ABB Protection Functions Explained – Complete Guide to Relion Relay Function Codes

Table Of Contents
  1. 1. Introduction to ABB Protection Functions
  2. 2. Understanding ABB Protection Function Names
  3. 3. ABB Function Codes, ANSI Numbers and IEC 61850 Logical Nodes
  4. 4. ABB Overcurrent Protection Functions
  5. 5. ABB Earth-Fault Protection Functions
  6. 6. ABB Distance Protection Functions
  7. 7. ABB Differential Protection Functions
  8. 8. ABB Voltage Protection Functions
  9. 9. ABB Frequency Protection Functions
  10. 10. ABB Thermal Protection Functions
  11. 11. ABB Generator Protection Functions
  12. 12. ABB Motor Protection Functions
  13. 13. ABB Breaker Failure and Circuit-Breaker Protection Functions
  14. 14. ABB Power Swing and Stability-Related Functions
  15. 15. ABB Arc Protection Functions
  16. 16. ABB Control and Monitoring Functions
  17. 17. ABB Protection Functions and PCM600
  18. 18. Testing ABB Protection Functions
  19. 19. ABB Protection Functions Training by Elec-Engg
  20. 20. Frequently Asked Questions About ABB Protection Functions
  21. 21. Conclusion

ABB Protection Functions Explained – Complete Guide to ABB Relion Function Codes, ANSI Numbers and IEC 61850

1. Introduction to ABB Protection Functions

ABB numerical protection relays use a wide range of protection, control, monitoring and measurement functions to protect electrical power systems.

These functions are implemented in different ABB Relion protection and control IEDs, including:

  • ABB Relion 615 series
  • ABB Relion 620 series
  • ABB Relion 650 series
  • ABB Relion 670 series

Each relay model is designed for specific applications, such as feeder protection, transformer protection, generator protection, motor protection, line distance protection and busbar protection.

ABB uses standardized function names and abbreviations to identify individual protection functions.

For example:

  • PHLPTOC – Three-phase non-directional overcurrent protection, low stage
  • DPHLPDOC – Three-phase directional overcurrent protection, low stage
  • EFLPTOC – Non-directional earth-fault protection, low stage
  • DEFLPDEF – Directional earth-fault protection, low stage
  • ZMFPDIS – Distance protection
  • HZPDIF – High-impedance differential protection
  • TR2PTDF – Stabilized and instantaneous differential protection for two-winding transformers
  • CCRBRF – Circuit-breaker failure protection

Understanding these abbreviations is essential for protection engineers working with ABB PCM600, relay configuration, protection settings, IEC 61850 engineering, testing and commissioning.

This guide introduces the ABB function naming system and provides a roadmap for understanding the main protection functions used in ABB Relion relays.

Important: Not every function is available in every ABB relay. Function availability depends on the relay family, product version, hardware, ordered configuration and application package. Always check the applicable ABB product guide and technical manual.

2. Understanding ABB Protection Function Names

ABB function names often contain abbreviations describing the measured electrical quantity, operating principle and protection stage.

Consider the following example:

PHLPTOC

This is the ABB function designation for three-phase non-directional overcurrent protection, low stage.

The name can be understood as follows:

  • PH – Phase
  • L – Low stage
  • PTOC – Time overcurrent protection

Another example is:

EFLPTOC

  • EF – Earth fault
  • L – Low stage
  • PTOC – Time overcurrent protection

The function designation identifies the protection block used in the IED engineering environment.

The exact interpretation of abbreviations should always be checked against the relevant ABB technical manual because naming conventions and function implementations can vary between product generations.

3. ABB Function Codes, ANSI Numbers and IEC 61850 Logical Nodes

Protection engineers commonly encounter three different types of identification:

  1. ABB function designation
  2. ANSI/IEEE device number
  3. IEC 61850 logical node

These identifiers are related, but they are not interchangeable.

3.1 ABB function designation

This is the name used by ABB to identify a particular protection function in its technical documentation and engineering tools.

Examples:

  • PHLPTOC
  • EFHPTOC
  • DEFLPDEF
  • HZPDIF
  • CCRBRF

3.2 ANSI device number

ANSI/IEEE C37.2 device numbers identify the function performed by electrical protection and control equipment.

Common examples include:

ANSI numberFunction
21Distance protection
24Overexcitation protection
25Synchronism check
27Undervoltage protection
32Directional power protection
37Undercurrent or underpower protection
40Loss-of-excitation protection
46Negative-sequence protection
49Thermal overload protection
50Instantaneous overcurrent protection
51Time overcurrent protection
52AC circuit breaker
59Overvoltage protection
63Pressure protection
64Ground protection
67Directional overcurrent protection
68Power swing blocking
78Out-of-step protection
79Autoreclosing
81Frequency protection
85Carrier or pilot-wire protection
86Lockout relay
87Differential protection
94Tripping relay

The ANSI number describes a protection or control function at a general level. ABB may implement that function using different internal function blocks depending on the relay family.

3.3 IEC 61850 logical nodes

IEC 61850 defines standardized logical nodes for representing protection, control, measurement and supervision functions.

Examples include:

IEC 61850 logical nodeGeneral purpose
PTOCTime overcurrent protection
PIOCInstantaneous overcurrent protection
PDISDistance protection
PDIFDifferential protection
PTUVUndervoltage protection
PTOVOvervoltage protection
PTEFEarth-fault protection
RRECAutoreclosing
RSYNSynchronism check
PTRCProtection trip conditioning
XCBRCircuit breaker
MMXUMeasurement
CILOInterlocking
GGIOGeneric input/output

The logical node is part of the IEC 61850 information model. It represents information and functions that can be exchanged between IEDs and substation automation systems.

A specific ABB function block may map to one or more IEC 61850 logical nodes or data objects. Therefore, an ABB function name, an ANSI number and an IEC 61850 logical node should not automatically be treated as a one-to-one mapping.

4. ABB Overcurrent Protection Functions

Overcurrent protection is one of the most widely used protection principles in electrical power systems.

It detects current exceeding a configured pickup level and initiates an alarm or trip according to the operating characteristics.

ABB provides several overcurrent protection functions.

ABB functionDescriptionTypical ANSI number
PHLPTOCThree-phase non-directional overcurrent, low stage51P
PHHPTOCThree-phase non-directional overcurrent, high stage51P
PHIPTOCThree-phase instantaneous overcurrent50P/51P
DPHLPDOCThree-phase directional overcurrent, low stage67
DPHHPDOCThree-phase directional overcurrent, high stage67
PHPVOCVoltage-dependent overcurrent51V

4.1 PHLPTOC – Low-stage phase overcurrent protection

PHLPTOC detects phase current exceeding a configured pickup level.

It is commonly used as the main time-delayed overcurrent protection stage for feeders and other electrical equipment.

Typical applications:

  • Feeder backup protection
  • Transformer backup protection
  • Cable protection
  • Motor backup protection
  • Industrial distribution systems

The function can use definite-time or inverse-time operating characteristics, depending on the product implementation.

4.2 PHHPTOC – High-stage phase overcurrent protection

PHHPTOC provides a higher pickup stage for phase overcurrent protection.

It can be used for faster fault clearing when the fault current is sufficiently high.

4.3 PHIPTOC – Instantaneous phase overcurrent protection

PHIPTOC detects high phase current and provides fast operation according to its configured operating behavior.

It is commonly applied for high-current faults close to the protected equipment.

4.4 DPHLPDOC – Directional phase overcurrent protection

DPHLPDOC determines whether the fault current flows in the configured operating direction.

It is particularly useful in networks with multiple sources, parallel feeders, ring systems and interconnected power networks.

4.5 DPHHPDOC – High-stage directional phase overcurrent protection

DPHHPDOC provides a higher directional overcurrent stage for faster operation under specified fault conditions.

4.6 PHPVOC – Voltage-dependent overcurrent protection

PHPVOC provides overcurrent protection with voltage-dependent behavior.

It can be useful where fault current decreases because of generator or network characteristics and voltage supervision is needed to improve protection sensitivity.

5. ABB Earth-Fault Protection Functions

Earth faults occur when an energized conductor makes contact with earth or an earthed structure.

Earth-fault protection is particularly important in distribution networks, industrial installations and transformer-connected systems.

ABB provides several earth-fault protection functions.

ABB functionDescriptionTypical ANSI number
EFLPTOCNon-directional earth-fault, low stage51N
EFHPTOCNon-directional earth-fault, high stage51N
EFIPTOCInstantaneous earth-fault protection50N/51N
DEFLPDEFDirectional earth-fault, low stage67N
DEFHPDEFDirectional earth-fault, high stage67N
EFPADMAdmittance-based earth-fault protectionApplication-dependent
WPWDEWattmetric earth-fault protection32N
INTRPTEFTransient/intermittent earth-fault protectionApplication-dependent
HAEFPTOCHarmonic-based earth-fault protection51NHA

5.1 EFLPTOC – Low-stage non-directional earth-fault protection

EFLPTOC measures residual current and detects earth faults when the configured pickup level is exceeded.

The residual current can be obtained from the sum of the three phase currents or from a suitable core-balance current transformer, depending on the application.

5.2 EFHPTOC – High-stage earth-fault protection

EFHPTOC provides a higher earth-fault current pickup stage.

It is commonly used for faster operation during high-current earth faults.

5.3 EFIPTOC – Instantaneous earth-fault protection

EFIPTOC provides fast earth-fault overcurrent protection for applications where high residual current is expected.

5.4 DEFLPDEF – Directional earth-fault protection

DEFLPDEF identifies earth faults in a specified direction.

It is important in networks where non-directional earth-fault protection cannot provide adequate selectivity.

5.5 DEFHPDEF – High-stage directional earth-fault protection

DEFHPDEF provides a higher directional earth-fault protection stage.

It can be used for faster clearing of high-current earth faults in the selected direction.

5.6 EFPADM – Admittance-based earth-fault protection

EFPADM uses admittance-related quantities for earth-fault detection.

It can be particularly relevant in isolated or compensated neutral networks, depending on the relay implementation and network grounding arrangement.

5.7 WPWDE – Wattmetric earth-fault protection

WPWDE uses active-power-related quantities for directional earth-fault detection.

It is applied in suitable neutral-grounding systems where wattmetric principles provide reliable fault direction identification.

5.8 INTRPTEF – Transient/intermittent earth-fault protection

INTRPTEF is intended for transient or intermittent earth-fault conditions.

It can help detect earth faults that produce short-duration or repeated transient current and voltage components.

6. ABB Distance Protection Functions

Distance protection is widely used for overhead transmission and sub-transmission line protection.

The relay calculates apparent impedance using measured voltage and current quantities.

The measured impedance is compared with configured protection characteristics and zones.

ABB functionDescriptionANSI number
ZMFPDISDistance protection21
PDISIEC 61850 distance protection logical node21
Fault locator functionFault location estimation21FL

Distance protection functions can include:

  • Phase-to-phase distance measurement
  • Phase-to-earth distance measurement
  • Multiple protection zones
  • Forward and reverse direction
  • Quadrilateral characteristics
  • Mho characteristics
  • Load encroachment supervision
  • Power swing-related logic

The exact implementation depends on the relay family.

ABB REL670 and REL650 are examples of line protection products using distance protection technology.

7. ABB Differential Protection Functions

Differential protection compares electrical quantities entering and leaving a protected zone.

It is widely used for transformers, generators, motors, lines and busbars.

ABB functionDescriptionTypical ANSI number
PDIFIEC 61850 differential protection logical node87
HZPDIFHigh-impedance differential protection87
TR2PTDFTwo-winding transformer differential protection87T
TR3PTDFThree-winding transformer differential protection87T
L2CPDIFLine differential protection function designation in applicable products87L
L3CPDIFThree-terminal line differential function in applicable products87L
MPDIFMotor differential protection87M
GENPDIFGenerator differential protection in applicable products87G

7.1 Transformer differential protection

Transformer differential protection detects internal faults within the transformer protection zone.

The relay compensates for transformer ratio and phase displacement and may use harmonic restraint or blocking to maintain security during magnetizing inrush.

7.2 Generator differential protection

Generator differential protection compares currents at the boundaries of the generator stator winding protection zone.

It provides sensitive protection against internal phase faults.

7.3 Motor differential protection

Motor differential protection compares currents entering and leaving the motor stator winding.

It can detect internal winding faults.

7.4 Busbar differential protection

Busbar differential protection compares the currents associated with all circuits connected to the protected busbar zone.

ABB uses different busbar protection architectures across its product portfolio.

REB650 uses high-impedance differential protection in its documented applications, while REB670 is a low-impedance numerical busbar protection solution.

7.5 Line differential protection

Line differential protection compares currents measured at different ends of a protected line using a communication channel.

It can provide fast and selective protection for internal line faults.

8. ABB Voltage Protection Functions

Voltage protection monitors the voltage level of electrical equipment and power system buses.

ABB functionDescriptionANSI number
PHPTUVThree-phase undervoltage27
PHPTOVThree-phase overvoltage59
ROVPTOVResidual overvoltage59N/59G
PSPTUVPositive-sequence undervoltage47U+
NSPTOVNegative-sequence overvoltage47O-

8.1 PHPTUV – Undervoltage protection

PHPTUV detects when the measured three-phase voltage falls below a configured threshold.

Typical applications:

  • Bus undervoltage protection
  • Motor undervoltage protection
  • Network supervision
  • Load shedding schemes
  • Backup protection

8.2 PHPTOV – Overvoltage protection

PHPTOV detects excessive voltage and initiates the configured alarm or trip response.

8.3 ROVPTOV – Residual overvoltage protection

ROVPTOV measures residual voltage, commonly associated with the sum of the three phase voltages.

It is frequently used for earth-fault detection in networks where residual voltage provides a useful indication.

8.4 PSPTUV – Positive-sequence undervoltage protection

PSPTUV evaluates positive-sequence voltage and can provide undervoltage protection under balanced or unbalanced network conditions.

8.5 NSPTOV – Negative-sequence overvoltage protection

NSPTOV monitors negative-sequence voltage, which can indicate unbalanced voltage conditions.

9. ABB Frequency Protection Functions

Frequency protection is important for maintaining power system stability.

Frequency deviations may occur following generation-load imbalance, system separation, generator trips or major disturbances.

ABB functionDescriptionANSI number
FRPFRQFrequency protection81
SAPTUFUnderfrequency protection81U
SAPTOFOverfrequency protection81O
SAPFRCRate-of-change-of-frequency protection81R

9.1 Underfrequency protection

Underfrequency protection detects a reduction in system frequency.

It is commonly used in underfrequency load shedding schemes.

9.2 Overfrequency protection

Overfrequency protection detects excessive system frequency, which may occur when generation exceeds the connected load.

9.3 Rate-of-change-of-frequency protection

Rate-of-change-of-frequency protection evaluates how quickly system frequency changes.

It can provide fast indication of significant power imbalance or system separation.

10. ABB Thermal Protection Functions

Thermal protection estimates the heating condition of electrical equipment.

It is particularly important for motors, transformers, cables and generators.

ABB functionDescriptionANSI number
MPTTRMotor thermal overload protection49M
T1PTTRThermal protection with one time constant49
T2PTTRThermal protection with two time constants49
TRPTTRThermal overload protection in applicable products49

Thermal models may consider:

  • Current loading
  • Rated current
  • Thermal time constants
  • Heating and cooling
  • Initial thermal state
  • Alarm and trip thresholds

The correct thermal model must match the protected equipment and the selected relay’s implementation.

11. ABB Generator Protection Functions

Generator protection requires several independent protection functions because generators can experience electrical, thermal and mechanical disturbances.

Important ABB generator protection functions include:

FunctionDescriptionANSI number
GENPDIFGenerator differential protection87G
OEXPVPHOverexcitation protection24
NS2PTOCNegative-sequence time overcurrent46
VRPVOC / VR2PVOCVoltage-restrained or voltage-dependent overcurrent, according to product51V
GUPPDUPDirectional underpower protection37
GOPPDOPDirectional overpower protection32
AEGGAPCAccidental energization protection50AE
STEFPHIZThird-harmonic-based stator earth-fault protection27/59THD, implementation-dependent
SAPTUFUnderfrequency protection81U
SAPTOFOverfrequency protection81O

Other generator protection applications may include:

  • Loss of excitation
  • Stator earth fault
  • Rotor earth fault
  • Reverse power
  • Pole slip
  • Overvoltage
  • Undervoltage
  • Overfrequency
  • Underfrequency
  • Negative-sequence protection
  • Thermal overload protection

The function inventory varies between ABB generator protection products, including REG650 and REG670.

12. ABB Motor Protection Functions

Motor protection functions are designed to protect motors against electrical and thermal operating conditions.

Common functions include:

FunctionDescriptionANSI number
MPTTRMotor thermal overload protection49M
MPDIFMotor differential protection87M
JAMPTOCMotor load jam protection51LR
STTPMSUMotor start-up supervision48/49/51LR, application-dependent
PHPTUCLoss-of-phase or undercurrent-related protection37
NSPTOCNegative-sequence overcurrent protection46
PREVPTOCPhase reversal protection46R
LOFLPTUCLoss-of-load supervision37M

Typical motor protection requirements include:

  • Thermal overload
  • Short circuit
  • Earth fault
  • Locked rotor
  • Long starting time
  • Excessive starting frequency
  • Phase loss
  • Phase unbalance
  • Phase reversal
  • Undercurrent or loss of load
  • Differential protection for large motors

13. ABB Breaker Failure and Circuit-Breaker Protection Functions

Circuit-breaker failure protection ensures that a fault is cleared even if the circuit breaker fails to operate correctly.

ABB functionDescriptionANSI number
CCRBRFCircuit-breaker failure protection50BF
CCRPLDPole discordance protection52PD
PTRC / TRPPTRCProtection trip conditioning or master trip94
XCBRIEC 61850 circuit-breaker logical nodeNot a separate protection device number
SPTTRTrip-circuit supervision in applicable products74

13.1 CCRBRF – Breaker failure protection

CCRBRF supervises whether the circuit breaker has interrupted the current after receiving a trip command.

If the breaker fails to clear the fault within the configured conditions, backup tripping is initiated.

13.2 CCRPLD – Pole discordance protection

CCRPLD detects disagreement between circuit-breaker pole positions.

It is useful in applications with independent pole operation.

13.3 Trip conditioning

Trip conditioning functions combine protection start and trip signals and support the delivery of protection trip commands to the circuit-breaker control logic.

The exact implementation depends on the relay application.

14. ABB Power Swing and Stability-Related Functions

Power swings can occur following large system disturbances.

The apparent impedance measured by a distance relay may move through the distance protection characteristic during a power swing.

ABB provides functions and logic for power swing detection and related protection applications.

Important functions include:

  • Power swing detection
  • Power swing blocking
  • Out-of-step protection
  • Switch-onto-fault protection
  • Load encroachment supervision

Examples include:

FunctionDescription
ZMRPSBPower swing detection/blocking-related function in applicable products
OOSPPAMOut-of-step protection
ZCVPSOF / CVPSOFSwitch-onto-fault protection, depending on product
Load encroachment logicPrevents inappropriate distance operation under heavy loading

These functions must be coordinated with the distance protection zones and power system stability requirements.

15. ABB Arc Protection Functions

Arc faults in medium-voltage switchgear can release a large amount of energy in a very short time.

Arc protection is designed to detect the light produced by an internal arc and, depending on the scheme, verify it using current measurement.

An arc protection function can initiate a fast trip to reduce the duration of the fault.

Examples include:

  • ARCSARC – Arc protection function in applicable ABB products
  • Arc sensor inputs
  • Arc current supervision
  • Zone-based arc protection logic
  • Circuit-breaker trip outputs

Arc protection is particularly important in switchgear applications where internal arc risks must be reduced.

16. ABB Control and Monitoring Functions

ABB Relion IEDs also include functions that are not direct protection elements but are essential for substation operation.

Examples include:

FunctionDescription
SESRSYNSynchronism check and energizing check
CILOInterlocking
XCBRCircuit-breaker information model
XSWIDisconnector or earthing switch information model
MMXUMeasurement
GGIOGeneric input/output
RDREDisturbance recording logical node
DRPRDREDisturbance recorder function in applicable products
SPCGAPCSingle-point control
DPCGAPCDouble-point control

These functions support:

  • Circuit-breaker operation
  • Disconnector control
  • Earthing switch control
  • Electrical and mechanical interlocking
  • Voltage and current measurements
  • Event recording
  • Disturbance recording
  • SCADA communication
  • Local and remote control

17. ABB Protection Functions and PCM600

ABB PCM600 is the engineering platform used to configure compatible ABB Relion protection and control IEDs.

Protection engineers use PCM600 to:

  • Create IED projects
  • Configure protection functions
  • Set protection parameters
  • Configure application logic
  • Map binary inputs and outputs
  • Configure IEC 61850 communication
  • Review function availability
  • Download and upload configurations
  • Maintain engineering projects

The available functions depend on the selected relay type and product configuration.

For example, the function inventory of a feeder protection relay is different from that of a transformer or generator protection relay.

An engineer should therefore start with the correct product documentation and installed IED configuration before preparing a protection design.

18. Testing ABB Protection Functions

Protection functions must be tested during factory acceptance, commissioning and maintenance.

A secondary injection test set such as Omicron CMC can be used to verify many ABB protection functions.

The test procedure depends on the function being tested.

Examples include:

Protection functionTypical testing approach
OvercurrentCurrent injection and pickup/time tests
Directional overcurrentCurrent and voltage injection with angle variation
Earth faultResidual current injection
DistanceR-X characteristic and zone timing tests
DifferentialDifferential and restraint quantity tests
Transformer differentialDifferential, harmonic restraint and stability tests
VoltageVoltage injection and pickup/drop-off tests
FrequencyFrequency variation and timing tests
ThermalThermal model and overload tests
Breaker failureTrip initiation, current supervision and timer tests
Arc protectionSensor and current supervision tests
AutoreclosingDead-time, reclaim and sequence tests
Synchronism checkVoltage, frequency and phase-angle tests

The test engineer must use the correct test method for the actual relay function and configuration.

For example, testing a high-impedance differential function requires a different understanding of the measuring circuit from testing a conventional low-impedance numerical differential function.

19. ABB Protection Functions Training by Elec-Engg

Elec-Engg provides practical power system protection training covering ABB Relion protection functions, relay configuration, protection settings and commissioning.

Training can be arranged for individual engineers and company engineering teams.

Available delivery methods include:

Customized company training

Customized programs can be prepared for utilities, power plants, industrial facilities, EPC contractors and commissioning companies.

The training can focus on the protection functions installed in the client’s substations.

Online instructor-led training

Online training can cover ABB protection principles, function settings, PCM600 engineering, IEC 61850 communication and relay testing.

Face-to-face training

Face-to-face courses can be arranged at client premises or at an agreed training location, subject to scheduling and practical arrangements.

Practical training topics

Training can include:

  • ABB protection function identification
  • ANSI and IEC 61850 function mapping
  • Overcurrent and earth-fault protection
  • Distance protection
  • Transformer differential protection
  • Generator protection
  • Motor protection
  • Busbar protection
  • Breaker failure protection
  • PCM600 engineering
  • IEC 61850 configuration
  • Omicron relay testing
  • Commissioning and troubleshooting

Course scope and duration can be customized according to the relay models, experience level and objectives of the participants.

For ABB protection relay training and customized technical courses, contact Elec-Engg:

https://elec-engg.com

20. Frequently Asked Questions About ABB Protection Functions

What are ABB protection functions?

ABB protection functions are numerical algorithms and logic blocks implemented in ABB protection relays to detect abnormal electrical conditions and initiate alarms, trips or control actions.

What is PHLPTOC in ABB relays?

PHLPTOC is the ABB function designation for three-phase non-directional overcurrent protection, low stage. It is generally associated with ANSI 51P.

What is the difference between PHLPTOC and DPHLPDOC?

PHLPTOC is non-directional overcurrent protection, while DPHLPDOC includes directional supervision to identify faults in a specified direction.

What is EFLPTOC?

EFLPTOC is non-directional earth-fault protection, low stage.

What is HZPDIF?

HZPDIF is ABB’s high-impedance differential protection function, used in suitable busbar and other differential protection applications.

What is the difference between ABB function codes and ANSI numbers?

ABB function codes identify ABB’s internal protection function blocks, while ANSI numbers provide standardized device function identification.

What is the relationship between ABB functions and IEC 61850 logical nodes?

IEC 61850 logical nodes provide standardized information models for protection, control and measurement. ABB functions can map to logical nodes and data objects according to the IED implementation.

Are all ABB protection functions available in every Relion relay?

No. Function availability depends on the relay family, model, product version, hardware and ordered configuration.

Which software is used to configure ABB protection functions?

ABB PCM600 is used for engineering and configuration of compatible ABB Relion protection and control IEDs.

How can ABB protection functions be tested?

Many functions can be tested using suitable secondary injection equipment, such as Omicron CMC, following the function-specific test procedure.

21. Conclusion

ABB Relion protection relays provide a comprehensive range of protection, control, monitoring and measurement functions.

Understanding the ABB function designations, ANSI device numbers and IEC 61850 logical nodes is essential for engineers involved in relay engineering, protection coordination, configuration, testing and commissioning.

The most effective way to understand these functions is to study each protection element individually, including its operating principle, settings, application, logic and practical testing requirements.

This Elec-Engg article series will provide detailed technical explanations of ABB protection functions and their applications across feeder, transformer, generator, motor, line and busbar protection systems.