Differential Protection – ANSI 87

Current Comparison, CT Matching, Restraint, Stability, Settings, and Testing

1. Introduction to Differential Protection

Differential protection is one of the most important and reliable protection principles used in modern electrical power systems.

It is based on a simple principle: the current entering a protected zone must be equal to the current leaving that zone, considering the defined current directions and transformation ratios.

If the difference between the incoming and outgoing currents exceeds a predefined operating threshold, the protection relay identifies an internal fault and issues a trip command.

Differential protection is widely used for protecting:

  • Power transformers
  • Generators
  • Busbars
  • Transmission lines
  • Large motors
  • Reactors
  • Cables
  • Large electrical machines

The ANSI device number for differential protection is 87.

Different applications have specific ANSI designations:

ANSI codeProtection function
87TTransformer differential protection
87GGenerator differential protection
87BBusbar differential protection
87LLine differential protection
87MMotor differential protection
87CCable differential protection
87NNeutral or restricted earth fault-related differential protection
87RReactor differential protection

The operating principle is similar, but CT arrangements, algorithms, protection zones, and practical settings differ between applications.

2. Basic Operating Principle

Consider a protected electrical zone with two current transformers installed at its boundaries.

Under normal operating conditions, current entering the zone is equal to current leaving the zone.

The differential Protection Fundamentals-1

For an ideal two-terminal protection zone:

Idiff=∣I1−I2∣Idiff​=∣I1​−I2​∣

Where:

  • I1I1​: Current entering the protected zone
  • I2I2​: Current leaving the protected zone
  • IdiffIdiff​: Differential operating current

Under normal load conditions:

I1=I2I1​=I2​

Therefore:

Idiff=0Idiff​=0

During an internal fault, the current relationship changes:

I1≠I2I1​=I2​

Consequently:

Idiff>0Idiff​>0

If the differential current exceeds the relay operating threshold, the relay initiates a trip.

Important: Current directions must be defined consistently. The relay normally processes currents using its own reference directions and polarity conventions.

3. Internal Faults and External Faults

Understanding the difference between internal and external faults is fundamental to differential protection engineering.

3.1 Internal Fault

An internal fault occurs inside the boundaries of the protected zone.

Examples include:

  • Phase-to-earth faults
  • Phase-to-phase faults
  • Three-phase faults
  • Inter-turn faults (depending on protection sensitivity and winding arrangement)
  • Winding insulation failures
  • Internal busbar faults
Figure 5 - from Fundamentals of Short-Circuit Protection for

During an internal fault, the currents entering the protected zone contribute to the fault current.

The differential relay detects the imbalance and operates.

3.2 External Fault

An external fault occurs outside the protected zone.

Examples include:

  • Faults on outgoing feeders
  • Transmission line faults outside the protected transformer zone
  • Faults on adjacent busbar sections
  • Faults beyond the protected generator terminals
How Does Differential Protection Respond to Faults Outside Its Protected Zone? - Electrical - Industrial Automation, PLC Programming, scada & Pid Control System

During an external fault, the current entering and leaving the protected zone should remain balanced.

Therefore, the differential relay must remain stable and should not trip.

This requirement is called differential protection stability.

4. Differential Protection Operating Characteristics

Modern differential relays generally use two important quantities:

  1. Differential current (operating current).
  2. Restraining current (bias current).

The differential current determines the tendency of the relay to operate.

The restraining current provides security against unwanted operation, especially during external faults and CT saturation.

A commonly used definition is:

Idiff=∣I1−I2∣Idiff​=∣I1​−I2​∣

For a two-terminal relay, a commonly used restraining-current definition is:

Ibias=∣I1∣+∣I2∣2Ibias​=2∣I1​∣+∣I2​∣​

The exact definitions vary among manufacturers and relay algorithms.

4.1 Percentage Differential Protection

Percentage differential protection uses a differential operating threshold that increases with the restraining current.

A simplified operating characteristic is:

Idiff>Ipickup+SIbiasIdiff​>Ipickup​+SIbias​

Where:

  • IpickupIpickup​: Minimum differential pickup
  • SS: Restraint slope
  • IbiasIbias​: Restraining current

The relay trips when the differential current exceeds the operating characteristic.

Venturing into Busbar Differential Protection: A B90 (GE) Application Expedition

4.2 Why Is Restraint Required?

In practical electrical systems, differential current is not always zero during healthy operating conditions.

Possible causes include:

  • CT ratio mismatch
  • CT accuracy errors
  • CT saturation
  • CT secondary wiring problems
  • Transformer tap-changer operation
  • Phase-angle compensation errors
  • Numerical measurement errors
  • Different CT characteristics

Without sufficient restraint, these errors could cause unwanted tripping.

5. CT Requirements for Differential Protection

Current transformers are among the most critical components in differential protection.

Incorrect CT selection, installation, wiring, or configuration can result in unwanted operation or failure to detect internal faults.

5.1 CT Ratio Selection

CT ratios must be selected according to:

  • Maximum continuous load current
  • Maximum fault current
  • Relay input ratings
  • CT accuracy requirements
  • CT saturation performance
  • Protection application
  • Short-time thermal and dynamic ratings

For example:

A transformer rated:

S=100 MVAS=100MVA

High-voltage side:

VHV=132 kVVHV​=132kV

Rated current:

IHV=100×1063×132×103IHV​=3​×132×103100×106​

IHV=437.4 AIHV​=437.4A

A possible CT selection could be 500/1 A, subject to the detailed CT performance and protection study.

5.2 CT Polarity

Correct CT polarity is essential.

The polarity markings P1, P2, S1 and S2 must be considered during installation and wiring.

Incorrect polarity can cause the relay to measure an incorrect differential current.

5.3 CT Saturation

CT saturation is one of the major challenges in differential protection.

During a high external fault, one CT may saturate earlier than the other.

This creates an artificial difference between the measured currents.

The differential relay may interpret this imbalance as an internal fault.

Fast Detection of Current Transformer Saturation Using Stacked Denoising Autoencoders

Modern differential relays use different methods to improve stability, including:

  • Percentage bias restraint
  • Multiple-slope characteristics
  • CT saturation detection
  • Waveform analysis
  • Harmonic and transient signal processing, depending on application

6. Transformer Differential Protection (87T)

Transformer differential protection is one of the most common applications of ANSI 87.

It protects the transformer against internal electrical faults.

6.1 Transformer Differential Protection Challenges

Transformer differential protection is more complicated than basic feeder differential protection because of:

  1. Different current magnitudes on transformer sides.
  2. Transformer vector group.
  3. Phase-angle displacement.
  4. On-load tap changer operation.
  5. Magnetizing inrush current.
  6. Overexcitation.
  7. CT ratio mismatch.
  8. CT saturation.

The differential relay must compensate for these conditions to maintain both sensitivity and stability.

6.2 Transformer Ratio Compensation

Consider a 100 MVA transformer:

  • HV: 132 kV
  • LV: 33 kV

HV rated current:

IHV=100MVA3×132kVIHV​=3​×132kV100MVA​

IHV=437.4AIHV​=437.4A

LV rated current:

ILV=100MVA3×33kVILV​=3​×33kV100MVA​

ILV=1749.5AILV​=1749.5A

The currents on the two sides are different because of the transformer voltage ratio.

The differential relay must compensate for this difference.

Modern numerical relays perform this compensation internally using configured CT ratios, transformer rated data, and vector group information.

6.3 Vector Group Compensation

Transformer vector groups introduce phase displacement between HV and LV currents.

For example:

  • Dyn11
  • YNd1
  • Yy0
  • Yd1
  • YNd11

The differential relay must correctly compensate for the phase-angle displacement.

Incorrect vector group configuration can produce differential current even under normal load conditions.

6.4 Magnetizing Inrush Current

Transformer energization creates magnetizing inrush current.

This current may be significantly higher than the normal transformer rated current.

Although the inrush current enters the transformer, it does not have a corresponding current leaving the transformer secondary.

Therefore, it can appear as differential current.

Harmonic Blocking Fundamentals with Practical Examples in Transformer Diff. Protection

To avoid unwanted operation, transformer differential relays commonly use:

  • Second-harmonic restraint
  • Second-harmonic blocking
  • Waveform-based inrush detection
  • Cross-phase blocking or restraint, depending on relay design

6.5 Overexcitation Protection

Overexcitation occurs when the magnetic flux density increases beyond its normal operating range.

It is commonly associated with an excessive voltage-to-frequency ratio:

VffV​

Overexcitation can generate harmonic components, particularly the fifth harmonic.

Some transformer differential relays use fifth-harmonic restraint to improve security during overexcitation.

However, dedicated overexcitation protection is generally ANSI 24.

7. Generator Differential Protection (87G)

Generator differential protection is used to detect internal stator winding faults.

It is particularly important for large synchronous generators.

Differential (87) Current Protection | Electric Power Measurement and Control Systems | Textbook

The protection compares the currents measured at the generator terminal and neutral ends of the stator winding.

During normal operation:

Idiff≈0Idiff​≈0

During an internal stator fault:

Idiff>IpickupIdiff​>Ipickup​

Generator differential protection is generally applied to detect:

  • Phase-to-phase faults
  • Three-phase stator faults
  • Phase-to-earth faults where the grounding arrangement and protection sensitivity permit

It should be noted that conventional generator differential protection may not detect every earth fault, particularly faults close to the neutral point.

Additional protection functions may be necessary, such as:

  • 64G – Generator stator earth fault protection
  • 87N – Neutral-related differential or restricted earth fault schemes
  • 59N – Neutral displacement/voltage-based earth fault protection
  • 100% stator earth fault schemes

8. Busbar Differential Protection (87B)

Busbar differential protection is designed to detect faults inside a busbar protection zone.

Busbar faults can produce very high short-circuit currents and require fast fault clearance.

Garantir a proteção da zona do barramento e solucionar problemas de fa
 – COMPRACO Soluções e Tecnologias

A busbar may have several incoming and outgoing feeders.

The differential relay compares the current contributions from all connected circuits.

The simplified operating principle is:

Idiff=∣∑k=1nIk∣Idiff​=​k=1∑n​Ik​​

Where currents are referenced consistently into or out of the protected zone.

8.1 Main and Check Zones

Modern busbar protection systems may use:

  • Main protection zones
  • Check zones
  • Isolator replica logic
  • CT supervision
  • Breaker failure integration
  • Bus section and coupler selection logic

The protection system must correctly identify which circuits belong to each busbar zone.

Incorrect isolator status or zone selection can cause serious protection problems.

8.2 High-Impedance and Low-Impedance Differential Protection

Two major approaches are used for busbar differential protection.

FeatureHigh-impedanceLow-impedance
Operating principleVoltage-based differential circuitNumerical current differential
CT requirementsMatched CT characteristics are importantMore flexible CT arrangements
Stabilizing resistorNormally requiredNot normally required
Nonlinear resistorMay be requiredNot normally required
Zone configurationHardware-oriented arrangementsFlexible numerical configuration
ApplicationEstablished busbar schemesModern numerical busbar protection

Both approaches require careful CT engineering and stability assessment.

9. Line Differential Protection (87L)

Line differential protection compares currents measured at different ends of a transmission line.

Differential Protection for Transmission Lines Explained | Muhammad Naveed posted on the topic | LinkedIn

The relays at both ends exchange current information through a communication channel.

The communication channel may use:

  • Optical fiber
  • Dedicated telecommunications links
  • Multiplexed communication systems
  • Other supported digital communication networks

The protection principle is based on Kirchhoff’s current law.

For a healthy line or external fault:

IA+IB≈0IA​+IB​≈0

For an internal line fault:

∣IA+IB∣>Ithreshold∣IA​+IB​∣>Ithreshold​

Line differential protection offers fast and selective protection for transmission lines and cables.

Important engineering considerations include:

  • Communication channel delay
  • Channel asymmetry
  • Time synchronization requirements, depending on the scheme
  • Communication failure handling
  • Current transformer performance
  • Line charging current compensation
  • Multi-terminal line arrangements

10. Restricted Earth Fault Protection (REF)

Restricted Earth Fault protection is a sensitive protection scheme for detecting earth faults within a defined transformer or generator winding zone.

Harmonizing Safety: The Role of Restricted Ground Fault Relays
 – COMPRACO Indústria e Construção

REF compares the residual current from the phase CTs with the neutral CT current.

Its operating principle is similar to differential protection but is specifically designed for earth faults within the restricted zone.

Two common types are:

  • High-impedance REF
  • Low-impedance REF

REF provides high sensitivity for earth faults that may not produce sufficient differential current for conventional transformer differential protection.

11. Differential Protection Relay Settings

Correct relay settings are essential for achieving dependable and secure protection.

The actual setting values depend on the protected equipment, CT characteristics, system fault levels, relay model, and manufacturer’s application guidelines.

Typical setting parameters include:

ParameterDescription
Differential pickupMinimum operating differential current
Bias slope 1Restraint at lower through-current levels
Bias slope 2Increased restraint at higher through-current levels
BreakpointTransition between restraint slopes
High-set differentialHigh differential current operating threshold
Second harmonic thresholdInrush detection setting for transformer protection
Fifth harmonic thresholdOverexcitation restraint setting where supported
CT supervisionMonitoring of CT circuit abnormalities
Trip delayIntentional delay, where required
Inrush blockingTransformer energization security function

11.1 Differential Pickup

The differential pickup should be selected to provide sufficient sensitivity while considering:

  • CT errors
  • Transformer tap variation
  • Measurement errors
  • Normal operating imbalance
  • Equipment-specific characteristics

11.2 Bias Slope

The bias slope provides stability during high through-current conditions.

A higher slope means that the relay requires a higher differential current to operate at a given restraining current.

11.3 High-Set Differential

High-set differential protection is intended to provide fast operation for severe internal faults.

Its setting must be coordinated with expected internal fault currents and possible transient conditions.

Not every relay implements this function in the same way.

12. Differential Protection Testing and Commissioning

Testing is essential to verify correct operation before energizing protected equipment.

Testing should include the complete protection chain, not just the numerical relay.

12.1 CT Circuit Inspection

Before secondary injection testing:

  • Verify CT ratios.
  • Check CT polarity.
  • Confirm CT secondary earthing.
  • Check terminal connections.
  • Verify shorting links and test blocks.
  • Confirm the correct CT inputs.
  • Check wiring diagrams against the actual installation.

12.2 Secondary Injection Testing

A relay test set can be used to inject currents into the differential relay.

The test should verify:

  • Differential pickup
  • Operating characteristic
  • Restraint characteristic
  • Slope 1
  • Slope 2
  • Breakpoint
  • High-set operation
  • Phase selection
  • Trip output

12.3 Stability Test

A stability test verifies that the relay does not operate when equal currents flow through the protected zone.

For a two-terminal differential scheme:

I1=I2I1​=I2​

Therefore:

Idiff≈0Idiff​≈0

The relay should remain stable.

12.4 Operating Test

An operating test introduces a differential current exceeding the configured operating threshold.

The relay should operate according to its configured characteristic.

12.5 Transformer Differential Testing

Additional tests should verify:

  • Vector group compensation
  • CT ratio compensation
  • Phase-angle compensation
  • Inrush restraint
  • Overexcitation restraint, where applicable
  • Transformer tap compensation
  • Differential trip logic

12.6 End-to-End Testing

For line differential protection, end-to-end testing is especially important.

Both terminals should be tested together to verify:

  • Communication channel performance
  • Current exchange
  • Internal fault operation
  • External fault stability
  • Communication failure response
  • Trip signals at both terminals

13. Common Differential Protection Problems

The following table summarizes practical problems frequently encountered during installation, commissioning, and operation.

ProblemPossible causeRecommended investigation
Differential current during normal loadCT polarity or ratio errorCheck CT wiring and configuration
Unwanted trip during external faultCT saturationReview CT performance and relay stability
Trip during transformer energizationInrush restraint issueCheck harmonic settings and energization records
Incorrect phase differential currentVector group mismatchVerify transformer compensation
Differential alarmCT circuit supervisionInspect CT secondary circuits
Relay does not trip during internal faultIncorrect settings or trip logicReview differential measurements and trip matrix
Busbar false operationIncorrect zone selectionCheck isolator replica and CT allocation
Line differential communication alarmChannel failure or delayInvestigate communication system

14. Differential Protection in Modern Numerical Relays

Most major protection manufacturers provide numerical differential protection relays.

The following table lists representative product families and applications.

ManufacturerRelay / Product familyMain application
SiemensSIPROTEC 5 7UT85 / 7UT86Transformer differential
SiemensSIPROTEC 5 7UM85Generator protection
SiemensSIPROTEC 5 7SS85Busbar protection
SiemensSIPROTEC 5 7SD seriesLine differential
ABB / Hitachi EnergyRET670Transformer protection
ABB / Hitachi EnergyREG670Generator protection
ABB / Hitachi EnergyREB670Busbar protection
ABB / Hitachi EnergyRED670Line differential protection
SELSEL-487ETransformer differential
SELSEL-400GGenerator protection
SELSEL-487BBusbar protection
SELSEL-411LLine protection including line differential
GE VernovaT60Transformer protection
GE VernovaG60Generator protection
GE VernovaB90Busbar protection
Schneider ElectricMiCOM P64x seriesTransformer differential
Schneider ElectricMiCOM P54x seriesLine differential
Schneider ElectricEasergy / MiCOM protection familiesApplication-dependent protection

Always verify the exact model, hardware configuration, and firmware-supported functions before specifying a relay.

15. Practical Engineering Example: Transformer Differential Protection

Consider a transformer with the following specifications:

ParameterValue
Rated power100 MVA
HV voltage132 kV
LV voltage33 kV
Vector groupDyn11
HV CT ratio500/1 A
LV CT ratio2000/1 A
Frequency50 Hz

Rated HV current:

IHV=437.4AIHV​=437.4A

Rated LV current:

ILV=1749.5AILV​=1749.5A

HV CT secondary current at rated load:

IHV,sec=437.4500=0.875AIHV,sec​=500437.4​=0.875A

LV CT secondary current at rated load:

ILV,sec=1749.52000=0.875AILV,sec​=20001749.5​=0.875A

Therefore, both CTs produce approximately equal secondary current magnitudes at rated transformer load.

The relay must still compensate for the transformer vector group and correctly process the phase relationship.

This example demonstrates the importance of selecting appropriate CT ratios before configuring transformer differential protection.

Engineering note: This is a simplified ratio-matching example. Actual relay configuration must also account for vector group compensation, CT connection, phase sequence, transformer tap range, and manufacturer-specific current normalization.

16. Important Documents for Differential Protection Engineers

For practical engineering work, the following documents should be available:

  1. Transformer or generator nameplate data.
  2. Single-line diagrams.
  3. Protection and metering CT data sheets.
  4. CT excitation curves.
  5. CT burden calculations.
  6. CT secondary wiring diagrams.
  7. Protection relay configuration files.
  8. Differential protection setting calculations.
  9. Relay logic diagrams.
  10. Trip circuit diagrams.
  11. Secondary injection test reports.
  12. End-to-end test reports, where applicable.
  13. Commissioning records.
  14. Disturbance records and event logs.

These documents are important for design, configuration, commissioning, troubleshooting, and maintenance.

At Elec-Engg.com, we provide practical training in power system protection, numerical protection relays, relay configuration, testing, and commissioning.

Our training covers:

  • Transformer differential protection (87T).
  • Generator differential protection (87G).
  • Busbar differential protection (87B).
  • Line differential protection (87L).
  • Restricted earth fault protection (REF).
  • CT selection, calculations, and testing.
  • Differential protection settings and coordination.
  • SIPROTEC 4 and SIPROTEC 5 configuration.
  • ABB PCM600 and Relion protection relays.
  • Omicron CMC and Test Universe practical testing.

17. Conclusion

Differential protection is one of the fundamental protection principles in modern power systems.

Its effectiveness depends on more than simply comparing currents. Engineers must understand CT selection, CT polarity, CT saturation, restraint characteristics, transformer compensation, communication channels, relay configuration, and practical testing.

A correctly engineered differential protection scheme provides fast, selective, and dependable protection for transformers, generators, busbars, transmission lines, motors, and other important electrical equipment.

For protection engineers, understanding the operating principle is only the beginning. The ability to calculate, configure, test, commission, and troubleshoot differential protection is what makes the knowledge practically valuable.