Generator Protection (ANSI 87G)

Generator Differential Protection, Stator Earth Fault, Rotor Earth Fault, Loss of Excitation, Reverse Power, Negative Sequence, Overexcitation and Generator Protection Testing

1. Introduction

Generator protection is one of the most important areas of power system protection engineering.

Synchronous generators are critical assets in power plants, industrial facilities, hydroelectric stations, thermal power stations, gas turbine plants, and renewable energy installations.

A generator converts mechanical energy into electrical energy. During operation, it is exposed to several electrical and mechanical abnormal conditions that can cause serious damage if not detected and cleared properly.

Generator faults may affect:

  • Stator windings.
  • Rotor windings.
  • Generator magnetic core.
  • Excitation system.
  • Bearings and cooling systems.
  • Generator terminals.
  • Associated step-up transformers.
  • Power system stability.

Unlike ordinary feeders, generators require a comprehensive protection scheme because they have unique operating characteristics and abnormal operating conditions.

A complete generator protection system typically includes:

  • Generator differential protection (87G).
  • Stator earth fault protection (64G).
  • Rotor earth fault protection (64R).
  • Loss of excitation protection (40).
  • Reverse power protection (32).
  • Negative sequence protection (46).
  • Overcurrent protection (50/51).
  • Overvoltage protection (59).
  • Undervoltage protection (27).
  • Overfrequency and underfrequency protection (81O/81U).
  • Overexcitation protection (24).
  • Thermal overload protection (49).
  • Inadvertent energization protection (50/27).
  • Pole slipping protection (78).
  • Generator breaker failure protection (50BF).

Modern numerical generator protection relays integrate many of these functions into a single IED.

Common manufacturers include Siemens, ABB/Hitachi Energy, GE Vernova, SEL, Schneider Electric, and Basler.

2. Generator Protection System Architecture

A typical generator protection scheme consists of several protection functions working together.

The protection system receives electrical measurements from:

  • Generator phase CTs.
  • Generator neutral CTs.
  • Generator voltage transformers.
  • Neutral grounding equipment.
  • Excitation system measurements.
  • Auxiliary contacts and protection signals.

Depending on the generator design, additional inputs may include temperature sensors, bearing protection, cooling system alarms, and mechanical protection signals.

The generator protection relay evaluates these measurements and initiates appropriate actions.

Possible actions include:

  1. Generator circuit breaker tripping.
  2. Generator field breaker tripping.
  3. Excitation suppression.
  4. Prime mover shutdown.
  5. Turbine trip.
  6. Alarm generation.
  7. Backup protection initiation.

The actual trip philosophy depends on generator type, plant design, and protection coordination.

09-1 Machine Prot. Exercises.ppt

3. Generator Differential Protection (ANSI 87G)

Generator differential protection is the main protection function against internal phase faults in the stator winding.

It operates according to Kirchhoff’s Current Law.

Under normal operating conditions, the current entering the generator stator protection zone should approximately equal the current leaving it.

Idiff=∣I1−I2∣Idiff​=∣I1​−I2​∣

Where:

  • I1I1​ = Current measured at one boundary of the protected zone.
  • I2I2​ = Current measured at the opposite boundary.
  • IdiffIdiff​ = Differential operating current.

During normal operation:

Idiff≈0Idiff​≈0

During an internal phase fault, the current balance is disturbed.

The differential relay detects the difference and initiates generator tripping.

3.1 Protected Zone

The generator differential protection zone is defined by the locations of the CTs.

Typically, CTs are installed at:

  • Generator terminals.
  • Generator neutral connections.

The protected zone includes the stator winding between these CT locations.

The exact protection coverage depends on the generator arrangement and CT installation.

3.2 Differential Protection Characteristics

Modern numerical generator differential relays use percentage-biased differential protection.

The relay evaluates:

  • Differential current.
  • Restraint current.
  • Minimum pickup.
  • Percentage bias.
  • CT saturation behavior.

Idiff>Ipickup+SIrestIdiff​>Ipickup​+SIrest​

Where SS represents the configured bias slope.

This improves stability during external faults and measurement errors.

3.3 Important Limitation

Conventional generator differential protection may not detect all stator earth faults, particularly faults very close to the neutral point.

This is why separate stator earth fault protection is required.

4. Stator Earth Fault Protection (ANSI 64G)

Stator earth faults are among the most important generator faults.

They may occur because of:

  • Insulation deterioration.
  • Winding contamination.
  • Thermal stress.
  • Mechanical vibration.
  • Moisture ingress.
  • Insulation aging.
  • Manufacturing defects.
08_C_3_Basis Stator Earth Fault Protection.ppt

The protection method depends on the generator neutral grounding arrangement.

Common arrangements include:

  • High-resistance grounding.
  • Low-resistance grounding.
  • Distribution transformer grounding.
  • Grounding through a neutral resistor.

4.1 Neutral Overvoltage Protection (59N)

Neutral overvoltage protection detects earth faults by monitoring the voltage between the generator neutral and earth.

Under healthy conditions, the neutral voltage is normally close to its expected reference value.

During an earth fault, the neutral voltage changes.

The protection relay detects this change and initiates an alarm or trip.

4.2 Neutral Overcurrent Protection (50N/51N)

When the generator neutral is grounded through a resistor or grounding transformer, a neutral CT can measure earth fault current.

The relay operates when the measured current exceeds the configured threshold.

4.3 100% Stator Earth Fault Protection

Conventional stator earth fault protection may leave a portion of the stator winding close to the neutral point insufficiently protected.

To improve coverage, dedicated 100% stator earth fault protection methods are used.

Common methods include:

  • Third harmonic undervoltage protection.
  • Third harmonic voltage differential protection.
  • Low-frequency injection methods.
What everyone should know about ground fault protection

Third harmonic protection

Generators may produce third harmonic voltages during normal operation.

The distribution of third harmonic voltage between the generator terminals and neutral changes during certain stator earth faults.

Numerical relays use these characteristics to detect faults near the neutral point.

The effectiveness depends on generator design and operating conditions.

Low-frequency injection

Some protection systems inject a low-frequency signal into the generator neutral circuit.

Changes in the measured response can indicate insulation deterioration or an earth fault.

This technique can provide stator earth fault coverage even under conditions where third harmonic methods are less suitable.

5. Rotor Earth Fault Protection (ANSI 64R)

The rotor winding of a synchronous generator is normally electrically isolated from earth.

A first earth fault on the rotor field circuit may not immediately cause a high fault current because the field circuit is generally ungrounded.

However, a second earth fault at another location can create a short-circuit path through the rotor structure.

This may cause:

  • Rotor winding damage.
  • Localized overheating.
  • Magnetic imbalance.
  • Mechanical vibration.
  • Severe rotor damage.
06_C_3_Rotor_Earth_Fault_Protection.ppt

Rotor earth fault protection detects insulation failure between the field winding and earth.

Common methods include:

  • DC injection.
  • AC injection.
  • Voltage divider monitoring.
  • Insulation resistance monitoring.

Modern generator protection systems may provide continuous rotor insulation monitoring.

A first earth fault normally initiates an alarm, while the final trip response depends on the generator manufacturer’s recommendations and plant protection philosophy.

6. Loss of Excitation Protection (ANSI 40)

Loss of excitation occurs when the generator loses its required field excitation.

Possible causes include:

  • Excitation system failure.
  • AVR malfunction.
  • Field breaker opening.
  • Excitation circuit failure.
  • Loss of DC supply.
  • Open-circuit field winding.
Loss of Field (Excitation) of Generator-Its Impact, protection practices and tripping modes-A comprehensive Overview

When excitation is lost, the generator may start operating as an induction generator by drawing reactive power from the electrical network.

This can cause:

  • Increased stator current.
  • Rotor overheating.
  • Reduced system voltage.
  • Power system instability.
  • Pole slipping.
  • Damage to the generator.

6.1 Operating Principle

Loss of excitation protection commonly uses impedance measurement.

The relay monitors the apparent impedance seen from the generator terminals.

A loss of excitation causes the measured impedance to enter a predefined operating region in the R-X plane.

Typical protection characteristics use offset mho circles.

Important settings include:

  • Zone 1 impedance.
  • Zone 2 impedance.
  • Time delay.
  • Directional supervision.
  • Under-voltage supervision, where applicable.

The exact characteristic depends on the generator capability curve and system conditions.

7. Reverse Power Protection (ANSI 32)

Reverse power protection detects when a generator begins absorbing active power from the electrical network instead of supplying it.

This condition is particularly important for steam turbines, gas turbines, and hydro generators.

(PDF) Enhancing the Performance of Reverse Power Relay for Generator Protection

For example, if the mechanical input to a generator is lost while the generator remains connected to the grid, the generator may start operating as a motor.

This can cause serious mechanical problems.

Examples include:

  • Steam turbine windage heating.
  • Mechanical stress.
  • Excessive fuel consumption.
  • Turbine damage.
  • Unwanted operating conditions.

The reverse power relay measures active power and detects power flow in the reverse direction.

A simplified operating condition is:

P<−PsetP<−Pset​

Where:

  • PP = Measured active power.
  • PsetPset​ = Configured reverse power threshold.

The protection usually includes a time delay to avoid operation during transient power reversals.

Settings must be selected according to the turbine manufacturer’s requirements.

8. Negative Sequence Protection (ANSI 46)

Negative sequence currents occur when the three-phase currents become unbalanced.

Possible causes include:

  • Unbalanced loads.
  • Phase-to-phase faults.
  • Single-phase faults.
  • Open conductor conditions.
  • Unbalanced system voltage.
  • Unequal phase impedances.
Protecciones

Negative sequence currents produce a magnetic field rotating opposite to the rotor.

This induces currents in the rotor body, damper winding, and other rotor components.

The resulting heating can cause serious rotor damage.

The protection relay calculates negative sequence current:

I2=13(IA+a2IB+aIC)I2​=31​(IA​+a2IB​+aIC​)

Where:

a=1∠120∘a=1∠120∘

The generator negative sequence thermal capability is commonly expressed using:

I22t=KI22​t=K

Where:

  • I2I2​ = Negative sequence current in per unit.
  • tt = Time.
  • KK = Generator-specific negative sequence withstand constant.

The relay setting must be coordinated with the generator manufacturer’s negative sequence capability.

9. Overexcitation Protection (ANSI 24)

Overexcitation occurs when the magnetic flux in the generator or associated transformer exceeds its normal design limit.

The main parameter is the voltage-to-frequency ratio:

VffV​

An increase in voltage or a decrease in frequency can result in excessive magnetic flux.

How Does Power Transformer Saturate? – Voltage Disturbance

Possible consequences include:

  • Magnetic core saturation.
  • Increased magnetizing current.
  • Core overheating.
  • Insulation deterioration.
  • Damage to the generator or step-up transformer.

The relay measures voltage and frequency and calculates the V/Hz ratio.

Protection normally uses an inverse-time characteristic with an additional high-set stage, depending on the equipment withstand capability.

10. Generator Overcurrent Protection (ANSI 50/51)

Generator overcurrent protection provides backup protection against excessive current.

It may operate during:

  • External phase faults.
  • Generator terminal faults.
  • Overload conditions.
  • Failure of primary protection.
  • Abnormal operating conditions.

However, generator overcurrent protection must be coordinated carefully because synchronous generators have a limited short-circuit current contribution.

Depending on the generator and excitation system, fault current may decrease significantly after the initial fault period.

Modern generator protection systems may use voltage-restrained or voltage-controlled overcurrent elements.

11. Generator Undervoltage and Overvoltage Protection (ANSI 27/59)

Voltage protection monitors generator terminal voltage.

Undervoltage protection (27) detects voltage reduction caused by:

  • Severe system faults.
  • Loss of excitation.
  • Abnormal network conditions.
  • Voltage regulator problems.

Overvoltage protection (59) detects excessive generator terminal voltage caused by:

  • AVR malfunction.
  • Sudden load rejection.
  • Incorrect excitation control.
  • Abnormal operating conditions.

The settings should be coordinated with generator operating limits and power system requirements.

12. Overfrequency and Underfrequency Protection (ANSI 81O/81U)

Generator frequency protection detects abnormal system frequency.

Overfrequency can occur due to:

  • Sudden load rejection.
  • Excessive mechanical input.
  • Incorrect governor operation.

Underfrequency can occur due to:

  • Generation deficiency.
  • Severe system disturbances.
  • Islanding conditions.
  • Load-generation imbalance.
Generator Operation with Abnormal Frequency (Under/Over)-Its Root Cause, impact, protection practices and tripping Modes-An Extract from Routine Study

Frequency protection settings must consider turbine-generator operating limitations and grid code requirements.

13. Thermal Overload Protection (ANSI 49)

Generator thermal overload protection protects the stator winding against excessive heating.

The heating can be caused by:

  • Prolonged overload.
  • Cooling system failure.
  • High ambient temperature.
  • Cooling gas or water problems.
  • Abnormal current conditions.

Numerical relays may use thermal replica models based on measured current and configured thermal constants.

Some generator protection systems also receive direct temperature measurements from embedded winding RTDs.

14. Pole Slipping Protection (ANSI 78)

Pole slipping occurs when a synchronous generator loses synchronism with the electrical network.

Possible causes include:

  • Severe network faults.
  • Loss of excitation.
  • Large disturbances.
  • Weak system connections.
  • Improperly cleared external faults.

Pole slipping can cause:

  • High mechanical torque.
  • Large electrical current.
  • Severe rotor and stator stresses.
  • Instability in the interconnected power system.

Out-of-step protection detects the impedance trajectory and determines whether the generator is losing synchronism.

The protection philosophy may require generator tripping at an appropriate electrical separation point.

15. Inadvertent Energization Protection (ANSI 50/27)

Inadvertent energization occurs when a generator is accidentally connected to the electrical network while stationary or at an inappropriate operating condition.

Possible causes include:

  • Circuit breaker malfunction.
  • Incorrect switching.
  • Control circuit failure.
  • Operator error.
  • Incorrect interlocking.

This can result in severe rotor and stator heating.

Inadvertent energization protection commonly combines current and voltage supervision to detect the abnormal condition.

16. Generator Protection Functions Summary

The following table summarizes the major generator protection functions.

ANSIProtection functionMain purpose
87GGenerator differentialInternal phase faults
64GStator earth faultStator insulation faults
64RRotor earth faultRotor field insulation faults
40Loss of excitationField excitation failure
32Reverse powerMotoring condition
46Negative sequenceUnbalanced current
50/51OvercurrentPhase overcurrent backup
27UndervoltageLow terminal voltage
59OvervoltageHigh terminal voltage
24OverexcitationExcessive V/Hz
49Thermal overloadExcessive heating
81OOverfrequencyHigh frequency
81UUnderfrequencyLow frequency
78Pole slippingLoss of synchronism
50BFBreaker failureBreaker fails to interrupt
50/27Inadvertent energizationAccidental generator energization

Note: ANSI device numbers describe protection functions, while the implementation and available elements vary by relay manufacturer.

17. Generator Protection Relay Manufacturers

Several manufacturers provide comprehensive numerical generator protection solutions.

Siemens – SIPROTEC 5 7UM85

Comprehensive generator protection for synchronous generators, including differential, stator earth fault, rotor earth fault, loss of excitation and other generator protection functions. Engineering through DIGSI 5.

ABB / Hitachi Energy – REG670

Advanced generator protection and monitoring for large synchronous generators, with extensive protection and control functions.

GE Vernova – Multilin G60

Comprehensive generator protection with differential, loss of excitation, reverse power, negative sequence and other protection elements.

SEL – SEL-700G

Generator protection with integrated protection, measurement, event recording and monitoring functions.

Schneider Electric – MiCOM P343

Generator protection relay offering differential and associated generator protection functions, depending on the model and configuration.

Basler Electric – BE1-11g

Generator protection solution for generator applications, with integrated electrical protection and monitoring functions.

18. Generator Protection Settings and Engineering

Generator protection settings require detailed engineering studies.

Important information includes:

  • Generator rated power.
  • Rated voltage.
  • Rated current.
  • Rated power factor.
  • Generator reactances.
  • Short-circuit capability.
  • Neutral grounding arrangement.
  • CT and VT ratios.
  • Generator capability curve.
  • Excitation system characteristics.
  • Turbine operating limitations.
  • Grid connection requirements.

For example, consider a 50 MVA generator operating at 11 kV.

The rated current is:

IG=S3×VIG​=3​×VS​

IG=50×1063×11×103IG​=3​×11×10350×106​

IG=2624.3AIG​=2624.3A

This rated current is an important starting point for CT selection and generator protection engineering.

However, individual protection functions require additional calculations and equipment-specific information.

19. Generator Protection Testing and Commissioning

Generator protection commissioning requires more than checking whether the relay trips.

Each protection element must be tested according to its operating principle and configured characteristic.

19.1 Generator Differential Testing

  • Differential pickup.
  • Percentage bias characteristic.
  • Operating current.
  • Restraint current.
  • Internal fault simulation.
  • External fault stability.

19.2 Stator Earth Fault Testing

  • Neutral overvoltage pickup.
  • Neutral overcurrent pickup.
  • Stator earth fault coverage.
  • Third harmonic protection, where applicable.
  • Low-frequency injection system checks, where applicable.

19.3 Rotor Earth Fault Testing

  • Insulation monitoring.
  • First earth fault detection.
  • Alarm operation.
  • Trip logic verification, where applicable.

19.4 Loss of Excitation Testing

  • Impedance measurement.
  • R-X characteristic.
  • Zone operation.
  • Time delay.
  • Directional supervision.

19.5 Reverse Power Testing

  • Active power measurement.
  • Power direction.
  • Reverse power pickup.
  • Time delay.
  • Trip output.

19.6 Negative Sequence Testing

  • Negative sequence current calculation.
  • Pickup verification.
  • Thermal characteristic.
  • Alarm and trip stages.

19.7 Overexcitation Testing

  • Voltage measurement.
  • Frequency measurement.
  • V/Hz calculation.
  • Inverse-time characteristic.
  • High-set stage.

19.8 Final Functional Testing

  • Trip matrix.
  • Generator breaker trip.
  • Field breaker trip.
  • Turbine trip.
  • Alarm and indication.
  • Disturbance recording.
  • Event recording.
  • SCADA communication.

The complete trip philosophy must be checked against the approved plant protection design.

20. Practical Generator Protection Case Study

Consider a synchronous generator with the following characteristics:

ParameterValue
Rated power50 MVA
Rated voltage11 kV
Frequency50 Hz
Power factor0.85
Generator typeSynchronous
Neutral groundingHigh-resistance grounding
Protection relayNumerical multifunction relay
Generator differentialANSI 87G

The engineering process should include:

  1. Calculate rated generator current.
  2. Select appropriate generator CTs.
  3. Verify CT polarity and ratio.
  4. Configure generator differential protection.
  5. Calculate stator earth fault protection settings.
  6. Configure rotor earth fault monitoring.
  7. Calculate loss of excitation settings using the generator capability curve.
  8. Configure reverse power protection based on turbine requirements.
  9. Calculate negative sequence settings using generator withstand data.
  10. Configure V/Hz protection.
  11. Verify all protection trip and alarm matrices.
  12. Perform secondary injection testing.
  13. Verify generator breaker and field breaker tripping.
  14. Review disturbance records and event reports.

Example fault scenario

Assume an internal phase-to-phase fault occurs within the generator stator winding.

The generator differential protection detects the current imbalance and issues a trip command.

Depending on the plant trip philosophy, the sequence may include:

  • Generator circuit breaker opening.
  • Field breaker opening.
  • Excitation suppression.
  • Turbine trip.
  • Alarm and event recording.

The objective is to isolate the generator from the power system and minimize equipment damage.

21. Conclusion

Generator protection is a specialized and comprehensive area of power system protection engineering.

Unlike conventional feeder protection, generator protection must consider electrical, thermal, magnetic, mechanical, and stability-related operating conditions.

A reliable generator protection scheme requires proper coordination between:

  • Generator differential protection.
  • Stator earth fault protection.
  • Rotor earth fault protection.
  • Loss of excitation.
  • Reverse power.
  • Negative sequence.
  • Overexcitation.
  • Voltage and frequency protection.
  • Thermal protection.
  • Pole slipping.
  • Circuit breaker failure protection.

Modern numerical relays provide powerful tools for implementing these functions, but successful protection depends on understanding the generator’s operating characteristics and correctly configuring and testing each protection element.

22. Practical Generator Protection Training by Elec-Engg

At Elec-Engg, we provide technical training and engineering resources for power system protection, generator protection, numerical relays, and substation automation.

Our practical training topics include:

  • Generator protection fundamentals.
  • Generator differential protection.
  • Stator and rotor earth fault protection.
  • Loss of excitation.
  • Reverse power protection.
  • Negative sequence protection.
  • Generator protection settings.
  • Numerical relay configuration.
  • Disturbance analysis.
  • OMICRON relay testing.
  • Practical applications of Siemens, ABB, GE, Schneider and other protection relays.

Trainer: Dr. Saeed Roostaee – Electrical Engineering

We focus on practical engineering knowledge that helps protection, commissioning, operation, and maintenance engineers understand real-world generator protection applications.

Explore our technical resources and training programs:

https://elec-engg.com

  1. Complete generator protection single-line diagram.
  2. Generator differential protection connection.
  3. Stator earth fault protection.
  4. 100% stator earth fault third harmonic principle.
  5. Rotor earth fault protection.
  6. Loss of excitation R-X characteristic.
  7. Reverse power protection diagram.
  8. Negative sequence protection waveform.
  9. V/Hz protection characteristic.
  10. Generator capability curve.
  11. Pole slipping impedance trajectory.
  12. Siemens SIPROTEC 5 7UM85.
  13. ABB REG670.
  14. GE Multilin G60.
  15. OMICRON generator relay testing setup.