Advanced Protection Relay Calculator

Three-phase voltage and current analysis, phasors, symmetrical components and relay-related quantities.

VALUE REFERENCE
Engineering note: Enter phase-to-neutral quantities as phasors unless you deliberately select another measurement convention. Sequence components require magnitude and angle. Confirm relay polarity, phase rotation, CT/VT ratios and manufacturer definitions before using results for settings or commissioning.

Voltage inputs

Phase-to-neutral RMS values · editable phasor magnitudes and angles

VA VB VC

Current inputs

RMS values · primary/secondary reference follows the selector above

IA IB IC

Instrument transformer ratios

For LL input mode, symmetrical components are calculated only after converting the line voltages to a consistent phase-voltage set using the assumed ABC sequence.

Base values (optional)

Used for per-unit conversion. Base voltage is line-to-line RMS; base power is three-phase VA.

Phase / Phasor View

Voltage and current phase vectors are linked to the editable magnitudes and angles above. All values follow the selected primary or secondary reference.

Combined phasor view

Voltage and current vectors are independently normalized for visibility; this is not a common magnitude scale.

Signal / Time-Domain View

Voltage and current waveforms are reconstructed from the same phasors shown above. The chart displays two cycles, with voltage and current using independent vertical scales.

Three-phase voltage and current waveforms

VA, VB, VC and IA, IB, IC · two cycles

RMS values calculated from waveform samples

RMS is calculated from the generated time-domain samples over two complete cycles. Values follow the selected SECONDARY reference.

ChannelRMS valueSampled peakUnit
VA——V
VB——V
VC——V
IA——A
IB——A
IC——A

These are reconstructed ideal steady-state sinusoidal samples, not RMS values extracted from a COMTRADE disturbance record.

Enter measurements and select Calculate all parameters.

Calculated voltage phasors

Calculated current phasors

Calculated impedance on R-X plane

Calculate the selected loop impedance to plot its point.

Overcurrent pickup assessment

Calculate to see pickup multiple.

IEC inverse-time estimate

Enter pickup setting and calculate.

Uses IEC 60255 curve equations: SI 0.14/(M^0.02−1), VI 13.5/(M−1), EI 80/(M²−1), multiplied by TMS. This is an idealized estimate, not a relay-specific guarantee.

Distance protection impedance

Calculate to see apparent impedance.

Ground-loop estimate uses Z = Vphase / [Iphase + k0 × 3I0]. Verify whether your relay uses k0, (Z0−Z1)/(3Z1), or another manufacturer-specific compensation definition. This simplified calculator does not implement all distance relay algorithms.

Protection characteristic graphing

Interactive IEC inverse-time curves for phase overcurrent and earth-fault elements, plus an R-X plane view of illustrative distance zones. Curves update when settings change.

Time-current characteristics (TCC)

Log-log axes · IEC characteristic with the measured phase-current operating point overlaid

Phase 51 Earth fault 51N Definite-time stages
Move over the graph to inspect a point.

Distance protection R-X characteristics

Illustrative forward mho zone reach and quadrilateral zones, in secondary ohms

Zone 1 Zone 2 Zone 3 Quadrilateral
Enter zone reaches to update the R-X diagram.

Time-domain fault laboratory

Generate sampled three-phase signals from a configurable simplified sequence-network model. The generated samples feed the virtual relay in the next tab.

Single-line network model

Set the source, transformer, line and load beside the network sketch. The derived network uses Z2 = Z1 as a simplified assumption; Z0 remains separately configurable below.

SOURCETRANSFORMERLINELOAD Ssc · X/R · VMVA · uk%Length · R/XMW · Mvar
Fault-lab value reference
Relay-side equivalent values are calculated from the configured CT and VT ratios.

Network parameters

Source and transformer impedances are referred to the source-voltage side. The load sets the prefault current. This is a simplified steady-state equivalent, not a complete load-flow or EMT model.

System and source model

Fault configuration

If the network checkbox is disabled, manual Z1 and Z2 are used. Z0 is manually configured in either mode. The network equivalent assumes Z2 = Z1 and does not include transformer vector-group compensation, load-flow voltage drops, line shunt capacitance or a full EMT model.

Generated current waveforms (relay secondary)

IA · IB · IC
Generate a scenario to view waveform and fault quantities.

Generated voltage waveforms (VT secondary)

Virtual protection relay

SIPROTEC 5-inspired training front panel with a simulated LCD, status LEDs, binary I/O indications and protection operation. This is an original Elec-Engg educational interface, not Siemens software or a device replica.

ELEC-ENGG.COMADVANCED PROTECTION RELAY · TRAINING DEVICE
DEVICE OVERVIEW50 Hz · SIM
Ready. Generate a fault record and run the relay simulation.
Page 1/4ENTER: SELECT · ESC: BACK
RUN
ERROR
PICKUP
TRIP
ALARM
Binary I/O statusBI1 · 52a BI2 BO1 TRIP OFF52a BREAKER CLOSED
F1F2F3F4F5F6F7F8F9

BI1 is assigned to the circuit-breaker 52a status contact (active when the simulated breaker is closed). BI2 remains a user-operated demonstration input.

Training device profile

The selected family is a training context only. The active calculation engine below currently implements phase overcurrent, residual earth-fault overcurrent and negative-sequence current elements. Other protection functions are planned, not implied by the selected profile.

Phase overcurrent 50/51

Earth-fault 50N/51N

Negative sequence 46

This first-stage 46 model uses a negative-sequence RMS pickup and definite-time delay. Generator-specific I2²t thermal memory and cooling are reserved for a later validated model.

Breaker model

Relay event timeline

No simulation run yet.

COMTRADE disturbance record reader

Load a matching CFG file and ASCII DAT file to inspect channel definitions, engineering values and sampled waveforms. Parsing is performed locally in your browser; files are not uploaded to the website server.

Waiting for CFG and DAT files.

COMTRADE analog channels

Supported DAT encodings: ASCII, BINARY, BINARY32 and FLOAT32 with CFG channel scaling and sample timestamps. Some vendor extensions and unusual legacy-format variants may require additional compatibility work. The parser reports unsupported or inconsistent records rather than silently treating them as valid. You can map three analog current channels into the virtual relay; verify that the selected channels are correctly scaled and expressed in the same units as the relay pickup settings.

Leave a Comment

Your email address will not be published. Required fields are marked *

Scroll to Top