Schneider Sepam Protection Relays

Schneider Sepam Protection Relays: Complete Guide to Architecture, Models, Protection Functions, Configuration, Applications and Engineering

1. Introduction to Schneider Sepam Protection Relays

Schneider Electric Sepam is a family of numerical protection and measurement relays designed primarily for medium-voltage (MV) electrical power systems. Sepam relays provide protection, monitoring, measurement, control and communication functions for electrical distribution networks and industrial power systems.

They are widely used in:

  • Medium-voltage distribution substations.
  • Industrial electrical networks.
  • Power generation facilities.
  • Transformer protection panels.
  • Motor control and protection systems.
  • Feeder and incoming circuit protection.
  • Capacitor bank protection.
  • Electrical infrastructure and utility networks.

Sepam relays combine multiple protection functions within a single numerical device. Depending on the model, they can measure electrical quantities, detect abnormal operating conditions, initiate circuit breaker tripping, monitor equipment status and communicate with supervisory control systems.

Unlike traditional electromechanical protection relays, Sepam devices use digital measurement and numerical processing to implement protection algorithms.

The Sepam family has been used extensively in industrial and utility installations, particularly in medium-voltage switchgear applications.

2. Sepam Relay Product Families

Sepam relays are available in different product families designed for different protection requirements.

The principal families include:

Sepam familyGeneral application
Sepam Series 20Basic MV feeder, transformer and motor protection
Sepam Series 40More advanced feeder, transformer and motor protection
Sepam Series 60Advanced protection and measurement applications
Sepam Series 80Complex protection, control and automation applications

The appropriate relay depends on the electrical equipment being protected, required protection functions, measurement requirements, communication interfaces and system architecture.

MERLIN GERIN SEPAM SERIES 20 QUICK START QUIDE Pdf Download | ManualsLib
Sepam series 40 | Schneider Electric Australia
Sepam series 60 | Schneider Electric Israel

2.1 Sepam Series 20

Sepam Series 20 is intended for relatively straightforward medium-voltage protection applications.

Typical applications include:

  • Incoming and outgoing feeders.
  • Distribution transformers.
  • Induction motors.
  • Basic overcurrent and earth fault protection.

These relays provide fundamental protection and measurement functions for conventional MV distribution installations.

2.2 Sepam Series 40

Sepam Series 40 provides additional protection and application capabilities compared with basic Series 20 devices.

Typical applications include:

  • Industrial feeders.
  • Transformer protection.
  • Motor protection.
  • Generator-related applications, depending on model.
  • More advanced protection coordination.

2.3 Sepam Series 60

Sepam Series 60 is designed for more demanding protection applications requiring additional measurement, protection and communication capabilities.

Its applications include industrial distribution systems and installations requiring advanced monitoring and protection functionality.

2.4 Sepam Series 80

Sepam Series 80 is intended for complex protection applications.

Depending on the exact model and configuration, applications include:

  • Advanced feeder protection.
  • Transformer differential protection.
  • Generator protection.
  • Motor protection.
  • Advanced protection logic.
  • Complex industrial electrical networks.

Important: Protection functions and model availability vary by Sepam reference, firmware and hardware configuration. Always verify the applicable Schneider Electric documentation before specifying or commissioning a relay.

3. Sepam Relay Hardware Architecture

A Sepam numerical protection relay consists of several functional hardware sections.

Understanding the hardware architecture is essential for relay selection, installation, configuration, testing and troubleshooting.

The main components include:

  1. Current measurement inputs.
  2. Voltage measurement inputs, where supported.
  3. Analog measurement circuits.
  4. Numerical processing unit.
  5. Binary input circuits.
  6. Binary output circuits.
  7. Communication interfaces.
  8. Local operator interface.
  9. Auxiliary power supply.
  10. Optional measurement and application modules.
PPT - SEPAM Digital Relay PowerPoint Presentation, free download - ID:1410379
59657 - 6 pins ring lug connector CCA627 for Sepam series 40 | Schneider Electric Ireland
Sepam80中通信模块怎么和主单元连接? | 施耐德电气 China

3.1 Current Transformer Inputs

Sepam relays receive current signals from external current transformers (CTs).

The CT secondary current is supplied to the relay’s current measurement circuits.

Depending on the relay model and configuration, measured currents can be used for:

  • Phase overcurrent protection.
  • Earth fault protection.
  • Negative sequence protection.
  • Thermal overload protection.
  • Differential protection.
  • Load monitoring.
  • Current measurement and recording.

Correct CT selection and connection are essential for accurate protection operation.

Important engineering parameters include:

  • CT primary current rating.
  • CT secondary current rating.
  • CT accuracy class.
  • CT burden.
  • CT polarity.
  • CT saturation performance.
  • Protection function requirements.

3.2 Voltage Measurement Inputs

Certain Sepam applications require voltage measurement.

Voltage transformers (VTs) provide the voltage signals used for functions such as:

  • Undervoltage protection.
  • Overvoltage protection.
  • Frequency protection.
  • Directional protection.
  • Power measurement.
  • Power factor measurement.
  • Synchronism-related functions, where supported.

The VT connection arrangement must be compatible with the selected relay and its configured measurement scheme.

3.3 Binary Inputs

Binary inputs allow Sepam relays to receive external status and control signals.

Typical applications include:

  • Circuit breaker open indication.
  • Circuit breaker closed indication.
  • Protection trip circuit supervision.
  • Local and remote control selection.
  • External protection trip.
  • Interlocking signals.
  • Transformer alarm signals.
  • Motor status signals.

Binary input configuration is particularly important when implementing protection logic and control schemes.

3.4 Binary Outputs

Binary outputs provide relay contact signals for external equipment.

Typical applications include:

  • Circuit breaker trip.
  • Circuit breaker closing.
  • Alarm indication.
  • Protection operation.
  • External interlocking.
  • Equipment control.
  • Remote signalling.

The output contact rating and trip circuit arrangement must be checked against the relevant equipment specifications.

3.5 Communication Interfaces

Sepam relays can communicate with supervisory and engineering systems through supported communication interfaces.

Depending on the model and installed communication equipment, communication technologies may include:

  • Modbus RTU.
  • Modbus TCP.
  • IEC 61850, through supported interfaces and configurations.
  • Other supported communication arrangements.

Communication capabilities must be checked for the exact relay reference and hardware version.

4. Sepam Protection Functions

Sepam relays implement different protection functions according to their model and configuration.

The following table summarizes important ANSI protection functions commonly encountered in Sepam applications.

ANSI codeProtection functionTypical application
50Instantaneous overcurrentShort-circuit protection
51Time overcurrentFeeder protection
50N/51NEarth fault protectionGround fault detection
67Directional overcurrentParallel networks
67NDirectional earth faultGround fault direction
46Negative sequenceUnbalanced conditions
49Thermal overloadMotors and transformers
27UndervoltageVoltage supervision
59OvervoltageAbnormal voltage
81Frequency protectionFrequency deviations
32Directional powerGenerator applications
37UndercurrentMotor and load supervision
48Incomplete startingMotor protection
66Excessive starting frequencyMotor protection
87Differential protectionApplicable transformer and machine schemes
50BFBreaker failureCircuit breaker backup

Not every function is available in every Sepam model.

4.1 Phase Overcurrent Protection (50/51)

Overcurrent protection is one of the most important functions in medium-voltage electrical distribution systems.

Sepam relays monitor the phase currents and detect abnormal current conditions.

Two main operating characteristics are commonly used:

Instantaneous overcurrent (50)

The relay operates when the measured current exceeds a configured pickup threshold without an intentional time delay, subject to its operating characteristics.

Time overcurrent (51)

The relay operates according to a selected time-current characteristic.

Typical characteristics include:

  • Standard inverse.
  • Very inverse.
  • Extremely inverse.
  • Definite time.

The selection depends on the network configuration, fault current levels and coordination requirements.

4.2 Earth Fault Protection (50N/51N)

Earth fault protection detects current flowing through an unintended ground fault path.

Depending on the installation, earth fault current can be measured using:

  • Residual current calculated from three phase CT measurements.
  • A dedicated core-balance CT.
  • A separate earth fault CT arrangement.

The engineer must verify the relay’s supported measurement configuration and wiring requirements.

4.3 Directional Overcurrent Protection (67)

Directional overcurrent protection is useful in networks where fault current can flow in different directions.

The relay evaluates current magnitude and the appropriate voltage reference to determine the fault direction.

Applications include:

  • Parallel feeders.
  • Ring networks.
  • Networks with distributed generation.
  • Industrial interconnected networks.

4.4 Thermal Overload Protection (49)

Thermal protection estimates the heating condition of protected equipment using current measurements and the applicable thermal model.

It is particularly important for motor protection.

Thermal overload protection helps prevent equipment damage resulting from prolonged excessive loading.

4.5 Undervoltage and Overvoltage Protection (27/59)

Voltage protection functions monitor system voltage and detect abnormal operating conditions.

Typical applications include:

  • Motor undervoltage protection.
  • Transformer voltage supervision.
  • Distribution network voltage monitoring.
  • Generator-related voltage supervision.

4.6 Frequency Protection (81)

Frequency protection detects abnormal system frequency.

Depending on the relay model, available functions may include underfrequency and overfrequency protection.

These functions can be used for equipment protection and load-shedding applications.

5. Sepam Applications in Electrical Power Systems

Sepam relays are used in different electrical installations.

5.1 MV Feeder Protection

A typical MV feeder protection arrangement includes:

  • Current transformers.
  • Voltage transformers, where required.
  • Sepam protection relay.
  • Vacuum circuit breaker.
  • Trip and close circuits.
  • Auxiliary DC supply.
  • Communication interface.

The relay continuously monitors the electrical quantities and initiates a trip when a configured protection function detects a qualifying fault.

5.2 Transformer Protection

Sepam relays can be applied to transformer protection according to the selected model and protection scheme.

Typical protection requirements include:

  • Phase overcurrent.
  • Earth fault.
  • Thermal overload.
  • Restricted earth fault, where supported.
  • Transformer differential protection, where supported.
  • External transformer alarm and trip integration.

Transformer differential protection requires careful consideration of CT ratios, vector group compensation and the selected relay’s capabilities.

5.3 Motor Protection

Motor protection applications require several complementary protection functions.

These may include:

  • Short-circuit protection.
  • Thermal overload.
  • Locked rotor protection.
  • Excessive starting time.
  • Negative sequence protection.
  • Earth fault protection.
  • Undercurrent protection.

Motor protection settings must consider rated current, starting current, acceleration time, thermal withstand capability and operating conditions.

5.4 Generator Protection

Sepam generator-related applications depend on the selected model.

Protection requirements may include:

  • Overcurrent.
  • Earth fault.
  • Negative sequence.
  • Reverse power.
  • Voltage protection.
  • Frequency protection.
  • Thermal protection.

For complex generator protection schemes, verify the required functions and whether dedicated generator protection equipment is more appropriate.

6. Sepam Engineering Software — SFT2841

SFT2841 is the engineering software historically associated with Sepam protection relays.

It is used for supported Sepam models to perform engineering, configuration and maintenance activities.

Typical tasks include:

  • Relay identification.
  • Reading relay configuration.
  • Protection parameter configuration.
  • Logic configuration.
  • Communication parameter management.
  • Monitoring measurements.
  • Retrieving event records.
  • Reviewing diagnostic information.
¿Cómo puedo anular el sellado del disparo en el relé Sepam 40? | Schneider Electric España
Checkbox to turn on 87T protection is disabled in SFT2841 for Sepam Series 80 | Schneider Electric España
Sepam MCS025 Synchro-check module - why are asterisks (" *** " or stars) displayed for the differences in the measurements screen of SFT2841? | ชไนเดอร์ อิเล็คทริค Thailand

6.1 Creating a Sepam Project

A typical engineering workflow includes:

  1. Install the compatible SFT2841 software version.
  2. Identify the Sepam relay reference.
  3. Select the correct device in the software.
  4. Create a new engineering configuration.
  5. Configure the measurement inputs.
  6. Enter CT and VT parameters.
  7. Enable the required protection functions.
  8. Configure protection settings.
  9. Configure binary inputs and outputs.
  10. Configure communication parameters.
  11. Review and validate the configuration.
  12. Save the engineering project.

6.2 Online and Offline Engineering

Sepam engineering can involve online and offline activities.

Offline engineering

The engineer prepares or reviews the configuration without an active connection to the relay.

Online engineering

The engineer establishes communication with the relay to retrieve information, monitor measurements or perform supported configuration operations.

Before downloading settings, verify the complete configuration and confirm that the proposed changes are approved.

6.3 Reading and Downloading Settings

A disciplined configuration process should include:

  • Reading the existing relay configuration.
  • Saving a backup copy.
  • Comparing existing and proposed settings.
  • Reviewing protection parameters.
  • Checking logic and output assignments.
  • Confirming communication parameters.
  • Obtaining authorization before applying changes.

Never overwrite an existing protection configuration without first preserving and reviewing the original settings.

7. Sepam Protection Settings Engineering

Correct protection settings are essential for reliable operation.

A protection engineer must understand the electrical network, equipment ratings, fault levels and coordination requirements before configuring a Sepam relay.

7.1 CT Ratio Configuration

Consider an MV feeder with:

  • CT primary current: 400 A.
  • CT secondary current: 1 A.
  • Feeder rated current: 300 A.

The CT ratio is:

CTR=4001=400CTR=1400​=400

The secondary current corresponding to 300 A primary current is:

Is=300400=0.75AIs​=400300​=0.75A

The relay measurement configuration must correspond to the actual installed CT arrangement.

7.2 Overcurrent Pickup Setting

The pickup current should be selected based on:

  • Maximum normal operating current.
  • Equipment thermal limits.
  • Minimum fault current.
  • CT characteristics.
  • Protection coordination.
  • Relay measurement characteristics.

A suitable setting must allow normal operating current while ensuring reliable detection of the intended fault conditions.

7.3 Time-Current Coordination

Overcurrent relay coordination ensures that the protection device nearest to the fault operates first whenever possible.

The coordination study should consider:

  • Upstream protection.
  • Downstream protection.
  • Maximum and minimum fault currents.
  • Circuit breaker operating time.
  • Relay operating time.
  • CT performance.
  • Equipment withstand characteristics.

8. Sepam Communication and SCADA Integration

Sepam relays can form part of a substation automation system.

They provide electrical measurements, protection status and equipment information to supervisory systems through supported communication interfaces.

Typical SCADA integration requirements include:

  • Current and voltage measurements.
  • Active and reactive power.
  • Circuit breaker status.
  • Protection pickup indications.
  • Protection trip indications.
  • Alarm information.
  • Event records.
  • Communication health.

8.1 Modbus Communication

Modbus is commonly used for exchanging measurements, status information and control-related data.

The engineering process generally involves:

  1. Selecting the supported communication interface.
  2. Configuring communication parameters.
  3. Defining the device address.
  4. Configuring the SCADA communication channel.
  5. Mapping the required data registers.
  6. Testing communication.
  7. Verifying measurements and indications.

8.2 IEC 61850 Integration

IEC 61850 integration depends on the exact Sepam generation, communication hardware and supported interface.

The engineer must verify whether the installed device supports native IEC 61850 communication or requires an external gateway or interface.

Important engineering topics include:

  • Logical nodes.
  • Data objects.
  • MMS communication.
  • GOOSE messaging, where supported.
  • SCL engineering.
  • IED integration.
  • SCADA data mapping.

9. Sepam Relay Testing and Commissioning

Testing and commissioning verify that the relay operates correctly and that its protection and control functions are properly integrated with the electrical installation.

A complete commissioning process should include the following activities.

9.1 Visual and Hardware Inspection

Check:

  • Relay model and reference.
  • Auxiliary supply rating.
  • CT wiring.
  • VT wiring.
  • Binary input connections.
  • Binary output connections.
  • Communication wiring.
  • Earthing arrangements.
  • Terminal tightness.

9.2 Secondary Injection Testing

Secondary injection testing verifies the relay’s protection functions using a suitable protection relay test set.

Typical equipment includes Omicron CMC test systems.

Testing may include:

  • Phase overcurrent pickup.
  • Overcurrent operating time.
  • Earth fault pickup.
  • Directional protection.
  • Voltage protection.
  • Frequency protection.
  • Thermal protection.
  • Binary input and output operation.

9.3 Trip Circuit Verification

The complete trip chain should be checked.

This includes:

  1. Protection element operation.
  2. Relay trip logic.
  3. Output contact operation.
  4. Trip circuit continuity.
  5. Circuit breaker trip coil operation.
  6. Circuit breaker opening.
  7. Auxiliary contact status feedback.

9.4 Communication Testing

Verify:

  • Communication availability.
  • Correct device identification.
  • Correct measurements.
  • Correct status indications.
  • Correct alarm mapping.
  • Event transmission.
  • SCADA communication recovery.

9.5 Final Commissioning Documentation

The commissioning report should include:

  • Relay model and serial number.
  • Firmware and configuration details.
  • Approved protection settings.
  • CT and VT information.
  • Test equipment details.
  • Test results.
  • Trip circuit verification.
  • Communication test results.
  • Outstanding issues.
  • Final approval.

10. Sepam Troubleshooting

Common Sepam problems encountered during operation and commissioning include:

ProblemPossible causeRecommended investigation
Relay does not power upAuxiliary supply problemCheck supply voltage and connections
Incorrect current measurementCT wiring or ratio errorVerify CT wiring and configuration
Incorrect voltage measurementVT wiring or configurationCheck phase connections and settings
Unwanted protection operationIncorrect settings or wiringReview fault records and protection settings
Communication failureIncorrect parameters or wiringCheck interface and communication configuration
Binary input not detectedIncorrect wiring or assignmentVerify input voltage and configuration
Trip output not operatingOutput logic or wiring problemCheck logic and trip circuit
Unable to connect through SFT2841Software or interface incompatibilityVerify software, connection and device support

10.1 Event and Fault Record Analysis

Event and fault records are important diagnostic tools.

They can help engineers investigate:

  • Protection element operation.
  • Circuit breaker operation.
  • Abnormal electrical quantities.
  • External trip signals.
  • Communication failures.
  • Incorrect control logic.
  • Unwanted relay operation.

The exact recording and retrieval capabilities depend on the Sepam model.

11. Important Engineering Considerations

Before selecting or commissioning a Sepam relay, consider the following:

Model compatibility: Verify the exact Sepam reference and supported protection functions.

Software compatibility: Use the appropriate engineering software and version.

Hardware configuration: Confirm the installed measurement, communication and I/O hardware.

Protection coordination: Complete the protection study before entering settings.

CT and VT selection: Verify ratios, accuracy, burden, polarity and wiring.

Firmware: Check the applicable firmware and compatibility requirements.

Communication: Verify the protocol and interface supported by the actual relay.

Lifecycle: Sepam is an established product family with different generations and product references. Check current Schneider Electric documentation for availability, technical support and replacement recommendations.

12. Schneider Sepam Protection Relay Training by Elec-Engg

Practical Power System Protection & Relay Engineering Training

Elec-Engg provides professional technical training and engineering education for electrical engineers working in power system protection, protection and control, substation automation, testing and commissioning.

Training topics can include:

  • Sepam protection relay architecture.
  • Sepam Series 20, 40, 60 and 80.
  • Sepam protection functions.
  • SFT2841 engineering software.
  • Protection settings and coordination.
  • CT and VT engineering.
  • Feeder, motor and transformer protection.
  • Relay testing using Omicron CMC.
  • Secondary injection testing.
  • Trip circuit verification.
  • Modbus and IEC 61850 integration.
  • Practical troubleshooting and commissioning.

Training by Dr Saeed Roostaee — Electrical Engineering

Elec-Engg focuses on practical engineering knowledge, real protection applications and the skills required by engineers working in electrical utilities, industrial facilities and substations.

Explore training resources:

  • Elec-Engg — Power System Protection Training
  • Elec-Engg — Training Courses
  • Elec-Engg — Substation Automation Training

13. Conclusion

Schneider Sepam protection relays have been widely applied in medium-voltage electrical distribution and industrial power systems.

Understanding the different Sepam families, hardware architecture, protection functions, engineering software, settings, communication interfaces and testing procedures is essential for protection engineers.

A systematic approach to relay selection, configuration, protection coordination and commissioning helps improve electrical system reliability and operational safety.

For engineers working with installed Sepam equipment, practical knowledge of SFT2841, protection function testing, event analysis and troubleshooting is particularly valuable.

Leave a Comment

Your email address will not be published. Required fields are marked *

Scroll to Top