Advanced Protection Relay Calculator
Three-phase voltage and current analysis, phasors, symmetrical components and relay-related quantities.
Voltage inputs
Phase-to-neutral RMS values · editable phasor magnitudes and angles
Current inputs
RMS values · primary/secondary reference follows the selector above
Instrument transformer ratios
For LL input mode, symmetrical components are calculated only after converting the line voltages to a consistent phase-voltage set using the assumed ABC sequence.
Base values (optional)
Used for per-unit conversion. Base voltage is line-to-line RMS; base power is three-phase VA.
Phase / Phasor View
Voltage and current phase vectors are linked to the editable magnitudes and angles above. All values follow the selected primary or secondary reference.
Combined phasor view
Voltage and current vectors are independently normalized for visibility; this is not a common magnitude scale.
Signal / Time-Domain View
Voltage and current waveforms are reconstructed from the same phasors shown above. The chart displays two cycles, with voltage and current using independent vertical scales.
Three-phase voltage and current waveforms
RMS values calculated from waveform samples
RMS is calculated from the generated time-domain samples over two complete cycles. Values follow the selected SECONDARY reference.
| Channel | RMS value | Sampled peak | Unit |
|---|---|---|---|
| VA | — | — | V |
| VB | — | — | V |
| VC | — | — | V |
| IA | — | — | A |
| IB | — | — | A |
| IC | — | — | A |
These are reconstructed ideal steady-state sinusoidal samples, not RMS values extracted from a COMTRADE disturbance record.
Enter measurements and select Calculate all parameters.
Calculated voltage phasors
Calculated current phasors
Calculated impedance on R-X plane
Overcurrent pickup assessment
IEC inverse-time estimate
Uses IEC 60255 curve equations: SI 0.14/(M^0.02−1), VI 13.5/(M−1), EI 80/(M²−1), multiplied by TMS. This is an idealized estimate, not a relay-specific guarantee.
Distance protection impedance
Ground-loop estimate uses Z = Vphase / [Iphase + k0 × 3I0]. Verify whether your relay uses k0, (Z0−Z1)/(3Z1), or another manufacturer-specific compensation definition. This simplified calculator does not implement all distance relay algorithms.
Protection characteristic graphing
Interactive IEC inverse-time curves for phase overcurrent and earth-fault elements, plus an R-X plane view of illustrative distance zones. Curves update when settings change.
Time-current characteristics (TCC)
Log-log axes · IEC characteristic with the measured phase-current operating point overlaid
Distance protection R-X characteristics
Illustrative forward mho zone reach and quadrilateral zones, in secondary ohms
Time-domain fault laboratory
Generate sampled three-phase signals from a configurable simplified sequence-network model. The generated samples feed the virtual relay in the next tab.
Single-line network model
Set the source, transformer, line and load beside the network sketch. The derived network uses Z2 = Z1 as a simplified assumption; Z0 remains separately configurable below.
Network parameters
Source and transformer impedances are referred to the source-voltage side. The load sets the prefault current. This is a simplified steady-state equivalent, not a complete load-flow or EMT model.
System and source model
Fault configuration
If the network checkbox is disabled, manual Z1 and Z2 are used. Z0 is manually configured in either mode. The network equivalent assumes Z2 = Z1 and does not include transformer vector-group compensation, load-flow voltage drops, line shunt capacitance or a full EMT model.
Generated current waveforms (relay secondary)
Generated voltage waveforms (VT secondary)
Virtual protection relay
SIPROTEC 5-inspired training front panel with a simulated LCD, status LEDs, binary I/O indications and protection operation. This is an original Elec-Engg educational interface, not Siemens software or a device replica.
BI1 is assigned to the circuit-breaker 52a status contact (active when the simulated breaker is closed). BI2 remains a user-operated demonstration input.
Training device profile
The selected family is a training context only. The active calculation engine below currently implements phase overcurrent, residual earth-fault overcurrent and negative-sequence current elements. Other protection functions are planned, not implied by the selected profile.
Phase overcurrent 50/51
Earth-fault 50N/51N
Negative sequence 46
This first-stage 46 model uses a negative-sequence RMS pickup and definite-time delay. Generator-specific I2²t thermal memory and cooling are reserved for a later validated model.
Breaker model
Relay event timeline
COMTRADE disturbance record reader
Load a matching CFG file and ASCII DAT file to inspect channel definitions, engineering values and sampled waveforms. Parsing is performed locally in your browser; files are not uploaded to the website server.
COMTRADE analog channels
Supported DAT encodings: ASCII, BINARY, BINARY32 and FLOAT32 with CFG channel scaling and sample timestamps. Some vendor extensions and unusual legacy-format variants may require additional compatibility work. The parser reports unsupported or inconsistent records rather than silently treating them as valid. You can map three analog current channels into the virtual relay; verify that the selected channels are correctly scaled and expressed in the same units as the relay pickup settings.