Earth Fault Protection

Ground Fault Detection, Neutral Earthing Systems, Residual Current, Sensitive Earth Fault, REF, and Relay Settings

1. Introduction to Earth Fault Protection

Earth fault protection is one of the most important protection functions in electrical power systems.

An earth fault occurs when an energized conductor comes into contact with earth or an earthed metallic structure, creating an unintended current path.

Earth faults can occur in:

  • Transmission lines.
  • Distribution networks.
  • Power transformers.
  • Generators.
  • Electric motors.
  • Underground cables.
  • Switchgear and busbar systems.
  • Industrial electrical installations.

Earth faults may result from insulation deterioration, cable damage, moisture, contamination, mechanical damage, equipment failure, or environmental conditions.

Depending on the system earthing arrangement, earth fault current can range from a few milliamperes to several kiloamperes.

The main objectives of earth fault protection are:

  1. Detect earth faults reliably.
  2. Disconnect faulty equipment selectively.
  3. Minimize equipment damage.
  4. Reduce fire and electrical shock risks.
  5. Maintain continuity of healthy circuits.
  6. Provide sensitive detection of low-current earth faults.

Earth fault protection is implemented using different protection principles depending on the network configuration and neutral earthing arrangement.

Why REF Protection?

2. Basic Principle of Earth Fault Detection

In a healthy three-phase electrical system, the vector sum of the three phase currents is approximately zero.

IA+IB+IC=0IA​+IB​+IC​=0

During an earth fault, some current flows through the earth or neutral return path.

Consequently:

IA+IB+IC≠0IA​+IB​+IC​=0

The resulting residual current can be used to detect the earth fault.

The residual current is:

Ires=IA+IB+ICIres​=IA​+IB​+IC​

In symmetrical component theory:

Ires=3I0Ires​=3I0​

Where:

  • IA,IB,ICIA​,IB​,IC​: Phase currents.
  • I0I0​: Zero-sequence current.

The protection relay detects this residual current and compares it with its configured pickup threshold.

If the operating conditions are satisfied, the relay initiates an alarm or trip.

CT connection to sense earth fault/Earth Faults Detection Philosophy - ELECTRICAL TECHNOLOGY AND INDUSTRIAL PRACTICE

Important: Earth fault protection must be designed according to the neutral earthing arrangement. The magnitude and direction of earth fault current are significantly different in solidly grounded, resistance-grounded, isolated, and resonant-grounded systems.

3. Different Neutral Earthing Systems

Neutral earthing has a major influence on earth fault current magnitude and protection philosophy.

The most common arrangements are:

  1. Solidly grounded neutral.
  2. Resistance-grounded neutral.
  3. Reactance-grounded neutral.
  4. Isolated neutral.
  5. Resonant grounding (Petersen coil).

3.1 Solidly Grounded System

In a solidly grounded system, the transformer or generator neutral is directly connected to earth without an intentional impedance.

Characteristics:

  • Relatively high earth fault current.
  • Fast fault detection.
  • Simple overcurrent protection.
  • Higher thermal and mechanical stress during faults.
  • Faulted circuits generally require rapid disconnection.

This arrangement is commonly used in many LV systems and selected MV/HV applications.

3.2 Resistance Grounded System

In resistance grounding, a resistor is connected between the neutral point and earth.

The resistor limits earth fault current.

Two common arrangements are:

  • Low-resistance grounding (LRG).
  • High-resistance grounding (HRG).
How are the grounding resistor value and grounding transformer for a 35 kV distribution system determined?-Orion Neutral Grounding Resistors

The approximate earth fault current is:

If=VphRNIf​=RN​Vph​​

Where:

  • VphVph​: Phase-to-neutral voltage.
  • RNRN​: Neutral grounding resistance.

This simplified equation assumes the grounding resistor dominates the fault-current limitation. Actual fault current also depends on system impedance and fault resistance.

Low-resistance grounding

LRG allows a controlled earth fault current, commonly suitable for selective protection using earth fault overcurrent relays.

High-resistance grounding

HRG limits earth fault current to a relatively low value and may allow continued operation following the first earth fault, subject to the system design and operating philosophy.

3.3 Reactance Grounding

In reactance grounding, an inductor is connected between neutral and earth.

The reactor limits the magnitude of earth fault current.

Reatores de Aterramento

This arrangement is used in selected power systems where controlled fault current is required.

3.4 Isolated Neutral System

In an isolated neutral system, the transformer or generator neutral is not intentionally connected to earth.

Ungrounded or Isolated Neutral System

During a single-phase earth fault:

  • The faulted phase voltage to earth approaches zero at the fault point.
  • The healthy phase-to-earth voltages increase.
  • The network’s distributed phase-to-earth capacitances contribute to earth fault current.

The first earth fault current may be relatively small, depending on network size and capacitance.

However, a second earth fault on another phase can produce a severe phase-to-phase fault through earth.

3.5 Resonant Grounding – Petersen Coil

Resonant grounding uses an adjustable reactor connected between the neutral and earth.

It is designed to compensate for the capacitive earth fault current of the network.

Working Principle of Petersen Coil - Electrical Concepts

The reactor is tuned to approximately compensate for the total network capacitive earth fault current.

The objective is to reduce the residual fault current and support self-extinction of arcing earth faults.

This arrangement is particularly important in certain MV distribution networks.

4. ANSI Earth Fault Protection Functions

Several ANSI protection functions are used for earth fault detection.

ANSI codeProtection functionApplication
50NInstantaneous neutral overcurrentEarth fault detection
51NTime-delayed neutral overcurrentCoordinated earth fault protection
50GInstantaneous ground overcurrentGround fault detection
51GTime-delayed ground overcurrentGround fault coordination
64Ground detector protectionGround fault detection
64RRestricted earth fault-related designation in some schemesWinding earth fault protection
59NNeutral displacement overvoltageEarth fault detection
67NDirectional earth faultDirectional earth fault protection
87NNeutral-related differential protectionSensitive winding earth fault protection, depending on scheme
21NDistance ground-fault measurementTransmission line protection

ANSI function labels and implementation can vary between relay manufacturers and application standards. The actual protection scheme should always be checked against the relay documentation.

5. Earth Fault Protection Using Residual CT Connection

One of the simplest earth fault detection methods is the residual connection of three phase CTs.

Bemutatjuk: Selec földzárlatvédelmi eszközök

The secondary currents of the three CTs are connected so that their vector sum is measured by the protection relay.

Under balanced conditions:

IA+IB+IC=0IA​+IB​+IC​=0

During an earth fault:

Ires=IA+IB+ICIres​=IA​+IB​+IC​

The relay detects the residual current.

Advantages

  • Simple arrangement.
  • Uses existing phase CTs.
  • Economical solution.
  • Suitable for many feeder applications.

Limitations

  • Sensitive to CT ratio and accuracy errors.
  • Can be affected by CT saturation.
  • May have limited sensitivity for small earth fault currents.
  • Requires correct CT polarity and wiring.

6. Core Balance Current Transformer (CBCT)

A Core Balance Current Transformer is widely used for sensitive earth fault protection.

It is also known as a zero-sequence current transformer (ZCT) in many applications.

CBCT vs CT for Earth Fault Detection in 3-Phase Systems | Hamdy Ahmed posted on the topic | LinkedIn

All three phase conductors pass through the same CT core.

Under healthy conditions, the magnetic effects of the three phase currents cancel each other.

Therefore:

Isecondary≈0Isecondary​≈0

During an earth fault, the current balance is disturbed and the CBCT produces a secondary output.

6.1 Advantages of CBCT

  • High sensitivity.
  • Better measurement of small residual currents.
  • Reduced influence of individual phase CT errors.
  • Compact installation.
  • Useful for MV cable feeders and industrial motor circuits.

6.2 Important Installation Considerations

  • All phase conductors must pass through the CT.
  • The earth conductor arrangement must follow the approved CBCT wiring diagram.
  • Cable screens and armour earthing conductors must be routed correctly.
  • CT polarity must be checked.
  • Secondary wiring must be protected against open circuits where applicable.

A common commissioning mistake is routing the cable earth conductor through the CBCT in a way that causes fault current to cancel the measured residual current.

The installation drawing must clearly show the intended routing.

7. Neutral CT Earth Fault Protection

Neutral CT protection is frequently used in transformer and generator applications.

Résistances de mise à la terre du neutre

A CT is installed in the neutral earthing connection to measure neutral current.

During an earth fault, the neutral current increases and can be detected by the relay.

This arrangement is particularly useful in resistance-grounded systems.

Typical protection functions include:

  • 50N
  • 51N
  • Sensitive neutral overcurrent
  • Neutral current monitoring
  • Restricted earth fault protection, where configured as part of a differential scheme

8. Directional Earth Fault Protection (ANSI 67N)

In interconnected and ring distribution networks, earth fault current may flow in different directions.

A non-directional earth fault relay may not provide sufficient selectivity.

Directional earth fault protection determines the direction of the fault current and operates only when the measured current is in the configured operating direction.

Erdschluss Mittelspannung

8.1 Operating Principle

Directional earth fault protection generally uses:

  • Residual current (3I0).
  • Residual voltage (3U0).
  • Directional characteristic.
  • Polarizing quantity.
  • Operating angle.

The relay compares the phase relationship between the measured current and voltage quantities.

The exact directional algorithm depends on the relay manufacturer and grounding system.

8.2 Applications

  • Ring networks.
  • Parallel feeders.
  • Interconnected MV distribution systems.
  • Networks with multiple infeed sources.
  • Resonant-grounded systems using specialized directional methods.

8.3 Directional Earth Fault Settings

Typical parameters include:

ParameterDescription
Earth fault pickupMinimum residual current
Residual voltage pickupMinimum polarizing voltage
Characteristic angleDirectional operating angle
Operating directionForward or reverse
Time delayCoordination delay
Blocking logicConditions preventing operation

Directional settings must be determined through a system grounding and protection coordination study.

9. Sensitive Earth Fault Protection (SEF)

Sensitive Earth Fault protection is used to detect low-magnitude earth fault currents.

It is especially important in:

  • High-resistance grounded systems.
  • Isolated neutral networks.
  • Resonant-grounded networks.
  • Long cable distribution systems.
  • Applications where conventional earth fault overcurrent protection lacks sufficient sensitivity.
Nanocrystalline cores for CBCT Application – Permanent Magnets Ltd

SEF may use:

  • Sensitive residual current measurement.
  • Core-balance CTs.
  • Residual voltage measurement.
  • Directional earth fault algorithms.
  • Specialized transient or admittance-based algorithms.

The required sensitivity must be balanced against normal leakage current, network capacitance, measurement errors, and unwanted operation.

10. Restricted Earth Fault Protection (REF)

Restricted Earth Fault protection is a highly sensitive differential protection scheme used to detect earth faults within a defined winding zone.

It is commonly applied to transformer star-connected windings and generator stator windings where the necessary CT arrangement is available.

Harmonizing Safety: The Role of Restricted Ground Fault Relays
 – COMPRACO Indústria e Construção

10.1 Operating Principle

The scheme compares:

  • Residual current from the three phase CTs.
  • Neutral CT current.

Under healthy conditions and external earth faults, the currents should balance.

During an internal earth fault within the protected zone, the balance is disturbed.

10.2 High-Impedance REF

High-impedance REF uses a high-impedance operating circuit.

It generally requires carefully matched CT performance and suitable stabilizing components.

Important considerations include:

  • CT ratio.
  • CT excitation characteristics.
  • CT secondary resistance.
  • Lead resistance.
  • Stabilizing resistor.
  • Nonlinear resistor, where required.

10.3 Low-Impedance REF

Low-impedance REF uses numerical relay measurement and differential algorithms.

It offers greater flexibility in CT application and settings, depending on the relay design.

Typical parameters include:

  • REF pickup.
  • Bias or restraint.
  • Directional supervision, where applicable.
  • Stabilization.
  • Trip logic.

10.4 REF Compared with Transformer Differential Protection

FeatureTransformer differential 87TREF
Main purposeInternal phase and earth faultsInternal earth faults
Protection zoneBetween transformer-side CTsDefined winding and neutral zone
SensitivityDepends on transformer and relay settingsOften higher for winding earth faults
CT arrangementCTs on transformer sidesPhase CTs plus neutral CT
Vector group compensationRequired where applicableScheme-specific
Main applicationTransformer overall protectionSensitive winding earth fault protection

REF complements transformer differential protection; it does not replace it.

11. Neutral Displacement Protection (ANSI 59N)

Neutral displacement protection uses residual or neutral voltage to detect earth faults.

It is particularly useful in isolated and resonant-grounded networks.

‏ما الفرق بين Open Delta والBroken Delta

Broken Delta
هو توصيل ملفات الثانوي لمحول الجهد مع بعضها على شكل دلتا مع ترك نهايتي الدلتا مفتوحة لتوصيل EF relay يعمل بالمجموع الاتجاهي لجهد الثلاث فازات ،…‏ | ‏Motaz Al-Fayomi‏

During a single-phase earth fault, the system neutral shifts relative to earth.

The relay detects the resulting residual voltage.

The residual voltage is:

3U0=UA+UB+UC3U0​=UA​+UB​+UC​

Under healthy balanced conditions:

3U0≈03U0​≈0

During an earth fault:

3U0>03U0​>0

A common measurement arrangement uses a broken-delta secondary winding of three voltage transformers.

Applications

  • Isolated neutral systems.
  • Resonant-grounded networks.
  • MV distribution networks.
  • Earth fault alarm and backup protection.

12. Earth Fault Protection in Power Transformers

Transformer earth fault protection depends on winding connection and neutral earthing.

Common protection functions include:

  • 50N/51N.
  • 50G/51G.
  • 67N.
  • 87T.
  • REF.
  • 59N.

For a grounded star winding, REF can provide sensitive protection for earth faults within the restricted winding zone.

For delta windings, the protection philosophy is different because there is no directly accessible neutral point.

Transformer vector group, grounding transformer arrangements, and zero-sequence current paths must all be considered.

13. Earth Fault Protection in Generators

Generator earth fault protection is critical because stator winding insulation failures can cause serious damage.

08_C_3_Basis Stator Earth Fault Protection.ppt

Common protection functions include:

  • 64G.
  • 59N.
  • 87G.
  • 87N, where applicable.
  • Neutral overcurrent protection.
  • Third-harmonic-based 100% stator earth fault protection.
  • Subharmonic injection-based protection.

13.1 Conventional Stator Earth Fault Protection

A neutral voltage or current-based scheme may protect a large portion of the stator winding.

However, conventional fundamental-frequency schemes may have a blind zone close to the generator neutral.

13.2 100% Stator Earth Fault Protection

For large generators, additional protection methods may be required to cover the entire stator winding.

Methods include:

  1. Third-harmonic voltage measurement.
  2. Subharmonic injection.
  3. Specialized neutral injection techniques.

The selected method depends on generator design, grounding arrangement, and manufacturer recommendations.

14. Earth Fault Protection in Transmission and Distribution Lines

Earth faults are common in overhead transmission and distribution networks.

They can result from:

  • Lightning.
  • Insulator failure.
  • Conductor contact with vegetation.
  • Broken conductors.
  • Pollution and contamination.
  • Equipment insulation failure.
Токовая направленная защита нулевой последовательности | Обслуживание устройств релейной защиты и автоматики | Різне

Protection schemes commonly use:

  • 50N/51N.
  • 67N.
  • 21N.
  • Distance protection ground-fault loops.
  • Line differential protection.
  • Auto-reclosing, where applicable.

For transmission line distance protection, zero-sequence compensation is important for accurate earth fault impedance measurement.

A commonly used compensation factor is:

K0=Z0−Z13Z1K0​=3Z1​Z0​−Z1​​

Where:

  • Z0Z0​: Zero-sequence line impedance.
  • Z1Z1​: Positive-sequence line impedance.

The exact compensation implementation and relay input conventions must be verified in the manufacturer’s documentation.

15. Practical Earth Fault Protection Calculation

Consider a 6.6 kV industrial distribution system with a resistance-grounded transformer neutral.

Assume:

ParameterValue
System voltage6.6 kV
Frequency50 Hz
Phase-to-neutral voltage3.81 kV
Neutral grounding resistor100 Ω
CT ratio100/1 A

15.1 Calculate the Earth Fault Current

Vph=66003Vph​=3​6600​

Vph=3810.5VVph​=3810.5V

Assuming the resistor dominates the fault-current limitation:

If=3810.5100If​=1003810.5​

If=38.1AIf​=38.1A​

15.2 Calculate CT Secondary Current

For a 100/1 A CT:

Isec=38.1100Isec​=10038.1​

Isec=0.381AIsec​=0.381A​

This is the approximate secondary current during a full-current earth fault at the assumed location.

15.3 Protection Setting Considerations

The relay pickup must be selected below the minimum expected fault current but above normal residual current and measurement errors.

The engineer must also consider:

  • Minimum earth fault current.
  • Maximum earth fault current.
  • Fault resistance.
  • CT accuracy.
  • Protection coordination.
  • NGR thermal rating.
  • Required operating time.

The example is illustrative; final settings require a complete network study.

16. Earth Fault Protection Relay Settings

Typical earth fault relay parameters include:

ParameterDescription
Earth fault pickupMinimum operating current
Time delayOperating delay
Curve typeDefinite or inverse-time characteristic
Directional angleDirectional operating characteristic
Residual voltage pickupVoltage threshold
CBCT ratioCore balance CT ratio
Neutral CT ratioNeutral current measurement ratio
REF pickupRestricted earth fault sensitivity
High-set pickupHigh-current earth fault operation
Blocking logicConditions preventing unwanted operation

16.1 IEC Inverse-Time Characteristics

Many numerical relays use IEC inverse-time curves.

Common curve types include:

  • Standard inverse.
  • Very inverse.
  • Extremely inverse.
  • Long-time inverse.

For an IEC standard inverse characteristic, a commonly used equation is:

t=0.14×TMS(IIs)0.02−1t=(Is​I​)0.02−10.14×TMS​

Where:

  • tt: Operating time.
  • TMSTMS: Time multiplier setting.
  • II: Measured current.
  • IsIs​: Pickup current.

The correct curve must be selected according to the protection coordination study.

17. Earth Fault Protection Testing and Commissioning

Practical testing is essential to confirm that the earth fault protection operates correctly.

Erdschlussschutz prüfen
Erdschlussversuche & Schutzprüfung

17.1 CT Circuit Verification

Check:

  • CT ratio.
  • CT polarity.
  • Secondary wiring.
  • Earthing point.
  • CT shorting links.
  • CBCT installation.
  • Cable screen earthing arrangement.
  • Neutral CT installation.

17.2 Secondary Injection Testing

Test the following:

  • 50N pickup.
  • 51N operating time.
  • 50G pickup.
  • 51G operating time.
  • 67N forward and reverse operation.
  • SEF pickup.
  • REF operating characteristic.
  • 59N voltage pickup.
  • Alarm and trip outputs.

17.3 Primary Injection Testing

Primary injection is used to verify the complete measurement chain.

For CBCT schemes, it is particularly important to confirm correct conductor routing and measurement polarity.

17.4 Functional Testing

Verify:

  • Circuit breaker trip.
  • Alarm outputs.
  • Lockout relay operation.
  • Trip circuit supervision.
  • SCADA indications.
  • Event recording.
  • Disturbance recording.
  • Interlocking and blocking logic.

18. Common Earth Fault Protection Problems

ProblemPossible causeRecommended investigation
Earth fault relay trips during normal operationCT mismatch or residual currentCheck CT wiring and measurements
CBCT does not detect earth faultIncorrect conductor routingInspect CBCT installation
REF unwanted operationCT polarity or wiring errorVerify phase and neutral CT connections
Directional relay operates in reverseIncorrect polarizing configurationReview voltage and current polarity
Earth fault relay does not operatePickup too highCheck minimum fault current
59N alarm during normal operationVT wiring or voltage unbalanceVerify VT secondary circuits
NGR overheatingExcessive fault duration or incorrect ratingCheck grounding resistor and trip time
Intermittent earth fault alarmInsulation deterioration or transient faultsReview event records and insulation condition

19. Earth Fault Protection Relay Manufacturers

The following manufacturers offer numerical relays with earth fault protection functions.

ManufacturerRelay family / modelMain application
SiemensSIPROTEC 5 7SJ82 / 7SJ85Feeder and earth fault protection
SiemensSIPROTEC 5 7UT85 / 7UT86Transformer differential and REF-related applications
SiemensSIPROTEC 5 7UM85Generator protection
SiemensSIPROTEC 5 7SA seriesDistance and ground fault protection
ABB / Hitachi EnergyREF615Feeder protection
ABB / Hitachi EnergyRET670Transformer and earth fault protection
ABB / Hitachi EnergyREG670Generator protection
ABB / Hitachi EnergyRED670Line protection
Schneider ElectricMiCOM P123Feeder protection
Schneider ElectricMiCOM P127Feeder protection
Schneider ElectricMiCOM P64xTransformer protection
Schneider ElectricMiCOM P54xLine protection
SELSEL-751Feeder protection
SELSEL-487ETransformer protection
SELSEL-421Line protection
GE VernovaMultilin 850Feeder protection
GE VernovaMultilin T60Transformer protection
GE VernovaMultilin G60Generator protection

Actual function availability depends on the exact model and configuration.

20. IEC Standards and Technical References

Engineers should refer to the following standards and technical documents.

StandardSubject
IEC 60255 seriesMeasuring relays and protection equipment
IEC 60076 seriesPower transformers
IEC 60034 seriesRotating electrical machines
IEC 60909Short-circuit currents in three-phase AC systems
IEC 61936-1Power installations exceeding 1 kV AC
IEC 60071 seriesInsulation coordination
IEC 61869 seriesInstrument transformers
IEC 60364 seriesLow-voltage electrical installations

For practical protection engineering, relay manuals, CT data sheets, transformer grounding information, and network studies should also be consulted.

21. Conclusion

Earth fault protection is an essential component of electrical power system protection.

The correct protection philosophy depends heavily on the system neutral earthing arrangement, fault current magnitude, network configuration, and equipment characteristics.

Protection engineers should understand the differences between:

  • Residual earth fault protection.
  • Neutral overcurrent protection.
  • Core balance CT protection.
  • Sensitive earth fault protection.
  • Directional earth fault protection.
  • Restricted earth fault protection.
  • Neutral displacement protection.
  • Generator stator earth fault protection.

Correct CT installation, relay settings, coordination, and commissioning tests are essential to achieve reliable fault detection and selective isolation.

22. Professional Training by Elec-Engg

At Elec-Engg.com, we provide practical training in power system protection, numerical relay configuration, testing, and commissioning.

Our training includes:

  • Earth fault protection principles.
  • Transformer REF protection.
  • Generator stator earth fault protection.
  • Directional earth fault protection.
  • Sensitive earth fault protection.
  • CT and CBCT applications.
  • Neutral grounding systems.
  • SIPROTEC 4 and SIPROTEC 5.
  • ABB Relion and PCM600.
  • Schneider MiCOM protection relays.
  • Omicron CMC and Test Universe.

Explore our training resources :Elec-Engg – Power System Protection and Substation Automation Training