Protection Functions and ANSI Device Numbers

Table Of Contents
  1. 1. Introduction
  2. 2. What Are ANSI Device Numbers?
  3. 3. Difference Between ANSI Device Numbers and Relay Models
  4. 4.1 ANSI Device Numbers 1–20
  5. 4.2 ANSI Device Numbers 21–40
  6. 4.3 ANSI Device Numbers 41–60
  7. 4.4 ANSI Device Numbers 61–80
  8. 4.5 ANSI Device Numbers 81–99
  9. Core protection functions
  10. ANSI 27 — Undervoltage
  11. ANSI 59 — Overvoltage
  12. Common suffixes
  13. Mistake 1 — Assuming a device number identifies a relay model
  14. Mistake 2 — Assuming all relays have the same functions
  15. Mistake 3 — Confusing 50 and 51
  16. Mistake 4 — Confusing 50N and 50G
  17. Mistake 5 — Treating ANSI numbers as settings
  18. Mistake 6 — Ignoring the relay manual
  19. Mistake 7 — Ignoring programmable logic
  20. Mistake 8 — Ignoring breaker-related functions

1. Introduction

In electrical power systems, protection relays are responsible for detecting abnormal operating conditions, identifying faults, and initiating appropriate actions to isolate faulty equipment while maintaining the continuity of the healthy parts of the network.

Protection functions are often identified by standardized ANSI/IEEE device numbers. These numbers are widely used in electrical drawings, single-line diagrams, protection schemes, relay configuration software, control panels, commissioning documents, and technical specifications.

For example:

  • 50 — Instantaneous overcurrent protection
  • 51 — Time overcurrent protection
  • 50N — Neutral or residual instantaneous overcurrent
  • 51N — Neutral or residual time overcurrent
  • 67 — Directional overcurrent protection
  • 87 — Differential protection
  • 27 — Undervoltage protection
  • 59 — Overvoltage protection
  • 49 — Thermal overload protection
  • 46 — Negative-sequence current protection

Understanding these numbers is essential for protection engineers, commissioning engineers, maintenance technicians, electrical designers, and anyone working with numerical protection relays such as VAMP, Siemens SIPROTEC, ABB/Hitachi Energy, Schneider Electric, SEL, GE, and other manufacturers.

ANSI device numbers identify protection or control functions. They do not, by themselves, identify a specific relay model or guarantee that the function is available in every relay.

2. What Are ANSI Device Numbers?

ANSI device numbers are standardized numerical identifiers used to describe electrical protection, control, switching, monitoring, and automation functions.

They are commonly associated with IEEE/ANSI C37.2 device-function designations and are frequently used in engineering documentation.

The purpose of these numbers is to make technical communication easier.

Instead of writing a long description such as:

A protection function that detects excessive phase current and operates according to an inverse time characteristic.

An engineer can identify the function as:

51 — AC time overcurrent protection.

This terminology is used across different manufacturers, making it easier to interpret drawings and protection schemes regardless of the relay brand.

Where are ANSI device numbers used?

  • Electrical single-line diagrams
  • Protection schematics
  • Relay function lists
  • Protection setting sheets
  • Relay configuration software
  • Control and interlocking diagrams
  • Substation design documents
  • FAT and SAT documentation
  • Commissioning reports
  • Protection coordination studies
  • Equipment specifications
  • Maintenance procedures

3. Difference Between ANSI Device Numbers and Relay Models

It is important to distinguish the protection function from the physical relay that implements it.

DescriptionExample
Device number51
Protection functionTime overcurrent protection
Physical deviceNumerical protection relay
Relay manufacturerVAMP, Siemens, ABB, SEL, Schneider
Relay modelModel-specific IED
Protection settingPickup current, time multiplier, curve type
Output actionAlarm, trip, block, control

A single numerical relay may contain dozens of protection functions. For example, a feeder relay may include:

  • 50 — Instantaneous overcurrent
  • 51 — Time overcurrent
  • 50N — Instantaneous earth fault
  • 51N — Time earth fault
  • 67 — Directional overcurrent
  • 67N — Directional earth fault
  • 46 — Negative-sequence protection
  • 49 — Thermal protection
  • 27 — Undervoltage
  • 59 — Overvoltage
  • 81 — Frequency protection
  • 79 — Auto-reclosing

Depending on the relay model, hardware, firmware, configuration, and licensed features, these functions may be available individually or in combination.

4. Common ANSI Device Numbers Used in Power System Protection

The following table introduces the device numbers commonly encountered in power systems.

4.1 ANSI Device Numbers 1–20

NumberDevice FunctionDescription
1Master elementInitiates or controls an overall operation
2Time-delay starting or closing relayDelays an operation before starting or closing
3Checking or interlocking relayPermits or prevents an operation based on conditions
4Master contactorControls a major circuit or equipment function
5Stopping deviceInitiates equipment stopping
6Starting circuit breakerControls starting-related circuit operation
7Rate-of-change relayResponds to a rate-of-change quantity
8Control power disconnecting deviceDisconnects control power
9Reversing deviceChanges the direction of operation
10Unit sequence switchControls a sequence of operations
11Multifunction deviceGeneral multifunction designation
12Overspeed deviceDetects excessive speed
13Synchronous-speed deviceDetects synchronous speed conditions
14Underspeed deviceDetects low speed
15Speed or frequency matching deviceChecks speed/frequency matching
16Data communication deviceModern designation used in data communication applications
17Shunting or short-circuiting switchProvides shunting or short-circuiting function
18Accelerating or decelerating deviceControls acceleration/deceleration
19Starting-to-running transition contactorChanges starting circuit to running circuit
20Electrically operated valveOperates an electrically controlled valve

4.2 ANSI Device Numbers 21–40

NumberDevice FunctionDescription
21Distance relayMeasures impedance to detect faults within a defined zone
22Equalizer circuit breakerAssociated with equalizing or balancing circuits
23Temperature control deviceControls temperature based on predefined conditions
24Volts-per-hertz relayDetects overexcitation or excessive V/Hz
25Synchronism-check or synchronizing deviceChecks synchronism or supervises synchronization
26Apparatus thermal deviceMonitors thermal condition of equipment
27Undervoltage relayDetects voltage below a threshold
28Flame detectorDetects flame conditions
29Isolating contactorIsolates a circuit or equipment section
30Annunciator relayProvides indication or annunciation
31Separate excitation deviceAssociated with excitation systems
32Directional power relayDetects power flow direction or power magnitude
33Position switchDetects equipment position
34Master sequence deviceControls operating sequences
35Brush or slip-ring short-circuiting/lifting deviceAssociated with brush/slip-ring equipment
36Polarity or voltage polarizing deviceAssociated with polarity or polarizing voltage functions
37Undercurrent or underpower relayDetects current or power below a threshold
38Bearing protective deviceMonitors bearing conditions
39Mechanical condition monitorMonitors mechanical equipment conditions
40Loss-of-excitation relayDetects loss or abnormal excitation in machines

4.3 ANSI Device Numbers 41–60

NumberDevice FunctionDescription
41Field circuit breakerControls the generator or machine field circuit
42Running circuit breakerAssociated with normal running circuit
43Transfer or selector deviceSelects or transfers between operating conditions
44Unit sequence starting relayControls sequence of starting operations
45Atmospheric condition monitorMonitors atmospheric/environmental conditions
46Negative-sequence or current-unbalance relayDetects current unbalance and negative sequence
47Phase-sequence or voltage-unbalance relayDetects phase sequence or voltage unbalance
48Incomplete sequence relayDetects incomplete starting or operating sequence
49Thermal overload relayProtects equipment against thermal overload
50Instantaneous overcurrent relayOperates when current exceeds a threshold without intentional delay
51AC time overcurrent relayOperates according to a time-current characteristic
52AC circuit breakerCircuit breaker for AC power circuits
53Excitation generator or field forcing deviceAssociated with excitation and field forcing
54Turning gear deviceAssociated with turning gear operation
55Power factor relayMonitors or controls power factor
56Field application relayControls application of field excitation
57Short-circuiting or grounding deviceProvides short-circuiting or grounding function
58Rectification failure relayDetects rectification system failure
59Overvoltage relayDetects voltage above a threshold
60Voltage or current balance / sensor supervision relayDetects imbalance or abnormal sensing conditions

4.4 ANSI Device Numbers 61–80

NumberDevice FunctionDescription
61Current balance or sensor relayMonitors current balance or sensing condition
62Time-delay stopping or closing relayProvides delay in stopping or closing operations
63Pressure switchDetects abnormal pressure
64Ground detector relayDetects ground faults or ground-related conditions
65GovernorControls speed or operating conditions
66Starts-per-hour or starting limitation deviceRestricts excessive starts or operations
67AC directional overcurrent relayOvercurrent protection with directional supervision
68Blocking or locking relayBlocks or locks selected operations
69Permissive control deviceEnables operation when required permissive conditions are met
70RheostatControls resistance or related adjustment
71Level switchDetects fluid or material level
72DC circuit breakerCircuit breaker for DC power circuits
73Load-resistor contactorControls load resistor circuits
74Alarm relayProvides alarm function
75Position-changing mechanismChanges equipment position or configuration
76DC overcurrent relayDetects DC overcurrent
77Pulse transmitterTransmits pulses for measurement or control
78Phase-angle or phase-measuring relayMeasures phase angle or related quantities
79AC reclosing relayControls automatic reclosing of AC circuit breakers
80Flow switchDetects flow conditions

4.5 ANSI Device Numbers 81–99

NumberDevice FunctionDescription
81Frequency relayDetects abnormal frequency
82DC reclosing relayControls DC reclosing applications
83Automatic transfer or selection deviceAutomatically selects or transfers operating conditions
84Operating mechanismAssociated with an operating mechanism
85Communication carrier or teleprotection deviceReceives or supervises communication-assisted protection signals
86Lockout relayProvides lockout following a specified fault or operation
87Differential relayDetects differential current within a protected zone
88Auxiliary motorAuxiliary motor associated with equipment
89Line or isolating switchProvides isolation
90Regulating deviceControls or regulates a quantity
91Voltage directional relayDirectional voltage-related function
92Power circuit breakerAssociated with power circuit switching
93Field-changing contactorChanges field circuit configuration
94Tripping or free-wheeling deviceAssociated with trip or free-wheeling operation
95–99Special/application-specific designationsMay be assigned to special functions, depending on applicable conventions and application

Note: Device-number descriptions may vary slightly between standard editions, application conventions, manufacturers, and utility documentation. Always consult the applicable standard and equipment documentation when creating formal engineering drawings.

5. The Most Important ANSI Numbers for Protection Engineers

While many device numbers are used in electrical control and machine applications, protection engineers most frequently work with a smaller group of numbers.

Core protection functions

50 / 51 / 67 / 87

Overcurrent, time overcurrent, directional overcurrent and differential protection form the foundation of many protection schemes.

ANSIProtection FunctionTypical Application
21Distance protectionTransmission and subtransmission lines
24V/Hz overexcitationTransformers and generators
25Synchronism checkGenerator and bus synchronization
27UndervoltageMotors, buses, generators
32Directional powerGenerators and power systems
37Undercurrent / underpowerMotors and equipment
40Loss of excitationSynchronous generators
46Negative sequenceMotors and generators
47Phase sequence / voltage unbalanceMotors and voltage systems
49Thermal overloadMotors, transformers, cables
50Instantaneous overcurrentFeeders, transformers, motors
51Time overcurrentFeeders and backup protection
52AC circuit breakerSwitching and fault interruption
55Power factorCapacitor banks and machines
59OvervoltageBuses, generators, transformers
60Sensor supervision / balanceVT/CT monitoring applications
61Current balanceCurrent sensing applications
64Ground detectionGround fault detection
67Directional overcurrentRing networks and parallel feeders
68Blocking / lockingProtection coordination and logic
79Auto-reclosingOverhead distribution and transmission
81Frequency protectionPower systems and generators
82DC reclosingDC applications
86LockoutTransformer, busbar, generator, and critical protection
87Differential protectionTransformers, generators, busbars, motors, lines
89Isolating switchIsolation and switching
90Regulating deviceVoltage and other regulating systems
91Voltage directionalDirectional voltage applications
92Power circuit breakerPower switching and control

6. ANSI 50 — Instantaneous Overcurrent Protection

Relaying Schemes and ANSI Device Numbers
Instantaneous and Time-overcurrent (50/51) Protection | Electric Power Measurement and Control Systems | Textbook
PPT - Protection Fundamentals PowerPoint Presentation, free download - ID:7076475

ANSI 50 is used to detect excessive current and operate when the measured current exceeds a configured threshold.

Unlike a time-overcurrent function, the instantaneous stage normally does not apply an intentional time delay, although the total operating time is never truly zero.

The overall operation includes:

  • Measurement and signal processing
  • Pickup detection
  • Logic processing
  • Output relay operation
  • Circuit breaker operating time
  • Fault current interruption

Applications

  • Feeder short-circuit protection
  • Transformer backup protection
  • Motor short-circuit protection
  • Busbar backup
  • Protection of cables and equipment

Example

Suppose a feeder relay has:

  • CT ratio: 400/1 A
  • Instantaneous pickup: 8 A secondary
  • Primary equivalent pickup: 3200 A

If the measured current rises above the configured pickup and the applicable logic conditions are satisfied, the relay may issue a trip command.

However, pickup must be carefully selected to avoid operating for downstream faults where selectivity is required.

7. ANSI 51 — Time Overcurrent Protection

Inverse Time Overcurrent Relays and Curves Explained - Articles - TestGuy Electrical Testing Network
Characteristic of idmt curves for overcurrent relays | PPTX
Difference between instantaneous, definite time and inverse time over current protection relays - Electrical Engineering Stack Exchange

ANSI 51 is a time-overcurrent function that operates when current exceeds a pickup threshold and the applicable operating time has elapsed.

Depending on the relay implementation, the operating characteristic can be:

  • Definite-time
  • Inverse-time
  • Very inverse
  • Extremely inverse
  • Long-time inverse
  • Other manufacturer-specific characteristics

Main parameters

ParameterMeaning
Pickup currentMinimum current required to initiate operation
Curve selectionDetermines time-current relationship
Time multiplierAdjusts operating time
Reset characteristicDefines behavior after fault current disappears
Directional supervisionMay be used with directional elements
Blocking inputMay prevent operation under selected conditions

ANSI 51 is particularly important for grading and coordination between upstream and downstream protection devices.

8. ANSI 50N / 51N — Neutral or Residual Overcurrent Protection

Earth faults can produce residual current even when phase currents are not significantly different from normal load currents.

Residual current can be calculated from the phase currents:

Ires=IA+IB+ICIres​=IA​+IB​+IC​

Under ideal balanced conditions:

IA+IB+IC≈0IA​+IB​+IC​≈0

During a ground fault, the residual current may increase.

Common earth-fault functions

DesignationFunction
50NInstantaneous neutral/residual overcurrent
51NTime neutral/residual overcurrent
50GInstantaneous ground overcurrent
51GTime ground overcurrent

The exact meaning of N and G suffixes may vary between manufacturers and system conventions. In some relays, N refers to residual or neutral current measured from summation or a neutral CT, while G may refer to current measured from a dedicated ground CT.

Typical applications

  • MV feeder earth-fault protection
  • Transformer neutral protection
  • Cable ground-fault protection
  • Generator stator ground protection schemes
  • Industrial distribution networks

9. ANSI 67 — Directional Overcurrent Protection

Electrical Friend: Directional Over Current Relay - Maximum Torque Angle
Electrical Friend: Directional Over Current Relay - Maximum Torque Angle
Alternative Methodology to Calculate the Directional Characteristic Settings of Directional Overcurrent Relays in Transmission and Distribution Networks

ANSI 67 adds directional discrimination to an overcurrent function.

A conventional overcurrent relay responds primarily to current magnitude and time. A directional overcurrent relay also evaluates the direction of fault current using reference quantities, typically voltage and current, depending on the function and implementation.

Why directional protection is needed

Directional protection is particularly useful in:

  • Ring networks
  • Parallel feeders
  • Networks with multiple sources
  • Distributed generation systems
  • Networks with power flow in both directions
  • Interconnected industrial power systems

In these networks, fault current may flow from more than one direction. A non-directional relay may not be able to discriminate correctly between faults inside and outside its intended protection zone.

Related functions

ANSIFunction
67Directional phase overcurrent
67NDirectional earth-fault overcurrent
67GDirectional ground overcurrent

The directional element may use voltage polarization, current polarization, or other methods depending on relay design.

10. ANSI 87 — Differential Protection

Transformer differential protection  | PDF

Differential protection compares electrical quantities entering and leaving a protected zone.

For an ideal protected zone:

Idiff≈0Idiff​≈0

For an internal fault, the differential current increases because the current entering the zone is no longer equal to the current leaving it, after appropriate compensation and reference-direction considerations.

Common differential applications

DesignationApplication
87TTransformer differential
87BBusbar differential
87GGenerator differential
87MMotor differential
87LLine differential
87CCable differential in some applications

Differential protection requires careful engineering

The relay may need to compensate for:

  • CT ratio differences
  • Transformer vector group
  • Phase shift
  • Transformer tap position
  • CT errors
  • CT saturation
  • Magnetizing inrush
  • Through-fault stability
  • Restricted protected-zone boundaries

Differential protection is generally designed to provide fast and selective protection for internal faults.

11. ANSI 21 — Distance Protection

ANSI 21 is a distance protection function primarily used for transmission and subtransmission line protection.

The relay measures apparent impedance:

Z=VIZ=IV​

Because line impedance is related to physical distance, the measured impedance can be used to estimate whether a fault is within a configured protection zone.

Typical distance protection zones

ZoneGeneral purpose
Zone 1Fast primary protection for a portion of the protected line
Zone 2Extended protection with coordination delay
Zone 3Remote backup protection

The actual reach, timing, directionality, and coordination must be engineered according to network conditions.

Distance protection is especially important where overcurrent protection alone cannot achieve adequate selectivity or sensitivity.

12. ANSI 27 and 59 — Undervoltage and Overvoltage Protection

ANSI 27 — Undervoltage

The 27 function detects voltage below a predefined threshold.

Applications include:

  • Motor protection
  • Bus voltage supervision
  • Load shedding
  • Voltage-based interlocking
  • Generator protection
  • Power quality supervision

Typical settings include:

  • Voltage pickup
  • Operating delay
  • Measurement quantity
  • Reset threshold
  • Blocking and permissive conditions

ANSI 59 — Overvoltage

The 59 function detects excessive voltage.

Applications include:

  • Generator protection
  • Transformer protection
  • Bus protection and supervision
  • Capacitor bank protection
  • Voltage control schemes
  • Grid-connected equipment

Overvoltage protection may be coordinated with voltage regulators, tap changers, excitation systems, and other protection functions.

13. ANSI 49 — Thermal Overload Protection

Загряване и охлаждане на електродвигателите - Електродвигатели VALIADIS България
Thermal Overload Relay – Construction, Working and Application - Electrical Concepts
전동기 특성곡선(Motor Performance Curve) 보는 방법

ANSI 49 is a thermal protection function that protects equipment against overheating.

Unlike simple overcurrent protection, thermal protection considers the heating effect of current over time.

A thermal model may take into account:

  • Load current
  • Rated current
  • Thermal capacity
  • Heating and cooling time constants
  • Previous thermal state
  • Ambient conditions, where supported
  • RTD or other temperature inputs, where supported

Applications

  • Induction motors
  • Transformers
  • Generators
  • Cables
  • Other equipment where thermal loading is important

For motor protection, 49 is particularly important because a motor may experience damaging thermal stress even when the current is not high enough to cause instantaneous short-circuit protection operation.

14. ANSI 46 — Negative-Sequence Protection

ANSI 46 detects negative-sequence current or related current unbalance.

In a three-phase electrical system, balanced currents ideally contain only positive-sequence components. When phase currents become unbalanced, negative-sequence components may appear.

Negative-sequence current can create additional heating in rotating machines, especially motors and generators.

Common causes of current unbalance

  • Phase-to-phase faults
  • Single-phase loading
  • Unequal phase impedance
  • Broken conductor
  • Abnormal supply conditions
  • Incorrect CT connections
  • Phase loss

Applications

  • Motor protection
  • Generator protection
  • Three-phase equipment protection
  • Phase-unbalance supervision

The protection settings must account for equipment withstand capability and the expected network operating conditions.

15. ANSI 47 — Phase Sequence and Voltage Unbalance

ANSI 47 is associated with phase-sequence or voltage-unbalance conditions.

It may detect conditions such as:

  • Incorrect phase sequence
  • Voltage phase unbalance
  • Loss or abnormality of a phase voltage
  • Abnormal phase rotation
  • Voltage asymmetry

Why it is important

For three-phase motors, incorrect phase sequence may cause rotation in the wrong direction. Voltage unbalance may also lead to excessive motor current unbalance and heating.

ANSI 47 is commonly used in motor control and protection schemes, particularly where correct phase sequence and voltage quality are important.

16. ANSI 40 — Loss of Excitation Protection

ANSI 40 is primarily associated with loss-of-excitation protection for synchronous machines.

Loss of excitation can cause a generator to operate abnormally, potentially leading to:

  • Rotor overheating
  • Increased reactive power demand
  • System voltage disturbance
  • Loss of stability
  • Abnormal stator currents
  • Damage to the generator

Loss-of-excitation protection may use impedance-based characteristics or other methods depending on the protection system.

This function is commonly integrated into generator protection relays or dedicated excitation protection systems.

17. ANSI 32 — Directional Power Protection

ANSI 32 is used to detect power direction or power magnitude conditions.

A typical application is reverse-power protection for generators.

When a generator loses its prime-mover input, it may begin absorbing power from the electrical network and operate as a motor.

Reverse-power protection detects this abnormal operating condition and can initiate generator disconnection.

Applications

  • Generator reverse-power protection
  • Prime-mover failure detection
  • Directional power supervision
  • Import/export control schemes
  • Power-flow monitoring

The function requires appropriate voltage and current measurements, direction references, and settings.

18. ANSI 24 — Overexcitation Protection

ANSI 24 protects equipment against excessive volts-per-hertz conditions.

The ratio is:

VffV​

Where:

  • VV = measured voltage
  • ff = frequency

An increase in voltage or decrease in frequency can increase magnetic flux in transformers and rotating machines.

Overexcitation can result in:

  • Core saturation
  • Increased magnetizing current
  • Excessive heating
  • Insulation stress
  • Equipment damage

ANSI 24 is important in generator and transformer protection applications.

19. ANSI 25 — Synchronism Check

ANSI 25 checks whether two electrical systems or circuit sides are suitable for synchronization or closing.

The function may evaluate:

  • Voltage magnitude difference
  • Frequency difference
  • Phase-angle difference
  • Slip frequency
  • Breaker closing conditions

Typical applications

  • Generator synchronization
  • Bus coupler closing
  • Grid connection
  • Transfer schemes
  • Interconnection between two energized systems

Synchronism-check protection helps prevent unsafe closing when voltage phase relationships are not acceptable.

20. ANSI 79 — Automatic Reclosing

ANSI 79 controls automatic reclosing of circuit breakers following a trip.

It is widely used in overhead distribution and transmission systems because many faults are temporary.

Typical sequence:

  1. A protection function detects a fault.
  2. The circuit breaker trips.
  3. The relay starts the autoreclosing sequence.
  4. A dead-time period is applied.
  5. The circuit breaker is commanded to close.
  6. The system checks whether the fault has cleared.
  7. If the fault remains, the protection trips again.
  8. Further reclose attempts may be blocked or performed according to the configured sequence.

Important considerations

  • Dead time
  • Reclose sequence
  • Number of attempts
  • Lockout conditions
  • Synchronism check
  • Live/dead bus conditions
  • Coordination with downstream protection
  • Circuit breaker duty

Automatic reclosing is generally more suitable for overhead lines than for many cable systems, where faults are more likely to be permanent.

21. ANSI 81 — Frequency Protection

ANSI 81 protects electrical systems against abnormal frequency.

Common subfunctions include:

DesignationFunction
81UUnderfrequency
81OOverfrequency
81RRate-of-change-of-frequency protection, where used
81UFUnderfrequency
81OFOverfrequency

Frequency protection is important because abnormal frequency may indicate a mismatch between generation and load.

Applications

  • Generator protection
  • Load shedding
  • Grid protection
  • Islanded networks
  • Frequency-based control schemes

Underfrequency protection may be used in staged load shedding schemes to restore the balance between generation and load.

22. ANSI 86 — Lockout Relay

ANSI 86 is a lockout function.

A lockout relay is used when a protection operation requires manual inspection, resetting, or authorization before the equipment can be returned to service.

It is commonly used for critical equipment such as:

  • Power transformers
  • Generators
  • Busbars
  • Large motors
  • Critical feeders

Example: Transformer protection

If transformer differential protection (87T) detects an internal fault, the trip logic may:

  • Trip transformer circuit breakers
  • Initiate ANSI 86 lockout
  • Block closing commands
  • Generate alarms
  • Record the protection event

The lockout function prevents automatic or unintended re-energization until the required reset conditions are fulfilled.

In numerical relays, the lockout function may be implemented using programmable logic rather than a separate physical electromechanical relay. However, the actual scheme must be checked.

23. ANSI 52 — Circuit Breaker

ANSI 52 identifies an AC circuit breaker.

Circuit breakers are the primary switching devices used to interrupt fault currents and isolate equipment.

Protection relays typically do not interrupt the primary fault current directly. They detect the fault and issue a trip command to the circuit breaker.

The protection chain includes:

  1. CT/VT sensing
  2. Relay measurement
  3. Fault detection
  4. Protection logic
  5. Trip output
  6. Trip coil energization
  7. Circuit breaker mechanical operation
  8. Fault interruption
  9. Auxiliary contact feedback

Understanding the relationship between protection functions and the circuit breaker is essential during commissioning and troubleshooting.

24. ANSI 30 — Annunciation and Alarm

ANSI 30 is associated with annunciator functions.

In modern numerical protection systems, alarms may be generated by programmable logic and displayed on:

  • Relay front panels
  • Local HMI systems
  • SCADA
  • Substation automation systems
  • Alarm/event lists
  • Remote monitoring systems

Examples include:

  • Protection pickup
  • Relay self-supervision
  • CT circuit abnormality
  • VT circuit failure
  • Communication failure
  • Breaker failure
  • DC supply abnormality
  • Trip circuit supervision alarm
  • Temperature alarm

Alarm design should distinguish between critical protection conditions and routine equipment status information.

25. ANSI 67N — Directional Earth-Fault Protection

ANSI 67N is directional earth-fault protection.

It evaluates residual or neutral current together with an appropriate directional reference, commonly residual voltage or other polarizing quantities, depending on the relay design and grounding system.

It is particularly important in:

  • Ring networks
  • Parallel feeders
  • Networks with multiple sources
  • Isolated-neutral networks
  • Compensated-neutral networks
  • Industrial networks with distributed generation

Engineering considerations

  • Grounding method
  • Zero-sequence network
  • CT connection
  • Residual current measurement
  • Polarizing voltage
  • Directional angle
  • Pickup sensitivity
  • Operating time
  • Coordination with other earth-fault protection

Directional earth-fault settings must be carefully selected according to the actual network grounding and fault-current characteristics.

26. ANSI Function Suffixes — Understanding 50, 50N, 50G, 50BF and Similar Designations

Device numbers are often combined with letters to identify a particular application or measurement quantity.

The numerical part identifies the basic device function, while the suffix helps clarify the implementation or application.

However, suffix conventions are not always universal. The same suffix may be interpreted differently in manufacturer documentation or utility standards.

Common suffixes

DesignationCommon meaning
50Instantaneous overcurrent
50NNeutral/residual instantaneous overcurrent
50GGround instantaneous overcurrent
51Time overcurrent
51NNeutral/residual time overcurrent
51GGround time overcurrent
67Directional phase overcurrent
67NDirectional earth-fault overcurrent
87TTransformer differential
87BBusbar differential
87GGenerator differential
87MMotor differential
87LLine differential
27Undervoltage
59Overvoltage
81UUnderfrequency
81OOverfrequency
50BFCircuit breaker failure protection
49Thermal overload
46Negative-sequence current
25Synchronism check

Important caution

In many modern relays, these suffixes are commonly used by engineers and utilities, but the exact implementation and naming convention should always be checked against the relay manual, drawing legend, and project protection standard.

27. ANSI Device Numbers and IEC Protection Function Names

ANSI device numbers and IEC terminology are frequently used together.

ANSI NumberCommon IEC / Functional Description
50Instantaneous overcurrent
51Time overcurrent
50N / 51NNeutral/residual earth-fault overcurrent
67Directional overcurrent
67NDirectional earth-fault overcurrent
21Distance protection
87Differential protection
49Thermal overload
27Undervoltage
59Overvoltage
46Negative-sequence protection
47Phase sequence / voltage unbalance
40Loss of excitation
32Reverse/directional power
24Overexcitation
25Synchronism check
79Auto-reclosing
81Frequency protection
86Lockout
52Circuit breaker

IEC protection function naming may use abbreviations such as:

  • I> — Overcurrent
  • I>> — High-set overcurrent
  • I0> — Earth-fault current
  • U< — Undervoltage
  • U> — Overvoltage
  • f< — Underfrequency
  • f> — Overfrequency
  • ΔI — Differential current

The exact symbols and naming conventions depend on manufacturer software and documentation.

28. ANSI Device Numbers in VAMP Protection Relays

VAMP numerical protection relays may combine multiple protection, measurement, monitoring, control, communication, and logic functions within one device.

Depending on the model, a VAMP relay may provide functions such as:

  • Phase overcurrent protection
  • Earth-fault protection
  • Directional overcurrent
  • Thermal protection
  • Negative-sequence protection
  • Voltage protection
  • Frequency protection
  • Power protection
  • Arc-fault protection
  • Breaker failure
  • Auto-reclosing
  • Programmable logic
  • Measurement and event recording

When working with a VAMP relay, the engineer should not assume that every ANSI function listed in a protection study is available in every relay.

The proper workflow is:

  1. Identify the protection requirement.
  2. Identify the corresponding ANSI function.
  3. Select an appropriate VAMP relay model.
  4. Verify the function availability in the technical manual.
  5. Check the required CT/VT inputs.
  6. Verify binary inputs and outputs.
  7. Confirm protection logic and interlocking.
  8. Configure the function.
  9. Calculate settings.
  10. Perform testing and commissioning.

29. Practical Example — Protection Functions for an MV Feeder

Consider an 11 kV feeder supplying an industrial load.

A typical protection scheme might include:

ANSI FunctionPurpose
50High-set instantaneous phase overcurrent
51Time phase overcurrent
50NInstantaneous earth fault
51NTime earth fault
67Directional phase overcurrent, if required
67NDirectional earth fault, if required
49Thermal protection or thermal monitoring, where applicable
46Current unbalance / negative-sequence protection
27Undervoltage supervision or protection
59Overvoltage protection, if required
81Frequency protection, if required
50BFBreaker failure protection, if implemented
79Auto-reclosing, if applicable
Principle Of Operation Of Over Current Relay at Patricia Mack blog
وحدة الربط الحلقي (Ring Main Unit - RMU) | هندسة كهربائية

The actual protection functions depend on:

  • Network configuration
  • Grounding method
  • Load type
  • CT/VT ratios
  • Short-circuit levels
  • Coordination study
  • Utility requirements
  • Relay capability
  • Operational philosophy

30. Practical Example — Transformer Protection

A power transformer may require a combination of protection functions.

ANSI FunctionPurpose
87TMain transformer differential protection
50/51Phase overcurrent backup
50N/51NEarth-fault protection
64Ground detection, depending on scheme
49Thermal protection
24Overexcitation protection
50BFBreaker failure protection
86Lockout
27/59Voltage protection, where applicable

Transformer protection design must consider:

  • Transformer rating
  • Vector group
  • CT ratios
  • CT locations
  • Inrush current
  • Differential restraint
  • Through-fault current
  • Grounding arrangement
  • Neutral protection
  • Backup coordination

31. Practical Example — Motor Protection

An MV motor protection scheme may include:

ANSI FunctionPurpose
50Instantaneous short-circuit protection
51Overcurrent backup
49Thermal overload protection
46Negative-sequence protection
48Incomplete starting / excessive starting time
66Starts-per-hour limitation
37Undercurrent or underpower
27Undervoltage
47Phase sequence / voltage unbalance
50N/51NEarth-fault protection
86Lockout, if required by the scheme

Motor protection requires coordination with the motor starting characteristics, thermal withstand capability, load profile, starting method, and process requirements.

32. Practical Example — Generator Protection

Generator protection functions may include:

ANSI FunctionPurpose
87GGenerator differential
50/51Overcurrent backup
46Negative-sequence current
40Loss of excitation
32Reverse power
24Overexcitation
27Undervoltage
59Overvoltage
81Frequency protection
25Synchronism check
64Ground-fault protection
49Thermal protection
86Lockout

Generator protection is highly dependent on generator type, grounding, excitation system, operating philosophy, and system interconnection requirements.

33. ANSI Device Numbers and Relay Testing

Knowing the ANSI number is also useful during protection testing and commissioning.

When performing secondary injection testing, the engineer should identify:

  • Protection function number
  • Protection stage
  • Setting value
  • Pickup threshold
  • Time characteristic
  • Operating delay
  • Logic conditions
  • Binary output mapping
  • Trip matrix
  • Circuit breaker operation
  • Alarm and event indication

Example: Testing ANSI 51

A test procedure may include:

  1. Verify relay settings.
  2. Confirm CT ratio and current scaling.
  3. Identify the active 51 stage.
  4. Check pickup value.
  5. Select the configured time-current curve.
  6. Inject current above pickup.
  7. Record operating time.
  8. Compare the measured time against the expected curve.
  9. Verify trip output.
  10. Confirm circuit breaker operation, where included in the test scope.

Example: Testing ANSI 50

Testing should verify:

  • Pickup threshold
  • Operating time
  • Output relay operation
  • Trip logic
  • Blocking conditions
  • Reset behavior
  • Correct phase selection

Example: Testing ANSI 87

Testing should verify:

  • Differential current calculation
  • Restraint/stabilization behavior
  • CT polarity and connections
  • Ratio compensation
  • Phase compensation
  • Internal-fault operation
  • Through-fault stability
  • Trip logic

The test procedure must follow the relay manual and approved commissioning documents.

34. Common Mistakes When Using ANSI Device Numbers

Mistake 1 — Assuming a device number identifies a relay model

ANSI 51 does not identify a particular relay. It identifies a protection function.

Mistake 2 — Assuming all relays have the same functions

Different relays have different protection capabilities, hardware, measurement inputs, algorithms, and logic features.

Mistake 3 — Confusing 50 and 51

  • 50 is instantaneous overcurrent.
  • 51 is time overcurrent.

They may be used together, but they are different protection stages.

Mistake 4 — Confusing 50N and 50G

The meaning of N and G depends on the measurement arrangement and convention used by the manufacturer or project.

Mistake 5 — Treating ANSI numbers as settings

Device number 51 does not provide the pickup value, curve, time multiplier, or coordination settings.

Mistake 6 — Ignoring the relay manual

A protection function may have different operating modes, characteristic curves, reset behavior, supervision, and logic options depending on the relay model.

Mistake 7 — Ignoring programmable logic

The ANSI function may be enabled, but its trip output may depend on additional logic, blocking signals, permissives, or output mapping.

Mistake 8 — Ignoring breaker-related functions

Protection relay operation and actual circuit breaker interruption are separate processes. Testing only the relay element does not necessarily prove the entire trip chain works correctly.

35. Engineering Workflow for Identifying Protection Functions

When reading a single-line diagram or protection scheme, use the following process:

Step 1 — Identify the equipment

Determine whether you are dealing with:

  • Feeder
  • Transformer
  • Motor
  • Generator
  • Busbar
  • Capacitor bank
  • Transmission line

Step 2 — Identify the protection requirements

Determine the fault conditions and abnormal operating conditions that must be detected.

Step 3 — Identify the ANSI device numbers

Map the protection requirements to the relevant protection functions.

Step 4 — Confirm relay capability

Check the selected relay manual, function list, hardware configuration, and firmware compatibility.

Step 5 — Identify measurements

Determine which CT and VT signals are required.

Step 6 — Identify trip and alarm logic

Determine which protection functions initiate trips, alarms, blocking, lockout, or other actions.

Step 7 — Calculate and coordinate settings

Perform protection setting calculations and grading studies.

Step 8 — Test and commission

Verify each function, logic, output, and trip chain according to the approved test plan.

36. Conclusion

ANSI device numbers are a fundamental language of electrical protection engineering. They allow engineers to communicate protection functions clearly across drawings, relay settings, technical specifications, commissioning procedures, and different manufacturers.

For engineers working with VAMP protection relays, the most important numbers to understand include:

  • 21 — Distance protection
  • 24 — Overexcitation
  • 25 — Synchronism check
  • 27 — Undervoltage
  • 32 — Directional power
  • 40 — Loss of excitation
  • 46 — Negative sequence
  • 47 — Phase sequence / voltage unbalance
  • 49 — Thermal overload
  • 50 — Instantaneous overcurrent
  • 51 — Time overcurrent
  • 59 — Overvoltage
  • 67 — Directional overcurrent
  • 79 — Auto-reclosing
  • 81 — Frequency protection
  • 86 — Lockout
  • 87 — Differential protection

A protection engineer should not only memorize these numbers but also understand their operating principles, application, settings, logic, limitations, and testing requirements.

This knowledge forms the foundation for relay selection, protection design, settings engineering, testing, commissioning, and troubleshooting.

37. Learn Protection & Substation Automation with Elec-Engg

Online Relay testing training using Our lab

Elec-Engg provides practical technical training for electrical engineers working in power system protection, relay testing, commissioning, control, and substation automation.

Training formats include:

  • Recorded technical courses
  • Structured self-paced training
  • Live online training
  • Face-to-face technical training
  • Customized in-house training for companies and utilities

Our training topics include VAMP, Siemens SIPROTEC, ABB protection relays, Schneider Electric, relay testing with OMICRON, protection settings and coordination, IEC 61850, substation automation systems, SCADA, and practical engineering projects.

Visit the platform for technical courses, engineering materials, updates, and training information.

Website: https://elec-engg.com

WhatsApp technical updates: https://elec-engg.com/update

References and Further Reading

  • IEEE/ANSI C37.2 — Electrical power system device function number designations
  • IEC 60255 — Measuring relays and protection equipment
  • IEC 61850 — Communication networks and systems for power utility automation
  • Manufacturer-specific protection relay manuals, function lists, setting guides, and commissioning manuals
  • Protection coordination and short-circuit study documentation
  • Electrical equipment protection and application engineering references