Motor Protection (ANSI 49, 50, 51, 46, 48, 66)

Motor Starting, Thermal Overload, Locked Rotor, Stall Protection, Phase Unbalance, Earth Fault, Differential Protection, Settings and Testing

1. Introduction

Electric motor protection is an essential part of industrial electrical engineering and power system protection.

Electric motors are widely used in industrial plants, oil and gas facilities, power stations, water treatment plants, mining operations, manufacturing facilities, and other industrial applications.

Motors drive important equipment such as:

  • Pumps.
  • Compressors.
  • Fans and blowers.
  • Conveyors.
  • Crushers.
  • Cooling water systems.
  • Circulation systems.
  • Industrial machinery.

An unexpected motor failure can cause production interruptions, equipment damage, and significant financial losses.

Motor protection systems are designed to detect abnormal electrical and mechanical operating conditions and prevent damage to the motor, driven equipment, and associated electrical system.

Unlike transformer and generator protection, motor protection must pay particular attention to starting conditions, thermal capacity, acceleration time, locked rotor conditions, and frequent starting.

A comprehensive motor protection scheme may include:

  • Thermal overload protection (49).
  • Instantaneous overcurrent protection (50).
  • Time overcurrent protection (51).
  • Earth fault protection (50N/51N).
  • Negative sequence protection (46).
  • Locked rotor protection (48).
  • Excessive starting time protection.
  • Number of starts protection (66).
  • Differential protection (87M).
  • Undercurrent protection (37).
  • Undervoltage protection (27).
  • Overvoltage protection (59).
  • Phase failure protection.
  • RTD temperature monitoring.
  • Mechanical protection interfaces.

Modern numerical motor protection relays combine multiple functions into a single intelligent electronic device (IED).

2. Types of Electric Motors

Before selecting motor protection functions, engineers must understand the motor type and its operating characteristics.

2.1 Induction Motors

Basic Parts of a Three Phase (3-Փ) Squirrel Cage Induction Motor ~ Learning Electrical Engineering

Three-phase induction motors are widely used in industrial applications.

They are generally classified into:

  • Squirrel cage induction motors.
  • Wound rotor induction motors.

The squirrel cage motor is particularly common because of its simple construction, reliability, and relatively low maintenance requirements.

2.2 Synchronous Motors

What is an AC Synchronous Motor? – HECO

Synchronous motors operate at synchronous speed and generally require an excitation system.

They are used in applications requiring:

  • High power ratings.
  • Constant operating speed.
  • Power factor improvement.
  • Large compressors.
  • Industrial drives.

Their protection schemes may include additional functions related to field excitation and loss of synchronism.

3. Basic Motor Electrical Characteristics

Motor protection engineering begins with understanding the motor nameplate.

Important parameters include:

ParameterDescription
Rated powerMotor output power in kW or MW
Rated voltageMotor operating voltage
Rated currentFull-load current
Rated frequencyNormally 50 or 60 Hz
Power factorRated power factor
EfficiencyMotor efficiency
Starting currentCurrent during motor starting
Starting timeTime required to accelerate
Locked rotor currentCurrent when the rotor cannot rotate
Locked rotor timePermissible duration at locked rotor
Service factorAdditional permissible loading where specified
Insulation classThermal insulation classification
Duty cycleOperating and starting duty

These parameters are essential for calculating and configuring motor protection settings.

4. Motor Starting Characteristics

Motor starting is one of the most important considerations in motor protection engineering.

When an induction motor starts, it initially draws a high current because the rotor is stationary.

The starting current may be approximately 5–8 times the rated current for many direct-on-line induction motors, although the actual value depends on motor design.

Helix Website - DynamicStarting

During starting:

  • Motor current is high.
  • Motor speed gradually increases.
  • Slip decreases.
  • Current reduces as the motor accelerates.
  • The motor reaches its normal operating speed.

The protection relay must distinguish between normal starting current and abnormal conditions.

If the overcurrent protection is configured incorrectly, the motor may trip during normal starting.

4.1 Direct-On-Line Starting

In direct-on-line (DOL) starting, the motor is connected directly to the supply voltage.

Advantages:

  • Simple arrangement.
  • Low installation cost.
  • High starting torque.
  • Simple control philosophy.

Disadvantages:

  • High starting current.
  • Voltage dips in the electrical network.
  • Mechanical stress.
  • Possible disturbance to other loads.

4.2 Star-Delta Starting

Star-delta starting reduces the motor winding voltage during the initial starting period.

The motor starts in star connection and changes to delta after reaching a suitable speed.

For an idealized comparison with DOL starting:

  • Starting line current is approximately one-third of DOL starting current.
  • Starting torque is approximately one-third of DOL starting torque.

The motor protection relay must consider the starter configuration and the CT measurement location.

4.3 Soft Starter

A soft starter controls the applied motor voltage during starting.

It reduces:

  • Starting current.
  • Mechanical shock.
  • Voltage dips.

However, the starting torque is also affected by the applied voltage.

4.4 Variable Frequency Drive (VFD)

A variable frequency drive controls motor speed by adjusting supply frequency and voltage.

Motor protection engineering for VFD-fed motors must consider:

  • Harmonics.
  • Frequency-dependent motor cooling.
  • Low-speed operation.
  • Drive current limitations.
  • Motor insulation stress.
  • Bearing currents.
  • Drive protection coordination.

Protection arrangements depend on whether the motor protection relay measures current on the supply side or motor side of the drive.

5. Thermal Overload Protection (ANSI 49)

Thermal overload protection is one of the most important motor protection functions.

Motor overheating can result from:

  • Excessive load.
  • Prolonged starting.
  • Locked rotor.
  • Frequent starting.
  • Phase unbalance.
  • Cooling system failure.
  • High ambient temperature.
  • Mechanical problems.
Motor Protection | PDF

Motor protection relays use thermal models to estimate the motor’s heating condition.

A simplified thermal relationship is:

θ∝I2tθ∝I2t

Where:

  • θθ = Thermal heating effect.
  • II = Motor current.
  • tt = Time.

The actual thermal model is more sophisticated and may consider cooling, thermal time constants, starting conditions, and separate heating characteristics.

Important settings include:

  • Rated motor current.
  • Thermal overload pickup.
  • Thermal time constant.
  • Heating time constant.
  • Cooling time constant.
  • Thermal capacity alarm.
  • Thermal capacity trip.
  • Hot and cold motor characteristics.

Modern numerical relays may also include separate thermal models for stator and rotor heating.

6. Short-Circuit Protection (ANSI 50/51)

Short-circuit protection detects high fault currents in the motor circuit.

Possible faults include:

  • Phase-to-phase short circuits.
  • Three-phase faults.
  • Cable faults.
  • Motor terminal faults.
  • Internal winding faults.

6.1 Instantaneous Overcurrent (50)

Instantaneous overcurrent protection operates when current exceeds a configured high-set threshold.

I>IpickupI>Ipickup​

It provides fast protection against severe short-circuit faults.

6.2 Time Overcurrent (51)

Time overcurrent protection operates when the current exceeds a configured threshold for a specified time.

It may use:

  • Definite-time characteristics.
  • Inverse-time characteristics.
  • Very inverse characteristics.
  • Extremely inverse characteristics.

The settings must be coordinated with:

  • Motor starting current.
  • Motor starting duration.
  • Cable thermal limits.
  • Upstream protection.
  • Downstream protection.
  • Available short-circuit current.

7. Earth Fault Protection (ANSI 50N/51N/64)

Earth faults are common causes of motor insulation damage.

They may occur due to:

  • Winding insulation deterioration.
  • Moisture ingress.
  • Cable insulation failure.
  • Mechanical damage.
  • Terminal box contamination.
  • Excessive thermal stress.

Common earth fault detection methods include:

Residual current measurement

The relay calculates the residual current from the three phase currents.

IE=∣IA+IB+IC∣IE​=∣IA​+IB​+IC​∣

Under balanced conditions, the residual current should be approximately zero.

Core balance CT

A core balance CT surrounds all three phase conductors.

Under normal conditions, the magnetic flux produced by the phase currents cancels.

During an earth fault, residual current flows through the CT and the relay detects the fault.

Neutral CT measurement

For certain motor grounding arrangements, a CT may be installed in the neutral grounding connection.

The earth fault protection sensitivity must be coordinated with the motor grounding method and the minimum expected fault current.

8. Negative Sequence Protection (ANSI 46)

Negative sequence protection detects current unbalance in a three-phase motor.

Possible causes include:

  • Single phasing.
  • Unbalanced supply voltage.
  • Open phase.
  • Unequal phase impedance.
  • Loose connections.
  • Unbalanced winding faults.
Applying Harmonic Solutions to Commercial and Industrial Power

Negative sequence current produces additional rotor heating.

For induction motors, this can result in excessive temperature rise and reduced motor life.

The relay calculates negative sequence current:

I2=13(IA+a2IB+aIC)I2​=31​(IA​+a2IB​+aIC​)

Where:

a=1∠120∘a=1∠120∘

The protection may use:

  • Negative sequence pickup.
  • Definite-time operation.
  • Inverse-time thermal characteristics.
  • Alarm and trip stages.

Negative sequence settings must consider the motor manufacturer’s permissible current unbalance and thermal withstand capability.

9. Locked Rotor Protection (ANSI 48)

A locked rotor condition occurs when the motor rotor cannot rotate despite the application of electrical supply.

Possible causes include:

  • Mechanical blockage.
  • Pump seizure.
  • Compressor problems.
  • Bearing failure.
  • Driven equipment damage.
  • Rotor mechanical defects.

During locked rotor operation:

  • Motor speed remains zero or very low.
  • Current remains high.
  • Rotor heating increases rapidly.
  • Thermal damage can occur.

Locked rotor protection must detect this condition before the motor exceeds its permissible thermal withstand time.

The protection may use:

  • High current detection.
  • Speed supervision.
  • Starting time supervision.
  • Thermal model.
  • Motor acceleration monitoring.

The exact ANSI function designation depends on the relay implementation; ANSI 48 is commonly used for incomplete sequence or excessive starting time, while locked rotor protection is often incorporated into motor starting and stall protection logic.

10. Excessive Starting Time Protection

A motor may draw high starting current for longer than expected if acceleration is delayed.

Possible causes include:

  • Excessive mechanical load.
  • Low supply voltage.
  • Incorrect starter operation.
  • Mechanical blockage.
  • Incorrect motor selection.
  • Faulty driven equipment.

The relay monitors the starting process.

If the motor does not reach its expected operating condition within the configured starting time, the protection operates.

Important settings include:

  • Maximum starting time.
  • Starting current threshold.
  • Starting detection level.
  • Acceleration time.
  • Starting thermal limit.

The starting time must be coordinated with the motor’s hot and cold stall withstand times.

11. Number of Starts Protection (ANSI 66)

Frequent motor starting can cause excessive thermal stress.

This is particularly important for large motors.

The motor manufacturer normally specifies limitations such as:

  • Maximum starts from cold condition.
  • Maximum starts from hot condition.
  • Minimum time between starts.
  • Permissible starts per hour.
Unit 1 electric drive | PPTX

The protection relay counts motor starts and prevents additional starting commands when the configured limits are reached.

For example, the relay may enforce:

  • Maximum two consecutive starts.
  • A minimum cooling period between starts.
  • A specified number of starts per hour.

Actual limits must always come from motor manufacturer’s documentation.

12. Motor Differential Protection (ANSI 87M)

Large and critical motors may use differential protection as their main protection against internal phase faults.

The principle is similar to transformer and generator differential protection.

CTs are installed at both ends of the motor stator winding protection zone.

CT secondary wye point grounding | Eng-Tips

Under normal operating conditions:

Idiff≈0Idiff​≈0

During an internal phase fault:

Idiff>IpickupIdiff​>Ipickup​

The relay detects the imbalance and trips the motor.

Motor differential protection is particularly useful for:

  • Large MV motors.
  • Critical industrial motors.
  • High-value compressor motors.
  • Important pumping systems.
  • Motors with accessible winding terminals at both ends.

Not all motors require differential protection. Its application depends on motor rating, criticality, design, and protection philosophy.

13. Undercurrent Protection (ANSI 37)

Undercurrent protection detects when motor current falls below a configured threshold.

This may indicate:

  • Pump running dry.
  • Loss of mechanical load.
  • Broken coupling.
  • Belt failure.
  • Loss of process fluid.
  • Mechanical disconnection.
Snadná a spolehlivá ochrana čerpadel proti chodu na sucho i v prostředí s nebezpečím výbuchu - ElektroPrůmysl.cz

For example, a centrifugal pump operating without sufficient liquid may experience reduced motor load and current.

The relay detects the reduction in current and generates an alarm or trip.

Undercurrent protection is therefore particularly useful for process protection.

14. Undervoltage Protection (ANSI 27)

Undervoltage protection detects a reduction in supply voltage.

Low voltage can cause:

  • Increased motor current under constant torque conditions.
  • Reduced motor torque.
  • Prolonged acceleration.
  • Motor stalling.
  • Contactor dropout.

For induction motors, electromagnetic torque is approximately proportional to the square of the applied voltage under simplified operating assumptions.

T∝V2T∝V2

Therefore, a significant voltage reduction can reduce available motor torque.

Undervoltage protection settings must consider motor starting and process requirements.

15. Phase Failure and Phase Reversal Protection

Phase failure occurs when one phase of the three-phase supply is lost.

This can result in:

  • Excessive current in the remaining phases.
  • Motor overheating.
  • Reduced torque.
  • Abnormal vibration.
  • Motor damage.

Phase reversal occurs when the phase sequence is incorrect.

This can cause a motor to rotate in the wrong direction.

This is particularly dangerous for:

  • Pumps.
  • Compressors.
  • Conveyors.
  • Fans.
  • Process machinery.

Modern motor protection relays may provide phase sequence and phase failure detection.

16. Motor RTD and Temperature Protection

Large motors are often equipped with embedded resistance temperature detectors (RTDs).

These sensors measure the temperature of important motor components.

Typical monitoring locations include:

  • Stator windings.
  • Bearings.
  • Motor frame.
  • Cooling air.
  • Cooling water.
Electric Machine Design Course Electric Machine Cooling Strategies

Common RTD types include:

  • Pt100.
  • Pt1000.
  • Ni100.

Temperature protection may include:

  • High-temperature alarm.
  • High-high-temperature trip.
  • Bearing temperature alarm.
  • Bearing temperature trip.
  • Sensor failure alarm.

Direct temperature measurement complements the relay’s electrical thermal model.

17. Motor Protection Functions Summary

ANSIProtection functionMain purpose
49Thermal overloadMotor overheating
50Instantaneous overcurrentShort-circuit protection
51Time overcurrentOvercurrent backup
50N/51NEarth faultGround fault protection
46Negative sequenceCurrent unbalance
48Incomplete starting sequenceExcessive starting time
66Starts per hourFrequent starting
87MMotor differentialInternal phase faults
37UndercurrentLoss of load
27UndervoltageLow supply voltage
59OvervoltageExcessive supply voltage
49RTDTemperature monitoringWinding and bearing overheating
47Phase sequence/unbalanceIncorrect phase conditions
51LRLocked rotor/stallMotor stall protection

Note: ANSI device numbering and exact function implementation can vary between relay manufacturers.

18. Motor Protection Relay Manufacturers

Several manufacturers provide dedicated numerical motor protection relays.

Siemens – SIPROTEC 5 7SK85

Numerical motor protection with thermal overload, starting supervision, current protection, earth fault and other motor protection functions. Engineering through DIGSI 5.

ABB / Hitachi Energy – REM615

Motor protection and control relay for industrial motor applications, with thermal, current, earth fault and motor starting protection.

GE Vernova – Multilin 369

Motor management and protection relay with thermal modeling, starting supervision, stall protection, current unbalance and monitoring functions.

Schneider Electric – MiCOM P220

Numerical motor protection for industrial applications, with overload, current, earth fault and other motor protection functions.

SEL – SEL-710

Motor protection with thermal overload, starting supervision, current protection, monitoring and event recording.

Siemens – SIMOCODE pro

Intelligent motor management system for low-voltage motors, providing protection, control, monitoring and communication capabilities.

19. Motor Protection Settings and Engineering Calculations

Motor protection settings must be calculated using the actual motor nameplate and manufacturer data.

Consider the following example.

ParameterValue
Motor rated power1,000 kW
Rated voltage6.6 kV
Frequency50 Hz
Power factor0.88
Efficiency95%
Starting methodDirect-on-line
Starting current6 × rated current
Starting time8 seconds

19.1 Rated Current Calculation

The three-phase motor input power is:

Pin=3VIcos⁡ϕPin​=3​VIcosϕ

Considering efficiency:

I=Pout3Vcos⁡ϕηI=3​VcosϕηPout​​

Substituting:

I=1000×1033×6600×0.88×0.95I=3​×6600×0.88×0.951000×103​

I=104.9AI=104.9A​

19.2 Starting Current

Assuming a starting current of six times rated current:

Istart=6×104.9Istart​=6×104.9

Istart=629.4AIstart​=629.4A​

This is the approximate starting current under the assumed conditions.

19.3 Protection Engineering Considerations

The engineer must verify:

  • Motor thermal withstand curve.
  • Hot and cold starting curves.
  • Starting time.
  • Locked rotor current.
  • CT ratio.
  • Overcurrent settings.
  • Earth fault sensitivity.
  • Thermal model.
  • Starts-per-hour limitation.
  • Cable thermal withstand.
  • Coordination with upstream protection.

These example calculations are preliminary engineering values, not final relay settings.

20. Motor Protection Testing and Commissioning

Testing is essential to ensure that motor protection functions operate correctly.

20.1 Initial Inspection

  • Verify motor nameplate data.
  • Verify CT ratios.
  • Verify CT polarity.
  • Verify VT connections where applicable.
  • Check relay configuration.
  • Check binary inputs and outputs.
  • Verify trip circuit wiring.

20.2 Thermal Overload Testing

  • Rated current verification.
  • Thermal pickup.
  • Thermal alarm.
  • Thermal trip.
  • Hot and cold thermal model.
  • Thermal memory reset.

20.3 Overcurrent Testing

  • Instantaneous pickup.
  • Definite-time operation.
  • Inverse-time characteristic.
  • Phase fault simulation.
  • Coordination verification.

20.4 Earth Fault Testing

  • Residual current measurement.
  • Core balance CT operation.
  • Earth fault pickup.
  • Earth fault time delay.
  • Trip and alarm verification.

20.5 Starting and Locked Rotor Testing

  • Motor starting detection.
  • Starting current supervision.
  • Starting time supervision.
  • Locked rotor simulation.
  • Excessive starting time.
  • Stall protection.

20.6 Negative Sequence Testing

  • Phase current unbalance.
  • Negative sequence calculation.
  • Pickup verification.
  • Thermal characteristic.

20.7 Additional Tests

  • Undercurrent.
  • Undervoltage.
  • RTD temperature inputs.
  • Starts-per-hour logic.
  • Differential protection where applicable.
  • Circuit breaker trip.
  • Motor control interlocking.
  • SCADA communication.

20.8 Disturbance and Event Analysis

After testing, engineers should review:

  • Event records.
  • Fault records.
  • Thermal capacity measurements.
  • Starting current trends.
  • Trip indications.
  • Relay oscillography.

This information is particularly useful when investigating repeated motor trips.

21. Practical Engineering Case Study

Consider a 6.6 kV industrial motor supplying a critical process pump.

ParameterValue
Rated power1,000 kW
Rated voltage6.6 kV
Rated current104.9 A
Starting methodDOL
Starting current6 × rated
Starting time8 seconds
ApplicationCritical process pump
ProtectionNumerical motor protection relay

The protection engineering process should include:

  1. Review the motor nameplate.
  2. Obtain motor hot and cold thermal curves.
  3. Verify the starting current and acceleration time.
  4. Select the CT ratio.
  5. Configure thermal overload protection.
  6. Configure short-circuit protection.
  7. Configure earth fault protection.
  8. Configure negative sequence protection.
  9. Configure locked rotor and starting supervision.
  10. Configure starts-per-hour protection.
  11. Configure undercurrent protection for pump load supervision.
  12. Configure RTD temperature monitoring.
  13. Verify the motor starter and trip circuits.
  14. Perform secondary injection tests.
  15. Verify actual starting performance during commissioning.

Example abnormal condition: Pump mechanical blockage

Assume the pump becomes mechanically blocked while the motor is running.

The motor current increases significantly, but the rotor cannot maintain normal rotation.

The motor protection relay identifies the abnormal current and stall condition.

Depending on the configured protection logic, it initiates a trip before the motor thermal withstand limit is exceeded.

This prevents severe motor damage and reduces the risk of an extended industrial process interruption.

22. Common Motor Protection Engineering Mistakes

Common mistakes include:

  1. Using incorrect motor rated current.
  2. Incorrect CT ratio configuration.
  3. Setting overcurrent pickup too low.
  4. Ignoring starting current.
  5. Incorrect starting time setting.
  6. Not checking hot and cold stall curves.
  7. Incorrect thermal time constant.
  8. Ignoring starts-per-hour limitations.
  9. Incorrect earth fault CT connection.
  10. Inadequate negative sequence protection.
  11. Incorrect RTD configuration.
  12. Not considering VFD operating characteristics.
  13. Incorrect motor trip logic.
  14. Failure to coordinate with upstream protection.
  15. Not testing the complete motor starting sequence.

One particularly important engineering principle is that motor protection must protect against abnormal starting and operating conditions without unnecessarily interrupting healthy motor operation.

23. Conclusion

Motor protection is a specialized area of industrial power system protection.

A reliable motor protection scheme must consider electrical faults, thermal limits, starting characteristics, mechanical loading, insulation condition, and process requirements.

Engineers must understand:

  • Motor starting characteristics.
  • Thermal overload protection.
  • Short-circuit protection.
  • Earth fault protection.
  • Negative sequence protection.
  • Locked rotor and stall protection.
  • Starts-per-hour limitations.
  • Motor differential protection.
  • RTD temperature monitoring.
  • Motor protection relay configuration.
  • Secondary injection testing.

Modern motor protection relays provide advanced thermal models, starting supervision, fault recording, communication, and motor management capabilities.

However, correct protection depends on accurate motor data, engineering calculations, appropriate settings, and comprehensive commissioning.

24. Practical Motor Protection Training by Elec-Engg

At Elec-Engg, we provide practical training and technical resources covering industrial motor protection, numerical protection relays, relay testing, and substation automation.

Our training includes practical applications of:

  • Siemens SIPROTEC 5.
  • Siemens SIMOCODE.
  • ABB REM615.
  • GE Multilin 369.
  • Schneider Electric MiCOM.
  • SEL motor protection relays.
  • OMICRON CMC and Test Universe.

Topics include motor protection settings, thermal models, starting supervision, fault analysis, relay configuration, and commissioning.

Trainer: Dr. Saeed Roostaee – Electrical Engineering

Our objective is to help protection, commissioning, operation, and maintenance engineers develop practical knowledge that can be applied to real industrial projects.

Explore our technical resources and training programs:

https://elec-engg.com

  1. Three-phase induction motor cross-section.
  2. Synchronous motor construction.
  3. Motor starting current and acceleration curve.
  4. DOL motor starter diagram.
  5. Star-delta starter power circuit.
  6. Soft starter diagram.
  7. VFD motor protection arrangement.
  8. Thermal overload characteristic.
  9. Motor earth fault protection circuit.
  10. Negative sequence protection diagram.
  11. Locked rotor protection characteristic.
  12. Motor differential protection diagram.
  13. RTD temperature monitoring.
  14. Siemens SIPROTEC 5 7SK85.
  15. ABB REM615.
  16. GE Multilin 369.
  17. OMICRON motor protection testing.