The SEL-787L Line Current Differential Relay from Schweitzer Engineering Laboratories (SEL) is a numerical protection relay designed for fast and dependable protection of two-terminal transmission lines, distribution feeders, underground cables and distributed-generation connections.
The relay combines line current differential protection (87L), directional overcurrent protection, arc-flash detection, high-impedance fault detection, fault locating and advanced monitoring functions in a compact device.
One of its important advantages is the combination of conventional CT/PT inputs and low-energy analog (LEA) sensor inputs. This makes the SEL-787L suitable for both traditional protection installations and modern installations using Rogowski coils and low-power instrument transformers.
This article explains the SEL-787L applications, protection functions, differential protection principles, CT requirements, communication channels, configuration using QuickSet and practical testing procedures.
SEL-787L Line Current Differential Relay: Complete Guide to 87L Protection, Applications, Settings and Testing
- 1. What is the SEL-787L relay?
- 2. Applications of the SEL-787L
- 3. Main protection functions and ANSI codes
- 4. Line current differential protection – ANSI 87L
- 5. Percentage-restrained differential protection
- 6. Line charging-current compensation
- 7. Differential communication channels
- 8. Conventional CT/PT and LEA sensor inputs
- 9. Directional overcurrent protection – ANSI 67
- 10. Arc-flash protection
- 11. High-impedance fault detection – Arc Sense Technology
- 12. Broken-conductor and open-conductor detection
- 13. Intermittent ground fault detection and zero-sequence phi protection
- 14. Fault locating
- 15. Additional monitoring and protection functions
- 16. Communication and IEC 61850
- 17. Configuration using acSELerator QuickSet
- 18. SEL-787L testing and commissioning
- 19. SEL-787L vs SEL-411L vs SEL-311L
- 20. Advantages of the SEL-787L
- 21. Frequently asked questions
- 22. SEL-787L relay training by Elec-Engg
- 23. Conclusion
1. What is the SEL-787L relay?
The SEL-787L is a numerical line current differential protection relay from SEL’s 700 Series.
Its primary function is to compare current measurements at the two ends of a protected line and identify internal faults.
In addition to differential protection, the relay provides:
- Line current differential protection (87L).
- Phase and ground directional overcurrent protection (67).
- Phase and ground overcurrent protection (50/51).
- Arc-flash detection.
- High-impedance fault detection using Arc Sense Technology (AST).
- Fault locating.
- Broken-conductor and open-conductor detection.
- Intermittent ground fault detection.
- Zero-sequence phi directional protection.
- Thermal overload protection (49).
- Voltage and frequency-related functions, where configured.
- Circuit-breaker and bay monitoring.
- Event recording and disturbance analysis.
The SEL-787L is particularly suitable for applications where a dedicated line differential relay is required without the additional complexity of a combined distance and differential protection system.
Official product information: https://selinc.com/products/787L/
2. Applications of the SEL-787L
The SEL-787L is designed for two-terminal line differential applications in utility, industrial and commercial power systems.
2.1 Short transmission lines
Short transmission lines can be difficult to protect using conventional distance protection because the line impedance is relatively small.
Line current differential protection provides an alternative protection principle. Instead of estimating fault distance from measured impedance, the relay compares the currents at the two terminals.
This makes differential protection particularly attractive for short lines and critical connections.
2.2 Underground cables
The SEL-787L can be used to protect underground cable circuits between substations, industrial facilities and distribution networks.
Cable differential protection provides fast and selective fault detection within the protected cable zone.
The differential protection scheme should be designed with consideration of cable charging current, CT performance and the communication channel.
2.3 Critical distribution feeders
Industrial plants and utility substations often have feeders where a fault must be cleared quickly to minimize equipment damage and interruption of supply.
The SEL-787L combines line differential protection with directional and nondirectional overcurrent functions, providing both primary and backup protection options.
2.4 Distributed generation connections
Distributed generation introduces bidirectional current flow and changes the traditional radial distribution protection philosophy.
Examples include:
- Solar photovoltaic plants.
- Wind power plants.
- Battery energy storage systems.
- Industrial cogeneration.
- Inverter-based generation connections.
Line differential protection is useful in these applications because it compares currents at the boundaries of the protected zone rather than relying only on current magnitude and direction at one terminal.
2.5 Industrial electrical networks
The relay can be used to protect critical industrial circuits, including connections between main substations, plant substations and important distribution sections.
Its flexible I/O and communication options also support integration into industrial automation systems.
3. Main protection functions and ANSI codes
| ANSI code | Protection function | Application |
|---|---|---|
| 87L | Line current differential | Primary protection of two-terminal lines |
| 50P / 51P | Phase overcurrent | Instantaneous and time-delayed phase protection |
| 50G / 51G | Ground overcurrent | Ground-fault backup protection |
| 67P | Phase directional overcurrent | Directional phase fault protection |
| 67G | Ground directional overcurrent | Directional ground-fault protection |
| 50N / 51N | Neutral overcurrent | Sensitive earth-fault protection, where configured |
| 50AFD | Arc-flash detection | High-speed arc-flash protection |
| 49 | Thermal overload | Cable and line thermal protection |
| 59 / 27 | Overvoltage / undervoltage | Voltage protection, where configured |
| 25 | Synchronism check | Supervision of breaker closing |
| 81 | Frequency protection | Frequency supervision, where configured |
| 46 | Negative-sequence current | Unbalanced-current protection, where configured |
| AST | High-impedance fault detection | Detection of arcing and downed conductors |
| IGF | Intermittent ground fault detection | Ground-fault detection in compensated and ungrounded systems |
| DFR | Digital fault recording | Fault waveform recording |
| SER | Sequential Events Recorder | Recording changes in relay status and logic |
The availability of individual elements depends on the relay’s ordered hardware, installed firmware and application settings.
4. Line current differential protection – ANSI 87L
The principal function of the SEL-787L is line current differential protection.
The operating principle is based on Kirchhoff’s current law.
For a two-terminal transmission line, the current entering the protected zone should approximately equal the current leaving it under normal operating conditions.
Using consistent current reference directions, a simplified differential current equation is:
[
I_{\mathrm{diff}}=|I_A+I_B|
]
where:
- (I_A) is the current measured at Terminal A.
- (I_B) is the current measured at Terminal B.
The actual relay algorithm uses percentage-restraint characteristics and additional security logic.
4.1 Normal operating condition
During normal operation, current enters the line at one terminal and leaves at the other.
The differential current should be close to zero, allowing for measurement errors and line charging current.
The relay remains stable and does not issue a trip command.
4.2 External fault
Consider a short circuit outside the protected line zone.
The current entering and leaving the protected zone should remain balanced when measured using the appropriate reference directions.
Even when high fault current causes CT saturation, the relay must remain stable.
The SEL-787L uses external-fault detection and disturbance detection logic to improve security during these conditions.
4.3 Internal fault
For a fault inside the protected line zone, currents from both terminals flow toward the fault.
The differential current increases, and the relay identifies the condition as an internal fault.
The 87L element can then initiate the required trip outputs.
This operating principle provides fast and selective protection of the line or cable between the two CT locations.
5. Percentage-restrained differential protection
The SEL-787L uses percentage-restrained differential protection.
The relay evaluates the differential operating quantity against a restraint quantity.
The percentage-restraint characteristic helps prevent unwanted operation caused by:
- CT ratio errors.
- CT measurement errors.
- External faults.
- CT saturation.
- Communication disturbances.
- Differences between the two terminal measurements.
The SEL-787L offers configurable normal and secure mode slopes.
The engineer must select the appropriate characteristic according to the application and follow the manufacturer’s recommendations.
5.1 External-fault detection
External-fault detection (EFD) improves the security of the differential element during heavy external faults.
This is important because CT saturation can create an apparent differential current even though the fault is outside the protected zone.
5.2 Disturbance detection logic
Disturbance detection logic helps protect the 87L function against undetected bit errors in communication packets.
This is particularly important because differential protection relies on the correct exchange of current measurements between the line terminals.
6. Line charging-current compensation
Long transmission lines and underground cables have distributed capacitance.
This capacitance causes charging current to flow even when there is no internal fault.
If charging current is not properly considered, it can affect differential protection sensitivity and stability.
The SEL-787L includes built-in charging-current compensation to improve the performance of 87L protection on long lines.
This feature is useful for applications involving:
- Long overhead lines.
- Underground cables.
- High-capacitance circuits.
- Critical line connections.
The engineer should verify the relevant line or cable parameters and the applicable compensation settings.
7. Differential communication channels
Reliable communication is essential for line current differential protection.
The SEL-787L supports direct serial fiber-optic communication using IEEE C37.94-compatible interfaces.
The product supports:
- 1,310 nm single-mode fiber, with a specified point-to-point range up to 25 km.
- 850 nm multimode fiber, with a specified point-to-point range up to 1 km.
The relay can also operate over supported multiplexed communication arrangements.
The communication medium must be selected according to the distance between terminals, fiber type, communication equipment and project requirements.
7.1 Communication channel monitoring
The SEL-787L provides channel monitoring and alarming functions.
Its 87L Communications Report can display:
- Differential communication configuration.
- Channel health information.
- Communication diagnostics.
- Channel delay histogram.
- Worst-case channel delay.
- Historical channel monitoring information.
These features are useful during commissioning and routine maintenance.
7.2 What happens if the communication channel fails?
If the differential communication channel becomes unavailable, the 87L function may become unavailable or restricted according to the relay’s operating logic and settings.
The relay’s directional and nondirectional overcurrent functions can provide backup protection, depending on the protection philosophy.
The scheme should include communication failure alarms and a clearly defined operating strategy for channel loss.
8. Conventional CT/PT and LEA sensor inputs
One of the distinguishing features of the SEL-787L is its support for conventional instrument transformers and low-energy analog sensors.
8.1 Conventional CT and VT inputs
Traditional protection installations use current transformers and voltage transformers to provide scaled secondary signals to the protection relay.
The SEL-787L supports conventional phase current inputs and optional voltage inputs.
Engineers must verify:
- CT ratio.
- CT polarity.
- CT secondary rating.
- VT ratio.
- VT connection.
- Phase sequence.
- Secondary grounding.
- Wiring and terminal identification.
8.2 Low-energy analog (LEA) inputs
The SEL-787L can also be ordered with an LEA sensor input card.
This supports:
- Rogowski coil current inputs.
- Low-power current transformer (LPCT) inputs.
- Low-energy voltage sensor inputs.
- A sensitive 200 mA neutral current input.
LEA sensors provide several advantages:
- Reduced size and weight.
- Excellent linearity over a wide dynamic range.
- Reduced conventional secondary wiring.
- Potentially improved personnel safety.
- Suitability for compact switchgear installations.
The current and voltage sensors must be compatible with the selected relay input card and relevant IEC sensor standards.
9. Directional overcurrent protection – ANSI 67
In addition to differential protection, the SEL-787L provides directional overcurrent elements.
Directional overcurrent protection evaluates both current magnitude and fault direction.
This is important in:
- Ring networks.
- Parallel feeders.
- Networks with distributed generation.
- Industrial networks with multiple sources.
- Resonant-grounded systems.
9.1 Phase directional overcurrent
Phase directional overcurrent protection can be used to detect phase faults in the selected direction.
The relay combines directional supervision with overcurrent elements.
9.2 Ground directional overcurrent
Ground directional overcurrent protection is important where earth-fault current can flow in multiple directions.
The SEL-787L includes Best Choice Ground Directional Element logic to optimize ground directional element performance and simplify settings.
The relay also supports sensitive earth-fault applications using the optional 200 mA neutral CT input.
10. Arc-flash protection
Arc-flash incidents can cause severe injury to personnel and extensive equipment damage.
The SEL-787L offers optional arc-flash detection using a combination of light detection and high-speed overcurrent detection.
The protection system evaluates the optical signal together with current conditions to identify an arc-flash event.
10.1 Arc-flash detection principle
A typical arc-flash scheme works as follows:
- An optical sensor detects light associated with an arc.
- The relay evaluates the current condition.
- The required detection criteria are satisfied.
- The relay issues a high-speed trip command.
This combination improves security compared with relying on optical detection alone.
10.2 Arc-flash sensor applications
The relay can be configured with compatible arc-flash detection input cards and sensors.
Depending on the selected hardware, the available options include four- or eight-sensor arrangements.
The sensor locations and coverage must be engineered according to the switchgear compartment layout.
11. High-impedance fault detection – Arc Sense Technology
High-impedance faults (HIFs) are difficult to detect using conventional overcurrent protection.
A conductor may fall onto a surface with poor electrical conductivity, producing a relatively low fault current.
Conventional feeder overcurrent elements may not detect this condition reliably.
The SEL-787L uses Arc Sense Technology (AST) to identify arcing associated with some high-impedance faults.
The algorithm analyzes electrical characteristics of the arcing current and can initiate an alarm or trip according to the configured application.
AST provides an additional protection capability beyond conventional feeder overcurrent protection.
It should not be interpreted as guaranteeing detection of every downed conductor or every high-impedance fault. Performance depends on the fault characteristics, surface, system configuration and settings.
12. Broken-conductor and open-conductor detection
An open conductor can create dangerous conditions and may develop into a high-impedance fault.
The SEL-787L includes phase-discontinuity detection and optional broken-conductor detection.
These functions help identify abnormal phase-current and voltage relationships associated with conductor discontinuities.
Applications include:
- Overhead distribution lines.
- Industrial feeders.
- Cable circuits.
- Networks where open-conductor faults are a concern.
Engineers should verify the detection logic and the required trip or alarm response during commissioning.
13. Intermittent ground fault detection and zero-sequence phi protection
The SEL-787L includes additional protection functions for ungrounded and resonant-grounded networks.
13.1 Intermittent ground fault detection
Intermittent ground faults can occur when insulation breakdown repeatedly starts and extinguishes.
These faults may produce repeated transient events and can be difficult to identify using conventional ground overcurrent protection.
The SEL-787L provides intermittent ground fault detection to support applications involving compensated and ungrounded systems.
13.2 Zero-sequence phi directional element
The zero-sequence phi directional element is designed to help identify the direction of ground faults in systems with different neutral grounding arrangements.
Applications include:
- Ungrounded systems.
- Impedance-grounded systems.
- Petersen coil-grounded systems.
The relay can use this information to support selective ground-fault alarm and trip schemes.
14. Fault locating
The SEL-787L provides fault-locating algorithms to help engineers identify the approximate location of a fault on a protected line.
Fault-location information can be communicated automatically to a control center using supported serial or Ethernet communication protocols.
Fault location can help:
- Reduce inspection time.
- Improve maintenance response.
- Identify damaged cable or line sections.
- Restore supply more quickly.
- Analyze recurring fault locations.
The SEL-787L’s fault-location function should not be confused with the traveling-wave fault-location technology available on certain other SEL transmission-line relays.
15. Additional monitoring and protection functions
The SEL-787L provides several other features for feeder and line applications.
15.1 Thermal overload protection – ANSI 49
The relay provides an IEC line/cable thermal element to protect cables and cable insulation against thermal damage.
15.2 Cold-load pickup
Cold-load pickup occurs when a distribution feeder is re-energized following an extended outage.
The initial load current may be significantly higher than normal operating current.
The cold-load pickup element helps prevent unwanted overcurrent operation during these conditions.
15.3 Incipient fault detection
The relay can identify self-extinguishing half-cycle faults that may indicate developing cable insulation problems.
This feature can provide an early warning of potential cable failure.
15.4 Harmonic metering and total harmonic distortion
The SEL-787L provides harmonic metering and a total harmonic distortion (THD) element.
These functions can be useful in industrial systems and networks with significant inverter-based resources or nonlinear loads.
15.5 Optional vector-shift detection
Vector-shift detection can help identify certain islanding conditions in distributed-generation applications.
It should be applied together with an appropriate interconnection protection philosophy and the applicable grid requirements.
16. Communication and IEC 61850
The SEL-787L supports a wide range of communication interfaces and protocols.
Depending on the ordered hardware and configuration, these include:
- IEC 61850 Edition 2.1.
- IEC 60870-5-103.
- DNP3.
- Modbus TCP.
- Modbus RTU.
- EtherNet/IP.
- SEL Mirrored Bits.
- FTP.
- Telnet.
- SNTP.
- IEEE 1588 PTP.
- IEEE C37.118 synchrophasors.
- PRP.
- HSR.
- RSTP.
- Fixed GOOSE.
16.1 IEC 61850 integration
The SEL-787L can be integrated into an IEC 61850 substation automation system.
Depending on the selected configuration, engineering considerations include:
- Logical nodes.
- MMS reporting.
- GOOSE communication.
- SCL configuration files.
- Time synchronization.
- Network redundancy.
- Communication supervision.
The relay also supports IEC 61850 Test Mode for testing system components in energized substations without operating control output contacts, when correctly configured.
16.2 Network redundancy
Models with the required dual-Ethernet hardware support network redundancy technologies including:
- PRP – Parallel Redundancy Protocol.
- HSR – High-availability Seamless Redundancy.
- RSTP – Rapid Spanning Tree Protocol.
These technologies can help improve communication availability in substation automation networks.
17. Configuration using acSELerator QuickSet
SEL acSELerator QuickSet SEL-5030 is used for relay settings, configuration and management.
A typical SEL-787L engineering workflow includes:
- Establish communication with the relay.
- Confirm the relay model and firmware.
- Read and save the existing settings.
- Configure the CT and VT ratios.
- Configure the line differential protection.
- Configure the differential communication channel.
- Set the normal and secure differential slopes.
- Configure external-fault detection.
- Configure phase and ground overcurrent protection.
- Configure directional elements.
- Configure AST high-impedance fault detection, where installed.
- Configure arc-flash detection, where installed.
- Configure IGF and zero-sequence phi elements, where applicable.
- Develop SELogic control equations.
- Configure communication and IEC 61850 settings.
- Verify trip logic, alarms and output contacts.
- Save and document the final settings.
For IEC 61850 engineering, acSELerator Architect SEL-5032 can be used for supported communication configuration.
For bay screens, SEL acSELerator Bay Screen Builder SEL-5036 provides additional configuration capabilities.
Always verify that the software version supports the installed relay firmware.
18. SEL-787L testing and commissioning
Testing is essential to verify both the relay protection functions and the communication channel.
A suitable OMICRON CMC test set can be used for secondary injection and functional testing.
18.1 Visual inspection and wiring checks
Before applying test signals:
- Verify the relay model and hardware.
- Check auxiliary DC supply.
- Verify CT polarity and ratios.
- Check VT wiring and phase sequence.
- Confirm neutral CT connections.
- Inspect trip and alarm wiring.
- Verify communication fiber connections.
- Check installed optional cards.
- Confirm the approved settings.
18.2 Line differential protection testing – 87L
The differential function should be tested using a suitable two-terminal or end-to-end test arrangement.
Test cases should include:
- Normal load stability.
- Differential pickup.
- Internal phase fault.
- Internal earth fault.
- External fault stability.
- Percentage-restraint characteristic.
- External-fault detection.
- Communication channel supervision.
- Channel failure behavior.
For a complete end-to-end test, the remote terminal relay and communication channel must also be included.
18.3 Directional overcurrent testing
Test the phase and ground directional elements using the configured voltage and current reference quantities.
Verify:
- Forward direction.
- Reverse direction.
- Pickup levels.
- Time delays.
- Directional polarization.
- Ground directional element behavior.
18.4 Arc-flash testing
For installations with arc-flash detection, verify the optical sensor inputs and current supervision.
Confirm that the required trip outputs operate only under the intended conditions.
Use the manufacturer’s recommended optical test equipment and procedures.
18.5 High-impedance fault detection testing
Verify the configured AST sensitivity and operating logic using the manufacturer’s recommended test procedures.
Confirm alarm and trip behavior without assuming that a simple conventional secondary current injection test reproduces every real-world arcing fault.
18.6 Communication testing
Verify the differential channel and communication interfaces.
Check:
- Channel availability.
- Channel delay and diagnostics.
- Communication alarms.
- IEC 61850 reports.
- GOOSE messages, where configured.
- Time synchronization.
- PRP or HSR network redundancy, where installed.
18.7 Final functional testing
Finally, verify:
- Relay trip contacts.
- Breaker trip circuits.
- Alarm contacts.
- Indications.
- Event recording.
- SER operation.
- SCADA communication.
- Final settings backup.
The commissioning report should include the actual test results, relay firmware, settings version and any outstanding issues.

19. SEL-787L vs SEL-411L vs SEL-311L
These SEL relays provide line current differential protection but differ in their applications and protection capabilities.
| Feature | SEL-787L | SEL-411L | SEL-311L |
|---|---|---|---|
| Primary application | Line differential and feeder protection | Advanced transmission-line protection | Line differential protection and automation |
| Line differential (87L) | Yes | Yes | Yes |
| Distance protection | Not its primary function | Yes | Model-specific protection functions |
| Directional overcurrent | Yes | Yes | Yes |
| Arc-flash detection | Optional | Not its primary focus | Not its primary focus |
| High-impedance fault detection | Yes, AST | Not its primary focus | Not its primary focus |
| LEA sensor inputs | Yes | Variant-dependent | Check exact hardware |
| Broken-conductor detection | Available | SEL-411L-1 | Check exact model |
| Traveling-wave fault location | Not its primary feature | SEL-411L-1 | Not its primary feature |
| IEC 61850 | Yes | Optional | Model-dependent |
The SEL-787L is an attractive option for economical two-terminal line and feeder differential applications.
The SEL-411L is better suited to applications requiring combined line differential and multizone distance protection.
The SEL-311L is another line differential protection option, particularly relevant when evaluating established transmission-line protection installations.
The final selection should be based on the required protection functions, number of terminals, communication arrangement and project specifications.
20. Advantages of the SEL-787L
The main advantages of the SEL-787L include:
- Economical two-terminal line differential protection.
- Percentage-restrained 87L protection.
- External-fault detection for CT saturation security.
- Built-in line charging-current compensation.
- Direct fiber-optic differential communication.
- Communication channel monitoring and diagnostics.
- Conventional CT/PT and LEA sensor input options.
- Directional and nondirectional overcurrent protection.
- Optional arc-flash detection.
- High-impedance fault detection using AST.
- Broken-conductor and open-conductor detection.
- Intermittent ground fault detection.
- Zero-sequence phi directional elements.
- Fault locating.
- IEC 61850 and other communication protocols.
- Flexible I/O and optional touchscreen display.
21. Frequently asked questions
What is the main function of the SEL-787L?
The main function is line current differential protection (87L) for two-terminal transmission lines, feeders and cables.
Does the SEL-787L provide distance protection?
The SEL-787L is primarily a line differential and overcurrent relay. It should not be selected as a replacement for a relay requiring conventional multizone distance protection.
What is the maximum fiber-optic communication distance?
SEL specifies up to 25 km for the single-mode 1,310 nm IEEE C37.94 interface and up to 1 km for the multimode 850 nm interface in the specified point-to-point arrangements.
Can the SEL-787L protect underground cables?
Yes. It is suitable for two-terminal cable differential protection. Cable charging current and the relevant application settings must be considered.
Does the SEL-787L support Rogowski coils?
Yes. The appropriate LEA input card supports Rogowski coil and low-power current sensor inputs, together with compatible low-energy voltage sensor inputs.
Does the SEL-787L support arc-flash protection?
Yes. Optional arc-flash detection combines light detection and high-speed overcurrent detection.
What is Arc Sense Technology?
AST is SEL’s high-impedance fault detection technology. It analyzes arcing characteristics to help identify certain downed-conductor and high-impedance fault conditions.
Does the SEL-787L support IEC 61850?
Yes. IEC 61850 Edition 2.1 is supported, subject to the ordered hardware and configuration.
Can the SEL-787L be tested using OMICRON CMC?
Yes. A suitable OMICRON CMC test set can be used for secondary injection and functional testing. The 87L function requires a suitable remote-terminal and communication test arrangement for complete end-to-end verification.
22. SEL-787L relay training by Elec-Engg
Understanding the SEL-787L requires practical knowledge of line differential protection, CT circuits, fiber-optic communication, directional protection and commissioning procedures.
At Elec-Engg, we provide practical power system protection and substation automation training for protection, commissioning, operation and maintenance engineers.
Training topics can include:
- Line differential protection principles.
- SEL-787L configuration and settings.
- CT ratio and polarity verification.
- Percentage-restraint differential protection.
- External-fault detection and CT saturation.
- Fiber-optic differential communication.
- Directional overcurrent protection.
- Arc-flash protection.
- High-impedance fault detection.
- IEC 61850 integration.
- Secondary injection and end-to-end testing using OMICRON CMC.
Online training can be arranged based on request. Customized training can also be developed around your company’s protection relays, drawings and commissioning requirements.
Visit https://elec-engg.com/ for more information about practical power system protection courses.
23. Conclusion
The SEL-787L is a versatile and economical line current differential protection relay designed for two-terminal transmission lines, distribution feeders, underground cables and distributed-generation connections.
Its combination of 87L differential protection, directional overcurrent, arc-flash detection, high-impedance fault detection, fault locating and flexible communication options makes it a useful solution for modern utility and industrial applications.
For protection engineers, understanding the differential protection principle, communication channel requirements, CT and LEA sensor inputs, directional elements and commissioning procedures is essential for successful application of the SEL-787L.
