Motor Protection

Complete Engineering Guide to Protection Functions, Relay Settings, Motor Starting, Thermal Overload, Short Circuit and Testing

1. Introduction to Motor Protection

Electric motors are among the most important electrical assets in industrial plants, power stations, oil and gas facilities, water treatment plants, and manufacturing industries.

Motors drive essential equipment such as:

  • Pumps
  • Compressors
  • Fans and blowers
  • Conveyors
  • Cooling water systems
  • Crushers and mills
  • Feedwater pumps
  • Cooling towers
  • Industrial process equipment

An unexpected motor trip can interrupt production, affect plant availability, and sometimes create serious operational consequences.

Motor protection is therefore essential to ensure:

  1. Protection against electrical faults.
  2. Protection against thermal damage.
  3. Protection against abnormal operating conditions.
  4. Protection during motor starting.
  5. Prevention of mechanical damage.
  6. Safe operation and equipment availability.

Modern numerical motor protection relays combine multiple protection functions in one device, providing comprehensive monitoring, protection, control, and event recording.

Preventing Water Ingress: Effective Solutions for Engineering Facilities | MKE Engineering Group | Engineering Motors | Kent, United Kingdom

2. Types of Electric Motors

Before discussing protection functions, it is important to understand the different motor types used in industrial applications.

2.1 Induction Motors

Induction motors are the most widely used motors in industrial facilities.

They are generally classified into:

  • Squirrel-cage induction motors.
  • Wound-rotor induction motors.

They are used in pumps, compressors, fans, conveyors, and many other applications.

2.2 Synchronous Motors

Synchronous motors operate at synchronous speed and are commonly used for large industrial drives.

Applications include:

  • Large compressors
  • Ball mills
  • Large pumps
  • Industrial process drives

Their protection requirements may include field-related protection, loss of excitation, out-of-step protection, and stator differential protection.

2.3 Low-Voltage and Medium-Voltage Motors

Motor protection requirements depend on rated voltage, power, application, starting method, and operational importance.

Motor categoryTypical application
LV motorsSmall pumps, fans, conveyors
MV motorsLarge pumps, compressors, industrial drives
HV motorsLarge industrial and specialized applications
Synchronous motorsLarge compressors and process drives

3. Motor Protection Functions and ANSI Codes

Motor protection relays use several ANSI protection functions.

The following table summarizes the most important functions.

ANSI codeProtection functionPurpose
49Thermal overloadProtects against overheating
50Instantaneous overcurrentDetects high short-circuit current
51Time overcurrentDetects overcurrent with time delay
50G/51GGround overcurrentDetects earth faults
46Negative-sequence protectionDetects current unbalance
48Incomplete sequence / excessive starting timeDetects abnormal starting
51LRLocked rotor protectionDetects rotor stall conditions
66Starts per hourLimits excessive motor starts
27UndervoltageDetects low supply voltage
59OvervoltageDetects excessive supply voltage
37UndercurrentDetects loss of load
47Phase sequence / voltage unbalanceDetects abnormal phase conditions
55Power factorDetects abnormal power factor
81U/81OUnderfrequency / overfrequencyDetects frequency abnormalities
87MMotor differentialDetects internal motor winding faults
86LockoutProvides latched trip function
14OverspeedDetects excessive speed where applicable

Not every motor requires all these functions. The protection scheme must be designed according to the motor characteristics and application.

4. Thermal Overload Protection (ANSI 49)

Thermal overload protection is one of the most important motor protection functions.

A motor can be damaged when its winding temperature exceeds the permissible insulation temperature.

Motor overheating may result from:

  • Mechanical overload
  • Excessive starting time
  • Frequent starting
  • High ambient temperature
  • Cooling system failure
  • Blocked ventilation
  • Phase current unbalance
  • Low voltage
  • Excessive operating current
What is Trip Class? Motor Protection Class 10 vs 20 Selection Guide | VIOX

4.1 Thermal Model

Numerical motor protection relays use a thermal model to estimate motor heating.

A simplified thermal relationship is:

θ(t)=θ∞(1−e−t/τ)θ(t)=θ∞​(1−e−t/τ)

Where:

  • θ(t)θ(t): Thermal state at time tt
  • θ∞θ∞​: Final thermal state
  • ττ: Thermal time constant

In practical relays, thermal models may be more sophisticated and account for heating, cooling, starting conditions, and negative-sequence currents.

4.2 Motor Thermal Capacity

A motor protection relay may calculate the thermal capacity used as a percentage.

For example:

  • 0%: Cold motor thermal state.
  • 50%: Half of the configured thermal capacity used.
  • 80%: High thermal loading.
  • 100%: Thermal trip threshold reached.

The actual interpretation depends on the relay manufacturer and configuration.

4.3 Cold and Hot Motor Conditions

A cold motor can normally withstand a longer starting time than a hot motor.

This is because the hot motor already has accumulated thermal energy.

Protection engineers must consider:

  • Cold stall time.
  • Hot stall time.
  • Starting current.
  • Starting duration.
  • Thermal withstand curve.
  • Acceleration time.

4.4 Thermal Overload Settings

Typical required motor data include:

ParameterDescription
Rated motor currentFull-load current
Service factorPermitted loading factor where applicable
Thermal time constantHeating/cooling characteristic
Cold stall timePermissible locked-rotor time from cold
Hot stall timePermissible locked-rotor time from hot
Starting currentExpected motor starting current
Starting timeExpected acceleration duration
Cooling methodMotor cooling arrangement

The relay settings must be checked against the motor manufacturer’s thermal withstand data.

5. Short-Circuit Protection (ANSI 50/51)

Short-circuit protection detects high fault currents and disconnects the motor from the electrical supply.

Possible short-circuit faults include:

  • Phase-to-phase faults.
  • Three-phase faults.
  • Phase-to-earth faults.

5.1 Instantaneous Overcurrent (50)

ANSI 50 operates when the measured current exceeds a predefined pickup threshold.

It is generally used for high-current faults.

5.2 Time Overcurrent (51)

ANSI 51 operates when current exceeds the pickup value for a specified time.

Depending on the relay, it may use:

  • Definite-time characteristics.
  • Inverse-time characteristics.
  • Very inverse characteristics.
  • Extremely inverse characteristics.

The selected characteristic must coordinate with upstream and downstream protection.

5.3 Motor Starting Current Considerations

During direct-on-line starting, an induction motor can draw several times its rated current.

Therefore, short-circuit protection must be coordinated to avoid unnecessary operation during normal starting.

Motor starting current, acceleration time, and maximum fault current must all be considered when selecting settings.

6. Earth Fault Protection (ANSI 50G/51G)

Earth faults can occur because of insulation deterioration, cable damage, moisture, contamination, or winding failures.

Earth fault protection detects current flowing through an unintended path to earth.

Difference Between 50/51G and 50/51N?

Common earth fault detection arrangements include:

  1. Residual connection of three phase CTs.
  2. Core-balance current transformer (CBCT).
  3. Neutral CT arrangement, where applicable.

The residual current is:

I0=IA+IB+ICI0​=IA​+IB​+IC​

Depending on the relay convention, the residual earth-fault current may be represented as 3I03I0​.

The protection pickup must consider:

  • System neutral earthing arrangement.
  • Cable charging current.
  • Motor leakage current.
  • CT sensitivity.
  • Fault current magnitude.
  • Required protection coordination.

In resistance-grounded systems, earth fault current may be intentionally limited, requiring sensitive earth fault protection.

7. Negative-Sequence Protection (ANSI 46)

Negative-sequence protection detects current unbalance.

Three-phase systems should ideally have balanced phase currents.

However, unbalanced conditions may occur due to:

  • Single-phase faults.
  • Unbalanced loading.
  • Broken conductors.
  • Defective contacts.
  • Unequal phase voltages.
  • CT problems.

Negative-sequence current produces additional heating in the motor rotor.

This is particularly important for induction motors because the negative-sequence magnetic field rotates in the opposite direction to the rotor.

The negative-sequence current can cause significant rotor heating even when the average phase current appears acceptable.

A simplified thermal relationship is:

I22t=KI22​t=K

Where:

  • I2I2​: Negative-sequence current.
  • tt: Operating time.
  • KK: Motor-specific withstand constant.

Actual relay characteristics and settings must follow motor manufacturer data and relay application guidance.

8. Locked Rotor Protection (ANSI 51LR)

A locked rotor condition occurs when the motor rotor cannot rotate despite the presence of an energized stator winding.

This can happen due to:

  • Mechanical blockage.
  • Bearing failure.
  • Pump or compressor seizure.
  • Excessive load torque.
  • Coupling problems.
  • Failure of the driven equipment.
Difference between Locked Rotor Current and Starting Current

During a locked rotor condition, the motor may draw a high current similar to starting current.

If the condition continues, the motor can overheat rapidly.

Protection may use:

  • Current magnitude.
  • Starting supervision.
  • Motor speed or acceleration information.
  • Thermal model.
  • Configured stall time.

It is important to distinguish a normal motor start from a locked rotor condition.

9. Excessive Starting Time Protection (ANSI 48)

A motor requires a certain amount of time to accelerate from standstill to operating speed.

If the motor fails to reach the required speed within the expected time, the protection relay may trip.

Possible reasons include:

  • Excessive mechanical load.
  • Low supply voltage.
  • Mechanical blockage.
  • Incorrect motor selection.
  • High system impedance.
  • Incorrect starting method.

The motor’s acceleration time must be compared with its permissible starting time under both hot and cold conditions.

9.1 Starting Current Curve

The starting current normally begins at a high value and decreases as the motor accelerates.

The actual starting profile depends on motor design, supply voltage, load torque, and starting method.

10. Starts Per Hour Protection (ANSI 66)

Frequent starting can cause excessive motor heating.

ANSI 66 limits the number of permitted starts within a defined period.

For example, a motor manufacturer may specify:

  • Maximum starts per hour.
  • Minimum interval between starts.
  • Maximum consecutive starts from cold.
  • Maximum consecutive starts from hot.

The actual limits must be obtained from the motor manufacturer.

The relay can prevent a new start when the permitted starting frequency has been exceeded.

11. Undervoltage Protection (ANSI 27)

Undervoltage protection detects when the motor supply voltage falls below a defined threshold.

Low voltage can result in:

  • Reduced motor torque.
  • Increased current for a given load condition.
  • Motor stalling.
  • Contactor dropout.
  • Process instability.

The torque of an induction motor is approximately proportional to the square of applied voltage under simplified operating conditions:

T∝V2T∝V2

For example, if voltage decreases to 90% of rated voltage:

T≈0.92=0.81T≈0.92=0.81

Available torque is approximately 81% of its original value, under the stated approximation.

This explains why undervoltage can seriously affect motor acceleration and operation.

12. Undercurrent Protection (ANSI 37)

Undercurrent protection detects a reduction in motor current below a configured threshold.

It is useful in applications where the motor normally operates under a predictable load.

Typical applications include:

  • Pumps.
  • Conveyors.
  • Fans.
  • Compressors.

Possible abnormal conditions include:

  • Pump dry running.
  • Broken coupling.
  • Loss of mechanical load.
  • Failure of driven equipment.

For example, a pump operating without sufficient liquid may experience a significant reduction in motor load current.

The undercurrent function can detect this condition and initiate an alarm or trip.

13. Motor Differential Protection (ANSI 87M)

Motor differential protection is used mainly for large and important motors.

It compares currents measured at different boundaries of the stator winding protection zone.

고압 전동기 고장 보호의 기초 (차동 과전류와 지락)

During normal operation, the currents should balance.

During an internal stator fault, differential current increases.

The protection can detect:

  • Phase-to-phase stator faults.
  • Three-phase winding faults.
  • Certain phase-to-earth faults, depending on the winding and grounding arrangement.

Differential protection is generally used where the motor size, criticality, and economic importance justify the additional CTs and relay functions.

14. Motor Starting Methods and Protection Considerations

Motor starting methods have a direct impact on protection settings.

14.1 Direct-On-Line (DOL)

How a Direct Online Starter Works

The motor is connected directly to the supply.

Advantages:

  • Simple arrangement.
  • Low equipment cost.
  • High starting torque.

Disadvantages:

  • High starting current.
  • Possible voltage dips.
  • Mechanical stress.

14.2 Star-Delta Starting

Star-delta starting reduces the starting voltage applied to each winding during the initial starting stage.

The motor subsequently changes to delta connection.

Protection engineering must consider CT location and current scaling during starting and transition.

14.3 Soft Starter

A soft starter controls the applied voltage during motor acceleration.

It can reduce starting current and mechanical stress.

However, protection coordination between the soft starter and external motor protection relay is essential.

14.4 Variable Frequency Drive (VFD)

Making Measurements on 3-Phase Motor Drives with an Oscilloscope | Tektronix

A VFD controls motor speed by varying supply frequency and voltage.

Protection considerations include:

  • Motor thermal protection.
  • Overcurrent.
  • Earth fault.
  • Overvoltage and undervoltage.
  • Cooling at low speed.
  • Harmonic effects.
  • Motor insulation stress.

The protection arrangement must account for the VFD manufacturer’s recommendations and whether the motor protection relay measures current on the input or output side.

15. Motor Protection Relay Settings: Practical Engineering Example

Consider a medium-voltage induction motor with the following specifications.

ParameterValue
Rated power2,000 kW
Rated voltage6.6 kV
Rated current220 A
Frequency50 Hz
Power factor0.88
Efficiency95%
Starting methodDirect-on-line
Starting current6 × rated current
Starting time8 seconds

15.1 Starting Current

Istart=6×IratedIstart​=6×Irated​

Istart=6×220Istart​=6×220

Istart=1320AIstart​=1320A

15.2 CT Selection

A possible CT selection is:

300/1A300/1A

Rated secondary current:

Isec=220300Isec​=300220​

Isec=0.733AIsec​=0.733A

Starting secondary current:

Istart,sec=1320300Istart,sec​=3001320​

Istart,sec=4.4AIstart,sec​=4.4A

The selected CT must be checked against the relay input capability, fault current, accuracy, burden, and saturation requirements.

15.3 Starting Protection

The expected starting time is 8 seconds.

The starting protection must allow the motor to accelerate successfully while remaining within the motor’s permissible hot and cold starting limits.

A suitable setting cannot be selected from the starting time alone.

The following additional data are necessary:

  • Cold and hot stall times.
  • Motor acceleration curve.
  • Load torque curve.
  • Motor thermal withstand curve.
  • Starting current profile.
  • Relay thermal model parameters.

15.4 Thermal Protection

The thermal model must be configured using the manufacturer’s motor data.

It should consider:

  • Rated current.
  • Thermal time constant.
  • Heating and cooling characteristics.
  • Locked-rotor withstand.
  • Negative-sequence heating.
  • Starting frequency.

This example demonstrates the engineering process rather than providing final commissioning settings.

16. Motor Protection Relay Manufacturers

Several manufacturers provide dedicated numerical motor protection relays.

ManufacturerRelay model / familyMain application
SiemensSIPROTEC 5 7SK82 / 7SK85Motor protection
SiemensSIPROTEC 4 7SJ seriesOvercurrent and motor feeder protection
ABB / Hitachi EnergyREM615Motor protection
ABB / Hitachi EnergyREM620Motor protection
ABB / Hitachi EnergyREM670Advanced motor protection
Schneider ElectricSepam M20 / M41Motor protection
Schneider ElectricMiCOM P24xMotor protection
Schneider ElectricTeSys TMotor management and protection
SELSEL-710Motor protection
SELSEL-849Motor management and protection
GE Vernova369 Motor Protection SystemMotor protection
GE VernovaMultilin 339Motor protection
EatonEMR seriesMotor protection and monitoring
Rockwell AutomationE300Electronic motor protection

The exact functions depend on the model, hardware, firmware, and licensed options.

17. Practical Motor Protection Configuration and Testing

Motor protection commissioning should verify the complete protection and control system.

17.1 Required Documents

Before starting the configuration and testing process, obtain:

  1. Motor nameplate.
  2. Motor manufacturer’s data sheet.
  3. Motor thermal withstand curves.
  4. Starting current and acceleration curves.
  5. CT and VT data sheets.
  6. Motor feeder single-line diagram.
  7. Protection and control schematics.
  8. Relay settings.
  9. Motor starting logic.
  10. Circuit breaker trip circuit diagrams.

17.2 Secondary Injection Testing

Using an appropriate relay test set, engineers should verify:

  • Phase overcurrent pickup.
  • Earth fault pickup.
  • Thermal overload operation.
  • Negative-sequence protection.
  • Undercurrent protection.
  • Undervoltage protection.
  • Locked rotor protection.
  • Excessive starting time.
  • Starts-per-hour logic.
  • Differential protection, where installed.

17.3 Functional Testing

Functional testing should also verify:

  • Trip output contacts.
  • Alarm output contacts.
  • Circuit breaker trip command.
  • Start permissive.
  • Motor start and stop commands.
  • Interlocking.
  • Lockout operation.
  • Emergency stop interface.
  • SCADA signals.
  • Event and disturbance records.

17.4 Primary Injection Testing

Where required, primary injection testing verifies the complete CT and current measurement chain.

It helps identify:

  • CT ratio errors.
  • Incorrect polarity.
  • Wiring mistakes.
  • Incorrect phase identification.
  • Incorrect relay current measurements.

18. Common Motor Protection Problems and Troubleshooting

ProblemPossible causeRecommended action
Motor trips during startingStarting time setting too shortCheck acceleration curve and stall limits
Thermal overload tripMechanical overload or inadequate coolingCheck load and cooling system
Negative-sequence alarmPhase imbalance or CT problemCheck phase currents and CT circuits
Earth fault tripCable or motor insulation faultPerform insulation and circuit tests
Motor fails to startStart permissive or interlock issueCheck control logic
Undervoltage tripSupply voltage disturbanceReview voltage records and settings
Starts-per-hour lockoutExcessive start frequencyReview process requirements and motor limits
Motor differential tripCT polarity or internal faultCheck CT circuits and relay records
Locked rotor tripMechanical blockage or failure to accelerateInvestigate motor and driven equipment

19. Motor Protection and IEC Standards

Motor protection design and application should consider relevant IEC standards.

StandardSubject
IEC 60034-1Rotating electrical machines – Rating and performance
IEC 60034-11Thermal protection
IEC 60034-12Starting performance of single-speed three-phase cage induction motors
IEC 60034-18Functional evaluation of insulation systems
IEC 60034-26Effects of unbalanced voltages on the performance of three-phase induction motors
IEC 60255 seriesMeasuring relays and protection equipment
IEC 60947-4-1Electromechanical contactors and motor-starters
IEC 60947-4-2Semiconductor motor controllers and starters
IEC 61800 seriesAdjustable-speed electrical power drive systems

Engineers should consult the applicable editions and the manufacturer’s documentation when designing protection schemes.

20. Conclusion

Motor protection is not limited to conventional overload and short-circuit protection.

A complete motor protection scheme must consider electrical, thermal, mechanical, and operational conditions.

Protection engineers should understand:

  • Thermal overload protection (49).
  • Overcurrent protection (50/51).
  • Earth fault protection (50G/51G).
  • Negative-sequence protection (46).
  • Locked rotor protection (51LR).
  • Excessive starting time protection (48).
  • Starts-per-hour protection (66).
  • Undervoltage protection (27).
  • Undercurrent protection (37).
  • Motor differential protection (87M).

Correct relay configuration, protection coordination, and practical testing are essential to ensure reliable motor operation and prevent costly equipment damage.

21. Professional Motor Protection Training – Elec-Engg

At Elec-Engg.com, we provide practical technical training for engineers working in power system protection, industrial electrical systems, and substation automation.

Our Motor Protection training includes:

  • Motor protection fundamentals.
  • Motor protection functions and ANSI codes.
  • Thermal overload calculations.
  • Motor starting and locked rotor protection.
  • Negative-sequence protection.
  • Motor differential protection.
  • Relay configuration and settings.
  • Practical relay testing and commissioning.
  • Siemens, ABB, Schneider Electric, SEL, and GE protection systems.

We also provide dedicated training on the GE Multilin 369 Motor Protection Relay, including configuration, settings, protection functions, and practical engineering applications.

Explore our training resources:Elec-Engg – Protection and Substation Automation Training

Trainer: Dr. Saeed Roostaee – Electrical Engineering / Power System Protection.

  1. Industrial induction motor.
  2. Motor protection single-line diagram.
  3. Thermal overload protection characteristic.
  4. Motor short-circuit protection diagram.
  5. Earth fault protection with CBCT.
  6. Negative-sequence protection diagram.
  7. Locked rotor protection illustration.
  8. Motor starting current curve.
  9. DOL starter diagram.
  10. Star-delta starter diagram.
  11. Soft starter connection.
  12. VFD motor protection arrangement.
  13. Motor differential protection diagram.
  14. GE Multilin 369 relay.
  15. Siemens SIPROTEC 5 7SK85 relay.
  16. ABB REM615 relay.
  17. Omicron motor relay testing arrangement.