IEC 61850 Time Synchronization in MiCOM Relays: SNTP, PTP, IRIG-B, Event Timestamps and Disturbance Analysis

Table Of Contents

Introduction

Accurate time synchronization is an essential requirement in modern digital substations. Protection relays, bay control units, disturbance recorders, SCADA servers and other Intelligent Electronic Devices (IEDs) must maintain a consistent time reference to ensure that events recorded by different devices can be correctly correlated.

In a MiCOM-based substation, time synchronization is particularly important for:

  • Sequence of Events (SOE) analysis.
  • Protection event records.
  • Fault and disturbance investigation.
  • Circuit breaker operation analysis.
  • IEC 61850 MMS reporting.
  • GOOSE event correlation.
  • SCADA alarm management.
  • Comparison of records from multiple protection relays.

IEC 61850 supports the exchange of time-related information, but the actual time synchronization method depends on the relay hardware, firmware and project architecture.

Common technologies used in substation time synchronization include SNTP, PTP and IRIG-B.

This article explains these technologies, their applications in MiCOM protection relays, practical engineering considerations and commissioning procedures.

Important: Not every MiCOM relay supports every synchronization method. Always verify the exact model, order code, communication hardware, firmware and supported synchronization interfaces using the manufacturer’s documentation.

1. Why Time Synchronization Is Important in Protection Systems

Consider a substation with several protection relays connected to the same electrical network.

A fault occurs on an outgoing feeder. Several devices may record related events:

  1. The feeder relay detects an overcurrent condition.
  2. The protection function issues a trip command.
  3. The circuit breaker opens.
  4. The upstream relay records a change in current.
  5. The station SCADA system receives the protection indication.
  6. A disturbance recorder captures the fault waveform.

If the clocks of these devices are not synchronized, their event records may show inconsistent times.

This makes it difficult to determine:

  • Which protection function operated first.
  • Whether the breaker opened within the expected time.
  • Whether the upstream protection operated as backup.
  • Whether a communication delay affected the event sequence.
  • How the fault developed across the substation.

Accurate synchronization allows engineers to compare records using a common time reference.

2. Understanding Time Synchronization Architecture

A typical substation time synchronization architecture contains a central time source that distributes time information to connected devices.

A simplified arrangement is:

              GNSS / GPS ANTENNA
                      |
                MASTER CLOCK
                      |
          -------------------------
          |           |           |
         SNTP        PTP        IRIG-B
          |           |           |
       Ethernet   Ethernet     Dedicated
          |           |         Interface
          |           |           |
       MiCOM       MiCOM        Protection
       Relay 1     Relay 2      Devices
          |           |           |
          -------- SUBSTATION -----
                 TIME REFERENCE

The diagram represents possible synchronization paths. An actual installation may use only one method or a combination of technologies.

Main components

ComponentFunction
GNSS antennaReceives satellite timing information
Master clockGenerates and distributes the reference time
SNTP serverProvides time over an IP network
PTP grandmasterDistributes precision time using PTP
Ethernet switchCarries synchronization messages
IRIG-B distribution equipmentDistributes a timing signal over dedicated connections
MiCOM relaySynchronizes its internal clock using supported methods

The master clock should be selected and configured according to the required accuracy and the synchronization capabilities of the connected devices.

3. SNTP Time Synchronization

SNTP stands for Simple Network Time Protocol.

It is a simplified form of Network Time Protocol used to synchronize clocks over IP networks.

SNTP is commonly used in industrial automation and substation systems where millisecond-level synchronization may be sufficient.

3.1 How SNTP works

The SNTP client periodically communicates with an SNTP server to obtain time information.

A simplified communication process is:

  1. The relay is configured with the IP address of an SNTP server.
  2. The relay sends a time request.
  3. The server responds with time information.
  4. The relay adjusts its internal clock.
  5. The process repeats according to the configured synchronization interval.

3.2 SNTP configuration parameters

Depending on the relay implementation, configuration may include:

  • SNTP enable/disable.
  • Primary time server IP address.
  • Secondary time server IP address.
  • Synchronization interval.
  • UTC configuration.
  • Time zone settings.
  • Synchronization status.

An illustrative configuration is:

ParameterExample
SNTP server192.168.10.100
Secondary server192.168.10.101
Time referenceUTC
Synchronization methodSNTP
NetworkStation Ethernet

These values are examples only and must be adapted to the actual substation network.

3.3 Advantages of SNTP

  • Uses an existing Ethernet network.
  • Relatively simple configuration.
  • Suitable for many monitoring and event-recording applications.
  • Does not require a dedicated timing cable to every relay.

3.4 Limitations of SNTP

SNTP generally provides lower timing accuracy than properly engineered precision time synchronization systems.

Accuracy depends on factors such as:

  • Network delay.
  • Network congestion.
  • Server performance.
  • Client implementation.
  • Synchronization interval.
  • Device clock characteristics.

For applications requiring high-precision time synchronization, engineers should evaluate PTP or a suitable dedicated timing interface.

4. PTP – Precision Time Protocol

PTP stands for Precision Time Protocol.

It is defined by IEEE 1588 and is designed to provide accurate time synchronization over packet-based networks.

PTP can achieve substantially better synchronization accuracy than ordinary SNTP when the complete system is correctly engineered.

It is particularly relevant in applications involving:

  • High-precision event recording.
  • Sampled Values.
  • Process bus architectures.
  • Time-critical measurement systems.
  • Coordinated protection and monitoring.

4.1 PTP architecture

A typical PTP network includes:

  • Grandmaster clock.
  • Boundary clocks.
  • Transparent clocks.
  • Ordinary clocks.
  • Ethernet network infrastructure.

Grandmaster clock: Provides the primary time reference.

Boundary clock: Receives time from an upstream PTP clock and distributes it to downstream devices.

Transparent clock: Measures the time a PTP message spends passing through network equipment and accounts for this delay.

Ordinary clock: A device that participates in PTP as a time source or time receiver.

4.2 PTP message exchange

PTP uses timing messages to calculate clock offset and network delay.

Important message types include:

  • Sync.
  • Follow_Up.
  • Delay_Req.
  • Delay_Resp.
  • Announce.

The exact message sequence depends on the selected PTP profile and implementation.

The synchronization process allows a receiving device to estimate the difference between its local clock and the reference clock.

4.3 PTP profiles

Different PTP profiles are designed for different application requirements.

In power utility automation, IEC/IEEE 61850-9-3 defines a PTP profile for power utility automation.

Engineers must verify that the grandmaster, network switches and receiving IEDs support compatible PTP profiles.

Do not assume that two devices supporting IEEE 1588 automatically interoperate with identical performance. Profile, transport, delay mechanism and configuration compatibility matter.

4.4 PTP configuration considerations for MiCOM relays

Before using PTP, verify:

  • Whether the relay supports PTP.
  • Supported IEEE 1588 version.
  • Supported PTP profile.
  • Supported transport mechanism.
  • Ethernet interface requirements.
  • Grandmaster compatibility.
  • Switch compatibility.
  • Required synchronization accuracy.

PTP should not be presented as a universal feature of all MiCOM protection relays.

5. IRIG-B Time Synchronization

IRIG-B is a standardized time-code format commonly used in electrical substations and protection systems.

It can distribute time information through a dedicated timing connection.

IRIG-B is often used with:

  • Protection relays.
  • Disturbance recorders.
  • Digital fault recorders.
  • Sequence-of-events systems.
  • Other substation monitoring equipment.

5.1 How IRIG-B works

A master clock generates an IRIG-B time-code signal.

The signal is distributed to connected devices through suitable cables and interfaces.

The receiving relay decodes the time information and updates its internal clock.

5.2 IRIG-B signal formats

IRIG-B has different signal formats and implementations.

Common distinctions include:

  • Modulated IRIG-B.
  • Unmodulated IRIG-B.
  • DCLS signal.
  • AM signal.
  • With or without additional time information, depending on implementation.

The receiving relay must support the selected signal type and electrical interface.

5.3 Advantages of IRIG-B

  • Dedicated time distribution.
  • Widely used in protection and disturbance recording systems.
  • Does not depend on normal Ethernet traffic.
  • Can provide accurate synchronization when properly implemented.

5.4 Limitations of IRIG-B

  • Requires dedicated wiring and distribution equipment.
  • Signal type must match the receiving device.
  • Cable and interface limitations must be considered.
  • Installation and maintenance can become more complex in large substations.

6. Comparison of SNTP, PTP and IRIG-B

CharacteristicSNTPPTPIRIG-B
Communication mediumEthernet/IPEthernetDedicated timing connection
Main standardRFC 4330IEEE 1588IRIG Standard 200-04
Typical applicationGeneral clock synchronizationPrecision network synchronizationDedicated substation timing
Network dependencyYesYesNo normal IP dependency
Timing accuracyGenerally lowerPotentially very highDepends on signal and implementation
Network switch requirementsStandard IP networkCompatible PTP networkNot applicable to timing signal path
Configuration complexityRelatively lowHigherModerate
MiCOM availabilityModel-dependentModel-dependentModel-dependent

There is no universal rule that one method is always best. The selection should be based on application requirements, device capabilities, network design and required synchronization accuracy.

7. UTC, Local Time and Time Zones

One of the most common sources of confusion in substation time synchronization is the difference between UTC and local time.

UTC is the international time reference used by many power system automation applications.

Local time includes the time-zone offset and may also include daylight-saving adjustments in some countries.

For example:

  • UTC: 08:00
  • Local time: 12:00
  • Offset: UTC+4

The actual time-zone configuration must reflect the project location and operating requirements.

7.1 Why UTC is important

Using UTC as a common reference makes it easier to compare event records from different locations and devices.

A protection relay in one country and a disturbance recorder in another can use the same UTC reference even if their local clocks display different times.

7.2 Engineering considerations

Check:

  • UTC versus local-time configuration.
  • Time-zone offset.
  • Daylight-saving handling.
  • Timestamp interpretation in SCADA.
  • Event-recording format.
  • Time synchronization status.

A relay can be accurately synchronized but still display an apparently incorrect time if the time-zone configuration is misunderstood.

8. IEC 61850 Timestamps and Quality Information

IEC 61850 data objects may include a timestamp attribute identified as t.

The timestamp provides time-related information associated with the value or event.

Quality information is commonly represented by q.

These attributes are important when SCADA systems receive data through MMS reports or when engineers analyze event information.

8.1 Timestamp components

IEC 61850 timestamps can contain:

  • Date.
  • Time.
  • Fractional seconds.
  • Time-quality information.

The timestamp structure also carries information relevant to synchronization quality.

8.2 Time-quality information

Time-quality information can indicate conditions such as:

  • Whether the time is synchronized.
  • Whether the time is reliable.
  • Whether clock failure has occurred.
  • Whether the time accuracy is known or specified.

The precise interpretation should follow the relevant IEC 61850 data type and device implementation.

8.3 Why timestamp quality matters

Suppose a MiCOM relay reports a breaker opening event at 10:15:32.250.

If the time source is unreliable, the displayed timestamp may not be sufficiently accurate for detailed sequence-of-events analysis.

SCADA engineers should therefore consider both the timestamp and its associated quality information where exposed.

9. Practical Example: Synchronizing MiCOM Relays Using SNTP

Consider a substation with four MiCOM protection relays connected to a station Ethernet network.

The project uses a central SNTP server.

Network arrangement

DeviceIP address
SNTP server192.168.10.100
MiCOM Feeder Relay 1192.168.10.21
MiCOM Feeder Relay 2192.168.10.22
MiCOM Transformer Relay192.168.10.23
MiCOM Busbar Relay192.168.10.24

All IP addresses are illustrative.

Step 1 – Check relay support

Confirm that each relay supports SNTP and identify the correct configuration procedure.

Do not assume that all four relays use identical menus or parameter names.

Step 2 – Configure the time server

Enter the approved SNTP server address in each relay.

If supported, configure a secondary time server.

Step 3 – Check network connectivity

Confirm that the relay can communicate with the SNTP server.

Check the relevant network path, routing and any access-control rules.

Step 4 – Verify synchronization

Use the relay’s diagnostic or status information to check whether synchronization has been established.

Step 5 – Compare relay clocks

Compare the clocks of all connected devices against the master reference.

Step 6 – Verify event timestamps

Generate suitable test events under an approved test procedure and compare their recorded timestamps.

The objective is to verify that the relays use a consistent time reference and that their event records can be correctly correlated.

10. Practical Example: Investigating an Incorrect Event Sequence

Assume a feeder protection relay and an upstream transformer protection relay record the following events:

DeviceEventRecorded time
Feeder relayOvercurrent start14:20:15.120
Feeder relayTrip command14:20:15.180
Feeder relayBreaker open14:20:15.260
Transformer relayCurrent disturbance14:20:15.100

At first glance, the transformer relay appears to have recorded a disturbance before the feeder relay detected the fault.

However, this does not necessarily mean the transformer protection system operated first.

Possible causes include:

  • Different clock offsets.
  • Incorrect synchronization.
  • Different timestamp sources.
  • Event-processing delays.
  • SCADA reception timestamps being confused with source timestamps.
  • Incorrect time-zone configuration.

The engineer should verify the clock status and timestamp quality of each device before drawing conclusions about the protection sequence.

11. Troubleshooting Time Synchronization in MiCOM Relays

ProblemPossible causeRecommended checks
Relay clock is incorrectWrong time source or configurationCheck server address and synchronization settings
Relay is not synchronizedNetwork or interface problemCheck communication path and relay diagnostics
Different relays show different timesDifferent sources or clock offsetsCompare synchronization source and UTC settings
Event timestamps are inconsistentClock accuracy or timestamp configurationCheck time quality and synchronization status
SNTP synchronization failsServer unavailable or network blockedCheck IP connectivity and network access rules
PTP synchronization failsProfile or configuration mismatchCheck grandmaster, profile and switch compatibility
IRIG-B signal is not detectedWrong signal type or wiringCheck signal format, polarity and interface
Time changes unexpectedlyMultiple time sources or configuration conflictReview synchronization architecture
SCADA displays an incorrect timeTime-zone or timestamp conversion issueCheck UTC and local-time handling

Useful engineering checks

For Ethernet-based synchronization, inspect:

  • Network connectivity.
  • IP configuration.
  • Firewall and access-control rules.
  • Time-server availability.
  • PTP message reception, where applicable.
  • Switch configuration.
  • Relay synchronization diagnostics.

For IRIG-B, inspect:

  • Master clock output.
  • Signal type.
  • Cable continuity.
  • Connector condition.
  • Signal level and waveform.
  • Relay input configuration.

12. Time Synchronization Commissioning Checklist

Master clock

  • Confirm the master clock installation.
  • Verify GNSS antenna and satellite reception, if used.
  • Check the selected time reference.
  • Confirm UTC configuration.
  • Verify available synchronization outputs.
  • Record master clock status.

MiCOM relay configuration

  • Confirm relay model and firmware.
  • Verify supported synchronization methods.
  • Configure the correct time source.
  • Check primary and secondary servers, where applicable.
  • Confirm the correct signal type for IRIG-B, if used.
  • Verify synchronization status.

Network synchronization

  • Check network connectivity.
  • Verify SNTP server availability.
  • Check PTP profile compatibility, if used.
  • Verify switch support and configuration.
  • Confirm that network policies allow the required traffic.

Functional testing

  • Compare relay clocks against the master reference.
  • Generate test events.
  • Compare event timestamps between IEDs.
  • Check time-quality information.
  • Verify SCADA timestamp interpretation.
  • Record synchronization accuracy and test results.

13. Best Practices for Substation Time Synchronization

For reliable time synchronization in MiCOM-based substations:

  1. Define the required timing accuracy before selecting the technology.
  2. Use a common and properly maintained time reference.
  3. Verify the capabilities of every installed IED.
  4. Keep UTC and local-time configuration consistent.
  5. Avoid conflicting or unintended time sources.
  6. Monitor synchronization status.
  7. Verify timestamp quality where available.
  8. Test event correlation between different devices.
  9. Document master clock settings and network architecture.
  10. Include time synchronization checks in periodic maintenance.

For high-accuracy applications, the complete timing chain must be evaluated. A high-precision grandmaster alone does not guarantee high accuracy at every receiving relay.

14. Conclusion

Time synchronization is a fundamental requirement for reliable protection event recording and disturbance analysis in digital substations.

SNTP provides a practical network-based synchronization method, PTP offers precision synchronization for supported systems, and IRIG-B provides dedicated time distribution through a separate interface.

For MiCOM protection relays, the correct solution depends on the specific relay model, hardware, firmware and project requirements.

Commissioning engineers should verify not only that the relay displays the correct time but also that its event timestamps are consistent, synchronized and suitable for protection sequence analysis.

Accurate time synchronization makes it possible to reconstruct fault events, compare protection operations and investigate substation disturbances with greater confidence.

Practical MiCOM Protection and IEC 61850 Training by Dr Saeed Roostaee – Elec-Engg

Elec-Engg provides practical training for protection, commissioning and substation automation engineers.

Relevant training topics include:

  • MiCOM protection relay configuration.
  • IEC 61850 communication and engineering.
  • MMS and GOOSE communication.
  • SNTP and substation time synchronization.
  • IEC 61850 timestamps and quality information.
  • SCL configuration and system integration.
  • Protection event analysis and troubleshooting.
  • Practical commissioning procedures.

Training is available through video courses, structured self-paced training, face-to-face courses and customized in-house programs.

Visit Elec-Engg for practical power system protection and substation automation training.