Voltage Transformers (VTs, PTs, CVTs)

Voltage Transformers (VTs), Potential Transformers (PTs) and Capacitive Voltage Transformers (CVTs)

1. Introduction

Voltage Transformers (VTs), also known as Potential Transformers (PTs), are essential components in electrical power systems. They are used to reduce high system voltages to standardized, measurable secondary voltages suitable for protection relays, measuring instruments, energy meters, and monitoring systems.

Protection relays require accurate voltage signals to perform several important protection functions, including:

  • Distance protection.
  • Overvoltage protection.
  • Undervoltage protection.
  • Directional overcurrent protection.
  • Synchronism-check protection.
  • Frequency protection.
  • Power and energy measurement.
  • Voltage-based fault detection.

Similar to Current Transformers (CTs), Voltage Transformers provide electrical isolation between high-voltage primary circuits and low-voltage secondary circuits.

However, unlike CTs, VTs are designed to operate with their secondary circuits supplying a relatively low-impedance burden within their specified ratings.

Incorrect VT selection, wiring, polarity, secondary fuse arrangements, or voltage configuration can result in incorrect relay measurements and unwanted protection operation.

Understanding VTs and CVTs is therefore essential for protection engineers, substation engineers, commissioning engineers, and electrical maintenance professionals.

Capacitive Voltage Transformer ECF – Pfiffner Group, Electrical Sensors: Potential Transformers (PTs) and Current Transformers (CTs) | Electric Power Measurement and Control Systems | Textbook

2. What Is a Voltage Transformer?

A Voltage Transformer is an instrument transformer designed to reproduce the primary voltage at a reduced secondary voltage.

For example, a VT with a ratio of:

132 kV / 110 V

reduces the primary system voltage to a nominal secondary voltage of 110 V.

The relationship is:

VpVs=NpNsVs​Vp​​=Ns​Np​​

Where:

  • VpVp​ = Primary voltage.
  • VsVs​ = Secondary voltage.
  • NpNp​ = Number of primary turns.
  • NsNs​ = Number of secondary turns.

For an ideal voltage transformer:

Vs=Vp×NsNpVs​=Vp​×Np​Ns​​

For a 132 kV system, assuming 132 kV is the rated phase-to-phase voltage, the phase-to-earth voltage is:

Vph=1323=76.2 kVVph​=3​132​=76.2 kV

If the VT secondary phase-to-earth voltage is 63.5 V:

KV=7620063.5=1200KV​=63.576200​=1200

Therefore, the phase-to-earth ratio is approximately 1200:1.

3. Difference Between VT and PT

The terms Voltage Transformer (VT) and Potential Transformer (PT) are commonly used to describe the same general type of instrument transformer.

TermMeaning
VTVoltage Transformer
PTPotential Transformer
CVTCapacitive Voltage Transformer
CCVTCoupling Capacitor Voltage Transformer

In modern IEC terminology, the term VT is generally preferred.

The term PT remains widely used in engineering documents, particularly in North American applications and older electrical installations.

4. Main Types of Voltage Transformers

Voltage transformers can be classified according to their operating principles and construction.

The main types are:

  1. Electromagnetic Voltage Transformers.
  2. Capacitive Voltage Transformers.
  3. Coupling Capacitor Voltage Transformers.

5. Electromagnetic Voltage Transformers

An electromagnetic VT operates according to the principle of electromagnetic induction.

Its construction is similar to a conventional power transformer, but it is designed for voltage measurement and protection applications.

The primary winding is connected to the high-voltage system, while the secondary winding supplies reduced voltage signals to protection relays and measuring instruments.

What Is a Potential Transformer (PT)? - Unikeyic

Main components:

  • Magnetic core.
  • Primary winding.
  • Secondary winding.
  • Insulation system.
  • Primary terminals.
  • Secondary terminals.
  • Oil or resin insulation, depending on design.
  • Protective housing.

Applications:

  • Medium-voltage switchgear.
  • High-voltage substations.
  • Voltage measurement.
  • Distance protection.
  • Overvoltage and undervoltage protection.
  • Synchronism-check protection.

Electromagnetic VTs are commonly used at medium voltage and are also available for high-voltage applications.

6. Capacitive Voltage Transformers (CVTs)

A Capacitive Voltage Transformer uses a capacitive voltage divider to reduce high system voltage before supplying an electromagnetic intermediate voltage transformer.

CVTs are widely used in high-voltage and extra-high-voltage substations.

A typical CVT consists of:

  • Capacitor voltage divider.
  • Intermediate electromagnetic transformer.
  • Tuning reactor or compensating circuit.
  • Protective elements.
  • Secondary windings.
  • Damping and ferroresonance suppression arrangements, depending on design.
Billing measurements in high & extra-high voltage considering new frequency classes according to IEC 61869-1 ED2

How does a CVT work?

The capacitor divider reduces the high primary voltage to an intermediate voltage.

The intermediate transformer then provides the required standardized secondary voltage.

The basic capacitive voltage divider relationship is:

V2=V1×C1C1+C2V2​=V1​×C1​+C2​C1​​

Where:

  • C1C1​ = High-voltage capacitor section.
  • C2C2​ = Low-voltage capacitor section.
  • V1V1​ = Applied voltage.
  • V2V2​ = Voltage across the lower capacitor.

This equation assumes ideal capacitors without considering the complete CVT compensation circuit.

Advantages of CVTs:

  • Economical for many high-voltage applications.
  • Suitable for transmission substations.
  • Can provide coupling for power-line carrier communication.
  • Lower insulation and construction costs in many EHV applications compared with equivalent inductive VTs.

Limitations:

  • More complex transient response.
  • Frequency-dependent characteristics.
  • Possible ferroresonance.
  • Performance affected by the compensation circuit.
  • Particular considerations for transient-based protection applications.

7. Difference Between Electromagnetic VT and CVT

ParameterElectromagnetic VTCVT
Operating principleElectromagnetic inductionCapacitive divider and electromagnetic transformer
Main componentsCore and windingsCapacitor divider and intermediate transformer
Typical applicationsMV and HVMainly HV and EHV
Transient responseGenerally fasterMore complex
FerroresonancePossiblePossible
Power-line carrier couplingRequires separate coupling equipmentCan provide coupling functionality
ConstructionMagnetic transformerCapacitive and magnetic assembly
Cost at EHVCan be relatively highOften more economical

The selection depends on the voltage level, measurement requirements, protection functions, communication requirements, and manufacturer specifications.

8. VT Ratios and Standard Secondary Voltages

VT ratio selection is essential when configuring protection relays and measuring instruments.

Common secondary voltage ratings include:

  • 100 V.
  • 110 V.
  • 100/√3 V.
  • 110/√3 V.
  • 120 V.
  • 115/√3 V.

The actual rating depends on the applicable standard, system configuration, and project specification.

Examples of VT ratios:

Primary VoltageSecondary VoltageApplication
11 kV110 VMV switchgear
33 kV110 VDistribution substations
66 kV110 VHV substations
110 kV110 VTransmission substations
132 kV110 VTransmission substations
220 kV110 VEHV substations
400 kV110 VEHV substations

The engineer must distinguish between phase-to-phase and phase-to-earth ratings when interpreting VT nameplates and relay settings.

9. VT Accuracy Classes

Similar to CTs, VTs have different accuracy classes depending on their applications.

According to IEC 61869-3, inductive voltage transformers have specific requirements for accuracy and performance.

Common measuring classes include:

  • 0.1
  • 0.2
  • 0.5
  • 1
  • 3

Protection classes include:

  • 3P
  • 6P

The accuracy class indicates the permitted voltage ratio error and phase displacement under specified conditions.

For example:

132000/√3 V : 110/√3 V, 3P

indicates a voltage transformer designed with a protection accuracy class of 3P for the specified rated conditions.

ABB VIZ-11 Indoor Voltage Transformer, 8400/14560Y 70:1 Ratio 7525A70G07

Important engineering consideration:

A VT may have multiple secondary windings, each intended for a different application.

For example:

Secondary WindingAccuracy ClassApplication
Secondary 10.5Metering
Secondary 23PProtection
Residual winding6P or specified ratingEarth-fault voltage measurement

Actual configurations depend on the VT design and project requirements.

10. VT Secondary Winding Configurations

VTs can have different secondary winding arrangements.

The most common configurations include:

10.1 Star-Connected Secondary

Three single-phase VT secondary windings can be connected in star.

This provides:

  • Phase-to-neutral voltages.
  • Phase-to-phase voltages.
  • Voltage signals for protection relays.
  • Voltage signals for measuring instruments.
ЗНОЛ(П)-6-35 - Руководство по эксплуатации измерительного трансформатора напряжения | СВЭЛ

For a 110 V phase-to-phase system:

Vph=1103=63.5VVph​=3​110​=63.5V

The relay can use these voltage signals for three-phase voltage measurement and protection functions.

10.2 Open-Delta Connection

An open-delta arrangement is commonly used to obtain residual voltage for earth-fault detection.

Three VT secondary windings are connected to form an open-delta circuit.

Under balanced operating conditions, the vector sum of the three phase voltages is approximately zero.

3V0=VA+VB+VC3V0​=VA​+VB​+VC​

During an earth fault, the residual voltage may increase.

Basics of overcurrent protection | PPTX

This arrangement is commonly used for:

  • Earth-fault overvoltage protection.
  • Neutral displacement detection.
  • Insulation monitoring.
  • Ground fault detection in certain network configurations.

11. Residual Voltage and Earth-Fault Protection

Residual voltage is an important measurement in electrical protection systems.

Under balanced conditions:

VA+VB+VC=0VA​+VB​+VC​=0

During an earth fault, the phase voltages may become unbalanced.

The residual voltage is:

3V0=VA+VB+VC3V0​=VA​+VB​+VC​

This signal can be used by protection functions such as:

  • 59N – Neutral overvoltage.
  • 64 – Earth-fault protection, depending on the application.
  • 27 – Undervoltage.
  • Directional earth-fault protection, together with appropriate current measurements.

For example, in an isolated or impedance-grounded network, a single-phase earth fault can produce significant neutral displacement voltage.

The residual voltage measurement allows the relay to detect this abnormal condition.

12. Ferroresonance in Voltage Transformers

Ferroresonance is an abnormal electrical phenomenon involving nonlinear inductance and capacitance in an electrical system.

It can occur in networks containing:

  • Voltage transformers.
  • Cable capacitance.
  • Capacitor banks.
  • Switching devices.
  • Ungrounded or weakly grounded systems.
Acoustic Noise-Based Detection of Ferroresonance Events in Isolated Neutral Power Systems with Inductive Voltage Transformers | MDPI

Main causes include:

  1. Switching operations.
  2. Single-phase circuit interruption.
  3. Unloaded transformer conditions.
  4. Cable capacitance interacting with VT inductance.
  5. Certain grounding arrangements.
  6. Network configurations with nonlinear magnetic characteristics.

Possible consequences:

  • Abnormally high voltage.
  • Excessive current.
  • VT overheating.
  • Insulation damage.
  • Distorted voltage waveforms.
  • Unwanted protection operation.

Ferroresonance mitigation methods include:

  • Appropriate VT design.
  • Damping resistors.
  • Ferroresonance suppression circuits.
  • Suitable network grounding.
  • Correct switching arrangements.
  • Manufacturer-recommended protective measures.

Protection engineers should pay particular attention to ferroresonance in ungrounded and resonant-grounded networks.

13. VT Secondary Fuses and MCBs

VT secondary circuits are normally protected against secondary-side short circuits using appropriate fuses or miniature circuit breakers (MCBs).

These devices protect the secondary wiring and help isolate faulty circuits.

Why are VT secondary fuses important?

A short circuit in a VT secondary circuit can result in excessive current and damage to the VT winding or secondary wiring.

Protection arrangements should consider:

  • Individual phase protection.
  • Neutral circuit arrangements.
  • Separate protection circuits for different relays.
  • Fuse failure detection.
  • Voltage circuit supervision.

Important: Unlike CT secondary circuits, VT secondary circuits must not be short-circuited. They are voltage sources and short circuits can cause excessive current.

14. Voltage Transformer Failure Supervision

Voltage transformer supervision is an important function in modern numerical protection relays.

A VT secondary fuse failure or wiring fault may cause the relay to receive incorrect voltage measurements.

For example, if one phase voltage disappears due to a blown fuse, a distance protection relay may calculate incorrect impedance.

This could result in unwanted operation.

Modern relays provide voltage transformer supervision or fuse failure detection functions.

Typical supervision methods include:

  • Detection of voltage unbalance.
  • Monitoring negative-sequence voltage.
  • Comparison of voltage and current conditions.
  • Monitoring residual voltage.
  • Detection of abnormal voltage loss.

Some manufacturers implement these functions using dedicated logic or protection functions.

For example, in Siemens SIPROTEC relays, voltage transformer failure supervision can be configured to block or supervise selected voltage-dependent protection functions.

15. Application of VTs in Distance Protection

Distance protection is one of the most important applications of voltage transformers.

A distance relay measures the voltage and current at the relay location and calculates the apparent impedance.

Z=VIZ=IV​

Where:

  • ZZ = Apparent impedance.
  • VV = Measured voltage.
  • II = Measured current.

The calculated impedance is compared with the configured protection zones.

Figure 3 - from Teaching Distance Relay using

If the measured impedance falls within the configured operating characteristic, the relay may issue a trip command according to the zone settings and operating logic.

Why is VT accuracy important?

Incorrect voltage measurement can affect impedance calculation.

For example:

  • Incorrect VT ratio may cause incorrect impedance.
  • VT fuse failure may create false voltage measurements.
  • Incorrect phase connections may affect phase selection.
  • CVT transient response may affect transient fault measurement.

Therefore, VT selection and verification are critical for reliable distance protection.

16. Application of VTs in Synchronism-Check Protection

Synchronism-check protection is commonly used before connecting two electrical systems through a circuit breaker.

The relay compares voltage measurements on both sides of the circuit breaker.

Important parameters include:

  • Voltage magnitude difference.
  • Phase-angle difference.
  • Frequency difference.
  • Phase sequence.
  • Circuit breaker closing conditions.
ဒူဒူႀကီး: Generator Synchronizing, Parallel Operation နဲ႔ Load Sharing (၁)

The synchronism-check function is commonly identified by ANSI device number:

25 – Synchronism Check

The purpose is to ensure that the two systems are sufficiently synchronized before the breaker is closed.

This is particularly important in:

  • Generator synchronization.
  • Busbar couplers.
  • Bus-section breakers.
  • Transmission line switching.
  • Interconnection points.

17. Application of VTs in Other Protection Functions

Protection FunctionANSI CodeApplication
Overvoltage59Detect excessive system voltage
Undervoltage27Detect low system voltage
Distance protection21Calculate apparent impedance
Directional overcurrent67Determine fault direction
Directional earth fault67NDetermine earth-fault direction
Synchronism check25Verify synchronization conditions
Frequency protection81Detect abnormal frequency
Reverse power32Determine power direction
Power measurement—Measure active and reactive power

18. VT Selection – Practical Engineering Considerations

Selecting an appropriate VT requires consideration of several technical parameters.

ParameterEngineering Consideration
Rated primary voltageSystem nominal voltage
Rated secondary voltageRelay and measurement requirements
Rated voltage factorAbility to withstand specified overvoltages
Accuracy classProtection or measurement requirements
Rated burdenTotal connected secondary load
Number of secondary windingsDifferent protection and measurement functions
Insulation levelSystem voltage and insulation coordination
Frequency50 Hz or 60 Hz
Connection arrangementStar, open delta, or other specified configuration
Ferroresonance protectionNetwork grounding and capacitance
CVT transient performanceDistance protection requirements
Secondary fuse arrangementCircuit protection and supervision

19. Practical Example – VT Selection for a 132 kV Substation

Consider a 132 kV transmission substation.

The protection system requires voltage signals for:

  • Distance protection.
  • Overvoltage and undervoltage protection.
  • Synchronism-check protection.
  • Voltage measurement.
  • Directional protection.

A possible preliminary VT specification could be:

ParameterExample
System voltage132 kV
VT typeInductive VT or CVT
Primary voltage132/√3 kV
Secondary voltage110/√3 V
Protection winding3P
Metering winding0.5
Frequency50 Hz
Number of phasesThree-phase arrangement
Secondary arrangementStar with additional residual voltage winding where required

The final selection must consider the applicable insulation level, voltage factor, rated burden, transient performance, grounding arrangement, and project specifications.

20. VT Testing and Commissioning

VT testing is an essential activity during substation commissioning.

Typical tests include:

TestPurpose
Ratio testVerify primary-to-secondary voltage ratio
Polarity testVerify terminal polarity
Winding resistance testCheck winding condition
Insulation resistance testVerify insulation condition
Accuracy testConfirm measurement accuracy
Burden testVerify connected secondary load
Secondary circuit continuityVerify wiring
Phase sequence testConfirm phase identification
Residual voltage testVerify open-delta arrangement
Functional relay testVerify protection operation

Common testing equipment includes:

  • Voltage transformer test sets.
  • Omicron CMC test equipment.
  • Digital multimeters.
  • Insulation resistance testers.
  • Instrument transformer analyzers.
  • Primary and secondary injection equipment where applicable.

During commissioning, engineers should also verify:

  • Correct VT phase identification.
  • Correct relay voltage input connections.
  • Correct VT ratio settings.
  • Correct secondary earthing.
  • Correct fuse and MCB arrangements.
  • Correct voltage supervision configuration.
  • Correct protection logic under VT failure conditions.

21. Common VT Problems in Substations

The following problems are frequently encountered during protection engineering and commissioning:

  1. Incorrect VT ratio configuration.
  2. Reversed secondary polarity.
  3. Incorrect phase sequence.
  4. Blown secondary fuse.
  5. Loose secondary terminal connections.
  6. Incorrect star-point connection.
  7. Missing secondary neutral earthing.
  8. Incorrect open-delta wiring.
  9. Ferroresonance.
  10. Excessive secondary burden.
  11. Incorrect voltage supervision settings.
  12. Incorrect CVT compensation or protection application.
  13. Wrong voltage source selection in the relay.
  14. Incorrect phase-to-phase and phase-to-earth voltage configuration.

These issues can cause measurement errors, protection maloperation, and loss of voltage-dependent protection functions.

22. CT and VT – Key Differences

CTs and VTs are both instrument transformers, but they have different operating characteristics and safety requirements.

ParameterCTVT
Main purposeCurrent measurementVoltage measurement
Primary connectionSeries with circuitParallel with circuit
Secondary ratingTypically 1 A or 5 ATypically 100 V or 110 V system rating
Secondary circuitMust not be open-circuited when energizedMust not be short-circuited
Main protection applicationsOvercurrent and differentialDistance and voltage protection
Main accuracy considerationsRatio error, phase displacement, saturationRatio error, phase displacement, transient response
Secondary protectionShorting facilities and suitable earthingFuses or MCBs and suitable earthing

23. VT Standards and Technical References

Engineers should refer to the relevant international standards and manufacturer documentation.

StandardSubject
IEC 61869-1Instrument transformers – General requirements
IEC 61869-3Additional requirements for inductive voltage transformers
IEC 61869-5Additional requirements for capacitor voltage transformers
IEEE C57.13Instrument transformer requirements
IEC 60255 seriesMeasuring relays and protection equipment
IEC 60044-2Historical inductive VT standard, superseded by IEC 61869-3

Always verify the applicable standard edition and project requirements.

24. Practical Training at Elec-Engg

At Elec-Engg, we provide practical technical training covering voltage transformers and their applications in modern power system protection.

Our training includes:

  • VT and CVT operating principles.
  • VT selection and ratio calculations.
  • Voltage transformer accuracy classes.
  • VT secondary wiring and connections.
  • Open-delta and residual voltage measurements.
  • Ferroresonance and mitigation.
  • VT fuse failure supervision.
  • Distance protection applications.
  • Synchronism-check protection.
  • CT/VT circuits and relay configuration.
  • Protection relay testing and commissioning.

We also provide practical training on numerical protection relays from Siemens, ABB, Schneider, SEL, GE, and other manufacturers.

Our objective is to connect theoretical knowledge with actual substation engineering, relay configuration, testing, and commissioning activities.

25. Conclusion

Voltage transformers are essential components of modern electrical protection and measurement systems.

Their accurate performance is particularly important for voltage-dependent protection functions such as distance protection, directional overcurrent, overvoltage, undervoltage, and synchronism-check protection.

Protection engineers must understand the differences between electromagnetic VTs and CVTs, VT ratios, accuracy classes, secondary connections, ferroresonance, fuse failure supervision, and commissioning requirements.

Correct VT selection and installation help ensure reliable voltage measurements and dependable operation of the complete protection system.