MiCOM IEC 61850 Data Model Explained: Logical Devices, Logical Nodes, Data Objects, Functional Constraints and Practical Examples

1. Introduction

Understanding the IEC 61850 data model is essential when configuring, testing and integrating MiCOM protection relays into modern substation automation systems.

IEC 61850 does not simply transfer electrical measurements and protection signals as unstructured data points. It organizes information into a standardized object-oriented structure consisting of logical devices, logical nodes, data objects and data attributes.

This structure allows different systems, such as MiCOM protection relays, Siemens SICAM PAS, SCADA servers and engineering tools, to exchange information using a common communication model.

For protection and commissioning engineers, understanding this structure is particularly important when:

  • Configuring IEC 61850 communication in MiCOM relays
  • Identifying protection indications
  • Mapping measurements into SCADA
  • Configuring MMS datasets and reports
  • Engineering GOOSE communication
  • Reviewing ICD and SCD files
  • Troubleshooting missing or incorrect data points
  • Testing IEC 61850 communication with Wireshark and IED simulation tools

This article explains the IEC 61850 data model from a practical engineering perspective, with examples relevant to MiCOM protection relays.

Important: The logical nodes and data references shown are standard examples. Their availability and exact implementation must be verified against the specific MiCOM model, order code, firmware and IEC 61850 documentation.

2. What Is the IEC 61850 Data Model?

The IEC 61850 data model defines how information inside an Intelligent Electronic Device (IED) is organized and identified.

For example, a MiCOM feeder protection relay may contain information about:

  • Phase currents
  • Voltages
  • Frequency
  • Overcurrent protection
  • Earth fault protection
  • Circuit breaker position
  • Protection trip commands
  • Device alarms
  • Communication status

IEC 61850 organizes these functions into logical nodes and data objects.

The main hierarchy is:

Substation
   |
   +-- IED
        |
        +-- Logical Device
              |
              +-- Logical Node
                    |
                    +-- Data Object
                          |
                          +-- Data Attribute

Each level has a specific role.

ElementDescription
SubstationOverall electrical installation
IEDIntelligent electronic device
Logical DeviceLogical grouping of related functions
Logical NodeStandardized functional element
Data ObjectInformation associated with a function
Data AttributeIndividual value or property

This structure allows an IEC 61850 client to identify and access information without relying exclusively on manufacturer-specific point names.

3. Intelligent Electronic Device (IED)

An IED is a device that performs protection, control, monitoring or automation functions.

Examples include:

  • MiCOM feeder protection relays
  • MiCOM distance protection relays
  • MiCOM transformer protection relays
  • Siemens SIPROTEC relays
  • ABB protection and control IEDs
  • SEL protection relays
  • Bay control units
  • Merging units

In an IEC 61850 system, an IED is represented through its logical structure and communication access points.

For example:

IED Name: MiCOM_FEEDER_01

   Access Point: Ethernet1

      Server
         |
         +-- Logical Device
                |
                +-- Logical Node
                +-- Logical Node
                +-- Logical Node

An IED name identifies the device within the SCL engineering project.

It is important to distinguish the IED name from its IP address. The IED name is part of the IEC 61850 configuration, while the IP address identifies its network interface.

4. Logical Devices (LD)

A Logical Device is a logical grouping of functions within an IED.

A physical MiCOM relay may contain one or more logical devices depending on its implementation.

For example, a simplified relay structure might be:

MiCOM_FEEDER_01
 |
 +-- ProtectionLD
 |      |
 |      +-- PTOC
 |      +-- PIOC
 |      +-- PTRC
 |
 +-- MeasurementLD
 |      |
 |      +-- MMXU
 |
 +-- ControlLD
        |
        +-- XCBR
        +-- CSWI

This is an illustrative organization, not a guaranteed MiCOM implementation.

Logical devices help organize related functions and provide a structured way to access the IED’s data.

4.1 Logical Device Naming

Logical devices are identified using names defined in the IED configuration.

For example:

  • PROT
  • MEAS
  • CTRL

These are illustrative names only.

The actual logical device names must be obtained from the device data model or SCL description.

5. Logical Nodes (LN)

A Logical Node represents a standardized function within an IED.

Logical nodes are one of the most important concepts in IEC 61850.

Instead of defining every manufacturer’s protection function using completely different names, IEC 61850 provides standardized logical-node classes for common functions.

For example:

Logical NodeDescription
PTOCTime overcurrent protection
PIOCInstantaneous overcurrent protection
PDISDistance protection
PDIFDifferential protection
MMXUMeasurement functions
XCBRCircuit breaker
XSWISwitch or disconnector
CSWISwitching control
PTRCProtection trip conditioning
RRECAutomatic reclosing
GGIOGeneric input/output
LPHDPhysical device information
LLN0Logical device common information

These standardized names make IEC 61850 data models easier to understand across different manufacturers.

5.1 Protection Logical Nodes

Protection logical nodes represent protection functions.

Common examples include:

PTOC – Time Overcurrent Protection

Used to represent time-delayed overcurrent protection functions.

PIOC – Instantaneous Overcurrent Protection

Used to represent instantaneous overcurrent protection functions.

PDIS – Distance Protection

Used to represent distance protection functions.

PDIF – Differential Protection

Used to represent differential protection functions.

PTRC – Protection Trip Conditioning

Used to represent protection trip conditioning and related information.

RREC – Automatic Reclosing

Used to represent automatic reclosing functions.

The presence of a logical node does not automatically mean that all its optional data objects are implemented in a particular MiCOM relay.

6. Measurement Logical Nodes

Electrical measurements are commonly represented using measurement-related logical nodes.

The most familiar example is MMXU.

6.1 MMXU – Measurement

MMXU represents three-phase electrical measurements and related quantities.

Depending on the implementation, it may provide:

  • Phase currents
  • Phase-to-phase voltages
  • Phase-to-neutral voltages
  • Active power
  • Reactive power
  • Apparent power
  • Power factor
  • Frequency

A simplified representation is:

MMXU
 |
 +-- Current
 |
 +-- Voltage
 |
 +-- Active Power
 |
 +-- Reactive Power
 |
 +-- Frequency

For a MiCOM feeder relay, the engineer may use MMXU information to transfer phase current and voltage measurements to SICAM PAS or another SCADA system.

6.2 Measurement Quality

Measurement values should be evaluated together with their quality information.

IEC 61850 uses the q attribute to indicate the quality of a data value.

For example, a measurement may have an invalid or questionable quality state even when a numerical value is available.

SCADA systems should handle quality information correctly rather than displaying every received value as valid.

7. Switching and Circuit Breaker Logical Nodes

Switching information is particularly important in protection and control systems.

Common switching-related logical nodes include:

Logical NodeFunction
XCBRCircuit breaker
XSWISwitch or disconnector
CSWISwitching control
CILOInterlocking
CPOWPoint-on-wave switching, where implemented

7.1 XCBR – Circuit Breaker

XCBR represents circuit breaker information.

Typical information may include:

  • Breaker position
  • Breaker operating information
  • Breaker health or related status
  • Supported control-related information

A simplified example:

XCBR
 |
 +-- Position
 |
 +-- Operating Information
 |
 +-- Status Information

The exact data objects and attributes depend on the IED implementation.

7.2 CSWI – Switching Control

CSWI represents switching control functionality.

It is associated with control operations such as:

  • Circuit breaker opening
  • Circuit breaker closing
  • Switch operation

The actual control capability depends on the relay configuration, control model and application logic.

7.3 XSWI – Switch or Disconnector

XSWI represents switchgear information for switching devices other than circuit breakers, depending on the equipment and implementation.

For example, a substation disconnector may be represented through XSWI.

8. Data Objects (DO)

A Logical Node contains one or more Data Objects.

A Data Object represents a particular item of information within the logical node.

For example, an MMXU logical node may contain data objects for current, voltage, power and frequency.

A protection logical node may contain data objects representing protection operation and settings.

A circuit breaker logical node may contain data objects representing position and related information.

A simplified structure is:

Logical Node: MMXU
       |
       +-- A
       |
       +-- PhV
       |
       +-- W
       |
       +-- Hz

These are common IEC 61850 data-object names, but the exact availability and content must be checked against the device model.

8.1 Data Object Examples

Logical NodeData Object exampleMeaning
MMXUACurrent
MMXUPhVPhase voltage
MMXUWActive power
MMXUHzFrequency
XCBRPosPosition
PTOCStrStart information
PTOCOpOperation information

The names above illustrate common IEC 61850 concepts. The complete reference must include the logical device and actual logical-node instance.

9. Data Attributes (DA)

A Data Object contains Data Attributes.

These attributes represent individual values, status information, configuration information or other properties.

For example, a switching position data object may contain:

  • stVal – Status value
  • q – Quality
  • t – Timestamp

A measurement data object may contain:

  • mag – Magnitude
  • q – Quality
  • t – Timestamp

The exact attributes depend on the data object and its Common Data Class.

9.1 Example: Circuit Breaker Position

A simplified circuit breaker position representation is:

XCBR
 |
 +-- Pos
       |
       +-- stVal
       +-- q
       +-- t

Here:

  • stVal represents the position state.
  • q represents quality.
  • t represents the associated timestamp.

The actual position encoding and status interpretation must be handled according to the IEC 61850 data type and device implementation.

9.2 Example: Current Measurement

A simplified current measurement representation is:

MMXU
 |
 +-- A
       |
       +-- phsA
       |     |
       |     +-- mag
       |
       +-- phsB
       |     |
       |     +-- mag
       |
       +-- phsC
             |
             +-- mag

This illustrates how phase current information may be organized.

Actual references and available phases depend on the relay implementation.

10. Common Data Classes (CDC)

IEC 61850 uses Common Data Classes to define the structure and meaning of data objects.

A CDC specifies the attributes and data types associated with a particular category of information.

Examples include:

CDCTypical use
SPSSingle-point status
DPSDouble-point status
INSInteger status
ENSEnumerated status
MVMeasured value
CMVComplex measured value
WYEThree-phase measurements
DELDelta-connected measurements
SPS/ACT-related structuresStatus and operation information, depending on the data model
SPCControllable single-point
DPCControllable double-point
INCControllable integer

The exact CDC used depends on the data object defined in the IEC 61850 model.

Understanding CDCs is useful when mapping relay data into SCADA databases because it helps engineers identify the nature and structure of each data object.

11. Functional Constraints (FC)

Functional Constraints identify the purpose or use of a data attribute.

They help distinguish measurements, status values, control information and configuration parameters.

Common functional constraints include:

FCMeaningTypical application
STStatusBreaker position
MXMeasurementCurrent and voltage
COControlSwitching command
SPSetpointSetpoint value
CFConfigurationConfigurable parameters
DCDescriptionDescriptive information
RPUnbuffered reportingReport configuration
BRBuffered reportingBuffered report configuration
SGSetting groupSetting group information
SESetting group editSetting group editing
SVSubstitutionSubstituted values
BLBlockingBlocking information
OROperational restrictionOperational restriction information

Not every FC applies to every logical node or data object.

11.1 Why Functional Constraints Matter

Consider a circuit breaker position and a circuit breaker control command.

Although both relate to the same physical circuit breaker, they represent different information.

  • Position is status information.
  • Control is an operation request.

Using the wrong functional constraint can result in incorrect data access or control configuration.

12. IEC 61850 Object Reference Structure

An IEC 61850 data reference identifies a specific item in the IED data model.

A typical structure is:

IEDName
   LogicalDevice
      LogicalNode
         DataObject
            DataAttribute

For example, an illustrative reference may look like:

MiCOM_FEEDER_01/PROT1.PTOC1.Op.general

This is a conceptual example, not a guaranteed MiCOM reference.

The components represent:

  • MiCOM_FEEDER_01 – IED name
  • PROT1 – Logical device
  • PTOC1 – Logical node instance
  • Op – Operation data object
  • general – Data attribute

The exact reference must be taken from the relay’s actual IEC 61850 data model.

12.1 Why Exact References Are Important

A SCADA system cannot reliably access a data point if the configured reference does not match the server’s actual data model.

For example, using the wrong logical device name, logical-node instance or data attribute may cause:

  • Failed data access
  • Missing measurements
  • Reports not received
  • Incorrect point mapping
  • Failed control operations

Always verify references against the actual device description and online data model.

13. IEC 61850 Data Model and MMS Communication

MMS is used to access IEC 61850 server data and services.

A typical architecture is:

           SICAM PAS
          MMS Client
               |
               |
          Ethernet
               |
               |
         MiCOM Relay
          MMS Server
               |
               |
         IEC 61850 Model

The client may perform supported services such as:

  • Association establishment
  • Server and logical-device discovery
  • Logical-node discovery
  • Data-object access
  • Data reads
  • Reporting
  • Supported control operations

The actual services available depend on the relay implementation.

13.1 MMS Data Access

When an MMS client requests a measurement, it uses the corresponding IEC 61850 data reference.

For example, a client may access a current measurement represented through MMXU.

The server returns the requested value together with associated information where supported.

The engineer should verify:

  • Correct object reference
  • Correct functional constraint
  • Data type
  • Quality
  • Timestamp
  • Engineering unit
  • Scaling

14. Data Model and GOOSE Communication

GOOSE uses IEC 61850 data objects as the basis for publishing selected information.

However, GOOSE communication does not simply transmit arbitrary MMS read requests.

A publisher is configured with a dataset and GOOSE control block.

The selected dataset members are transmitted through Ethernet multicast messages.

A simplified architecture:

          MiCOM Relay A
           Publisher
               |
          GOOSE Dataset
               |
          GOOSE Control
               |
        Ethernet Multicast
               |
          MiCOM Relay B
           Subscriber
               |
        External Reference
               |
        Protection or Control Logic

14.1 Dataset Members

A GOOSE dataset may contain selected status information, such as:

  • Protection operation
  • Breaker status
  • Interlocking status
  • Blocking signals

The publisher and subscriber must be configured consistently.

14.2 External References

In SCL engineering, ExtRef elements are commonly used to describe external references, including the relationship between received GOOSE information and subscriber data.

Correct external-reference mapping is important for ensuring that the subscriber uses the intended published information.

15. Data Model and SCL Files

The IEC 61850 data model is described through SCL configuration files.

Common file types include:

FilePurpose
ICDIED capability description
CIDConfigured IED description
IIDInstantiated IED description
SCDSubstation configuration description
SSDSystem specification description

An SCL file may contain information about:

  • IEDs
  • Access points
  • Servers
  • Logical devices
  • Logical nodes
  • Data objects
  • Datasets
  • Report control blocks
  • GOOSE control blocks
  • Communication parameters
  • External references

15.1 Example of SCL Data Model Structure

A simplified conceptual structure is:

<SCL>
  <IED name="MiCOM_FEEDER_01">
    <AccessPoint name="AP1">
      <Server>
        <LDevice inst="PROT1">
          <LN0 lnClass="LLN0" inst="">
            <DataSet name="Measurements">
              <!-- Dataset members -->
            </DataSet>
          </LN0>
          <LN lnClass="MMXU" inst="1"/>
          <LN lnClass="PTOC" inst="1"/>
          <LN lnClass="XCBR" inst="1"/>
        </LDevice>
      </Server>
    </AccessPoint>
  </IED>
</SCL>

This is an illustrative XML structure, not an actual configuration file for a specific MiCOM relay. A valid SCL file requires the appropriate schema elements, attributes, data types and references.

16. Practical Example: Mapping MiCOM Feeder Protection Data

Consider a feeder protected by a MiCOM relay.

The SCADA system needs the following information:

  • Phase currents
  • Frequency
  • Circuit breaker position
  • Overcurrent start
  • Overcurrent trip
  • Earth fault trip
  • Relay alarm

A practical mapping table may be prepared as follows:

SCADA informationIEC 61850 logical nodeData object example
Phase currentMMXUA
FrequencyMMXUHz
Breaker positionXCBRPos
Overcurrent startPTOCStr
Overcurrent operationPTOCOp
Earth fault operationApplicable protection LNImplementation-dependent
Relay alarmDevice status or alarm LNImplementation-dependent

This is a functional mapping guide. The exact logical nodes, data objects and attributes must be checked in the selected MiCOM relay.

16.1 Engineering Procedure

  1. Identify the MiCOM relay model and firmware.
  2. Obtain its IEC 61850 documentation.
  3. Review the available logical devices.
  4. Identify the required logical nodes.
  5. Locate the required data objects.
  6. Confirm functional constraints.
  7. Verify the data types and CDCs.
  8. Prepare the SCADA point list.
  9. Configure MMS reporting.
  10. Test the actual values and status indications.

17. Common Data Model Errors

Incorrect interpretation of the IEC 61850 data model can create problems during commissioning.

ErrorConsequenceSolution
Wrong logical deviceData access failsVerify the actual LD name
Wrong LN instanceIncorrect or unavailable pointCheck the configured LN instance
Wrong data objectMissing or incorrect informationCheck the device data model
Wrong attributeInvalid data referenceVerify the complete reference
Incorrect FCAccess or configuration problemConfirm functional constraint
Incorrect CDC interpretationWrong SCADA data typeCheck the common data class
Assuming all standard LNs existMissing data pointsVerify the relay implementation
Ignoring qualityInvalid data displayed as validMap and process quality correctly
Ignoring timestampsIncorrect event sequencePreserve timestamp information

18. Practical Testing of IEC 61850 Data

Data model verification should be part of the commissioning process.

18.1 Online Data Model Verification

Use the supported engineering or IEC 61850 client tools to:

  • Establish communication.
  • Discover logical devices.
  • Discover logical nodes.
  • Identify available data objects.
  • Read supported attributes.
  • Verify measurements.
  • Check quality and timestamps.

18.2 Measurement Testing

Compare the values received through IEC 61850 with:

  • Relay front-panel measurements
  • Test equipment measurements
  • Expected secondary values
  • SCADA display values

Check engineering units and scaling.

18.3 Protection Indication Testing

Using approved test procedures:

  1. Apply the appropriate test condition.
  2. Verify protection start.
  3. Verify protection operation.
  4. Check the corresponding IEC 61850 data.
  5. Confirm SICAM PAS or SCADA indication.
  6. Verify event timestamps and quality.

18.4 Control Testing

For supported control objects:

  1. Verify the object reference.
  2. Confirm the control model.
  3. Check local/remote selection.
  4. Verify interlocking.
  5. Test the command under approved conditions.
  6. Confirm actual equipment feedback.

19. Engineering Recommendations

For effective IEC 61850 data-model engineering in MiCOM relays:

  1. Start with the actual device documentation, not assumed logical-node lists.
  2. Verify the complete logical device and logical-node structure.
  3. Understand the difference between data objects and data attributes.
  4. Learn the main CDCs and functional constraints.
  5. Verify quality and timestamp handling.
  6. Use exact data references in SCADA databases.
  7. Review the ICD and SCD files carefully.
  8. Distinguish MMS data access from GOOSE publishing and subscription.
  9. Test every important indication against the physical relay behaviour.
  10. Maintain a complete data-point list for commissioning and future maintenance.

20. Conclusion

The IEC 61850 data model is the foundation of communication and interoperability in modern substation automation systems.

For MiCOM protection relays, understanding logical devices, logical nodes, data objects, data attributes, CDCs and functional constraints is essential for successful configuration and SCADA integration.

This knowledge helps engineers identify the correct data references, configure MMS reporting, engineer GOOSE applications and troubleshoot communication problems.

The most important practical lesson is that standard IEC 61850 names provide a common framework, but the actual implementation must always be verified against the selected MiCOM relay’s documentation and configuration.

21. Practical IEC 61850 and MiCOM Training by Elec-Engg

Elec-Engg provides practical training in protection relays, IEC 61850 engineering and substation automation.

Relevant training subjects include:

  • MiCOM protection relay engineering
  • IEC 61850 data models
  • Logical nodes and data objects
  • Functional constraints and CDCs
  • MMS communication and reporting
  • GOOSE configuration and testing
  • ICD, CID and SCD files
  • SICAM PAS integration
  • Wireshark protocol analysis
  • Protection relay testing and commissioning

Training is available through video courses, structured self-paced training, face-to-face courses and customized in-house programs.