- 1. What is the SEL-351 Protection System?
- 2. SEL-351 Models and Product Family
- 3. Main Applications of the SEL-351
- 4. SEL-351 Protection Functions and ANSI Device Numbers
- 4.1 Phase Overcurrent Protection – 50P and 51P
- 4.2 Ground Overcurrent Protection – 50G, 51G, 50N and 51N
- 4.3 Directional Overcurrent Protection – 67
- 4.4 Negative-Sequence Protection – 50Q, 51Q and 67Q
- 4.5 Automatic Reclosing – 79
- 4.6 Breaker Failure Protection – 50BF
- 4.7 Voltage and Frequency Protection – 27, 59 and 81
- 4.8 Harmonic Blocking
- 4.9 Fault Locator
- 4.10 Breaker Monitoring
- 5. Communication and Substation Automation
- 6. SEL-351 Configuration Using acSELerator QuickSet
- Step 1 – Establish Communication
- Step 2 – Retrieve the Existing Settings
- Step 3 – Configure CT and VT Ratios
- Step 4 – Configure Overcurrent Protection
- Step 5 – Configure Directional Elements
- Step 6 – Configure Reclosing and Breaker Failure Logic
- Step 7 – Configure SELogic Control Equations
- Step 8 – Save and Verify the Settings
- 7. SEL-351 Relay Testing and Commissioning
- 8. SEL-351 vs SEL-351A vs SEL-351S
- 9. Common Engineering Mistakes
- 10. SEL-351 Protection Relay Training by Elec-Engg
- 11. Frequently Asked Questions
- What is the SEL-351 relay used for?
- Does the SEL-351 support directional overcurrent protection?
- Can the SEL-351 be used in a looped distribution network?
- Does the SEL-351 support IEC 61850?
- Which software is used to configure the SEL-351?
- Can the SEL-351 perform automatic reclosing?
- Can the SEL-351 provide breaker failure protection?
- Can the SEL-351 be tested using OMICRON CMC?
- What is the difference between SEL-351 and SEL-351A?
- 12. Conclusion
The SEL-351 Protection System from Schweitzer Engineering Laboratories (SEL) is a multifunction numerical relay designed for protection, monitoring, control and automation of electrical power systems. It is widely applied in utility and industrial substations, particularly for distribution feeder protection and directional overcurrent applications.
The SEL-351 combines phase and ground overcurrent protection, directional elements, automatic reclosing, breaker failure protection, fault location, frequency and voltage protection, event recording, breaker monitoring and advanced communication capabilities.
For protection engineers, commissioning teams and substation automation specialists, understanding the SEL-351 is important when designing, configuring, testing and maintaining modern protection systems.
This guide introduces the SEL-351 family, explains its main applications and protection functions, and describes the engineering workflow using acSELerator QuickSet.
SEL-351 Protection System: Complete Guide to Applications, Protection Functions, Settings, Communication and Testing
Learn about the SEL-351 protection system, including feeder protection, directional overcurrent, reclosing, breaker failure, IEC 61850, QuickSet configuration and relay testing.

1. What is the SEL-351 Protection System?
The SEL-351 is a multifunction protection system designed primarily for protecting and controlling electrical feeders and other power system equipment.
Its capabilities extend beyond conventional feeder overcurrent protection. Depending on the model and ordered options, it can support:
- Radial and looped distribution feeder protection.
- Directional and nondirectional overcurrent protection.
- Transformer, bus-main and bus-tie breaker protection.
- Transmission and subtransmission line backup protection.
- Pilot protection schemes.
- Automatic reclosing and synchronism checking.
- Breaker failure protection.
- Capacitor bank protection.
- Small generator and distributed generation protection.
- Underfrequency load shedding.
- Substation automation and SCADA integration.
The relay also provides event reports, sequential event recording, metering, breaker monitoring and fault-location capabilities.
Important: SEL-351 variants, hardware revisions and ordering options do not necessarily have identical functions. Engineers should always check the exact device model, firmware, instruction manual and ordering information before preparing a protection design or settings file.
2. SEL-351 Models and Product Family
The SEL-351 product family includes several versions developed for different protection and control requirements.
SEL-351 Protection System
The SEL-351 is suitable for feeder protection and applications requiring directional overcurrent protection, advanced communication and monitoring capabilities.
Typical applications include:
- Radial and looped distribution networks.
- Grounded, impedance-grounded and ungrounded power systems.
- Feeder protection with directional elements.
- Pilot protection and communications-assisted tripping.
- Breaker failure protection.
- Automatic reclosing.
SEL-351-5, SEL-351-6 and SEL-351-7
The SEL-351-5, SEL-351-6 and SEL-351-7 are documented versions of the SEL-351 Protection System.
They provide combinations of protection, monitoring, control and communication functions. Their detailed capabilities and ordering options should be checked against the applicable SEL documentation.
One notable distinction in the product information is that directional power elements are identified for the SEL-351-7. Do not assume that every function or hardware option is available in all three versions.
SEL-351A Protection System
The SEL-351A is an economical protection solution focused on overcurrent protection for utility and industrial power systems.
Typical applications include:
- Primary feeder overcurrent protection.
- Backup overcurrent protection.
- Phase and ground fault protection.
- Directional ground protection.
- Load-encroachment supervision.
- Feeder protection and control.
Although the SEL-351 and SEL-351A share some application areas, they should not be treated as identical relays. Their protection functions, communication options and hardware configurations must be compared using their individual product documentation.
SEL-351S Protection System
The SEL-351S is another member of the family, featuring a protection and control platform with operator-interface and monitoring capabilities.
Its application areas include feeder protection, breaker control, automation and power system monitoring. The product family documentation describes features such as programmable operator pushbuttons, event recording, breaker monitoring and communication options.
SEL-351RS Kestrel
The SEL-351RS Kestrel is a single-phase recloser control designed for single-phase distribution applications. It should be considered a separate application-specific product rather than simply another version of a conventional three-phase SEL-351 feeder relay.

3. Main Applications of the SEL-351
3.1 Distribution Feeder Protection
One of the most common applications of the SEL-351 is protecting medium-voltage distribution feeders.
A typical feeder protection scheme may include:
- Phase overcurrent protection.
- Ground overcurrent protection.
- Directional overcurrent protection.
- Automatic reclosing.
- Breaker failure protection.
- Fault recording and fault location.
- Voltage and frequency protection.
The relay measures current and, where provided by the selected configuration, voltage. It evaluates the measured quantities against configured protection elements and initiates the appropriate trip or control logic.
3.2 Radial and Looped Network Protection
In a radial network, fault current generally flows from one source toward the fault location. Time-graded overcurrent protection can often provide the required selectivity.
In a looped network, current can flow from more than one direction. Directional overcurrent elements become important because the relay must distinguish forward faults from reverse faults.
The SEL-351 provides directional phase and ground overcurrent functions to support these applications.
3.3 Transformer and Bus-Main Protection
The SEL-351 can be applied for directional or nondirectional overcurrent protection of transformer, bus-main and bus-tie breakers.
It may serve as primary overcurrent protection in suitable applications or as backup protection alongside dedicated transformer or busbar differential protection.
It should not be assumed to replace a dedicated differential protection system where differential protection is required by the protection philosophy.
3.4 Pilot Protection
The SEL-351 supports communications-assisted protection schemes for suitable line applications.
Pilot protection can be applied to transmission, subtransmission and distribution circuits, including certain three-terminal line applications.
Depending on the scheme, traditional pilot communication equipment or SEL Mirrored Bits communications may be used.
The engineering design must consider communication-channel availability, channel delay, failure modes, permissive or blocking logic and backup protection.
3.5 Ground Fault Protection in Different Grounding Systems
Ground fault detection can be challenging in systems with high-resistance grounding, ungrounded neutral arrangements or Petersen-coil grounding.
The SEL-351 provides sensitive ground directional protection capabilities intended to support different system grounding practices.
Correct application requires an understanding of:
- Neutral grounding arrangements.
- Zero-sequence current.
- Residual voltage.
- Current-transformer connections.
- Directional polarization.
- Expected fault current magnitude.
- Required sensitivity and security.
4. SEL-351 Protection Functions and ANSI Device Numbers
The following table summarizes important protection functions associated with the SEL-351 family. Availability depends on the exact relay version and configuration.
| ANSI code | Protection function | Typical application |
|---|---|---|
| 50P | Phase instantaneous overcurrent | High-current phase faults |
| 51P | Phase time overcurrent | Phase fault protection and grading |
| 50G / 50N | Ground or neutral instantaneous overcurrent | Earth fault detection |
| 51G / 51N | Ground or neutral time overcurrent | Time-graded earth fault protection |
| 50Q / 51Q | Negative-sequence overcurrent | Unbalanced fault detection |
| 67P | Directional phase overcurrent | Directional feeder protection |
| 67G / 67N | Directional ground or neutral overcurrent | Directional earth fault protection |
| 67Q | Directional negative-sequence overcurrent | Directional unbalanced fault protection |
| 27 | Undervoltage | Voltage supervision and load shedding |
| 59 | Overvoltage | Abnormal voltage protection |
| 81U | Underfrequency | Load shedding and system protection |
| 81O | Overfrequency | Frequency supervision |
| 81R | Rate of change of frequency | Frequency disturbance detection |
| 79 | Automatic reclosing | Restoration after transient faults |
| 25 | Synchronism check | Safe breaker closing |
| 50BF | Breaker failure protection | Backup clearing when a breaker fails |
| 32 | Directional power | Power-flow supervision and protection |
The table is an engineering overview, not a complete function list for every SEL-351 model.
4.1 Phase Overcurrent Protection – 50P and 51P
Phase overcurrent protection is a fundamental function in feeder protection.
The SEL-351 supports instantaneous and time-overcurrent elements that can be configured according to the system fault levels and protection coordination requirements.
Engineers should consider:
- Maximum load current.
- Minimum and maximum short-circuit current.
- CT ratio and accuracy.
- Transformer and cable limitations.
- Downstream protective-device characteristics.
- Upstream relay coordination.
- Cold-load pickup and motor starting conditions.
For time-overcurrent protection, the selected curve and time dial or equivalent operating-time settings must provide adequate grading margins.
4.2 Ground Overcurrent Protection – 50G, 51G, 50N and 51N
Ground fault protection detects earth faults using residual, ground or neutral current measurements, depending on the selected configuration.
The protection engineer must understand how the current signal is obtained and how the relay interprets the connected CT inputs.
Important engineering checks include:
- Residual CT connection.
- Core-balance CT connection, where applicable.
- Neutral CT input.
- CT polarity.
- Grounding-system characteristics.
- Minimum earth fault current.
- Coordination with downstream earth fault protection.
4.3 Directional Overcurrent Protection – 67
Directional overcurrent protection is especially important in interconnected and looped distribution systems.
A conventional overcurrent relay responds to current magnitude. A directional relay additionally evaluates the direction of the fault current using voltage and current quantities.
The SEL-351 includes directional phase and ground protection capabilities.
When configuring directional protection, engineers must consider:
- Voltage and current polarities.
- Phase rotation.
- Directional characteristic.
- Polarizing quantities.
- Forward and reverse fault conditions.
- Minimum operating quantities.
- System grounding arrangement.
Incorrect CT or VT polarity can cause a directional element to operate in the wrong direction. Polarity verification is therefore an essential part of commissioning.
4.4 Negative-Sequence Protection – 50Q, 51Q and 67Q
Negative-sequence current is useful for detecting unbalanced conditions.
These elements can provide protection and supervision for phase-to-phase faults and other unbalanced system conditions.
They may also be useful in applications where phase current elements alone do not provide the required sensitivity or discrimination.
4.5 Automatic Reclosing – 79
Automatic reclosing is commonly used in overhead distribution networks because many feeder faults are temporary.
The SEL-351 supports reclosing functions, including multi-shot reclosing arrangements in suitable configurations.
Typical engineering considerations include:
- Number of reclosing shots.
- Dead time.
- Reclaim time.
- Reclose sequence.
- Breaker status.
- Lockout conditions.
- Synchronism check.
- Voltage check.
- Coordination with downstream reclosers and fuses.
The reclosing scheme must be designed according to the utility’s operating philosophy. Automatic reclosing should not be enabled without considering the connected equipment and system safety requirements.
4.6 Breaker Failure Protection – 50BF
Breaker failure protection provides backup protection when a circuit breaker does not interrupt fault current after receiving a trip command.
A typical breaker failure scheme evaluates:
- Whether a trip command has been issued.
- Whether current continues to flow.
- Whether the breaker has successfully interrupted the current within the configured time.
- Whether backup tripping should be initiated.
The SEL-351 provides high-speed breaker failure detection elements and associated logic.
4.7 Voltage and Frequency Protection – 27, 59 and 81
Voltage and frequency elements can support:
- Undervoltage protection.
- Overvoltage protection.
- Underfrequency load shedding.
- Overfrequency supervision.
- Rate-of-change-of-frequency detection.
- Distributed generation interconnection schemes.
The actual protection philosophy depends on the system study, grid-code requirements and utility standards.
4.8 Harmonic Blocking
Transformer energization can produce magnetizing inrush current, which may cause unwanted operation of overcurrent protection.
The SEL-351 includes second-harmonic blocking capabilities that can be used to supervise selected tripping elements during transformer energization.
The engineer must identify which elements are supervised and verify that the blocking logic does not compromise protection security.
4.9 Fault Locator
The SEL-351 includes an impedance-based fault locator.
Fault-location information can help maintenance teams identify the approximate location of faults on overhead lines and distribution feeders.
The accuracy of the result depends on factors such as:
- Correct line impedance data.
- CT and VT measurement quality.
- Fault type.
- Fault resistance.
- Network configuration.
- Source impedance and system conditions.
Fault location is an aid to fault investigation; it should not be treated as an exact physical measurement.
4.10 Breaker Monitoring
The relay can monitor breaker operating information, including trip and close operating times and operation trends.
This information can support condition-based maintenance and help identify changes in breaker performance.
5. Communication and Substation Automation
Modern protection relays are important components of substation automation systems. The SEL-351 provides several communication capabilities, with exact options depending on the model and hardware configuration.
Communication protocols and technologies
- IEC 61850: Integration with substation automation systems and communication between compatible IEDs.
- DNP3: Communication with SCADA systems.
- Modbus TCP and RTU: Data exchange with automation and monitoring systems.
- SEL Mirrored Bits: Fast relay-to-relay logic communication for selected protection and control schemes.
- IEEE C37.118: Synchrophasor data communication.
- SNTP: Network-based time synchronization.
- PRP: Network redundancy on supported configurations.
Not every protocol or communication option is necessarily included in every device. Confirm the ordered hardware, firmware and applicable manual.
IEC 61850 Engineering
For IEC 61850-based substations, engineers may need to work with:
- Logical nodes.
- Data objects and data attributes.
- GOOSE messaging.
- MMS communication.
- SCL files.
- IED configuration.
- Signal mapping.
- Communication testing.
The SEL-351 product documentation identifies IEC 61850 support as an available communication capability. The precise implementation and available services should be verified for the selected device.

6. SEL-351 Configuration Using acSELerator QuickSet
acSELerator QuickSet SEL-5030 is the main engineering software used to configure and manage many SEL protection devices, including the SEL-351.
A typical engineering workflow includes the following steps.
Step 1 – Establish Communication
Connect the engineering computer to the relay using an available communication interface.
Depending on the device configuration, this may involve:
- Front-panel USB.
- Serial communication.
- Ethernet.
Verify the communication parameters and confirm that the connected device is the intended relay.
Step 2 – Retrieve the Existing Settings
Before modifying an installed relay, retrieve and save its existing settings.
Record:
- Relay model and serial number.
- Firmware revision.
- Settings group information.
- CT and VT ratios.
- Protection settings.
- Logic equations.
- Communication parameters.
Keep an unmodified backup of the original settings file.
Step 3 – Configure CT and VT Ratios
Enter the applicable instrument-transformer ratios and verify that the relay’s measurement quantities correspond to the actual primary system values.
Check:
- Phase CT ratios.
- Ground or neutral CT arrangement.
- VT ratios.
- Phase sequence.
- CT and VT polarity.
- Current and voltage input assignments.
Step 4 – Configure Overcurrent Protection
Set the required phase, ground and negative-sequence overcurrent elements.
The settings study should determine:
- Pickup values.
- Operating curves.
- Time multipliers or equivalent timing parameters.
- Instantaneous element thresholds.
- Directional supervision.
- Blocking and interlocking conditions.
Do not select settings simply by copying values from another feeder. Each application requires an appropriate coordination study.
Step 5 – Configure Directional Elements
For directional applications, configure the required directional elements and verify the polarizing quantities and operating directions.
Test both forward and reverse conditions before placing the relay in service.
Step 6 – Configure Reclosing and Breaker Failure Logic
If the application requires automatic reclosing or breaker failure protection, configure the corresponding settings and logic.
Verify trip circuits, breaker auxiliary contacts, lockout conditions and interlocking signals.
Step 7 – Configure SELogic Control Equations
SELogic control equations allow engineers to create customized protection and control logic.
Possible applications include:
- Trip logic.
- Alarm logic.
- Breaker status supervision.
- External blocking.
- Interlocking.
- Communications-assisted protection.
- Custom operator indications.
All logic should be documented, reviewed and tested before commissioning.
Step 8 – Save and Verify the Settings
After completing the configuration:
- Save the settings file.
- Compare it with the approved protection study.
- Review the logic.
- Check the communication configuration.
- Verify the correct settings group.
- Confirm that the relay is operating as intended.
7. SEL-351 Relay Testing and Commissioning
A correct settings file does not guarantee a correct protection system. The relay, instrument transformers, trip circuits, breaker and communication interfaces must be tested as an integrated system.
7.1 Visual and Hardware Inspection
Check:
- Relay model and ordering code.
- Auxiliary supply voltage.
- Wiring and terminal connections.
- CT and VT circuits.
- Earthing and shielding.
- Binary input and output wiring.
- Communication connections.
7.2 CT and VT Circuit Tests
Verify:
- CT ratio.
- CT polarity.
- CT secondary continuity.
- CT earthing arrangement.
- VT ratio.
- VT polarity.
- Phase rotation.
- Correct phase identification.
Incorrect instrument-transformer wiring can lead to incorrect protection operation even when the relay settings are correct.
7.3 Secondary Injection Testing
A relay test set, such as an OMICRON CMC, can be used to inject current and voltage signals into the relay.
Typical tests include:
- Phase overcurrent pickup and timing.
- Ground overcurrent pickup and timing.
- Negative-sequence protection.
- Directional overcurrent.
- Voltage protection.
- Frequency protection.
- Reclosing logic.
- Breaker failure logic.
The test plan should follow the approved protection settings and the manufacturer’s testing recommendations.
7.4 Binary Input and Output Testing
Test all relevant digital inputs and outputs.
Examples include:
- Circuit breaker open indication.
- Circuit breaker closed indication.
- External trip.
- Protection trip output.
- Breaker failure initiation.
- Reclosing enable.
- Lockout indication.
- Alarm output.
Confirm the actual field wiring and end-to-end operation, not only the relay’s internal logic status.
7.5 Communication Testing
For SCADA and substation automation applications, verify:
- Communication link status.
- Protocol configuration.
- Data mapping.
- Measurements.
- Status indications.
- Control commands, where applicable.
- Time synchronization.
- GOOSE or relay-to-relay signals, where used.
7.6 Event and Oscillography Analysis
After testing or a real system disturbance, retrieve the relay event reports and oscillography.
Use the event records to examine:
- Fault currents and voltages.
- Protection element pickup.
- Trip initiation.
- Breaker operation.
- Timing of protection events.
- External signals.
- Relay logic response.
SEL synchroWAVe Event software can be used to display and analyze SEL relay event reports and COMTRADE files.
8. SEL-351 vs SEL-351A vs SEL-351S
These relays belong to the same product family, but their applications and capabilities should be evaluated individually.
| Relay | General application emphasis |
|---|---|
| SEL-351 | Multifunction protection system, particularly directional overcurrent and advanced feeder applications |
| SEL-351A | Economical overcurrent and feeder protection |
| SEL-351S | Protection, control, operator-interface and monitoring applications |
| SEL-351RS | Single-phase recloser control |
When selecting a relay, compare the exact model and ordering information rather than relying only on the family name.
Important comparison criteria include:
- Protection elements.
- Current and voltage inputs.
- Binary inputs and outputs.
- Communication interfaces.
- IEC 61850 availability.
- Reclosing functions.
- Breaker failure capabilities.
- Metering and recording options.
- Mounting and enclosure requirements.
9. Common Engineering Mistakes
During SEL-351 configuration and commissioning, engineers should pay particular attention to the following issues:
- Incorrect CT polarity: Can affect directional protection and measured quantities.
- Incorrect CT or VT ratios: Can cause incorrect measurement and protection settings.
- Incorrect directional settings: Can result in unwanted forward or reverse operation.
- Poor coordination: Can cause unnecessary feeder or upstream breaker trips.
- Incorrect reclosing logic: Can create unsafe or undesirable breaker operation.
- Unverified SELogic equations: Can cause unexpected trip, blocking or control behavior.
- Incorrect communication mapping: Can result in missing or misleading SCADA information.
- Insufficient end-to-end testing: Can leave wiring, breaker and interlocking problems undetected.
- Using settings from another relay without review: Different models and configurations may not have identical elements or setting ranges.
10. SEL-351 Protection Relay Training by Elec-Engg
Understanding the SEL-351 requires more than knowing its ANSI protection functions. Engineers should be able to configure the relay, understand its logic, perform secondary injection tests and analyze actual fault records.
Elec-Engg provides practical training in power system protection, SEL protection relays, relay configuration and testing.
Training can be arranged according to the requirements of engineers and organizations, including:
- Online technical training.
- Customized company training.
- Face-to-face training, subject to arrangement.
- Practical relay configuration using acSELerator QuickSet.
- Protection function explanation and settings.
- SELogic control equations.
- Relay testing using OMICRON CMC and Test Universe.
- Event report and oscillography analysis.
- Protection and commissioning case studies.
The training is intended for protection engineers, commissioning engineers, substation engineers, maintenance teams and electrical engineers working with utility and industrial power systems.
For information about SEL relay training and customized technical courses, contact Elec-Engg.
11. Frequently Asked Questions
What is the SEL-351 relay used for?
The SEL-351 is mainly used for feeder protection, directional overcurrent protection, breaker control, automatic reclosing, breaker failure protection and substation automation.
Does the SEL-351 support directional overcurrent protection?
Yes. The SEL-351 provides directional phase and ground overcurrent capabilities. The available functions and settings depend on the selected model and configuration.
Can the SEL-351 be used in a looped distribution network?
Yes. Its directional overcurrent protection capabilities make it suitable for certain radial and looped network applications.
Does the SEL-351 support IEC 61850?
SEL identifies IEC 61850 communication as an available capability for the SEL-351. Confirm the ordered option and device documentation for the specific installation.
Which software is used to configure the SEL-351?
The main configuration software is acSELerator QuickSet SEL-5030.
Can the SEL-351 perform automatic reclosing?
Yes. The SEL-351 supports automatic reclosing functions, including configurable multi-shot reclosing schemes in suitable configurations.
Can the SEL-351 provide breaker failure protection?
Yes. The SEL-351 includes high-speed breaker failure detection elements and associated logic.
Can the SEL-351 be tested using OMICRON CMC?
Yes. An OMICRON CMC test set can be used for secondary injection testing of applicable protection functions, binary inputs and outputs, and control logic.
What is the difference between SEL-351 and SEL-351A?
Both are members of the SEL-351 family, but the SEL-351A is positioned as an economical overcurrent protection solution. The SEL-351 offers a broader set of application capabilities and options. Always compare the exact model documentation before selecting or replacing a relay.
12. Conclusion
The SEL-351 Protection System is a versatile numerical relay for utility and industrial power systems. Its combination of overcurrent protection, directional elements, automatic reclosing, breaker failure protection, fault location, event recording and communication capabilities makes it a valuable solution for modern feeder protection and automation.
For engineers, practical knowledge of CT and VT circuits, directional protection, protection coordination, SELogic programming, QuickSet configuration and relay testing is essential to applying the SEL-351 correctly.
Explore more practical protection relay training and substation automation resources at Elec-Engg.com.