- 1. Introduction
- 2. What Are ANSI Device Numbers?
- 3. Difference Between ANSI Device Numbers and Relay Models
- 4.1 ANSI Device Numbers 1–20
- 4.2 ANSI Device Numbers 21–40
- 4.3 ANSI Device Numbers 41–60
- 4.4 ANSI Device Numbers 61–80
- 4.5 ANSI Device Numbers 81–99
- Core protection functions
- ANSI 27 — Undervoltage
- ANSI 59 — Overvoltage
- Common suffixes
- Mistake 1 — Assuming a device number identifies a relay model
- Mistake 2 — Assuming all relays have the same functions
- Mistake 3 — Confusing 50 and 51
- Mistake 4 — Confusing 50N and 50G
- Mistake 5 — Treating ANSI numbers as settings
- Mistake 6 — Ignoring the relay manual
- Mistake 7 — Ignoring programmable logic
- Mistake 8 — Ignoring breaker-related functions
1. Introduction
In electrical power systems, protection relays are responsible for detecting abnormal operating conditions, identifying faults, and initiating appropriate actions to isolate faulty equipment while maintaining the continuity of the healthy parts of the network.
Protection functions are often identified by standardized ANSI/IEEE device numbers. These numbers are widely used in electrical drawings, single-line diagrams, protection schemes, relay configuration software, control panels, commissioning documents, and technical specifications.
For example:
- 50 — Instantaneous overcurrent protection
- 51 — Time overcurrent protection
- 50N — Neutral or residual instantaneous overcurrent
- 51N — Neutral or residual time overcurrent
- 67 — Directional overcurrent protection
- 87 — Differential protection
- 27 — Undervoltage protection
- 59 — Overvoltage protection
- 49 — Thermal overload protection
- 46 — Negative-sequence current protection
Understanding these numbers is essential for protection engineers, commissioning engineers, maintenance technicians, electrical designers, and anyone working with numerical protection relays such as VAMP, Siemens SIPROTEC, ABB/Hitachi Energy, Schneider Electric, SEL, GE, and other manufacturers.
ANSI device numbers identify protection or control functions. They do not, by themselves, identify a specific relay model or guarantee that the function is available in every relay.
2. What Are ANSI Device Numbers?
ANSI device numbers are standardized numerical identifiers used to describe electrical protection, control, switching, monitoring, and automation functions.
They are commonly associated with IEEE/ANSI C37.2 device-function designations and are frequently used in engineering documentation.
The purpose of these numbers is to make technical communication easier.
Instead of writing a long description such as:
A protection function that detects excessive phase current and operates according to an inverse time characteristic.
An engineer can identify the function as:
51 — AC time overcurrent protection.
This terminology is used across different manufacturers, making it easier to interpret drawings and protection schemes regardless of the relay brand.
Where are ANSI device numbers used?
- Electrical single-line diagrams
- Protection schematics
- Relay function lists
- Protection setting sheets
- Relay configuration software
- Control and interlocking diagrams
- Substation design documents
- FAT and SAT documentation
- Commissioning reports
- Protection coordination studies
- Equipment specifications
- Maintenance procedures
3. Difference Between ANSI Device Numbers and Relay Models
It is important to distinguish the protection function from the physical relay that implements it.
| Description | Example |
|---|---|
| Device number | 51 |
| Protection function | Time overcurrent protection |
| Physical device | Numerical protection relay |
| Relay manufacturer | VAMP, Siemens, ABB, SEL, Schneider |
| Relay model | Model-specific IED |
| Protection setting | Pickup current, time multiplier, curve type |
| Output action | Alarm, trip, block, control |
A single numerical relay may contain dozens of protection functions. For example, a feeder relay may include:
- 50 — Instantaneous overcurrent
- 51 — Time overcurrent
- 50N — Instantaneous earth fault
- 51N — Time earth fault
- 67 — Directional overcurrent
- 67N — Directional earth fault
- 46 — Negative-sequence protection
- 49 — Thermal protection
- 27 — Undervoltage
- 59 — Overvoltage
- 81 — Frequency protection
- 79 — Auto-reclosing
Depending on the relay model, hardware, firmware, configuration, and licensed features, these functions may be available individually or in combination.
4. Common ANSI Device Numbers Used in Power System Protection
The following table introduces the device numbers commonly encountered in power systems.
4.1 ANSI Device Numbers 1–20
| Number | Device Function | Description |
|---|---|---|
| 1 | Master element | Initiates or controls an overall operation |
| 2 | Time-delay starting or closing relay | Delays an operation before starting or closing |
| 3 | Checking or interlocking relay | Permits or prevents an operation based on conditions |
| 4 | Master contactor | Controls a major circuit or equipment function |
| 5 | Stopping device | Initiates equipment stopping |
| 6 | Starting circuit breaker | Controls starting-related circuit operation |
| 7 | Rate-of-change relay | Responds to a rate-of-change quantity |
| 8 | Control power disconnecting device | Disconnects control power |
| 9 | Reversing device | Changes the direction of operation |
| 10 | Unit sequence switch | Controls a sequence of operations |
| 11 | Multifunction device | General multifunction designation |
| 12 | Overspeed device | Detects excessive speed |
| 13 | Synchronous-speed device | Detects synchronous speed conditions |
| 14 | Underspeed device | Detects low speed |
| 15 | Speed or frequency matching device | Checks speed/frequency matching |
| 16 | Data communication device | Modern designation used in data communication applications |
| 17 | Shunting or short-circuiting switch | Provides shunting or short-circuiting function |
| 18 | Accelerating or decelerating device | Controls acceleration/deceleration |
| 19 | Starting-to-running transition contactor | Changes starting circuit to running circuit |
| 20 | Electrically operated valve | Operates an electrically controlled valve |
4.2 ANSI Device Numbers 21–40
| Number | Device Function | Description |
|---|---|---|
| 21 | Distance relay | Measures impedance to detect faults within a defined zone |
| 22 | Equalizer circuit breaker | Associated with equalizing or balancing circuits |
| 23 | Temperature control device | Controls temperature based on predefined conditions |
| 24 | Volts-per-hertz relay | Detects overexcitation or excessive V/Hz |
| 25 | Synchronism-check or synchronizing device | Checks synchronism or supervises synchronization |
| 26 | Apparatus thermal device | Monitors thermal condition of equipment |
| 27 | Undervoltage relay | Detects voltage below a threshold |
| 28 | Flame detector | Detects flame conditions |
| 29 | Isolating contactor | Isolates a circuit or equipment section |
| 30 | Annunciator relay | Provides indication or annunciation |
| 31 | Separate excitation device | Associated with excitation systems |
| 32 | Directional power relay | Detects power flow direction or power magnitude |
| 33 | Position switch | Detects equipment position |
| 34 | Master sequence device | Controls operating sequences |
| 35 | Brush or slip-ring short-circuiting/lifting device | Associated with brush/slip-ring equipment |
| 36 | Polarity or voltage polarizing device | Associated with polarity or polarizing voltage functions |
| 37 | Undercurrent or underpower relay | Detects current or power below a threshold |
| 38 | Bearing protective device | Monitors bearing conditions |
| 39 | Mechanical condition monitor | Monitors mechanical equipment conditions |
| 40 | Loss-of-excitation relay | Detects loss or abnormal excitation in machines |
4.3 ANSI Device Numbers 41–60
| Number | Device Function | Description |
|---|---|---|
| 41 | Field circuit breaker | Controls the generator or machine field circuit |
| 42 | Running circuit breaker | Associated with normal running circuit |
| 43 | Transfer or selector device | Selects or transfers between operating conditions |
| 44 | Unit sequence starting relay | Controls sequence of starting operations |
| 45 | Atmospheric condition monitor | Monitors atmospheric/environmental conditions |
| 46 | Negative-sequence or current-unbalance relay | Detects current unbalance and negative sequence |
| 47 | Phase-sequence or voltage-unbalance relay | Detects phase sequence or voltage unbalance |
| 48 | Incomplete sequence relay | Detects incomplete starting or operating sequence |
| 49 | Thermal overload relay | Protects equipment against thermal overload |
| 50 | Instantaneous overcurrent relay | Operates when current exceeds a threshold without intentional delay |
| 51 | AC time overcurrent relay | Operates according to a time-current characteristic |
| 52 | AC circuit breaker | Circuit breaker for AC power circuits |
| 53 | Excitation generator or field forcing device | Associated with excitation and field forcing |
| 54 | Turning gear device | Associated with turning gear operation |
| 55 | Power factor relay | Monitors or controls power factor |
| 56 | Field application relay | Controls application of field excitation |
| 57 | Short-circuiting or grounding device | Provides short-circuiting or grounding function |
| 58 | Rectification failure relay | Detects rectification system failure |
| 59 | Overvoltage relay | Detects voltage above a threshold |
| 60 | Voltage or current balance / sensor supervision relay | Detects imbalance or abnormal sensing conditions |
4.4 ANSI Device Numbers 61–80
| Number | Device Function | Description |
|---|---|---|
| 61 | Current balance or sensor relay | Monitors current balance or sensing condition |
| 62 | Time-delay stopping or closing relay | Provides delay in stopping or closing operations |
| 63 | Pressure switch | Detects abnormal pressure |
| 64 | Ground detector relay | Detects ground faults or ground-related conditions |
| 65 | Governor | Controls speed or operating conditions |
| 66 | Starts-per-hour or starting limitation device | Restricts excessive starts or operations |
| 67 | AC directional overcurrent relay | Overcurrent protection with directional supervision |
| 68 | Blocking or locking relay | Blocks or locks selected operations |
| 69 | Permissive control device | Enables operation when required permissive conditions are met |
| 70 | Rheostat | Controls resistance or related adjustment |
| 71 | Level switch | Detects fluid or material level |
| 72 | DC circuit breaker | Circuit breaker for DC power circuits |
| 73 | Load-resistor contactor | Controls load resistor circuits |
| 74 | Alarm relay | Provides alarm function |
| 75 | Position-changing mechanism | Changes equipment position or configuration |
| 76 | DC overcurrent relay | Detects DC overcurrent |
| 77 | Pulse transmitter | Transmits pulses for measurement or control |
| 78 | Phase-angle or phase-measuring relay | Measures phase angle or related quantities |
| 79 | AC reclosing relay | Controls automatic reclosing of AC circuit breakers |
| 80 | Flow switch | Detects flow conditions |
4.5 ANSI Device Numbers 81–99
| Number | Device Function | Description |
|---|---|---|
| 81 | Frequency relay | Detects abnormal frequency |
| 82 | DC reclosing relay | Controls DC reclosing applications |
| 83 | Automatic transfer or selection device | Automatically selects or transfers operating conditions |
| 84 | Operating mechanism | Associated with an operating mechanism |
| 85 | Communication carrier or teleprotection device | Receives or supervises communication-assisted protection signals |
| 86 | Lockout relay | Provides lockout following a specified fault or operation |
| 87 | Differential relay | Detects differential current within a protected zone |
| 88 | Auxiliary motor | Auxiliary motor associated with equipment |
| 89 | Line or isolating switch | Provides isolation |
| 90 | Regulating device | Controls or regulates a quantity |
| 91 | Voltage directional relay | Directional voltage-related function |
| 92 | Power circuit breaker | Associated with power circuit switching |
| 93 | Field-changing contactor | Changes field circuit configuration |
| 94 | Tripping or free-wheeling device | Associated with trip or free-wheeling operation |
| 95–99 | Special/application-specific designations | May be assigned to special functions, depending on applicable conventions and application |
Note: Device-number descriptions may vary slightly between standard editions, application conventions, manufacturers, and utility documentation. Always consult the applicable standard and equipment documentation when creating formal engineering drawings.
5. The Most Important ANSI Numbers for Protection Engineers
While many device numbers are used in electrical control and machine applications, protection engineers most frequently work with a smaller group of numbers.
Core protection functions
50 / 51 / 67 / 87
Overcurrent, time overcurrent, directional overcurrent and differential protection form the foundation of many protection schemes.
| ANSI | Protection Function | Typical Application |
|---|---|---|
| 21 | Distance protection | Transmission and subtransmission lines |
| 24 | V/Hz overexcitation | Transformers and generators |
| 25 | Synchronism check | Generator and bus synchronization |
| 27 | Undervoltage | Motors, buses, generators |
| 32 | Directional power | Generators and power systems |
| 37 | Undercurrent / underpower | Motors and equipment |
| 40 | Loss of excitation | Synchronous generators |
| 46 | Negative sequence | Motors and generators |
| 47 | Phase sequence / voltage unbalance | Motors and voltage systems |
| 49 | Thermal overload | Motors, transformers, cables |
| 50 | Instantaneous overcurrent | Feeders, transformers, motors |
| 51 | Time overcurrent | Feeders and backup protection |
| 52 | AC circuit breaker | Switching and fault interruption |
| 55 | Power factor | Capacitor banks and machines |
| 59 | Overvoltage | Buses, generators, transformers |
| 60 | Sensor supervision / balance | VT/CT monitoring applications |
| 61 | Current balance | Current sensing applications |
| 64 | Ground detection | Ground fault detection |
| 67 | Directional overcurrent | Ring networks and parallel feeders |
| 68 | Blocking / locking | Protection coordination and logic |
| 79 | Auto-reclosing | Overhead distribution and transmission |
| 81 | Frequency protection | Power systems and generators |
| 82 | DC reclosing | DC applications |
| 86 | Lockout | Transformer, busbar, generator, and critical protection |
| 87 | Differential protection | Transformers, generators, busbars, motors, lines |
| 89 | Isolating switch | Isolation and switching |
| 90 | Regulating device | Voltage and other regulating systems |
| 91 | Voltage directional | Directional voltage applications |
| 92 | Power circuit breaker | Power switching and control |
6. ANSI 50 — Instantaneous Overcurrent Protection
ANSI 50 is used to detect excessive current and operate when the measured current exceeds a configured threshold.
Unlike a time-overcurrent function, the instantaneous stage normally does not apply an intentional time delay, although the total operating time is never truly zero.
The overall operation includes:
- Measurement and signal processing
- Pickup detection
- Logic processing
- Output relay operation
- Circuit breaker operating time
- Fault current interruption
Applications
- Feeder short-circuit protection
- Transformer backup protection
- Motor short-circuit protection
- Busbar backup
- Protection of cables and equipment
Example
Suppose a feeder relay has:
- CT ratio: 400/1 A
- Instantaneous pickup: 8 A secondary
- Primary equivalent pickup: 3200 A
If the measured current rises above the configured pickup and the applicable logic conditions are satisfied, the relay may issue a trip command.
However, pickup must be carefully selected to avoid operating for downstream faults where selectivity is required.
7. ANSI 51 — Time Overcurrent Protection
ANSI 51 is a time-overcurrent function that operates when current exceeds a pickup threshold and the applicable operating time has elapsed.
Depending on the relay implementation, the operating characteristic can be:
- Definite-time
- Inverse-time
- Very inverse
- Extremely inverse
- Long-time inverse
- Other manufacturer-specific characteristics
Main parameters
| Parameter | Meaning |
|---|---|
| Pickup current | Minimum current required to initiate operation |
| Curve selection | Determines time-current relationship |
| Time multiplier | Adjusts operating time |
| Reset characteristic | Defines behavior after fault current disappears |
| Directional supervision | May be used with directional elements |
| Blocking input | May prevent operation under selected conditions |
ANSI 51 is particularly important for grading and coordination between upstream and downstream protection devices.
8. ANSI 50N / 51N — Neutral or Residual Overcurrent Protection
Earth faults can produce residual current even when phase currents are not significantly different from normal load currents.
Residual current can be calculated from the phase currents:
Ires=IA+IB+IC
Under ideal balanced conditions:
IA+IB+IC≈0
During a ground fault, the residual current may increase.
Common earth-fault functions
| Designation | Function |
|---|---|
| 50N | Instantaneous neutral/residual overcurrent |
| 51N | Time neutral/residual overcurrent |
| 50G | Instantaneous ground overcurrent |
| 51G | Time ground overcurrent |
The exact meaning of N and G suffixes may vary between manufacturers and system conventions. In some relays, N refers to residual or neutral current measured from summation or a neutral CT, while G may refer to current measured from a dedicated ground CT.
Typical applications
- MV feeder earth-fault protection
- Transformer neutral protection
- Cable ground-fault protection
- Generator stator ground protection schemes
- Industrial distribution networks
9. ANSI 67 — Directional Overcurrent Protection
ANSI 67 adds directional discrimination to an overcurrent function.
A conventional overcurrent relay responds primarily to current magnitude and time. A directional overcurrent relay also evaluates the direction of fault current using reference quantities, typically voltage and current, depending on the function and implementation.
Why directional protection is needed
Directional protection is particularly useful in:
- Ring networks
- Parallel feeders
- Networks with multiple sources
- Distributed generation systems
- Networks with power flow in both directions
- Interconnected industrial power systems
In these networks, fault current may flow from more than one direction. A non-directional relay may not be able to discriminate correctly between faults inside and outside its intended protection zone.
Related functions
| ANSI | Function |
|---|---|
| 67 | Directional phase overcurrent |
| 67N | Directional earth-fault overcurrent |
| 67G | Directional ground overcurrent |
The directional element may use voltage polarization, current polarization, or other methods depending on relay design.
10. ANSI 87 — Differential Protection
Differential protection compares electrical quantities entering and leaving a protected zone.
For an ideal protected zone:
Idiff≈0
For an internal fault, the differential current increases because the current entering the zone is no longer equal to the current leaving it, after appropriate compensation and reference-direction considerations.
Common differential applications
| Designation | Application |
|---|---|
| 87T | Transformer differential |
| 87B | Busbar differential |
| 87G | Generator differential |
| 87M | Motor differential |
| 87L | Line differential |
| 87C | Cable differential in some applications |
Differential protection requires careful engineering
The relay may need to compensate for:
- CT ratio differences
- Transformer vector group
- Phase shift
- Transformer tap position
- CT errors
- CT saturation
- Magnetizing inrush
- Through-fault stability
- Restricted protected-zone boundaries
Differential protection is generally designed to provide fast and selective protection for internal faults.
11. ANSI 21 — Distance Protection
ANSI 21 is a distance protection function primarily used for transmission and subtransmission line protection.
The relay measures apparent impedance:
Z=IV
Because line impedance is related to physical distance, the measured impedance can be used to estimate whether a fault is within a configured protection zone.
Typical distance protection zones
| Zone | General purpose |
|---|---|
| Zone 1 | Fast primary protection for a portion of the protected line |
| Zone 2 | Extended protection with coordination delay |
| Zone 3 | Remote backup protection |
The actual reach, timing, directionality, and coordination must be engineered according to network conditions.
Distance protection is especially important where overcurrent protection alone cannot achieve adequate selectivity or sensitivity.
12. ANSI 27 and 59 — Undervoltage and Overvoltage Protection
ANSI 27 — Undervoltage
The 27 function detects voltage below a predefined threshold.
Applications include:
- Motor protection
- Bus voltage supervision
- Load shedding
- Voltage-based interlocking
- Generator protection
- Power quality supervision
Typical settings include:
- Voltage pickup
- Operating delay
- Measurement quantity
- Reset threshold
- Blocking and permissive conditions
ANSI 59 — Overvoltage
The 59 function detects excessive voltage.
Applications include:
- Generator protection
- Transformer protection
- Bus protection and supervision
- Capacitor bank protection
- Voltage control schemes
- Grid-connected equipment
Overvoltage protection may be coordinated with voltage regulators, tap changers, excitation systems, and other protection functions.
13. ANSI 49 — Thermal Overload Protection
ANSI 49 is a thermal protection function that protects equipment against overheating.
Unlike simple overcurrent protection, thermal protection considers the heating effect of current over time.
A thermal model may take into account:
- Load current
- Rated current
- Thermal capacity
- Heating and cooling time constants
- Previous thermal state
- Ambient conditions, where supported
- RTD or other temperature inputs, where supported
Applications
- Induction motors
- Transformers
- Generators
- Cables
- Other equipment where thermal loading is important
For motor protection, 49 is particularly important because a motor may experience damaging thermal stress even when the current is not high enough to cause instantaneous short-circuit protection operation.
14. ANSI 46 — Negative-Sequence Protection
ANSI 46 detects negative-sequence current or related current unbalance.
In a three-phase electrical system, balanced currents ideally contain only positive-sequence components. When phase currents become unbalanced, negative-sequence components may appear.
Negative-sequence current can create additional heating in rotating machines, especially motors and generators.
Common causes of current unbalance
- Phase-to-phase faults
- Single-phase loading
- Unequal phase impedance
- Broken conductor
- Abnormal supply conditions
- Incorrect CT connections
- Phase loss
Applications
- Motor protection
- Generator protection
- Three-phase equipment protection
- Phase-unbalance supervision
The protection settings must account for equipment withstand capability and the expected network operating conditions.
15. ANSI 47 — Phase Sequence and Voltage Unbalance
ANSI 47 is associated with phase-sequence or voltage-unbalance conditions.
It may detect conditions such as:
- Incorrect phase sequence
- Voltage phase unbalance
- Loss or abnormality of a phase voltage
- Abnormal phase rotation
- Voltage asymmetry
Why it is important
For three-phase motors, incorrect phase sequence may cause rotation in the wrong direction. Voltage unbalance may also lead to excessive motor current unbalance and heating.
ANSI 47 is commonly used in motor control and protection schemes, particularly where correct phase sequence and voltage quality are important.
16. ANSI 40 — Loss of Excitation Protection
ANSI 40 is primarily associated with loss-of-excitation protection for synchronous machines.
Loss of excitation can cause a generator to operate abnormally, potentially leading to:
- Rotor overheating
- Increased reactive power demand
- System voltage disturbance
- Loss of stability
- Abnormal stator currents
- Damage to the generator
Loss-of-excitation protection may use impedance-based characteristics or other methods depending on the protection system.
This function is commonly integrated into generator protection relays or dedicated excitation protection systems.
17. ANSI 32 — Directional Power Protection
ANSI 32 is used to detect power direction or power magnitude conditions.
A typical application is reverse-power protection for generators.
When a generator loses its prime-mover input, it may begin absorbing power from the electrical network and operate as a motor.
Reverse-power protection detects this abnormal operating condition and can initiate generator disconnection.
Applications
- Generator reverse-power protection
- Prime-mover failure detection
- Directional power supervision
- Import/export control schemes
- Power-flow monitoring
The function requires appropriate voltage and current measurements, direction references, and settings.
18. ANSI 24 — Overexcitation Protection
ANSI 24 protects equipment against excessive volts-per-hertz conditions.
The ratio is:
fV
Where:
- V = measured voltage
- f = frequency
An increase in voltage or decrease in frequency can increase magnetic flux in transformers and rotating machines.
Overexcitation can result in:
- Core saturation
- Increased magnetizing current
- Excessive heating
- Insulation stress
- Equipment damage
ANSI 24 is important in generator and transformer protection applications.
19. ANSI 25 — Synchronism Check
ANSI 25 checks whether two electrical systems or circuit sides are suitable for synchronization or closing.
The function may evaluate:
- Voltage magnitude difference
- Frequency difference
- Phase-angle difference
- Slip frequency
- Breaker closing conditions
Typical applications
- Generator synchronization
- Bus coupler closing
- Grid connection
- Transfer schemes
- Interconnection between two energized systems
Synchronism-check protection helps prevent unsafe closing when voltage phase relationships are not acceptable.
20. ANSI 79 — Automatic Reclosing
ANSI 79 controls automatic reclosing of circuit breakers following a trip.
It is widely used in overhead distribution and transmission systems because many faults are temporary.
Typical sequence:
- A protection function detects a fault.
- The circuit breaker trips.
- The relay starts the autoreclosing sequence.
- A dead-time period is applied.
- The circuit breaker is commanded to close.
- The system checks whether the fault has cleared.
- If the fault remains, the protection trips again.
- Further reclose attempts may be blocked or performed according to the configured sequence.
Important considerations
- Dead time
- Reclose sequence
- Number of attempts
- Lockout conditions
- Synchronism check
- Live/dead bus conditions
- Coordination with downstream protection
- Circuit breaker duty
Automatic reclosing is generally more suitable for overhead lines than for many cable systems, where faults are more likely to be permanent.
21. ANSI 81 — Frequency Protection
ANSI 81 protects electrical systems against abnormal frequency.
Common subfunctions include:
| Designation | Function |
|---|---|
| 81U | Underfrequency |
| 81O | Overfrequency |
| 81R | Rate-of-change-of-frequency protection, where used |
| 81UF | Underfrequency |
| 81OF | Overfrequency |
Frequency protection is important because abnormal frequency may indicate a mismatch between generation and load.
Applications
- Generator protection
- Load shedding
- Grid protection
- Islanded networks
- Frequency-based control schemes
Underfrequency protection may be used in staged load shedding schemes to restore the balance between generation and load.
22. ANSI 86 — Lockout Relay
ANSI 86 is a lockout function.
A lockout relay is used when a protection operation requires manual inspection, resetting, or authorization before the equipment can be returned to service.
It is commonly used for critical equipment such as:
- Power transformers
- Generators
- Busbars
- Large motors
- Critical feeders
Example: Transformer protection
If transformer differential protection (87T) detects an internal fault, the trip logic may:
- Trip transformer circuit breakers
- Initiate ANSI 86 lockout
- Block closing commands
- Generate alarms
- Record the protection event
The lockout function prevents automatic or unintended re-energization until the required reset conditions are fulfilled.
In numerical relays, the lockout function may be implemented using programmable logic rather than a separate physical electromechanical relay. However, the actual scheme must be checked.
23. ANSI 52 — Circuit Breaker
ANSI 52 identifies an AC circuit breaker.
Circuit breakers are the primary switching devices used to interrupt fault currents and isolate equipment.
Protection relays typically do not interrupt the primary fault current directly. They detect the fault and issue a trip command to the circuit breaker.
The protection chain includes:
- CT/VT sensing
- Relay measurement
- Fault detection
- Protection logic
- Trip output
- Trip coil energization
- Circuit breaker mechanical operation
- Fault interruption
- Auxiliary contact feedback
Understanding the relationship between protection functions and the circuit breaker is essential during commissioning and troubleshooting.
24. ANSI 30 — Annunciation and Alarm
ANSI 30 is associated with annunciator functions.
In modern numerical protection systems, alarms may be generated by programmable logic and displayed on:
- Relay front panels
- Local HMI systems
- SCADA
- Substation automation systems
- Alarm/event lists
- Remote monitoring systems
Examples include:
- Protection pickup
- Relay self-supervision
- CT circuit abnormality
- VT circuit failure
- Communication failure
- Breaker failure
- DC supply abnormality
- Trip circuit supervision alarm
- Temperature alarm
Alarm design should distinguish between critical protection conditions and routine equipment status information.
25. ANSI 67N — Directional Earth-Fault Protection
ANSI 67N is directional earth-fault protection.
It evaluates residual or neutral current together with an appropriate directional reference, commonly residual voltage or other polarizing quantities, depending on the relay design and grounding system.
It is particularly important in:
- Ring networks
- Parallel feeders
- Networks with multiple sources
- Isolated-neutral networks
- Compensated-neutral networks
- Industrial networks with distributed generation
Engineering considerations
- Grounding method
- Zero-sequence network
- CT connection
- Residual current measurement
- Polarizing voltage
- Directional angle
- Pickup sensitivity
- Operating time
- Coordination with other earth-fault protection
Directional earth-fault settings must be carefully selected according to the actual network grounding and fault-current characteristics.
26. ANSI Function Suffixes — Understanding 50, 50N, 50G, 50BF and Similar Designations
Device numbers are often combined with letters to identify a particular application or measurement quantity.
The numerical part identifies the basic device function, while the suffix helps clarify the implementation or application.
However, suffix conventions are not always universal. The same suffix may be interpreted differently in manufacturer documentation or utility standards.
Common suffixes
| Designation | Common meaning |
|---|---|
| 50 | Instantaneous overcurrent |
| 50N | Neutral/residual instantaneous overcurrent |
| 50G | Ground instantaneous overcurrent |
| 51 | Time overcurrent |
| 51N | Neutral/residual time overcurrent |
| 51G | Ground time overcurrent |
| 67 | Directional phase overcurrent |
| 67N | Directional earth-fault overcurrent |
| 87T | Transformer differential |
| 87B | Busbar differential |
| 87G | Generator differential |
| 87M | Motor differential |
| 87L | Line differential |
| 27 | Undervoltage |
| 59 | Overvoltage |
| 81U | Underfrequency |
| 81O | Overfrequency |
| 50BF | Circuit breaker failure protection |
| 49 | Thermal overload |
| 46 | Negative-sequence current |
| 25 | Synchronism check |
Important caution
In many modern relays, these suffixes are commonly used by engineers and utilities, but the exact implementation and naming convention should always be checked against the relay manual, drawing legend, and project protection standard.
27. ANSI Device Numbers and IEC Protection Function Names
ANSI device numbers and IEC terminology are frequently used together.
| ANSI Number | Common IEC / Functional Description |
|---|---|
| 50 | Instantaneous overcurrent |
| 51 | Time overcurrent |
| 50N / 51N | Neutral/residual earth-fault overcurrent |
| 67 | Directional overcurrent |
| 67N | Directional earth-fault overcurrent |
| 21 | Distance protection |
| 87 | Differential protection |
| 49 | Thermal overload |
| 27 | Undervoltage |
| 59 | Overvoltage |
| 46 | Negative-sequence protection |
| 47 | Phase sequence / voltage unbalance |
| 40 | Loss of excitation |
| 32 | Reverse/directional power |
| 24 | Overexcitation |
| 25 | Synchronism check |
| 79 | Auto-reclosing |
| 81 | Frequency protection |
| 86 | Lockout |
| 52 | Circuit breaker |
IEC protection function naming may use abbreviations such as:
- I> — Overcurrent
- I>> — High-set overcurrent
- I0> — Earth-fault current
- U< — Undervoltage
- U> — Overvoltage
- f< — Underfrequency
- f> — Overfrequency
- ΔI — Differential current
The exact symbols and naming conventions depend on manufacturer software and documentation.
28. ANSI Device Numbers in VAMP Protection Relays
VAMP numerical protection relays may combine multiple protection, measurement, monitoring, control, communication, and logic functions within one device.
Depending on the model, a VAMP relay may provide functions such as:
- Phase overcurrent protection
- Earth-fault protection
- Directional overcurrent
- Thermal protection
- Negative-sequence protection
- Voltage protection
- Frequency protection
- Power protection
- Arc-fault protection
- Breaker failure
- Auto-reclosing
- Programmable logic
- Measurement and event recording
When working with a VAMP relay, the engineer should not assume that every ANSI function listed in a protection study is available in every relay.
The proper workflow is:
- Identify the protection requirement.
- Identify the corresponding ANSI function.
- Select an appropriate VAMP relay model.
- Verify the function availability in the technical manual.
- Check the required CT/VT inputs.
- Verify binary inputs and outputs.
- Confirm protection logic and interlocking.
- Configure the function.
- Calculate settings.
- Perform testing and commissioning.
29. Practical Example — Protection Functions for an MV Feeder
Consider an 11 kV feeder supplying an industrial load.
A typical protection scheme might include:
| ANSI Function | Purpose |
|---|---|
| 50 | High-set instantaneous phase overcurrent |
| 51 | Time phase overcurrent |
| 50N | Instantaneous earth fault |
| 51N | Time earth fault |
| 67 | Directional phase overcurrent, if required |
| 67N | Directional earth fault, if required |
| 49 | Thermal protection or thermal monitoring, where applicable |
| 46 | Current unbalance / negative-sequence protection |
| 27 | Undervoltage supervision or protection |
| 59 | Overvoltage protection, if required |
| 81 | Frequency protection, if required |
| 50BF | Breaker failure protection, if implemented |
| 79 | Auto-reclosing, if applicable |
The actual protection functions depend on:
- Network configuration
- Grounding method
- Load type
- CT/VT ratios
- Short-circuit levels
- Coordination study
- Utility requirements
- Relay capability
- Operational philosophy
30. Practical Example — Transformer Protection
A power transformer may require a combination of protection functions.
| ANSI Function | Purpose |
|---|---|
| 87T | Main transformer differential protection |
| 50/51 | Phase overcurrent backup |
| 50N/51N | Earth-fault protection |
| 64 | Ground detection, depending on scheme |
| 49 | Thermal protection |
| 24 | Overexcitation protection |
| 50BF | Breaker failure protection |
| 86 | Lockout |
| 27/59 | Voltage protection, where applicable |
Transformer protection design must consider:
- Transformer rating
- Vector group
- CT ratios
- CT locations
- Inrush current
- Differential restraint
- Through-fault current
- Grounding arrangement
- Neutral protection
- Backup coordination
31. Practical Example — Motor Protection
An MV motor protection scheme may include:
| ANSI Function | Purpose |
|---|---|
| 50 | Instantaneous short-circuit protection |
| 51 | Overcurrent backup |
| 49 | Thermal overload protection |
| 46 | Negative-sequence protection |
| 48 | Incomplete starting / excessive starting time |
| 66 | Starts-per-hour limitation |
| 37 | Undercurrent or underpower |
| 27 | Undervoltage |
| 47 | Phase sequence / voltage unbalance |
| 50N/51N | Earth-fault protection |
| 86 | Lockout, if required by the scheme |
Motor protection requires coordination with the motor starting characteristics, thermal withstand capability, load profile, starting method, and process requirements.
32. Practical Example — Generator Protection
Generator protection functions may include:
| ANSI Function | Purpose |
|---|---|
| 87G | Generator differential |
| 50/51 | Overcurrent backup |
| 46 | Negative-sequence current |
| 40 | Loss of excitation |
| 32 | Reverse power |
| 24 | Overexcitation |
| 27 | Undervoltage |
| 59 | Overvoltage |
| 81 | Frequency protection |
| 25 | Synchronism check |
| 64 | Ground-fault protection |
| 49 | Thermal protection |
| 86 | Lockout |
Generator protection is highly dependent on generator type, grounding, excitation system, operating philosophy, and system interconnection requirements.
33. ANSI Device Numbers and Relay Testing
Knowing the ANSI number is also useful during protection testing and commissioning.
When performing secondary injection testing, the engineer should identify:
- Protection function number
- Protection stage
- Setting value
- Pickup threshold
- Time characteristic
- Operating delay
- Logic conditions
- Binary output mapping
- Trip matrix
- Circuit breaker operation
- Alarm and event indication
Example: Testing ANSI 51
A test procedure may include:
- Verify relay settings.
- Confirm CT ratio and current scaling.
- Identify the active 51 stage.
- Check pickup value.
- Select the configured time-current curve.
- Inject current above pickup.
- Record operating time.
- Compare the measured time against the expected curve.
- Verify trip output.
- Confirm circuit breaker operation, where included in the test scope.
Example: Testing ANSI 50
Testing should verify:
- Pickup threshold
- Operating time
- Output relay operation
- Trip logic
- Blocking conditions
- Reset behavior
- Correct phase selection
Example: Testing ANSI 87
Testing should verify:
- Differential current calculation
- Restraint/stabilization behavior
- CT polarity and connections
- Ratio compensation
- Phase compensation
- Internal-fault operation
- Through-fault stability
- Trip logic
The test procedure must follow the relay manual and approved commissioning documents.
34. Common Mistakes When Using ANSI Device Numbers
Mistake 1 — Assuming a device number identifies a relay model
ANSI 51 does not identify a particular relay. It identifies a protection function.
Mistake 2 — Assuming all relays have the same functions
Different relays have different protection capabilities, hardware, measurement inputs, algorithms, and logic features.
Mistake 3 — Confusing 50 and 51
- 50 is instantaneous overcurrent.
- 51 is time overcurrent.
They may be used together, but they are different protection stages.
Mistake 4 — Confusing 50N and 50G
The meaning of N and G depends on the measurement arrangement and convention used by the manufacturer or project.
Mistake 5 — Treating ANSI numbers as settings
Device number 51 does not provide the pickup value, curve, time multiplier, or coordination settings.
Mistake 6 — Ignoring the relay manual
A protection function may have different operating modes, characteristic curves, reset behavior, supervision, and logic options depending on the relay model.
Mistake 7 — Ignoring programmable logic
The ANSI function may be enabled, but its trip output may depend on additional logic, blocking signals, permissives, or output mapping.
Mistake 8 — Ignoring breaker-related functions
Protection relay operation and actual circuit breaker interruption are separate processes. Testing only the relay element does not necessarily prove the entire trip chain works correctly.
35. Engineering Workflow for Identifying Protection Functions
When reading a single-line diagram or protection scheme, use the following process:
Step 1 — Identify the equipment
Determine whether you are dealing with:
- Feeder
- Transformer
- Motor
- Generator
- Busbar
- Capacitor bank
- Transmission line
Step 2 — Identify the protection requirements
Determine the fault conditions and abnormal operating conditions that must be detected.
Step 3 — Identify the ANSI device numbers
Map the protection requirements to the relevant protection functions.
Step 4 — Confirm relay capability
Check the selected relay manual, function list, hardware configuration, and firmware compatibility.
Step 5 — Identify measurements
Determine which CT and VT signals are required.
Step 6 — Identify trip and alarm logic
Determine which protection functions initiate trips, alarms, blocking, lockout, or other actions.
Step 7 — Calculate and coordinate settings
Perform protection setting calculations and grading studies.
Step 8 — Test and commission
Verify each function, logic, output, and trip chain according to the approved test plan.
36. Conclusion
ANSI device numbers are a fundamental language of electrical protection engineering. They allow engineers to communicate protection functions clearly across drawings, relay settings, technical specifications, commissioning procedures, and different manufacturers.
For engineers working with VAMP protection relays, the most important numbers to understand include:
- 21 — Distance protection
- 24 — Overexcitation
- 25 — Synchronism check
- 27 — Undervoltage
- 32 — Directional power
- 40 — Loss of excitation
- 46 — Negative sequence
- 47 — Phase sequence / voltage unbalance
- 49 — Thermal overload
- 50 — Instantaneous overcurrent
- 51 — Time overcurrent
- 59 — Overvoltage
- 67 — Directional overcurrent
- 79 — Auto-reclosing
- 81 — Frequency protection
- 86 — Lockout
- 87 — Differential protection
A protection engineer should not only memorize these numbers but also understand their operating principles, application, settings, logic, limitations, and testing requirements.
This knowledge forms the foundation for relay selection, protection design, settings engineering, testing, commissioning, and troubleshooting.
37. Learn Protection & Substation Automation with Elec-Engg

Elec-Engg provides practical technical training for electrical engineers working in power system protection, relay testing, commissioning, control, and substation automation.
Training formats include:
- Recorded technical courses
- Structured self-paced training
- Live online training
- Face-to-face technical training
- Customized in-house training for companies and utilities
Our training topics include VAMP, Siemens SIPROTEC, ABB protection relays, Schneider Electric, relay testing with OMICRON, protection settings and coordination, IEC 61850, substation automation systems, SCADA, and practical engineering projects.
Visit the platform for technical courses, engineering materials, updates, and training information.
Website: https://elec-engg.com
WhatsApp technical updates: https://elec-engg.com/update
References and Further Reading
- IEEE/ANSI C37.2 — Electrical power system device function number designations
- IEC 60255 — Measuring relays and protection equipment
- IEC 61850 — Communication networks and systems for power utility automation
- Manufacturer-specific protection relay manuals, function lists, setting guides, and commissioning manuals
- Protection coordination and short-circuit study documentation
- Electrical equipment protection and application engineering references