Operating Principles, Vector Group Compensation, CT Selection, REF, Settings, Stability and Testing
1. Introduction
Transformer differential protection (ANSI 87T) is one of the most important protection functions used to protect power transformers in electrical power systems.
Power transformers are critical assets in generating stations, transmission substations, distribution networks, and industrial facilities. Internal transformer faults can cause severe damage to windings, insulation, magnetic cores, bushings, and other internal components.
Transformer differential protection provides fast and selective protection against internal faults by comparing the currents entering and leaving the protected transformer zone.
Unlike overcurrent protection, which operates based on current magnitude and time coordination, differential protection operates based on the difference between currents measured at different boundaries of the protected equipment.
The main objectives of transformer differential protection are:
- Detect internal phase-to-phase faults.
- Detect phase-to-earth faults within the protected zone.
- Detect winding faults and internal short circuits.
- Provide fast fault clearance.
- Maintain stability during external faults.
- Avoid unwanted operation during transformer energization.
- Compensate for transformer vector group and CT ratio differences.
Modern numerical transformer protection relays include advanced algorithms to improve sensitivity, security, and reliability.
Examples include:
- Siemens SIPROTEC 5 7UT85 / 7UT86.
- ABB/Hitachi Energy RET670.
- Schneider Electric MiCOM P63x.
- GE Vernova Multilin T60.
- SEL-487E.
- NR Electric transformer protection relays.
2. Basic Operating Principle
Transformer differential protection is based on Kirchhoff’s Current Law.
Under normal operating conditions, the current entering the transformer should approximately equal the current leaving the transformer after accounting for transformer ratio and phase displacement.
For an ideal protected zone:
Idiff=∣I1−I2∣
Where:
- I1 = compensated current entering the protected zone.
- I2 = compensated current leaving the protected zone.
- Idiff = differential operating current.
Under normal load conditions:
I1≈I2
Therefore:
Idiff≈0
During an external fault, the current entering and leaving the transformer zone should also remain balanced, provided the CTs and protection circuits operate correctly.
However, during an internal fault, the current balance is disturbed.
Idiff>0
When the differential operating current exceeds the relay’s operating characteristic, the relay issues a trip command.
3. Transformer Differential Protection Scheme
A typical transformer differential protection scheme includes:
- Current transformers on the HV side.
- Current transformers on the LV side.
- Transformer differential protection relay.
- CT secondary wiring circuits.
- Circuit breakers on the transformer terminals.
- Trip circuits and auxiliary protection functions.
The CTs measure currents at both sides of the transformer.
The relay receives the secondary currents, performs ratio and vector group compensation, calculates differential and restraint currents, and determines whether the fault is internal or external.
For transformers with three or more windings, differential protection can include current measurements from all transformer terminals.
4. Differential Current and Restraint Current
Modern transformer differential relays use percentage-biased differential protection.
This approach improves relay stability during external faults and prevents unwanted operation caused by CT errors, saturation, and measurement inaccuracies.
Two important quantities are calculated:
Differential current
Idiff=∣I1−I2∣
Restraint current
A commonly used definition is:
Irest=2∣I1∣+∣I2∣
The exact definition depends on the relay manufacturer and algorithm.
The relay compares the differential current against a biased operating characteristic.
A simplified operating condition is:
Idiff>Ipickup+S×Irest
Where:
- Ipickup = minimum differential pickup.
- S = percentage bias or slope.
- Irest = restraint current.
Modern relays typically use multiple slopes to provide improved stability across different operating conditions.
5. Percentage Differential Protection Characteristics
A typical transformer differential protection characteristic contains three important regions.
Region 1 – Minimum pickup
The relay remains stable when the differential current is below the minimum operating threshold.
Region 2 – First bias slope
The relay applies a moderate restraint characteristic to accommodate normal CT errors and transformer ratio mismatch.
Region 3 – Second bias slope
A higher restraint slope is applied at high through-current levels, particularly to improve stability during severe external faults when CT saturation may occur.
The settings must be selected according to the protected transformer’s characteristics, CT performance, and relay manufacturer’s recommendations.
6. Transformer Vector Group Compensation
One of the most important differences between transformer differential protection and simple feeder differential protection is transformer phase displacement.
Power transformers may introduce a phase shift between HV and LV currents depending on their vector group.
For example:
- Dyn11
- Dyn1
- YNd11
- YNd1
- Yy0
- Yd11
- Yd1
Consider a Dyn11 transformer.
The transformer has:
- HV winding: Delta.
- LV winding: Star with neutral.
- Phase displacement: 30 degrees according to the vector group clock notation.
If the relay compares uncompensated HV and LV currents, the currents will not balance correctly.
The relay must therefore compensate for:
- Transformer ratio.
- Phase displacement.
- Zero-sequence current behavior.
- CT ratios and connection arrangements.
Modern numerical relays perform these compensations internally through software configuration.
This eliminates the need for traditional external CT interconnections used in older differential protection schemes.
7. CT Selection for Transformer Differential Protection
Correct CT selection is essential for reliable transformer differential protection.
The CTs must be selected considering:
- Rated primary current.
- Rated secondary current.
- CT ratio.
- Accuracy class.
- Protection class.
- Knee-point voltage where applicable.
- CT secondary burden.
- Maximum through-fault current.
- CT saturation performance.
- Secondary cable resistance.
For example, consider a 40 MVA transformer with:
- HV voltage: 132 kV.
- LV voltage: 33 kV.
The rated HV current is:
IHV=3×132×10340×106
IHV=174.95A
The rated LV current is:
ILV=3×33×10340×106
ILV=699.77A
Possible CT ratios could be:
| Side | Rated current | Example CT ratio |
|---|---|---|
| HV | 175 A | 200/1 A |
| LV | 700 A | 800/1 A |
These are illustrative ratios, not final CT specifications.
The relay must compensate for the different CT ratios and transformer ratio.
The final CT selection must also consider the actual maximum fault current and CT saturation calculations.
8. Transformer Energization and Inrush Current
Transformer energization can produce a high magnetizing inrush current.
This current may be several times the rated transformer current, depending on:
- Switching instant.
- Residual flux.
- Transformer core characteristics.
- Source impedance.
- Transformer design.
The inrush current can contain a significant second harmonic component.
If the differential relay does not distinguish inrush current from an internal fault, unwanted tripping may occur during transformer energization.
Modern transformer differential relays use several methods to prevent this.
Second harmonic restraint
The relay evaluates the second harmonic component of the differential current.
A simplified relationship is:
I1I2>K
Where:
- I2 = second harmonic component.
- I1 = fundamental component.
- K = configured harmonic threshold.
If the harmonic content exceeds the configured threshold, the relay applies inrush restraint or blocking according to its algorithm.
Other inrush detection methods
Modern relays may also use:
- Waveform-based inrush detection.
- Cross-phase blocking.
- Adaptive harmonic restraint.
- Advanced saturation detection.
The exact implementation differs between manufacturers.
9. Overexcitation Protection and Fifth Harmonic
Transformer overexcitation occurs when the magnetic flux density exceeds its normal operating level.
This condition can occur due to:
- Excessive voltage.
- Reduced frequency.
- Incorrect voltage control.
- Generator operating conditions.
Overexcitation may produce increased magnetizing current and transformer heating.
The fifth harmonic component can be used by some differential protection algorithms to identify overexcitation conditions.
However, fifth harmonic restraint is not a substitute for dedicated overexcitation protection.
The dedicated overexcitation function is:
ANSI 24 – Volts per Hertz Protection.
It monitors the voltage-to-frequency ratio and provides protection against excessive magnetic flux.
10. Internal and External Faults
Understanding the difference between internal and external faults is essential when engineering transformer differential protection.
Internal faults
Examples include:
- HV winding phase-to-phase fault.
- LV winding phase-to-earth fault.
- Inter-turn winding fault.
- Internal winding insulation failure.
- Fault between winding and transformer core.
- Internal bushing faults within the CT-defined zone.
During internal faults, differential current increases and the relay should operate.
External faults
Examples include:
- Faults on an outgoing LV feeder.
- Faults on the HV busbar outside the differential zone.
- External phase-to-earth faults.
- External three-phase short circuits.
During external faults, the relay should remain stable.
This is particularly important during high-current external faults because CT saturation can create false differential current.
11. CT Saturation and Differential Protection Stability
CT saturation is one of the most important challenges in differential protection.
During severe external faults, one CT may saturate before another.
This creates an imbalance between measured currents.
As a result:
Idiff=0
Even though the actual fault is outside the transformer protection zone.
Modern differential relays improve stability through:
- Percentage differential restraint.
- Dual-slope characteristics.
- CT saturation detection.
- Advanced waveform analysis.
- Appropriate CT selection.
- Correct secondary circuit design.
Engineers must not rely exclusively on relay settings to compensate for poorly selected CTs.
12. Restricted Earth Fault Protection (ANSI 64REF / 87N)
Restricted Earth Fault protection is a sensitive protection function used to detect earth faults within a defined transformer winding zone.
It is particularly useful for detecting earth faults close to the transformer neutral.
For a grounded star winding, REF protection compares:
- Residual current from the three phase CTs.
- Neutral CT current.
Under normal conditions and external earth faults, the currents should balance according to the scheme’s polarity and connection arrangement.
For an internal earth fault within the REF zone, the balance is disturbed and the protection operates.
REF protection provides higher sensitivity than conventional transformer differential protection for certain winding earth faults.
There are two main approaches:
- High-impedance REF protection.
- Low-impedance REF protection.
Modern numerical relays commonly provide low-impedance REF algorithms.
13. Transformer Differential Protection Settings
Transformer differential protection settings must be calculated and verified during engineering and commissioning.
Typical settings include:
| Parameter | Description |
|---|---|
| Differential pickup | Minimum differential operating current |
| Slope 1 | First percentage bias |
| Slope 2 | Second percentage bias |
| Breakpoint | Transition between bias slopes |
| Inrush restraint | Second harmonic or other inrush detection settings |
| Fifth harmonic restraint | Overexcitation-related restraint, if supported |
| Unrestrained differential | High-set differential element |
| REF pickup | Restricted earth fault sensitivity |
| CT ratios | HV/LV/tertiary CT ratios |
| Vector group | Transformer phase displacement |
| Zero-sequence compensation | Appropriate current compensation |
| Trip matrix | Circuit breakers and associated trip outputs |
There is no single universal setting applicable to all transformers.
Settings should be determined from transformer data, CT data, fault studies, relay characteristics, and manufacturer application guidelines.
14. Unrestrained Differential Protection
Many numerical transformer protection relays provide an additional high-set differential element.
This function is commonly called:
- High-set differential.
- Unrestrained differential.
- Instantaneous differential.
Its purpose is to provide very fast operation for severe internal faults.
The operating principle is:
Idiff>Ihigh-set
The high-set element generally operates without the normal percentage restraint characteristic.
Its setting must be selected carefully to avoid operation during external faults with CT saturation or other abnormal conditions.
15. Transformer Differential Protection Testing
Testing is an essential part of transformer protection commissioning.
Testing should verify both operating and stability conditions.
Typical test activities include:
A. Basic relay checks
- Relay configuration verification.
- CT ratio verification.
- Transformer vector group verification.
- Nominal current verification.
- Binary input and output checks.
- Trip circuit verification.
B. Differential operating tests
- Minimum differential pickup.
- Differential characteristic.
- First slope.
- Second slope.
- Breakpoint.
- High-set differential operation.
C. Stability tests
- Normal load stability.
- External three-phase fault.
- External phase-to-earth fault.
- CT ratio mismatch.
- CT polarity verification.
- Simulated CT saturation where supported.
D. Harmonic restraint tests
- Second harmonic inrush restraint.
- Fifth harmonic restraint, if configured.
- Harmonic blocking and release behavior.
E. REF protection tests
- REF pickup.
- REF operating characteristic.
- External earth fault stability.
- Internal earth fault operation.
The test results should be compared against the relay settings and manufacturer specifications.
16. Transformer Differential Protection Using Different Manufacturers
Several manufacturers provide advanced transformer differential protection solutions.
Siemens – SIPROTEC 5 7UT85 / 7UT86
Transformer differential protection, REF, overcurrent backup, advanced measurement and disturbance recording. Engineering and configuration through DIGSI 5.
ABB / Hitachi Energy – RET670
Advanced transformer differential protection, winding earth fault protection, harmonic restraint and comprehensive transformer protection functions.
Schneider Electric – MiCOM P63x
Transformer differential protection with percentage bias, harmonic restraint and associated transformer protection functions.
GE Vernova – Multilin T60
Transformer differential protection with advanced restraint, harmonic supervision and integrated transformer protection.
SEL – SEL-487E
Transformer differential protection with advanced compensation, monitoring and protection capabilities.

17. Common Engineering and Commissioning Mistakes
Some common problems encountered in transformer differential protection projects include:
- Incorrect CT polarity.
- Incorrect CT ratio configuration.
- Incorrect transformer vector group.
- Incorrect phase rotation.
- Incorrect zero-sequence compensation.
- Wrong CT terminal connections.
- Incorrect differential pickup.
- Inappropriate percentage bias.
- Incorrect harmonic restraint configuration.
- Failure to test external fault stability.
- Incorrect REF CT connections.
- Incorrect circuit breaker trip matrix.
- Failure to verify all transformer winding currents.
- Incorrect relay nominal current configuration.
These mistakes can cause either unwanted tripping or failure to detect internal faults.
A complete engineering review and commissioning test program are therefore essential.
18. Practical Engineering Case Study
Consider the following transformer:
| Parameter | Value |
|---|---|
| Rated power | 40 MVA |
| HV voltage | 132 kV |
| LV voltage | 33 kV |
| Vector group | Dyn11 |
| HV CT ratio | 200/1 A |
| LV CT ratio | 800/1 A |
| Frequency | 50 Hz |
| Protection | Numerical transformer differential |
The engineering process should include:
- Calculate the rated HV and LV currents.
- Verify the selected CT ratios.
- Configure the transformer vector group.
- Configure the nominal CT secondary currents.
- Verify phase compensation.
- Calculate the differential protection characteristic.
- Configure harmonic restraint.
- Configure REF protection if required.
- Verify trip outputs and circuit breaker assignments.
- Perform secondary injection and stability tests.
The final objective is to ensure that the relay remains stable under normal load and external faults while operating rapidly and selectively for internal transformer faults.
19. Conclusion
Transformer differential protection (ANSI 87T) is a fundamental protection function for power transformers.
Reliable implementation requires more than simply enabling a differential protection function in a numerical relay.
Engineers must understand transformer characteristics, CT selection, vector group compensation, differential operating characteristics, harmonic restraint, CT saturation, REF protection, relay settings, and commissioning procedures.
Modern numerical relays provide powerful tools for implementing these functions, but their performance depends on correct engineering, configuration, testing, and maintenance.
For protection engineers, commissioning engineers, and substation automation specialists, practical knowledge of transformer differential protection is essential.

20. Practical Training – Transformer Differential Protection
At Elec-Engg, we provide practical training in power system protection and numerical protection relays, including transformer differential protection.
Our training covers:
- Transformer differential protection principles.
- CT selection and ratio calculations.
- Vector group compensation.
- Differential and restraint characteristics.
- Harmonic restraint.
- REF protection.
- Transformer protection settings.
- Numerical relay configuration.
- Secondary injection testing.
- Fault analysis and troubleshooting.
Training is available through video-recorded courses, structured self-paced training, online sessions, and customized face-to-face training.
Trainer: Dr. Saeed Roostaee – Electrical Engineering
Website: https://elec-engg.com/
Explore our technical resources and training programs to improve your practical knowledge of power system protection.

- Transformer differential protection single-line diagram.
- Percentage differential operating characteristic.
- Dyn11 transformer vector group phasor diagram.
- Transformer CT connection diagram.
- Magnetizing inrush waveform.
- CT saturation waveform.
- Restricted earth fault protection diagram.
- Siemens SIPROTEC 5 7UT85 relay.
- ABB RET670 relay.
- OMICRON transformer differential relay testing setup.