ABB REL650 Line Distance Protection Relay – Complete Technical Guide

Table Of Contents
  1. 1. Introduction to the ABB REL650 Relay
  2. 2. Main Applications of ABB REL650
  3. 3. How Distance Protection Works
  4. 4. Distance Protection Zones in REL650
  5. 5. Quadrilateral and Mho Distance Characteristics
  6. 6. Main Protection Functions of ABB REL650
  7. 7. Earth-Fault Distance Protection
  8. 8. Autoreclosing and Synchronism Check
  9. 9. Circuit-Breaker Control and Trip Logic
  10. 10. Load Encroachment and Heavy-Load Conditions
  11. 11. PCM600 Engineering for ABB REL650
  12. 12. IEC 61850 Communication in REL650
  13. 13. Testing and Commissioning of ABB REL650
  14. 14. Common REL650 Problems and Troubleshooting
  15. 15. REL650 Compared with REL670
  16. 16. Practical Engineering Checklist
  17. 17. ABB REL650 Training by Elec-Engg
  18. 18. Frequently Asked Questions About ABB REL650
  19. 19. Conclusion

1. Introduction to the ABB REL650 Relay

The ABB REL650 Line Distance Protection Relay is a numerical protection and control IED designed primarily for overhead transmission and sub-transmission lines and underground cables. It belongs to the ABB Relion 650 series and is intended for applications requiring dependable distance protection, backup protection, circuit-breaker control and substation automation.

The REL650 is particularly suitable for networks with solidly earthed or impedance-earthed neutral systems. It can be applied to heavily loaded lines and multi-terminal line arrangements, subject to the selected configuration and application requirements.

Its main protection function is distance protection, which determines the apparent impedance between the relay location and the fault. Because the measured impedance is approximately proportional to the distance to the fault, the relay can identify faults within predefined protection zones.

The REL650 provides configurable protection characteristics, including quadrilateral and mho characteristics. Its protection architecture also includes supporting functions such as power swing detection, switch-onto-fault logic, overcurrent protection, earth-fault protection, autoreclosing and synchronism check.

For protection engineers, the REL650 is an important platform to understand when working with ABB distance protection systems in substations.

2. Main Applications of ABB REL650

The REL650 can be used in several power system applications.

2.1 Overhead transmission line protection

The relay provides primary distance protection for overhead lines. It measures phase currents and voltages to determine the apparent impedance seen from the relay location.

Depending on the application configuration, it can provide:

  • Phase-to-phase fault detection
  • Three-phase fault detection
  • Phase-to-earth fault detection
  • Multiple distance protection zones
  • Forward and reverse fault detection
  • Backup protection for adjacent network sections

2.2 Underground cable protection

Distance protection can also be applied to underground cables when the network and cable characteristics are suitable.

Correct application requires accurate positive- and zero-sequence impedance data, consideration of cable charging current, grounding arrangements and the characteristics of the connected network.

2.3 Heavily loaded lines

Distance protection on heavily loaded lines requires particular attention to load encroachment.

During high power transfer, the apparent impedance may enter parts of the distance protection characteristic. Load encroachment logic helps prevent unwanted operation under heavy-load conditions while maintaining suitable fault coverage.

2.4 Multi-terminal line applications

The REL650 can be applied to multi-terminal line arrangements. However, engineers must carefully consider infeed and outfeed effects, remote-end contributions, fault resistance and the resulting distance measurement errors.

The protection scheme must be studied using the actual network configuration and appropriate short-circuit calculations.

2.5 Backup protection

In addition to distance protection, the relay can provide backup functions such as:

  • Phase overcurrent protection
  • Residual overcurrent protection
  • Breaker failure protection
  • Undervoltage protection
  • Pole discordance protection
  • General current and voltage protection

The exact functions depend on the product version and ordered configuration.

3. How Distance Protection Works

Distance protection is based on measuring the apparent impedance between the relay installation point and the fault location.

The fundamental relationship is:

Z = V / I

Where:

  • Z is the apparent impedance measured by the relay
  • V is the measured voltage
  • I is the measured current

For a transmission line with approximately uniform impedance per kilometre, the impedance measured by the relay is related to the electrical distance to the fault.

For example, consider a 50 km transmission line with a positive-sequence impedance of:

Z1 = 0.195 + j0.410 Ω/km

The total positive-sequence line impedance is:

Zline = 50 × (0.195 + j0.410)

Zline = 9.75 + j20.5 Ω

The distance relay uses the line impedance data and its configured reach settings to establish the protection zones.

This example is illustrative. Actual settings must account for CT and VT ratios, primary and secondary quantities, line configuration, system grounding, fault resistance and the relay’s measuring conventions.

4. Distance Protection Zones in REL650

A distance protection scheme normally uses several zones with different reach and operating times.

The REL650 product documentation describes a six-zone distance protection arrangement with independently configurable measuring and setting ranges. The exact zone implementation and available settings depend on the selected product version and application configuration.

Zone 1 – Main instantaneous protection

Zone 1 normally covers approximately 80–90% of the protected line, although the actual reach must be determined through a protection coordination study.

The intentional underreach helps avoid unwanted operation for faults beyond the remote busbar, particularly when measurement errors and system conditions are considered.

Typical characteristics:

  • High-speed operation
  • Normally no intentional time delay
  • Covers the majority of the protected line
  • Does not normally reach the remote busbar

Zone 2 – Overreaching protection

Zone 2 normally covers the remaining part of the protected line and extends beyond the remote busbar to provide backup protection.

It is generally time-delayed to coordinate with protection on the adjacent line or network section.

The reach must consider:

  • Remote-end infeed
  • Adjacent line impedance
  • Fault resistance
  • Network configuration
  • Coordination with other protection devices

Zone 3 – Remote backup protection

Zone 3 can provide backup protection for faults on adjacent network sections.

Its reach and delay must be coordinated carefully to avoid unwanted operation during external faults and heavy loading conditions.

Additional distance zones

Further zones may be configured for specific protection and coordination requirements, including reverse-looking applications where supported by the selected configuration.

Engineers should not assume that every zone has the same direction, characteristic or purpose. Each zone must be studied and configured according to the protection philosophy.

ABB REL650 line distance protection relay front panel ABB Relion REL650 A11 protection IED ABB REL650 relay rear terminals and hardware ABB REL650 transmission line protection panel Six-zone distance protection impedance diagram ABB PCM600 REL650 configuration

5. Quadrilateral and Mho Distance Characteristics

One of the important features of REL650 is support for quadrilateral and mho distance protection characteristics.

5.1 Quadrilateral characteristic

The quadrilateral characteristic provides separate control of resistive and reactive reach.

This is particularly useful when the protection scheme must detect faults with significant fault resistance.

Advantages include:

  • Adjustable resistive reach
  • Adjustable reactive reach
  • Flexible coverage for phase and earth faults
  • Better adaptation to different line and fault conditions

However, the resistive reach must be coordinated with load impedance and the load encroachment function.

5.2 Mho characteristic

The mho characteristic is represented by a circular operating region on the R-X impedance plane.

It has a directional property and is widely used in transmission line distance protection.

Advantages include:

  • Natural directional behavior
  • Good suitability for many transmission line applications
  • Established application principles
  • Useful coordination characteristics

5.3 Selecting the correct characteristic

The choice between quadrilateral and mho characteristics depends on the system study and protection philosophy.

Factors include:

  • Line length and impedance
  • Fault resistance
  • Maximum load transfer
  • Network stability requirements
  • Remote-end infeed
  • Grounding arrangements
  • Protection coordination

The characteristic must be selected and tested for the actual application rather than simply copying settings from another line.

6. Main Protection Functions of ABB REL650

6.1 Distance protection – ZMFPDIS

ZMFPDIS is the main distance protection function, associated with ANSI device number 21.

It evaluates the measured impedance and determines whether a fault falls within the configured operating zones.

Important engineering considerations include:

  • Zone reach
  • Zone direction
  • Operating time
  • Quadrilateral or mho characteristic
  • Phase selection
  • Earth-fault compensation
  • Load encroachment
  • Fault resistance coverage

The function must be configured using reliable line impedance data and the correct CT and VT information.

6.2 Phase preference logic – PPL2PHIZ

Phase preference logic supports the identification and selection of the faulted phase or phases for appropriate protection operation.

This is particularly relevant to applications involving single-phase faults and single-phase tripping schemes.

The complete protection logic must coordinate phase selection, distance measurement and trip output behavior.

6.3 Power swing detection – ZMRPSB

Power swings can cause the apparent impedance measured by a distance relay to move through its operating characteristic.

If the relay does not distinguish between a stable power swing and a fault, unwanted tripping may occur.

Power swing detection helps identify these conditions and supports the protection scheme’s response.

Engineers should evaluate:

  • Power swing impedance trajectories
  • System stability requirements
  • Blocking and unblocking logic
  • Fault detection during power swings
  • Coordination with distance protection zones

6.4 Power swing logic – PSLPSCH

Power swing logic supports the application of power swing-related protection schemes.

Its operation must be coordinated with the distance protection elements and the overall system protection philosophy.

6.5 Out-of-step protection – OOSPPAM

Out-of-step conditions occur when generators or parts of the power system lose synchronism.

Out-of-step protection can be used to identify specified unstable conditions and initiate the required system separation or tripping strategy.

The application requires detailed stability studies and careful coordination with other system protection functions.

6.6 Switch-onto-fault logic – ZCVPSOF

Switch-onto-fault protection is important when a circuit breaker closes onto an existing fault.

A fault may exist on a line that is being energized, and normal distance protection may not provide the expected high-speed response in every operating condition.

The switch-onto-fault function uses voltage- and current-based logic to support rapid protection operation when its configured conditions are satisfied.

6.7 Instantaneous phase overcurrent – PHPIOC

PHPIOC provides instantaneous phase overcurrent protection.

It can be used as backup protection or as part of a specific application scheme.

The pickup setting must be coordinated with:

  • Maximum load current
  • Minimum fault current
  • CT performance
  • Adjacent protection devices
  • Required sensitivity and selectivity

6.8 Four-step phase overcurrent – OC4PTOC

OC4PTOC provides four-step phase overcurrent protection.

Depending on the configuration, the stages can support different pickup levels, operating delays and directional characteristics.

Directional operation requires the appropriate voltage measurement and configuration.

6.9 Instantaneous residual overcurrent – EFPIOC

EFPIOC provides instantaneous residual or earth-fault overcurrent protection.

It detects residual current associated with earth faults.

The function’s application depends on the network grounding method and the available current measurements.

6.10 Four-step residual overcurrent – EF4PTOC

EF4PTOC provides four-step residual overcurrent protection.

It can be used for earth-fault backup protection and coordination with other network protection devices.

Where directional earth-fault protection is required, the correct polarizing quantities and measurement connections must be configured.

6.11 Breaker failure protection – CCRBRF

CCRBRF is the circuit-breaker failure protection function, associated with ANSI 50BF.

It supervises whether the circuit breaker has successfully interrupted the fault current following a trip command.

If the breaker fails to clear the fault within the configured conditions and time, the breaker failure scheme initiates backup tripping.

Important settings include:

  • Current detection criteria
  • Retrip logic
  • Breaker failure timer
  • Initiating trip signals
  • Backup breaker trip matrix

The breaker failure scheme must be tested together with the actual trip circuit and breaker interface.

6.12 Pole discordance protection – CCPDSC

CCPDSC supervises disagreement between circuit-breaker pole positions.

It can detect situations in which the three poles do not operate consistently.

The function is particularly important in applications where single-pole operation or independent pole control is used.

6.13 Undervoltage protection – UV2PTUV

UV2PTUV provides two-step undervoltage protection.

It can be used for line and network supervision, backup protection or other application-specific requirements.

The settings must consider normal operating voltage variations and the required coordination with other protection functions.

6.14 General current and voltage protection – CVGAPC

CVGAPC is a general-purpose current and voltage protection function.

It can be applied to different protection requirements where a configurable current and voltage-based function is needed.

The application must be designed carefully and verified through testing.

7. Earth-Fault Distance Protection

Earth-fault distance protection requires special attention because the impedance measured during a phase-to-earth fault is influenced by the zero-sequence network.

For a simplified single-phase-to-earth fault measurement, the relay uses phase voltage, phase current and residual-current compensation.

A commonly used compensation factor is:

k0 = (Z0 − Z1) / (3 × Z1)

Where:

  • Z0 is the zero-sequence line impedance
  • Z1 is the positive-sequence line impedance

The precise compensation convention used by the relay must be checked in the relevant ABB technical documentation and setting interface.

Incorrect zero-sequence compensation can cause distance protection underreach or overreach.

Before commissioning, verify:

  • Positive-sequence line impedance
  • Zero-sequence line impedance
  • CT and VT ratios
  • Residual current measurement
  • Grounding arrangement
  • Mutual coupling with parallel lines, where applicable
  • Earth-fault zone reach

For parallel transmission lines, mutual coupling may significantly affect zero-sequence measurements. This should be included in the protection study where relevant.

8. Autoreclosing and Synchronism Check

8.1 Autoreclosing – SMBRREC

The autoreclosing function supports automatic reclosing following a protection trip.

It is particularly useful for overhead lines, where many faults are temporary.

Typical autoreclosing considerations include:

  • Single-phase or three-phase reclosing
  • Dead time
  • Reclaim time
  • Number of reclosing shots
  • Single-pole and three-pole trip logic
  • Breaker readiness
  • Reclosing initiation and blocking conditions

The autoreclosing scheme must be coordinated with the distance protection trip logic and the circuit-breaker operating characteristics.

8.2 Synchronism check – SESRSYN

SESRSYN supervises voltage and phase-angle conditions before a circuit breaker is closed.

It can be used to check whether the two sides of the breaker satisfy configured synchronism or energizing conditions.

Important parameters include:

  • Voltage difference
  • Phase-angle difference
  • Frequency difference
  • Synchronism check time
  • Energizing check conditions

The function is particularly important when reclosing connects two energized parts of the power system.

9. Circuit-Breaker Control and Trip Logic

The REL650 can include apparatus control and circuit-breaker-related functions as part of its configured application.

The engineering design must ensure that protection trips, autoreclosing commands, breaker failure logic and control commands are correctly coordinated.

Typical signals include:

  • Protection start
  • Protection trip
  • Circuit-breaker open command
  • Circuit-breaker close command
  • Breaker position indication
  • Trip-circuit supervision
  • Breaker failure initiation
  • Autoreclosing initiation
  • Reclosing block
  • Synchronism check permissive

The final trip and close logic must be verified against the substation control philosophy and the actual wiring diagrams.

10. Load Encroachment and Heavy-Load Conditions

Load encroachment is an important consideration in distance protection.

Under heavy loading, the apparent impedance seen by the relay may approach or enter the distance protection operating characteristic.

This can create a risk of unwanted distance protection operation.

A proper application study should consider:

  • Maximum continuous load
  • Emergency loading
  • Minimum operating voltage
  • Power factor
  • Permitted overload conditions
  • Distance zone reach
  • Resistive reach
  • Load encroachment settings

The objective is to maintain dependable fault detection without compromising security during heavy-load conditions.

11. PCM600 Engineering for ABB REL650

ABB PCM600 is the engineering platform used for configuration, parameter setting, application engineering and maintenance of compatible ABB Relion IEDs.

The exact PCM600 version and connectivity requirements depend on the REL650 product version and installed engineering environment.

Typical engineering activities include:

11.1 Creating the project

The engineer creates a PCM600 project and adds the relevant REL650 IED using the correct product and connectivity information.

The correct IED version and configuration must be selected.

11.2 Parameter setting

The protection engineer configures:

  • CT ratios
  • VT ratios
  • Line impedance
  • Distance zone reach
  • Zone operating times
  • Directional settings
  • Earth-fault compensation
  • Power swing settings
  • Overcurrent settings
  • Breaker failure settings
  • Autoreclosing parameters
  • Synchronism check parameters

11.3 Application configuration

The application configuration defines how protection functions, logic blocks, binary inputs and outputs interact.

Typical engineering tasks include:

  • Mapping protection starts to logic
  • Connecting trip signals
  • Configuring breaker control
  • Assigning binary inputs
  • Assigning binary outputs
  • Configuring interlocking and control logic
  • Verifying signal paths

11.4 Signal matrix configuration

The signal matrix is used to connect internal IED signals to physical binary inputs and outputs and, where applicable, communication interfaces.

Engineers should verify the complete signal path from protection function to trip output.

11.5 Hardware and configuration verification

Before downloading a configuration, verify that the selected hardware and I/O arrangement match the actual relay.

A mismatch between the engineered configuration and installed hardware can cause commissioning problems.

11.6 Reading and downloading configurations

The engineer should follow the approved project workflow when reading from or downloading to the IED.

Before modifying an operational relay, preserve the existing configuration and settings, confirm authorization and follow the site’s change-management procedure.

12. IEC 61850 Communication in REL650

The REL650 can be integrated into IEC 61850-based substation automation systems, subject to the selected product version and communication configuration.

IEC 61850 provides standardized communication and data modelling for protection and control IEDs.

12.1 IEC 61850 logical nodes

Logical nodes represent standardized protection, control, measurement and supervision functions.

Examples of logical node classes commonly associated with line protection applications include:

  • PDIF – Differential protection
  • PDIS – Distance protection
  • PTOC – Overcurrent protection
  • PTUV – Undervoltage protection
  • RREC – Autoreclosing
  • RSYN – Synchronism check
  • PTRC – Protection trip conditioning
  • XCBR – Circuit breaker
  • MMXU – Measurement

The exact logical node implementation and data objects must be checked against the REL650 edition, product version and ICD/CID files.

12.2 MMS communication

Manufacturing Message Specification (MMS) is commonly used for supervisory communication between IEDs and the substation control system.

Typical information includes:

  • Measurements
  • Status indications
  • Alarms
  • Events
  • Protection signals
  • Control information

12.3 GOOSE communication

Generic Object Oriented Substation Event (GOOSE) communication provides fast peer-to-peer communication between IEDs.

Possible applications include:

  • Interlocking
  • Breaker failure intertripping
  • Protection blocking
  • Direct transfer trip
  • Busbar-related signals
  • Inter-IED protection logic

GOOSE communication must be engineered and tested carefully. The publisher dataset, subscriber configuration, VLAN, priority and network architecture must all be verified.

12.4 SCL engineering

Substation Configuration Language (SCL) is used to describe IEC 61850 system configurations.

Depending on the engineering workflow, relevant files may include:

  • ICD – IED Capability Description
  • CID – Configured IED Description
  • SCD – Substation Configuration Description
  • IID – Instantiated IED Description

The correct file exchange and revision management process is essential when integrating REL650 into a larger SAS project.

13. Testing and Commissioning of ABB REL650

Commissioning is a critical stage in ensuring that the distance protection scheme operates correctly.

Testing should cover the complete protection chain, including instrument transformers, relay measurements, protection logic, trip circuits and circuit-breaker operation.

13.1 Visual inspection

Check:

  • Relay type and ordering information
  • Hardware modules
  • Terminal connections
  • Auxiliary supply
  • CT wiring
  • VT wiring
  • Binary input wiring
  • Binary output wiring
  • Earthing
  • Communication connections

13.2 CT and VT verification

Verify CT and VT ratios, polarity, phase identification and wiring.

Incorrect CT or VT connections can cause incorrect impedance measurement and unwanted distance protection operation.

13.3 Secondary injection testing

A relay test set such as an Omicron CMC can be used to inject current and voltage quantities into the relay.

Typical tests include:

  • Phase-to-earth faults
  • Phase-to-phase faults
  • Three-phase faults
  • Forward faults
  • Reverse faults
  • Zone 1 operation
  • Zone 2 operation
  • Zone 3 operation
  • Zone timing
  • Directional supervision
  • Fault resistance coverage

The test quantities must be calculated using the relay’s configured CT and VT ratios and impedance reference.

13.4 Distance characteristic testing

The distance protection characteristic should be tested on the R-X plane.

For quadrilateral characteristics, verify the resistive and reactive boundaries.

For mho characteristics, verify the configured operating circle and directional behavior.

Test points should include:

  • Inside the operating characteristic
  • Outside the operating characteristic
  • Near the operating boundary
  • Forward direction
  • Reverse direction
  • Different fault loops

13.5 Earth-fault distance testing

Earth-fault distance protection testing should include the correct residual current and zero-sequence compensation.

Verify the phase-to-earth measuring loops and the configured earth-fault reach.

13.6 Autoreclosing testing

Test the complete autoreclosing sequence, including:

  • Initiation
  • Dead time
  • Reclosing permission
  • Synchronism check
  • Reclosing block
  • Reclaim time
  • Final lockout conditions

13.7 Breaker failure testing

Verify the breaker failure initiation signal, current supervision, timers, retrip logic and backup trip outputs.

13.8 IEC 61850 testing

For IEC 61850 applications, verify:

  • MMS communication
  • GOOSE publishing
  • GOOSE subscription
  • Dataset configuration
  • Communication supervision
  • Time synchronization
  • Alarm and event reporting
  • SCADA signal mapping

Tools such as IEDScout and suitable network analysis software can support communication troubleshooting.

13.9 End-to-end testing

Where the protection scheme uses communication-assisted tripping or other remote-end protection signals, end-to-end testing may be required.

The test should verify the complete scheme, including communication channels, relay logic and trip outputs at both terminals.

14. Common REL650 Problems and Troubleshooting

Problem 1: Incorrect distance measurement

Possible causes:

  • Incorrect CT ratio
  • Incorrect VT ratio
  • Wrong phase identification
  • Incorrect line impedance
  • Incorrect secondary/primary setting reference
  • Wiring or polarity problems

Recommended action: Verify instrument transformer data, wiring, phase sequence and the configured line impedance.

Problem 2: Distance relay overreach

Possible causes:

  • Incorrect reach settings
  • Incorrect zero-sequence compensation
  • Remote infeed effects
  • Instrument transformer errors
  • Incorrect application assumptions

Recommended action: Review the short-circuit study, zone calculations and actual network conditions.

Problem 3: Distance relay underreach

Possible causes:

  • Incorrect impedance data
  • Excessive fault resistance
  • Incorrect compensation
  • Weak infeed conditions
  • Incorrect measurement loop selection

Recommended action: Examine fault records, disturbance recordings and the relevant distance measurement quantities.

Problem 4: Unwanted operation during heavy loading

Possible causes:

  • Insufficient load encroachment security
  • Incorrect resistive reach
  • Incorrect zone configuration
  • Inadequate loadability study

Recommended action: Review maximum loading conditions and coordinate the distance characteristic with the load encroachment settings.

Problem 5: Autoreclosing does not operate

Possible causes:

  • Reclosing blocked
  • Incorrect initiation signal
  • Breaker not ready
  • Synchronism check not satisfied
  • Incorrect dead-time configuration
  • Lockout condition active

Recommended action: Trace the complete autoreclosing logic and verify all permissive and blocking signals.

Problem 6: IEC 61850 communication failure

Possible causes:

  • Incorrect IP configuration
  • Incorrect SCL engineering
  • Dataset mismatch
  • GOOSE subscription errors
  • VLAN or switch configuration problems
  • Time synchronization issues

Recommended action: Check the IED communication settings, SCL files, network configuration and communication diagnostics.

15. REL650 Compared with REL670

Both REL650 and REL670 belong to ABB’s Relion line protection portfolio, but they address different application requirements.

FeatureREL650REL670
Main applicationLine distance protectionAdvanced line protection
Typical application focusSub-transmissionTransmission
Distance protectionYesYes
Quadrilateral characteristicSupported in applicable configurationsSupported
Mho characteristicSupported in applicable configurationsSupported
Backup protectionAvailableAvailable
AutoreclosingAvailable in applicable configurationsAvailable
Synchronism checkAvailable in applicable configurationsAvailable
IEC 61850SupportedSupported
Engineering platformPCM600PCM600

The REL650 is positioned as a practical solution for sub-transmission applications, while REL670 is intended for more demanding transmission applications.

The correct selection should be based on the required protection functions, network architecture, performance requirements, communication scheme and available hardware configuration.

16. Practical Engineering Checklist

Before placing an ABB REL650 into service, protection and commissioning engineers should verify the following:

Protection study

  • Confirm the protected line and network configuration
  • Calculate positive- and zero-sequence impedance
  • Calculate distance protection zone reaches
  • Check fault resistance requirements
  • Review load encroachment
  • Coordinate backup protection
  • Review power swing requirements

Relay engineering

  • Confirm the correct REL650 product version
  • Verify hardware and I/O configuration
  • Configure CT and VT ratios
  • Configure distance zones
  • Configure earth-fault compensation
  • Configure overcurrent protection
  • Configure breaker failure logic
  • Configure autoreclosing and synchrocheck
  • Verify trip and close logic

Communication

  • Verify IEC 61850 configuration
  • Check MMS communication
  • Check GOOSE publishing and subscription
  • Verify time synchronization
  • Confirm SCADA signal mapping

Commissioning

  • Perform visual inspection
  • Verify CT and VT circuits
  • Perform secondary injection tests
  • Test distance characteristics
  • Test earth-fault distance protection
  • Test autoreclosing
  • Test breaker failure
  • Perform communication tests
  • Verify trip circuit and circuit-breaker operation
  • Save final settings and test reports

17. ABB REL650 Training by Elec-Engg

Elec-Engg provides practical power system protection and substation automation training for engineers working with ABB protection relays and other major protection platforms.

Training can be arranged according to the technical requirements of individual engineers, utilities, industrial companies and engineering teams.

Available delivery methods include:

Customized company training

Training programs can be tailored for utilities, power plants, industrial facilities, EPC contractors and commissioning companies.

The course scope can be adapted to the participants’ experience, installed relay models and project requirements.

Online instructor-led training

Online training can cover REL650 protection principles, distance protection settings, PCM600 engineering, application configuration, IEC 61850 communication and testing procedures.

Face-to-face training

Face-to-face courses can be arranged at the client’s premises or at an agreed training location, subject to scheduling and practical arrangements.

Practical engineering and testing topics

A customized REL650 training program may include:

  • Introduction to ABB Relion 650 series
  • REL650 hardware and architecture
  • Distance protection principles
  • Quadrilateral and mho characteristics
  • Distance zone calculation and coordination
  • Earth-fault distance protection
  • Load encroachment and power swing
  • Autoreclosing and synchronism check
  • PCM600 configuration and parameter setting
  • IEC 61850 MMS and GOOSE engineering
  • Secondary injection testing
  • Protection commissioning and troubleshooting

The training duration, technical depth and practical exercises can be adapted to the client’s objectives and available equipment.

For ABB REL650 training, customized protection courses, online instruction or face-to-face training, contact Elec-Engg:

Website: https://elec-engg.com/

18. Frequently Asked Questions About ABB REL650

What is the ABB REL650 relay?

ABB REL650 is a numerical line distance protection and control IED designed primarily for overhead lines and cables in sub-transmission applications.

What is the main protection function of REL650?

Its main protection function is distance protection, associated with ANSI device number 21 and the ABB function designation ZMFPDIS.

Does REL650 support quadrilateral distance protection?

Yes. The REL650 documentation identifies quadrilateral and mho distance protection characteristics. The available functions and application details depend on the product version and configuration.

How many distance zones are available in REL650?

The REL650 2.2 product documentation describes six distance zones with independent measuring and setting ranges. Always verify the exact implementation in the product guide for the installed version.

Does REL650 support earth-fault distance protection?

The relay supports distance protection applications that include earth-fault measurement. Correct zero-sequence compensation and network grounding information are essential.

Does REL650 support power swing detection?

Yes. Power swing detection and associated logic are included in the documented protection function portfolio, subject to the selected version and configuration.

Does REL650 have autoreclosing?

Yes. The relay can include autoreclosing functionality, with the available application depending on the selected configuration.

Can REL650 communicate using IEC 61850?

Yes. REL650 supports IEC 61850-based substation automation integration. The exact communication services and engineering requirements depend on the product version and system configuration.

Which software is used to configure ABB REL650?

ABB PCM600 is the engineering platform used for compatible Relion 650 series IED configuration, parameter setting and application engineering.

Can REL650 be tested using Omicron CMC?

Yes. Suitable Omicron CMC test equipment can be used for secondary injection testing of distance protection, overcurrent protection, earth-fault protection, autoreclosing and other functions. The test setup and procedures must match the relay configuration.

What is the difference between REL650 and REL670?

REL650 is positioned primarily for sub-transmission line protection applications, while REL670 is intended for more demanding transmission applications. The required functions and system design should determine the selection.

19. Conclusion

The ABB REL650 is a versatile numerical line distance protection relay for overhead lines and cables. Its distance protection, backup protection, power swing functions, switch-onto-fault logic, autoreclosing and synchronism check capabilities make it suitable for a range of sub-transmission protection applications.

Successful application requires more than entering distance zone settings. Engineers must understand line impedance calculations, earth-fault compensation, load encroachment, power swing behavior, breaker control logic and IEC 61850 communication.

Proper engineering, secondary injection testing, commissioning and periodic maintenance are essential to ensure dependable operation.

For engineers involved in ABB protection systems, understanding REL650 provides a strong practical foundation in modern numerical distance protection.