engineering Workflow
Protection functions must be configured, verified, and tested according to the application and the applicable Sepam model.
A typical engineering workflow includes:
Step 1 — Identify the Relay Model
Confirm the exact Sepam family, model number, hardware, firmware, current and voltage inputs, and available protection functions.
Step 2 — Define the Protection Application
Identify the protected equipment:
- Feeder
- Transformer
- Motor
- Generator
- Busbar
- Capacitor bank
- Incoming supply
Step 3 — Collect Network Data
Collect the required technical information:
- Single-line diagram
- CT ratios
- VT ratios
- Equipment ratings
- Short-circuit study
- Grounding system
- Load current
- Starting or inrush characteristics
- Circuit breaker characteristics
- Coordination study
- Existing protection settings
Step 4 — Select Protection Functions
Enable only functions required for the protection philosophy and supported by the relay model.
Step 5 — Calculate Protection Settings
Calculate pickups, operating delays, curves, directional parameters, and other settings based on the network study and equipment requirements.
Step 6 — Configure Logic and Outputs
Configure:
- Trip logic
- Alarm logic
- Blocking logic
- Interlocking
- Breaker failure initiation
- Auto-reclosing conditions
- Load shedding logic
- Communication signals
Step 7 — Verify Configuration
Check settings, logic, CT/VT ratios, polarity, trip matrix, and coordination with other protective devices.
Step 8 — Test the Relay
Perform suitable secondary injection tests, logic tests, trip circuit verification, and functional tests using approved test procedures.
Step 9 — Commission and Document
Record final approved settings, test results, configuration files, wiring verification, commissioning observations, and relevant protection changes.
21. Testing Sepam Protection Functions
Testing must confirm that each protection function operates correctly under the intended conditions and remains stable under conditions where it should not operate.
Typical protection testing may include:
| Function | Typical test objective |
|---|---|
| 50/51 | Verify pickup, timing, and trip operation |
| 50N/51N | Verify residual or neutral current response |
| 67 | Verify directional discrimination |
| 49 | Verify thermal model response and alarm/trip thresholds |
| 46 | Verify negative sequence measurement and operation |
| 27 | Verify undervoltage pickup and delay |
| 59 | Verify overvoltage pickup and delay |
| 81 | Verify frequency thresholds and timers |
| 32 | Verify active power direction and trip threshold |
| 87 | Verify differential operation and restraint/stability |
| 64REF | Verify sensitivity and stability |
| 50BF | Verify initiation, timer, retrip and backup trip logic |
| 25 | Verify synchronism-check permissive and blocking |
| 79 | Verify sequence, timers, lockout and reclosing conditions |
| Cold load pickup | Verify temporary protection adaptation |
| Load shedding | Verify triggering logic and load trip matrix |
| Breaker monitoring | Verify alarms, supervision, counters and monitoring logic |
Actual test methods and test values must be derived from the approved protection design, manufacturer documentation, and commissioning procedures.
22. Troubleshooting Sepam Protection Functions
Protection engineers may encounter problems during configuration, commissioning, testing, or operation.
| Symptom | Possible causes | Investigation |
|---|---|---|
| Unexpected phase overcurrent trip | Incorrect CT ratio, setting, transient current, wiring issue | Review disturbance records, measured currents and settings |
| Earth fault trip without apparent fault | CT polarity, residual calculation, leakage current, wiring issue | Check residual current, CT circuit and network grounding |
| Directional protection operates incorrectly | Incorrect VT/CT polarity, phase sequence, directional settings | Verify phasors, connections and directional characteristic |
| Thermal trip during normal operation | Incorrect thermal parameters, excessive loading, cooling problem | Review thermal state, current and equipment cooling |
| Negative sequence alarm | Phase imbalance, phase loss, CT problem | Review three-phase currents and negative sequence value |
| Undervoltage trip | System voltage disturbance, VT circuit problem | Review voltage measurements and VT supervision |
| Overvoltage alarm | Network voltage rise, regulator problem, VT configuration | Review voltage trends and control systems |
| Frequency trip | Actual frequency disturbance, incorrect measurement | Review frequency records and system event |
| Reverse power trip | Generator motoring, power direction configuration, polarity problem | Verify active power, CT/VT polarity and operating conditions |
| Differential trip | Internal fault, CT circuit issue, incorrect compensation | Review differential and restraint values, CT wiring |
| REF trip | Internal earth fault, neutral CT issue, polarity or wiring error | Review phase residual and neutral current measurements |
| Breaker failure operation | Breaker failure to interrupt, wrong current detection, timer logic | Review breaker status, current and initiation logic |
| Synchrocheck blocking close | Voltage/frequency/phase mismatch or VT circuit issue | Verify both voltage inputs and synchronism limits |
| Auto-reclosing not initiated | Reclose blocked, trip source excluded, scheme conditions not met | Review trip origin, enable signals, timers and lockout |
| Cold load pickup unavailable | Incorrect trigger, logic or parameterization | Verify restoration conditions and enabled settings |
| Load shedding not operating | Threshold, logic, output, or communication issue | Test the complete scheme from trigger to breaker output |
| Breaker monitoring alarm | Trip circuit fault, auxiliary contact issue, abnormal operation | Inspect circuit, contacts, DC supply and monitoring parameters |
23. Sepam Protection Function Availability
Not every Sepam relay supports all the functions covered in this article.
Protection function availability depends on:
- Sepam series
- Specific model
- Application type
- Firmware version
- Hardware configuration
- Measurement inputs
- Enabled functions
- Engineering software and configuration
For example, a motor protection relay may offer extensive thermal, negative sequence, and motor-specific protection features, while a feeder relay may focus on overcurrent, earth fault, directional protection, voltage, frequency, and switching-related functions.
Differential, REF, synchrocheck, auto-reclosing, load shedding, and breaker failure capabilities must be checked against the specific Sepam model and application. Some functions may be implemented using external protection devices, external logic, or the substation automation system rather than directly in the relay.
24. Conclusion
Sepam protection relays provide a wide range of protection and supervision functions for industrial power systems and electrical substations. Understanding the operating principles of individual protection elements is essential for selecting appropriate functions, calculating settings, coordinating protection devices, commissioning relays, and troubleshooting abnormal operation.
The major functions covered in this technical reference include phase overcurrent, earth fault, directional protection, thermal overload, negative sequence, undervoltage, overvoltage, frequency, reverse power, differential protection, restricted earth fault, breaker failure, synchrocheck, auto-reclosing, cold load pickup, load shedding, and circuit breaker monitoring.
A properly engineered protection system requires more than enabling individual functions. It requires a complete understanding of the network, fault levels, equipment limitations, CT/VT characteristics, protection coordination, control logic, circuit breaker performance, and operating philosophy.
For protection engineers working with Schneider Electric Sepam relays, systematic configuration, calculation, testing, documentation, and maintenance are essential to achieving dependable and selective protection.