GE Multilin 850 Feeder Protection Relay: Complete Technical Guide to Overcurrent, Earth-Fault, Directional Protection, Autoreclosing, Configuration and Testing

Table Of Contents
  1. 1. Introduction
  2. 2. Overview of the GE Multilin 850
  3. 3. Feeder Protection Philosophy
  4. 4. Phase Overcurrent Protection (ANSI 50/51)
  5. 5. Earth-Fault Protection (ANSI 50N/51N and 50G/51G)
  6. 6. Directional Overcurrent Protection (ANSI 67 and 67N)
  7. 7. Feeder Coordination and Time-Current Curves
  8. 8. Practical Feeder Overcurrent Calculation
  9. 9. Autoreclosing Protection (ANSI 79)
  10. 10. Circuit Breaker Failure Protection (ANSI 50BF)
  11. 11. Voltage and Frequency Protection
  12. 12. CT and VT Configuration
  13. 13. GE Multilin 850 Configuration Using EnerVista
  14. 14. Communication and Substation Automation Integration
  15. 15. Testing and Commissioning of the GE Multilin 850
  16. 16. Practical Commissioning Test Matrix
  17. 17. Common Problems and Troubleshooting
  18. 18. Practical Engineering Checklist
  19. 19. Training on GE Multilin Feeder Protection by Elec-Engg
  20. 20. Conclusion
  21. 21. Frequently Asked Questions (FAQs)

1. Introduction

The GE Multilin 850 is a feeder protection system in the GE Multilin 8 Series family. It is designed for protection and control applications in distribution and industrial power systems.

Feeder protection is essential for detecting faults, isolating faulty sections, maintaining supply continuity, and coordinating protection devices throughout an electrical network.

A modern numerical feeder relay may combine several protection and control functions, including phase overcurrent, earth-fault protection, directional overcurrent, voltage protection, frequency protection, autoreclosing, breaker failure, and monitoring. The actual functions available depend on the relay model, ordered hardware, and firmware.

This article explains the engineering applications of the GE Multilin 850, its protection functions, CT and VT configuration, time-current coordination, autoreclosing, EnerVista engineering, testing, and troubleshooting.

2. Overview of the GE Multilin 850

The GE Multilin 850 is intended for feeder protection applications in suitable distribution and industrial systems.

Typical applications include:

  • Medium-voltage distribution feeders.
  • Industrial power distribution.
  • Radial feeder protection.
  • Ring-main and interconnected distribution networks, where suitable functions are available.
  • Transformer feeder protection.
  • Motor and industrial load feeder protection.
  • Feeder automation and control.

The exact application suitability depends on the system voltage, current inputs, available hardware, protection functions, and engineering requirements.

Before selecting an 850, verify the product documentation, order code, CT and VT requirements, communication options, and firmware capabilities.

3. Feeder Protection Philosophy

A feeder protection scheme should detect faults within its protected section and isolate them without unnecessarily interrupting healthy parts of the network.

The protection philosophy normally considers:

  • Maximum load current.
  • Minimum and maximum fault current.
  • Source impedance.
  • Feeder impedance.
  • Earthing arrangement.
  • Downstream protection.
  • Upstream protection.
  • Circuit breaker characteristics.
  • Autoreclosing requirements.

Typical feeder protection functions include:

ANSI functionApplication
50Instantaneous phase overcurrent
51Time phase overcurrent
50N/51NNeutral or residual earth-fault overcurrent
50G/51GGround-fault overcurrent, depending on measurement arrangement
67/67NDirectional phase and earth-fault overcurrent
27/59Undervoltage and overvoltage
81U/81OUnderfrequency and overfrequency
79Autoreclosing
50BFCircuit breaker failure
46Negative-sequence current
49Thermal overload, where provided

Not every function is necessarily available in every 850 configuration. Check the exact relay documentation before preparing a setting schedule.

4. Phase Overcurrent Protection (ANSI 50/51)

Phase overcurrent protection is a fundamental feeder protection function.

It detects excessive phase current caused by short circuits, overloads, and other abnormal operating conditions.

4.1 Instantaneous overcurrent (ANSI 50)

ANSI 50 operates when the measured phase current exceeds a configured pickup threshold.

[
I>I_{50}
]

The pickup must be high enough to avoid unwanted operation for downstream faults outside the intended zone, but low enough to detect the faults for which the element is intended.

4.2 Time overcurrent (ANSI 51)

ANSI 51 provides time-delayed protection.

It may use:

  • Definite-time characteristics.
  • IEC inverse-time characteristics.
  • ANSI/IEEE inverse-time characteristics.
  • Other manufacturer-supported curves.

A commonly used IEC standard inverse equation is:

[
t=\frac{0.14TMS}
{\left(\frac{I}{I_s}\right)^{0.02}-1}
]

where:

  • (t) is operating time.
  • (TMS) is the time multiplier setting.
  • (I) is measured current.
  • (I_s) is pickup current.

This equation applies to the IEC standard inverse curve only. Other curve families use different equations.

4.3 Pickup selection

The pickup should be selected with consideration of:

  • Maximum continuous feeder load.
  • Emergency loading.
  • CT ratio.
  • Minimum fault current.
  • Maximum fault current.
  • Downstream protection.
  • Upstream protection.
  • Conductor thermal limits.

A pickup value should not be selected using rated load current alone.

5. Earth-Fault Protection (ANSI 50N/51N and 50G/51G)

Earth-fault protection detects current flowing through an unintended path to ground.

The appropriate measurement method depends on the system grounding arrangement and CT installation.

5.1 Residual earth-fault measurement

Residual current can be calculated from the three phase currents:

[
I_{\text{res}}=I_A+I_B+I_C
]

Under balanced conditions:

[
I_{\text{res}}\approx0
]

During an earth fault, residual current may increase.

The relay can use this quantity for neutral or residual overcurrent protection, depending on its configuration.

5.2 Core-balance CT measurement

A core-balance CT surrounds all phase conductors and measures the resultant current.

Under healthy conditions, the vector sum of the phase currents is approximately zero.

During an earth fault, the imbalance produces a secondary output.

Core-balance CTs can provide sensitive earth-fault measurement, but their application requires correct conductor routing, CT selection, and wiring.

5.3 System earthing

Earth-fault current depends on the neutral grounding arrangement.

Common systems include:

  • Solidly grounded.
  • Resistance grounded.
  • Reactance grounded.
  • Isolated neutral.
  • Resonant grounded.

The earth-fault pickup and timing must be suitable for the actual system.

A setting appropriate for a solidly grounded system may be unsuitable for a high-resistance-grounded network.

6. Directional Overcurrent Protection (ANSI 67 and 67N)

Directional overcurrent protection is important where fault current can flow in more than one direction.

Applications include:

  • Ring networks.
  • Parallel feeders.
  • Networks with multiple supply sources.
  • Distributed generation connections.
  • Interconnected industrial systems.

6.1 Directional phase overcurrent

ANSI 67 uses current and a suitable polarizing voltage quantity to determine the direction of a phase fault.

The relay evaluates the relationship between current and voltage according to its configured directional characteristic.

6.2 Directional earth-fault protection

ANSI 67N determines the direction of earth-fault current.

Depending on the system and relay design, directional polarization may use residual voltage, negative-sequence quantities, or another supported method.

6.3 Directional settings

Important considerations include:

  • CT polarity.
  • VT polarity.
  • Phase sequence.
  • Polarizing quantity.
  • Characteristic angle.
  • Forward and reverse definitions.
  • Minimum operating current.
  • Voltage supervision.

The exact directional method and available settings must be verified in the 850 documentation.

7. Feeder Coordination and Time-Current Curves

Protection coordination ensures that the relay nearest to a fault operates first, while upstream devices provide backup.

Consider a radial network:

      Utility Source
            |
       Main Breaker
            |
      Upstream Relay
            |
       Distribution
            |
      GE Multilin 850
            |
       MV Feeder
            |
       Downstream
        Protection
            |
          Loads

The 850 setting must coordinate with both upstream and downstream protection devices according to its position in the network.

7.1 Coordination time interval

A coordination time interval (CTI) provides a time margin between primary and backup protection.

The required margin depends on:

  • Relay operating time.
  • Circuit breaker clearing time.
  • Relay overshoot and reset behaviour.
  • CT performance.
  • Protection philosophy.
  • Applicable standards.

There is no single CTI value suitable for every network.

7.2 Time-current curve review

The coordination study should include:

  • Feeder relay curves.
  • Transformer protection curves.
  • Fuse characteristics, where applicable.
  • Upstream relay curves.
  • Cable and conductor thermal limits.
  • Transformer damage curves.
  • Maximum and minimum fault currents.

The complete operating characteristic should be checked across the relevant fault-current range.

8. Practical Feeder Overcurrent Calculation

Consider an 11 kV feeder with:

  • Maximum load current: 180 A.
  • Maximum three-phase fault current: 5,000 A.
  • CT ratio: 300/1 A.

Suppose an illustrative phase overcurrent pickup is selected at 1.25 times the maximum load current for preliminary study.

[
I_{\text{pickup,primary}}=1.25\times180
]

[
I_{\text{pickup,primary}}=225\text{ A}
]

The corresponding relay secondary pickup is:

[
I_{\text{pickup,secondary}}=
\frac{225}{300}
]

[
I_{\text{pickup,secondary}}=0.75\text{ A}
]

The maximum fault current referred to the relay secondary is:

[
I_{\text{fault,secondary}}=
\frac{5000}{300}
]

[
I_{\text{fault,secondary}}\approx16.67\text{ A}
]

This demonstrates the CT scaling process.

The final pickup must also consider minimum fault current, feeder thermal limits, downstream coordination, emergency loading, and the relay’s measurement characteristics.

9. Autoreclosing Protection (ANSI 79)

Autoreclosing is commonly applied to overhead distribution feeders where many faults are temporary.

Examples include:

  • Lightning-related flashovers.
  • Temporary conductor contact.
  • Transient insulation breakdown.
  • Momentary contact with vegetation or other objects.

The autoreclosing function attempts to restore supply after a fault has been cleared and the configured dead time has elapsed.

9.1 Single-shot and multi-shot autoreclosing

A single-shot scheme performs one reclose attempt.

A multi-shot scheme can perform multiple attempts with different dead times and operating conditions.

The number of shots and operating sequence must be determined by the network protection philosophy.

9.2 Dead time

Dead time is the interval between breaker opening and the reclose command.

It must allow sufficient time for the fault arc to deionize and the equipment to recover.

9.3 Reclaim time

Reclaim time defines the period during which the autoreclosing sequence remains active after a successful reclose.

If another fault occurs during this period, the relay may treat it as part of the existing sequence.

9.4 Reclose blocking

Autoreclosing should be blocked for conditions such as:

  • Transformer differential operation.
  • Busbar protection operation.
  • Breaker failure.
  • Manual trip.
  • Lockout relay operation.
  • Certain cable or equipment faults.
  • Other conditions defined by the protection design.

The exact 79 functionality and logic options must be checked against the installed 850 configuration.

10. Circuit Breaker Failure Protection (ANSI 50BF)

Circuit breaker failure protection provides backup when a breaker does not interrupt current after receiving a trip command.

The protection may supervise:

  • Trip initiation.
  • Current persistence.
  • Breaker auxiliary contacts.
  • Breaker failure timer.

A simplified operating condition is:

[
\text{BF}=
\text{Trip Initiated}
\land
\text{Current Persists}
\land
\text{Timer Expired}
]

Actual breaker failure logic may include retrip and backup trip arrangements.

The 850’s support for the required breaker failure logic must be confirmed in the product documentation. External logic or another protection device may be required in some schemes.

11. Voltage and Frequency Protection

Feeder relays may provide voltage and frequency supervision where appropriate hardware and firmware options are available.

11.1 Undervoltage protection (ANSI 27)

Undervoltage protection detects a reduction in measured voltage below a configured threshold.

Applications may include:

  • Motor feeder supervision.
  • Load shedding.
  • Network abnormal-condition detection.
  • Backup voltage protection.

11.2 Overvoltage protection (ANSI 59)

Overvoltage protection detects voltage exceeding the configured threshold.

It may be used for network supervision and equipment protection according to the scheme.

11.3 Frequency protection (ANSI 81)

Underfrequency and overfrequency elements can support load shedding, islanding supervision, and network protection.

The actual availability of these functions in the 850 depends on its configuration.

12. CT and VT Configuration

Correct measurement configuration is essential for reliable feeder protection.

12.1 CT configuration

Verify:

  • CT ratio.
  • Secondary rating.
  • Phase assignment.
  • Polarity.
  • Accuracy class.
  • Relay input rating.
  • Residual or neutral CT arrangement.

For a 300/1 A CT:

[
I_s=\frac{I_p}{300}
]

A primary current of 150 A produces an ideal secondary current of:

[
I_s=\frac{150}{300}=0.5\text{ A}
]

12.2 VT configuration

Where voltage-dependent protection is used, verify:

  • VT ratio.
  • Secondary voltage.
  • Phase-to-phase or phase-to-neutral measurement.
  • Phase sequence.
  • Polarity.
  • VT connection.
  • Voltage scaling.

Directional protection is particularly sensitive to incorrect CT and VT polarity.

13. GE Multilin 850 Configuration Using EnerVista

EnerVista provides engineering facilities for supported GE Multilin relays. The exact software package, menus, and setting names depend on the relay model and firmware.

A general workflow is described below.

Step 1: Confirm the relay

Verify:

  • GE Multilin 850 model and order code.
  • Firmware version.
  • Installed hardware.
  • Current and voltage input availability.
  • Communication options.

Step 2: Create the project

  • Select the correct device.
  • Establish communication.
  • Retrieve the existing settings.
  • Save a backup.
  • Confirm that the project matches the installed relay.

Step 3: Configure CT and VT data

Enter and verify:

  • CT ratios.
  • CT secondary ratings.
  • VT ratios.
  • Phase assignments.
  • Polarity.
  • Voltage references.
  • Residual and neutral current sources.

Step 4: Configure phase overcurrent

Review:

  • ANSI 50 pickup.
  • ANSI 51 pickup.
  • Curve type.
  • Time multiplier.
  • Definite-time delay, where used.
  • Blocking and supervision logic.
  • Output assignments.

Step 5: Configure earth-fault protection

Where supported, configure:

  • Residual or neutral current source.
  • Earth-fault pickup.
  • Operating curve.
  • Time delay.
  • Directional supervision, where applicable.
  • Trip logic.

Step 6: Configure directional protection

Where required and supported, review:

  • Directional element enable status.
  • Polarizing voltage source.
  • Characteristic angle.
  • Forward and reverse definitions.
  • Minimum operating current.
  • Voltage supervision.
  • Trip logic.

Step 7: Configure autoreclosing

Where supported, configure:

  • Reclose enable.
  • Shot sequence.
  • Dead times.
  • Reclaim time.
  • Initiating elements.
  • Blocking conditions.
  • Breaker status inputs.
  • Lockout conditions.

Step 8: Configure communication

Where supported, verify:

  • Ethernet settings.
  • Serial communication.
  • Supported protocols.
  • SCADA data mapping.
  • Time synchronization.
  • Event reporting.

Step 9: Save and verify

  • Save the project.
  • Compare settings with the approved schedule.
  • Download under an approved procedure.
  • Verify final settings.
  • Archive the final project.

14. Communication and Substation Automation Integration

Feeder protection relays may exchange protection and monitoring data with SCADA and substation automation systems.

Depending on the ordered hardware and firmware, supported interfaces and protocols may include:

  • IEC 61850.
  • Modbus.
  • DNP3.
  • Other manufacturer-supported communication options.

The exact supported protocols must be confirmed for the installed 850.

14.1 IEC 61850 integration

Where IEC 61850 is supported, engineering may involve:

  • Logical device configuration.
  • Logical node mapping.
  • Data sets.
  • Report control blocks.
  • MMS communication.
  • GOOSE communication, where supported.
  • SCL file integration.
  • SCADA signal mapping.

14.2 Communication testing

Verify:

  • Network connectivity.
  • IP configuration.
  • Data mapping.
  • Report operation.
  • GOOSE publisher/subscriber configuration where used.
  • Time synchronization.
  • Alarm and event transmission.

15. Testing and Commissioning of the GE Multilin 850

A complete commissioning procedure should verify measurement circuits, protection elements, breaker control, communication, and trip logic.

15.1 Preliminary checks

Inspect:

  • Relay nameplate and order code.
  • Auxiliary supply.
  • Panel wiring.
  • CT and VT circuits.
  • Communication connections.
  • Earthing.
  • Firmware and settings files.

15.2 CT and VT tests

Verify:

  • CT ratios.
  • CT polarity.
  • Phase sequence.
  • Secondary circuit continuity.
  • VT ratio and polarity.
  • Correct relay measurement scaling.

Never open an energized CT secondary circuit.

15.3 Phase overcurrent testing

Test:

  • ANSI 50 pickup.
  • ANSI 50 operating time.
  • ANSI 51 pickup.
  • Inverse-time characteristic.
  • Time multiplier.
  • Reset behaviour.
  • Trip output.

15.4 Earth-fault testing

Verify:

  • Residual or neutral current measurement.
  • Pickup threshold.
  • Operating time.
  • Directional response, where applicable.
  • Trip logic.

15.5 Directional protection testing

Inject suitable current and voltage quantities.

Verify:

  • Forward operation.
  • Reverse restraint.
  • Characteristic angle.
  • Minimum operating current.
  • Voltage supervision.
  • Phase and earth directional functions as applicable.

15.6 Autoreclosing testing

Where supported, test:

  • Reclose initiation.
  • Breaker open feedback.
  • Dead time.
  • Reclose command.
  • Breaker closed feedback.
  • Reclaim time.
  • Shot sequence.
  • Blocking conditions.
  • Lockout after unsuccessful sequence.

15.7 Communication and trip circuit tests

Verify:

  • SCADA status.
  • Alarm indications.
  • Event records.
  • Communication protocols.
  • Breaker trip output.
  • Breaker close command where used.
  • Trip circuit supervision where provided.

16. Practical Commissioning Test Matrix

TestExpected result
CT measurementCorrect phase currents
VT measurementCorrect voltage values and phase relationships
ANSI 50Correct instantaneous pickup and operation
ANSI 51Correct pickup and time-current characteristic
Earth-fault protectionCorrect residual or neutral current response
Directional phase overcurrentCorrect forward/reverse response
Directional earth faultCorrect directional response where supported
AutoreclosingCorrect sequence and timing where supported
Breaker failureCorrect initiation and backup logic where provided
CommunicationCorrect data and status transfer
Trip circuitCorrect breaker trip operation
Event recordingCorrect fault and operation records

17. Common Problems and Troubleshooting

Problem 1: Phase overcurrent operates during normal loading

Possible causes:

  • Incorrect CT ratio.
  • Incorrect current scaling.
  • Pickup too low.
  • Incorrect phase assignment.
  • Actual feeder overload.

Recommended checks:

  • Verify CT ratio and polarity.
  • Compare relay measurements with an independent instrument.
  • Review load current and approved settings.
  • Confirm the correct setting group is active.

Problem 2: Earth-fault protection does not detect a fault

Possible causes:

  • Incorrect residual CT wiring.
  • Incorrect core-balance CT installation.
  • Pickup too high.
  • Wrong neutral grounding assumptions.
  • Incorrect input assignment.

Recommended checks:

  • Verify CT wiring and polarity.
  • Confirm the selected measurement method.
  • Review minimum earth-fault current.
  • Check the actual grounding arrangement.

Problem 3: Directional protection operates in the wrong direction

Possible causes:

  • CT polarity error.
  • VT polarity error.
  • Incorrect phase sequence.
  • Incorrect characteristic angle.
  • Incorrect forward/reverse definition.

Recommended checks:

  • Verify CT and VT circuits.
  • Check phasor measurements.
  • Perform forward and reverse injection tests.
  • Confirm the directional reference in the relay manual.

Problem 4: Autoreclosing does not operate

Possible causes:

  • Reclose function disabled.
  • Initiating element not assigned.
  • Reclose blocked.
  • Breaker status input incorrect.
  • Lockout active.
  • Incorrect dead-time or shot configuration.

Recommended checks:

  • Review autoreclose status.
  • Check the initiation and blocking logic.
  • Verify breaker auxiliary contacts.
  • Test the sequence using the approved procedure.

Problem 5: SCADA communication is unavailable

Possible causes:

  • Incorrect IP address.
  • Network configuration problem.
  • Incorrect protocol settings.
  • Wrong data mapping.
  • Communication hardware or firmware limitation.

Recommended checks:

  • Verify network connectivity.
  • Check supported protocol options.
  • Review relay communication diagnostics.
  • Confirm SCADA data mapping.

18. Practical Engineering Checklist

Feeder data

  • Feeder voltage and load current confirmed.
  • Maximum and minimum fault currents calculated.
  • System earthing arrangement documented.
  • Upstream and downstream protection identified.
  • Breaker ratings and operating times verified.

Measurement configuration

  • CT ratios confirmed.
  • CT polarity checked.
  • VT ratios verified where applicable.
  • Phase sequence confirmed.
  • Residual or neutral CT arrangement checked.

Protection settings

  • ANSI 50 pickup approved.
  • ANSI 51 curve and time multiplier approved.
  • Earth-fault settings coordinated.
  • Directional settings verified where required.
  • Autoreclosing philosophy approved where applicable.
  • Breaker failure logic reviewed.

Commissioning

  • CT and VT tests completed.
  • Phase overcurrent tested.
  • Earth-fault protection tested.
  • Directional protection tested where applicable.
  • Autoreclosing sequence tested where supported.
  • Trip circuit tested.
  • Communication verified.
  • Final settings and reports archived.

19. Training on GE Multilin Feeder Protection by Elec-Engg

Practical feeder protection engineering requires an understanding of CT and VT configuration, phase and earth-fault protection, directional characteristics, time-current coordination, autoreclosing, breaker failure, and secondary injection testing.

Elec-Engg provides practical technical training by Dr Saeed Roostaee (Electrical Engineering) for engineers working in power system protection, commissioning, operation, maintenance, and substation automation.

Relevant training subjects include:

  • GE Multilin 850 feeder protection.
  • ANSI 50/51 phase overcurrent protection.
  • Earth-fault protection (ANSI 50N/51N and 50G/51G).
  • Directional overcurrent protection (ANSI 67/67N).
  • Time-current coordination and grading.
  • Autoreclosing protection (ANSI 79).
  • Circuit breaker failure protection (ANSI 50BF).
  • CT and VT configuration.
  • EnerVista configuration and troubleshooting.
  • Omicron secondary injection testing and commissioning.
  • IEC 61850 and SCADA integration where supported.

Training delivery options include pre-recorded video courses, structured self-paced training, live online training, face-to-face technical training, and customized in-house programmes.

Visit Elec-Engg or contact us to discuss practical feeder protection training.

20. Conclusion

The GE Multilin 850 is a feeder protection platform intended for distribution and industrial feeder applications.

Effective application requires accurate CT and VT configuration, appropriate phase and earth-fault protection settings, directional supervision where necessary, and proper coordination with upstream and downstream devices.

Autoreclosing and breaker failure functions can further improve feeder protection and system reliability where they are supported and correctly engineered.

Commissioning should include measurement verification, pickup and timing tests, directional tests, autoreclosing tests, communication checks, and complete breaker trip verification.

Always verify the exact protection functions, hardware options, and setting definitions against the official GE Multilin 850 documentation for the installed model and firmware.

21. Frequently Asked Questions (FAQs)

1. What is the GE Multilin 850?

The GE Multilin 850 is a feeder protection relay in the GE Multilin 8 Series family, intended for distribution and industrial feeder protection applications.

2. Which protection functions are used in feeder applications?

Typical functions include phase overcurrent, earth-fault protection, directional overcurrent, voltage and frequency protection, autoreclosing, and breaker failure. Actual availability depends on the relay configuration.

3. What is the difference between ANSI 50 and ANSI 51?

ANSI 50 is instantaneous overcurrent protection, while ANSI 51 provides time-delayed overcurrent protection.

4. When is directional overcurrent protection required?

Directional overcurrent protection is useful in ring networks, parallel feeders, multi-source systems, and networks where fault current can flow in different directions.

5. What is the difference between residual CT and core-balance CT measurement?

Residual measurement calculates the vector sum of three phase currents. A core-balance CT measures the resultant current by surrounding all relevant phase conductors with one CT.

6. Does the GE Multilin 850 support autoreclosing?

Autoreclosing capability and available sequence options must be confirmed against the exact 850 model, hardware, and firmware documentation.

7. Why is time-current coordination important?

Coordination ensures that the protection device closest to the fault operates first, while upstream devices provide backup without unnecessarily disconnecting healthy sections.

8. Can the GE Multilin 850 communicate using IEC 61850?

Protocol availability depends on the installed hardware and firmware. Check the applicable product documentation before designing the communication system.

9. How is feeder overcurrent protection tested?

Testing normally includes CT measurement verification, pickup testing, operating-time measurement, curve testing, trip logic verification, and breaker trip testing.

10. Which software is used to configure the GE Multilin 850?

EnerVista software is used for supported GE Multilin relay families. Confirm the compatible software package and version for the installed relay.

GE Multilin 850, GE 850 feeder protection relay, GE Multilin feeder relay, feeder protection, ANSI 50/51, ANSI 50N/51N, ANSI 67/67N, directional overcurrent protection, ANSI 79 autoreclosing, ANSI 50BF, EnerVista 850, feeder protection coordination, GE Multilin relay testing, feeder protection training.